ADAM-6060W 6-channel Relay Output with DI Module
The ADAM-6060W is a high-density I/O module built-in a 10/100 based-T interface for seamless Ethernet
connectivity. Bonding with an Ethernet port and web page, the ADAM-6060W offers 6 relay (form A) output and 6
digital input channels. It supports contact rating as AC 120V @ 0.5A, and DC 30V @ 1A. All of the Digital Input
channels support input latch function for important signal handling. Mean while, these DI channels allows to be used
as 1 KHz counter. Opposite to the intelligent DI functions, the Digital Output channels also support pulse output
function.
ADAM-6060W
Figure 1: ADAM-6060W 6-channel Relay Output w/DI Module
ADAM-6060W Specification
• Channel: 12
• I/O type: 6 Relay & 6 DI
• Relay Output (Form A):Contact rating: AC: 120 V @ 0.5 A
DC: 30 V @ 1 A
Breakdown voltage: 500 V
(50/60 Hz)
AC
Relay on time: 7 msec.
Relay off time: 3 msec.
Total switching time: 10 msec.
Insulation resistance:1000 MW minimum at 500 V
• Digital Input:
Dry Contact:
Logic level 0: Close to GND
Logic level 1: Open
Wet Contact:
Logic level 0: +3 V
Logic level 1: +10 to 30 V
• Optical Isolation: 5000V
• Communication: Wireless LAN IEEE802.11b
max
RMS
DC
• Power Consumption: 2 W (Typical)
DC
Application Wiring
Figure 2: ADAM-6060W Digital Input (Wet Contact) Wiring
Figure 3: ADAM-6060W Digital Input (Dry Contact) Wiring
Figure 4: ADAM-6060W Relay Output Wiring
ADAM-6060W Configuration
Network Configuration
Step 1 : Please open the ADAM-5000TCP-6000 utility software. The utility software will automatically
scan the ADAM-6000 modules. Please wait for the A DAM-6060W being found by utility software.
Step 2 : Please go the “Network” page to change the IP address/Subnet Address/Default Gateway of
ADAM-6060W module to be compatible with user’s existing network and set the host idle time out value
(the ADAM-6000 module can only accept 8 connection from host station. Any host station doesn’t request
the communication with this ADAM-6000 module over the time out setting, the connection of this host
station will be released for the other stations).
press “Apply” to download the new IP address to ADAM-6060W module (the default password for the
changing configuration is “00000000”).
Step 3 : Re-configuring the IP address of the configuration PC to be the original setting (compatible with
user’s existing network) then re-start the utility software. The software will automatically search the
ADAM-6060W module again.
Step 4 : Go to the “Wireless” page to set the wireless LAN configuration.
Please set the wireless LAN mode to be “Infrastructure” or “Adhoc” based on exact system architecture.
Please assign the SSID for the specific wireless AP to be connected with ADAM-6000W modules. User
can place “ANY” key to let the ADAM-6000W modules to automatically search the existing wireless AP. Or
key in the specific SSID to assign the dedicated AP (strongly recommending to set up the dedicated SSID,
it can guarantee the communication of ADAM-6000W modules to be stable)
For assigning the dedicated wireless LAN AP, user can use the site survey function to check the existing
AP in connection environment. Please go to the “Site Survey” page.
Press “Scan” bottom to search the existing AP.
Selecting the AP in the searching result table.
Press “Apply” bottom to accept the AP to finish the set up action.