ADTRAN 1000 User Manual

Total Access® 1000 DSLAM Local Power ATM Power Supply Unit
Installation and Maintenance
CONTENTS
1. GENERAL.......................................................... 1
2. INSTALLATION ............................................... 2
3. MAINTENANCE ............................................... 2
4. SPECIFICATIONS ............................................ 3
5. WARRANTY AND CUSTOMER SERVICE ... 3
FIGURE
Figure 1. Total Access 1000 DSLAM Local Power
ATM PSU .................................................. 1
TABLES
Table 1. Compliance Codes ...................................... 2
Table 2. Specifications .............................................. 3
Section 61179018L1-5A
Issue 1, November 2002
CLEI Code: VAPUCMEC_ _
ATM PSU
1179018L1
POWER
1. GENERAL
This practice provides installation and maintenance procedures for the ADTRAN Total Access 1000 DSLAM Local Power ATM Power Supply Unit. Figure 1 is an illustration of the Total Access 1000 DSLAM ATM PSU.
This is the initial release of this document. Future revisions to this document will be explained in this subsection.
Features
The Total Access 1000 DSLAM Local Power ATM PSU, P/N 1179018L1, includes the following features:
Converts incoming -48 VDC local power to regulated buss voltages
Provision free plug and play
Front Panel status LED
Meets FCC, NEBS Level 3, and UL 60950
requirements
General Description
The Total Access 1000 DSLAM Local Power ATM PSU is a common module plug-in unit designed for use in the ADTRAN Total Access 1000 DSLAM channel bank. The PSU accepts local power (-42 VDC minimum -56 VDC maximum) from local power
Figure 1. Total Access 1000 DSLAM Local
Power ATM PSU
terminal on the backplane. Through switchmode operation, the PSU converts the local voltage to four buss voltages: +5 V, +3.3 V, +2.5 V, and +22 V. These voltages are distributed on the Total Access 1000 backplane for use by other cards in the system.
This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Changes or modifications not expressly approved by ADTRAN could void the users authority to operate this equipment.
61179018L1-5A
Trademarks: Any brand names and product names included in this document are trademarks, registered trademarks, or trade names of their respective holders.
1
C A U T I O N
2. INSTALLATION
C A U T I O N
SUBJECT TO ELECTROSTATIC DAMAGE
OR DECREASE IN RELIABILITY.
HANDLING PRECAUTIONS REQUIRED.
!
After unpacking the unit, inspect it for damage. If damage is noted, file a claim with the carrier, then contact ADTRAN. Refer to Warranty and Customer Service.
3. MAINTENANCE
The Total Access 1000 DSLAM Local Power ATM PSU does not require routine maintenance for normal operation.
Field Repairs
ADTRAN does not recommend that repairs be attempted in the field. Repair services are obtained by returning the defective unit to ADTRAN Customer Service Department.
The Total Access 1000 DSLAM ATM PSU inserts directly into the common card area in the position labeled PSU.
To install the PSU, grasp the unit by the front panel while supporting the bottom side. Align the card edges to the guide grooves and insert the unit until the edge connector seats firmly into the backplane. Lock the card in place by pushing in on the lock levers.
Provisioning Options
The Total Access 1000 DSLAM Local Power ATM PSU has no options or adjustments. It does not require provisioning prior to insertion into the channel bank.
Front Panel LED
The front panel LED will indicate GREEN when proper local power voltage is present and system voltages are present. An off LED indicates the loss of a system voltage.
Compliance Codes
Table 1 shows the Compliance Codes for the Total Access 1000 DSLAM Local Power ATM PSU. This product is intended to be installed in a Total Access 1000 Chassis providing a Type “B” or “E” enclosure, with Restricted Access.
Table 1. Compliance Codes
4. SPECIFICATIONS
Refer to Table 2 for Total Access 1000 DSLAM Local Power ATM PSU Specifications.
5. WARRANTY AND CUSTOMER SERVICE
ADTRAN will replace or repair this product within ten (10) years from the date of shipment if it does not meet its published specifications or fails while in service. Refer to ADTRAN U.S. and Canada Carrier Networks Equipment Warranty, Document 60000087-10.
Contact Customer and Product Service (CAPS) prior to returning equipment to ADTRAN.
For service, CAPS requests or further information, contact one of the following numbers:
ADTRAN Sales
Pricing and availability (800) 827-0807
ADTRAN Technical Support
Pre-sales Applications/Post-sale Technical Assistance (800) 726-8663
Standard support hours:
Monday-Friday, 7 a.m. - 7 p.m. CST
Emergency support:
7 days/week, 24 hours/day
Code Input Output
Power Code (PC) C C Telecommunication Code (TC) X – Installation Code (IC) A
2
ADTRAN Repair/CAPS
Return for repair / upgrade (256) 963-8722
Repair and Return Address:
ADTRAN, Inc. CAPS 901 Explorer Boulevard Huntsville, Alabama 35806-2807
61179018L1-5A
Loading...
+ 2 hidden pages