AEG 220D-W, 220D-D, 220D-B User Manual

220 D
Dunstabzugshaube Fume Extractor Hood Hotte aspirante Afzuigkap Cappa aspirante
Montage- und Gebrauchsanweisung Installation and Operating Instructions Instructions de montage et mode d'emploi Montage- en gebruiksaanwijzing Istruzioni di montaggio ed istruzioni per l'uso
Printed on recycled paper. AEG – putting words into action.
18
Contents
Introduction 20
Extractor version 20 Filter version 21
Electrical connections 22 Safety warnings for electrician 22
Technical details 23 Installation 24
Safety warnings for kitchen unit installer 24 Wall unit mounting 26 Wall mounting 27
Hood operation 28 Safety warnings for user 29 Maintenance and care 30 Opening the grid 30
Grease filter 30 Carbon filter 31 Changing the light bulb 32
Cleaning 32 Special Accessories 33 Technical Assistance Service 33
19
Introduction
Extractor version
The hood is supplied as an extractor unit and can also be used with a filtering function by fitting activated carbon filters (special accessory).
The unit features two outlet holes, one of which A is located on the top of the unit while the other B is located on the rear.
To connect up the hose, you should first fit the bayonet­mounting flange C (Ø120 mm) on the outlet required (if using the top outlet, fix the flange in place using the screw supplied as shown in Fig. 1). Close off the unused hole using the bayonet fitting caps D.
D
A
B
C
1
D
C
A
B
Important! To use the back hole B, remove switch F from the top hole. — Fig 2.
F
2
A
B
20
Move the lever L to position AFig. 3.
EXHAUSTING ABLUFT
A
EVACUATION ASPIRANTE
RECIRCULATION
UMLUFT
F
RECICLAGE FILTRANTE
3
L
EXHAUSTING ABLUFT EVACUATION ASPIRANTE
RECIRCULATION
UMLUFT RECICLAGE FILTRANTE
A
F
L
When connecting up the hood using a telescopic wall pipe, you should preferably using an uninflammable outlet hose ABS 120 (120 mm Ø) E-Nr. 942 118 611 from our range of special accessories.
Filter version
The air is filtered and recirculated through the front grid.
Move the lever L to position F — Fig. 3.
You will need an original KFF activated carbon filter for filtering function. (See special accessories).
Summer/Winter Hood Conversion
To avoid excessive heat loss during the winter months, we recommend that the hood be converted from outdoor ventilation to ventless operation (air recycling).
In order to convert the hood, a charcoal filter (special accessory) is required. Follow the instructions for operating the hood to recycle air.
When the temperature outdoors becomes more mild (spring), the filter can be removed and the hood converted once again for outdoor ventilation. Please consult the assembly instructions for operating the hood with outdoor ventilation.
21
Electrical connections
Safety warnings for electrician
Check that the power supply voltage shown on the rating plate corresponds to the mains supply before proceeding to make any electrical connections. If the unit is supplied ready-fitted with a plug, it can be connected to any easily accessible socket installed in compliance with the regulations in force. If a fixed connection is required, the hood must be installed exclusively by an electrician registered with the local electrical company. The hood should be installed using an omnipolar switch with contacts that open to at least 3 mm. Fused switches can be used for this purpose (with cartridge fuses that can be extracted from the fuse holder), as can automatic circuit breakers and contactors which open to more than 3 mm. We decline all responsibility for any problems or faults caused by a failure to observe the above instructions.
Installing the socket directly above the hood or above the wall unit mounted above the hood offers the following advantages:
22
1. The socket cannot be seen.
2. The unit can be disconnected whenever required by simply taking out the plug.
Electrical connections
220-230 V - using fixed power supply line with plug. (The unit should only be connected up by an authorized electrician).
Loading...
+ 11 hidden pages