AdobeAir C110A, C230A, E110A, C210A, C430A Specifications

...
Page 1
Complete packaged system with all internal pump and motor wiring complete.
Standard and low profile models.
U.L. Listed for safety.
More cooling capacity and lower operating costs than comparably sized blower wheel models.
For low static pressure installations in commercial, industrial & warehouse applications
High Capacity Fan Evaporative Coolers
THE WORLD LEADER IN EVAPORATIVE COOLING FOR OVER 50 YEARS
(Patent Pending)
AdobeAir, Inc. certifies that the evaporative air cooling products shown in this catalog are licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and comply with the requirements of the AMCA Certified Ratings Program.
Page 2
Features
Energy Efficient Fan Design
Arctic Circle High Capacity Evaporative Coolers use energy efficient fan blades to move the air. Our fan coolers move more air while using less horsepower than comparably sized blower wheel (squirrel cage) models. And since simply any fan blade won’t do, Arctic Circle adjusts the pitch of the blades for each specific model to assure maximum air delivery!
Designed For Low Static Pressure Applications
Arctic Circle High Capacity Evaporative Coolers were developed for applications where air from the cooler is being discharged directly into a space making them ideal for factories, warehouses, agricultural buildings and other installations with straight discharge plenums without ancillary duct work. For ducted applications with external static pressure exceeding 0.2” water gauge, Arctic Circle recommends their line of blower wheel models.
U.L. Listed
Arctic Circle High Capacity Evaporative Coolers are U.L. listed for non-ducted installations, meaning you can rest assured that they meet or exceed most local and national codes.
Design and Construction Features:
Heavy duty galvanized steel construction using industry proven best methods and practices.
Industrial grade, electrostatically applied powder coated finish for maximum durability.
High grade aspen pads ensure maximum cooling efficiency.
Center fed PVC water distributor system maintains crucial pad wet-out.
Specially designed fan blades provide maximum air delivery at minimum cost.
Separate GFCI receptacle offers a convenient and safe method of supplying power to the pump.
Arctic Circle can deliver around 17,000 cfm at 0.0” water gauge using a 1
1
/2 HP motor. A comparable blower wheel model requires up to 5 HP to deliver the same volume of air. That’s at least 65% lower cost!
Shown with optional
diffuser grille.
$$$$$$$$$$$$$$
Blower
VS.
Fan
Save Up To 65% In Energy Costs!
$$$$$$$
Page 3
Double Sided Louvered Pad Frame Design
Arctic Circle has over 50 years of experience in designing evaporative coolers for commercial, industrial and agricultural applications. We’ve designed this special pad frame to assure that water stays where it is supposed to be — in the pad! Both the external and internal louvers constantly direct water into the pad, and away from the air stream.
Certified Air Delivery CFM At Various External Static Pressures
Inches Water Gauge
AMCA Licensed Ratings
• Performance shown is for installation type B: Free inlet Ducted outlet.
• Performance ratings include the effect of evaporative media in the airstream.
• Power rating (BHP) does not include drive loses.
11,000 9,500 7,400
17,000 15,100 12,800
All external wiring and components such as disconnects, motor starters, and over-current protection are to be field supplied and are not included as part of the evaporative cooler from the factory.
A separate 120 volt, 60 hertz, 1-phase pump electrical circuit is required to maintain the integrity of the GFCI pump protection and to maintain the U.L. listing of the evaporative cooler.
120V/60Hz/1Ph
Nameplate Fan Voltage Motor Pump
Model HP BHp RPM (60Hz) Phase Amperage Amperage 0.0” 0.1” 0.2”
AFD4242 C110A 3/4 .76 510 120 1 10.5 1.2 AFD4242 C210A 3/4 .76 510 240 1 5.3 1.2 AFD4242 C230A 3/4 .76 510 208/240 3 3.0 1.2 AFD4242 C430A 3/4 .76 510 480 3 1.5 1.2 AFD4262 E110A 1-1/2 1.34 510 120 1 14.5 1.2 AFD4262 E210A 1-1/2 1.34 510 240 1 6.3 1.2 AFD4262 E230A 1-1/2 1.34 510 208/240 3 4.6 1.2 AFD4262 E430A 1-1/2 1.34 510 480 3 2.2 1.2
Complete Packaged System
With Motor And Pump Pre-wired
With an Arctic Circle High Capacity Evaporative Cooler you get a complete system, with factory installed motor and circulating pump that have all internal wiring complete. The separate pump circuit is GFCI protected for safety, and all internal wiring is in water tight conduit to a weatherproof junction box.
1
2
1
2
Water Trough
External Louvers
Internal Louvers
Aspen Pad
Page 4
The most accurate sizing is accomplished by the use of KoolKalk, our software program, when you have already calculated the sensible cooling load of the building. KoolKalk combines ASHRAE design day conditions, the principles of psychrometrics, and hourly weather data of typical meteorological years for key cities around the world. Contact your AdobeAir sales representative for a free copy of KoolKalk, or see our website at www.AdobeAir.com.
Although not the preferred method, alternate sizing by considering only air changes in the building may be adequate for some warehouse and other industrial applications. To select a cooler or coolers based on air changes only, follow these simple steps:
1) Determine the size (in cubic feet) of the space to be cooled (length x width x height). Remember that in most cases a height of from 10-12 feet is all that needs to be considered since that is typically only the height to which cooling is required.
2) Determine how frequently the air needs to be changed in the building (minutes per air change) by referring to the chart and map above. As an example, a warehouse in El Paso, Texas (zone 2) with an average interior heat load and exposed exterior heat load needs an air change at least every 3 minutes as a rule of thumb.
3) Determine the total CFM required for the building by dividing the cubic feet of the space to be cooled by the number of minutes for each air change.
Example:
Building size = 200’ long x 100’ wide x 12’ height to be cooled = 240,000 cubic feet to be cooled.
Air needs to be changed every 3 minutes (El Paso, Texas example from #2 above)
240,000 / 3 = 80,000 cfm total delivered air required from coolers.
Select coolers delivering a combined total of 80,000 cfm.
Arctic Circle evaporative coolers and components are designed and tested in accordance with one or more of the following standards or agencies:
Air Delivery: Data published derived from tests conducted in accordance with A.M.C.A. (Air Movement and Control Assoc.) Standard 210. Aspen Pads: Built to Federal Specification PP-E-911 for Type 1, Class A, Grade 4. Sealant: Water Immersion: per ASTM D870. Flexibility: per ASTM D756. Corrosion Resistance: per ASTM B117. Cycle Freeze/Thaw: per ASTM C117. POLYBOND®: Corrosion Resistance: per ASTM B117. Pencil Hardness: per ASTM D3363. Adhesion: per ASTM D3359. Impact Resistance: per ASTM D2794.
Flexibility: per ASTM D522. Specular Gloss: per ASTM D523. Surface Burning Characteristics of Building Materials (best rating) per U/L 723 and ASTM E-84. Pumps: Recognized under the U/L component recognition program for the application – construction, thermal overload, running overload, and locked rotor protection.
Fan Motors: U/L recognized general purpose drip-proof. Polymeric Materials: Tested in accordance with U/L 94 and 746C. Covered by City of Los Angeles Research Reports (C.O.L.A.) RR930224 (for all single
phase applications), or RR930190 (for 3 phase applications) Electrical, and RR8141 Mechanical.
Since AdobeAir, Inc. follows a policy of continuous product improvement, we reserve the right to change specifications and design without notice. © 2002 All rights reserved, AdobeAir, Inc.
L900786A January 2002
Designed and manufactured in the United States by: Adobe Air, Inc., 500 S. 15th Street, Phoenix, Arizona 85034 www.AdobeAir.com
MADE IN
THE U.S.A.
Water Electric Effective Approx. Model Cabinet Duct Location Drain Bottom Pan Service Service Pad Sump Approximate Series Opening Location Location Depth Riser Location Location Pads Area Capacity Weights (lbs.)
H W D A B C E F G L J K M N Y Z No/Ht/Wd Sq. Ft. Gal. Ship. Oper.
AFD 4242 41 62 62 46 46 7 8 7.72 4.56 46.50 3.50 12.12 1.00 5.06 40.12 33.00 8/35/28.56 48.75 20 445 609
AFD 4262 61 62 62 46 46 7 8 7.72 4.56 46.50 3.50 12.12 1.00 5.06 60.12 33.00 8/55/28.56 77.63 20 536 700
Plan View
Elevation View
Dimensional Data
Sizing Instructions
Heat Load Zone
Exterior Interior 1 2 3 4
Exposed High 3 2 2 1 Insulated High 4 3 2.5 1.5 Exposed Average 4 3 2 1.5 Insulated Average 5 4 2.5 2
Zones
3
3
4
2
1
Drain is 3/4” male thread. Water connection is to
factory supplied 3/8” O. D. copper tubing stub from internal float valve.
Electric service entrance is 7/8” I. D.
1
3
2
1
3
2
M
E
C
B
Electric
Water
Electric
L
A
Y
H
D
W
G
F
N
J
K
Z