Connections
TTL-level Digital Input/Output
The PCI-1730U has 16 TTL-level digital inputs and 16
TTL-level digital outputs. The following figure shows
connections to exchange digital signals with other TTL
devices:
U
PCI-1730 TTL device
DO
DI
GND
If you want to receive an OPEN/SHORT signal from a
switch or relay, add a pull-up resistor to ensure that the
input is held at a high level when the contacts are open.
See the figure below:
+5V
U
PCI-1730
DI
GND
4 Startup Manual
4.7K
Switch
Isolated Digital Input
Each of the 16 isolated digital input channels accept
voltages from 5 to 30 V. Every eight input channels
share one external common. (Channels 0 ~ 7 use
ECOM0. Channels 8 ~ 15 use ECOM1.) The following figure shows how to connect an external input
source to the card's isolated inputs.
Wet
contact
External
IDI0
Internal
ECOM
Isolated
Circuit
Dry
Contact
IDI1
EGND
Isolated Digital Output
PCI-1730U provides 16 isolated DO channels. If the
external voltage (5 ~ 40V) is connected to each isolated
output channel (IDO) and its isolated digital output
turns on (300 mA per channel maximum), the card's
current will sink from the external voltage.
CN5 provides two EGND pins for IDO connection.
PCI-1730U
32-channel Isolated Digital I/O Card
Packing List Specifications
Before installation, please make sure that you have
received the following:
• PCI-1730U card
• Driver CD
• Quick Start User Manual
If a nyt hin g is mis sing or dam aged, con tac t yo ur
distributor or sales representative immediately.
User Manual
For more detailed information on this product,
please refer to the PCI-1730U_1733_1734 User
Manual on the CD-ROM (PDF format).
CD:\Documents\Hardware Manuals\PCI.
Declaration of Conformity
FCC Class A
This equipment has been tested and found to comply with
the limits for a Class A digital device, pursuant to part 15 of
the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the
equipment is operated in a commercial environment. This
equipment generates, uses, and can radiate radio frequency
energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area is likely to cause interference in which case the
user is required to correct interference at his own expense.
CE
This product has passed the CE test for environmental specifications when shielded cables are used for external wiring.
We recommend the use of shielded cables. This kind of
cable is available from Advantech. Please contact your local
supplier for ordering information.
Overview
The Advantech PCI-1730U is a 32-channel isolated
digital input/output card for the PCI bus. For easy
monitoring, each isolated digital input channel is
equipped with one red LED, and each isolated digital output channel is equipped with one green LED
to show its ON/OFF status. The PCI-1730U’s isolated digital input channels are ideal for digital input
in noisy environments or with floating potentials.
The PCI-1730U provides specific functions for different user requirements.
Notes
For more information on this and other Advantech
products, please visit our websites at:
http://www.advantech.com/eAutomation
For technical support and service:
http://www.advantech.com/support/
This startup manual is for PCI-1730U.
Part No.2003173020 1st Edition
April 2009
Isolated Digital Input
Number of Channel
Optical Isolation 2,500 V
Opto-isolator response
time
Over-voltage Protect 70 V
Input Voltage
Input Current
Isolated Digital Output
Number of Channel 16
Optical Isolation 2,500 V
Output Voltage Open collector 5 to 40 VDC
Sink/Source Current 200 mA max./channel
Non-isolated Digital Input/Output
Input Channels 16
Input Voltage
Output Channels 16
Output Voltage
General
I/O Connector
Typ e
Dimensions 175 mm x 100 mm ( 6.9" x 3.9" )
Power
Consumption
Temperature
Relative Humidity
Certification CE certified
16(bi-directional)
DC
25 µs
DC
VIH (max.) 30 V
VIH (min.) 5 VDC
VIL (max.) 2 VDC
DC 1.4 mA (typical)
5 V
DC 3.9 mA (typical)
12 V
24 V
DC 8.2 mA (typical)
DC 10.3 mA (typical)
30 V
DC
Low 0.8 V max.
High 2.0V min.
Low 0.5 V max. @ + 24 mA (sink)
High 2.4V min. @ - 15 mA (source)
37-pin D-Sub female
Typ ica l
Max.
Operation
Storage -20 ~ +85°C ( -4 ~185°F )
5 ~ 95% RH non-condensing
( refer to IEC 68-2-3)
+5 V @ 250 mA
+12 V @ 35 mA
+5 V @ 400A
+12 V @ 60mA
0 ~ +60°C ( 32~ 140°F )
(refer to IEC 68 -2 - 1 ,2)
DC
1 Startup Manual
STARTUP MANUAL
Installation PIN Assignments
PIN Assignments
Software Installation
CN1 CN2
IDO 0 1 2 IDO 1 IDI 0 1 2 IDI 1
IDO 2 3 4 IDO 3 IDI 2 3 4 IDI 3
IDO 4 5 6 IDO 5 IDI 4 5 6 IDI 5
IDO 6 7 8 IIDO 7 IDI 6 7 8 IDI 7
IDO 8 9 10 IDO 9 IDI 8 9 10 IDI 9
IDO 10 11 12 IDO 11 IDI 10 11 12 IDI 11
IDO 12 13 14 IDO 13 IDI 12 13 14IDI 13
IDO 14 15 16 IDO 15 IDI 14 15 16IDI 15
EGND 17 18EGND ECOM0 17 18 ECOM1
NC 19 20 NC ECOM0 19 20 ECOM1
CN3 CN4
DO 0 1 2DO 1 DI 0 1 2 DI 1
DO 2 3 4DO 3 DI 2 3 4 DI 3
DO 4 5 6DO 5 DI 4 5 6 DI 5
DO 6 7 8DO 7 DI 6 7 8 DI 7
DO 8 9 10DO 9 DI 8 9 10 DI 9
DO 10 11 12 DO 11 DI 10 11 12 DI 11
DO 12 13 14DO 13 DI 12 13 14 DI 13
DO 14 15 16DO 15 DI 14 15 16 DI 15
GND 17 18 GND GND 17 18 GND
+5 V 19 20 +12 V +5 V 19 20 +12 V
CN6
Description of pin use:
IDI 0 1 20 IDI 1
IDI 2 2 21 IDI 3 IDIn (n=0 ~ 15):
IDI 4 3 22 IDI 5 Isolated digital input
IDI 6 4 23 IDI 7 IDOn (n=0 ~ 15):
IDI 8 5 24 IDI 9 Isolated digital output
IDI 10 6 25 IDI 11 ECOMn (n=0 ~ 1):
IDI 12 7 26 IDI 13 External common Vcc/GND of
IDI 14 8 27 IDI 15
ECOM0 9 28 ECOM1 NC:
NC 10 29 EGND Not connected
IDO 0 11 30 IDO 1
IDO 2 12 31 IDO 3 EGND:
IDO 4 13 32 IDO 5 External ground for IDO
IDO 6 14 33 IDO 7
IDO 8 15 34 IDO 9 DIn (n=0 ~ 15):
IDO 10 16 35 IDO 11 Digital input
IDO 12 17 36 IDO 13 DOn (n=0 ~ 15):
IDO 14 18 37 IDO 15 Digital output
NC 19 GND:
IDI
Digital ground
Hardware Installation
1. Turn off your computer and unplug the power cord
and cables. TURN OFF your computer before
installing or removing any components on the
computer.
2. Remove the cover of your computer.
3. Remove the slot cover on the back panel of your
computer.
4. Touch the metal part on the surface of your computer
to neutralize the static electricity that might be on
your body.
5. Insert the PCI-1730U card into a PCI slot. Hold the
card only by its edges and carefully align it with the
slot. Insert the card firmly into place. Use of excessive force must be avoided; otherwise, the card might
be damaged.
6. Fasten the bracket of the PCI card on the back panel
rail of the computer with screws.
7. Connect appropriate accessories (37-pin cable, wir-
ing terminals, etc. if necessary) to the PCI card.
8. Replace the cover of your computer chassis. Re-con-
nect the cables you removed in step 2.
9. Plug in the power cord and turn on the computer.
2 Startup Manual
CN5
EGND 1 2 EGND
3 Startup Manual