Please find CAS, CAD, CAM (R or I), CMP, etc.. in separate papers!
1. DIAGNOSTIC CHART 1
2. The service rules of the R407C(R410a) product 5
3. MAS 8
4. MES 45
5. CES/CED/CEM 65
6. GES 97
7. GIS 115
8. LIS 127
9. CUS 139
10. BES 157
11. CES I 178
12.
CED I & CEM I
197
Diagnostic Chart(5000Btu/h-12000Btu/h)
1. Self-diagnose the failure
COOLWEX units have self-diagnose function.
Note: for the following series
CES
CED
CEM
2. After energizing, no indicator is lighted and the air conditioner can’t be operated.
After energizing, the air conditioner can’t be operated
Check if AC220V power supply outputs to Indoor PCB.
Yes
Check if AC220V exists at the primary coil of transformer.
YesNo
Indoor PCB is defective
Or current fuse is melt.
Check if AC14.5V exists at the secondary coil of transformer.
Take off the secondary plug of transformer, and then check if
AC14.5V exists at the secondary coil of transformer.
No Yes
Yes
No
The transformer is defective. Indoor PCB is defective
3. Resetting phenomenon often occurs during operation. (That is automatically entering to
the status when power is on.)
The reason is that the instantaneous voltage of main chip is less than 4.5V. Check
according to the following procedure:
Resetting phenomenon often occurs during operation.
After changing Indoor PCB, check if the failure releases.
NoYes
After changing indoor fan motor, check if the failure releases.
Power supply circuit has problems.
No
Indoor PCB is defective
1
A
4.
Failure phenomenon for cooling only type
Failure phenomenon Operation lamp Timer lamp
Indoor fan speed has been out of control for over 1 minute
Indoor room temp. or evaporator sensor is open circuit or short circuit
Over current protection of the compressor occurs 4 times X
EEPROM error On
r Extinguish
☆ Flash at 5Hz
☆
☆
4.1 Operation lamp flashes and Timer lamp off.
Operation lamp flashes and Timer lamp off.
Yes
Change the main control board
4.2 Operation lamp flashes and Timer lamp on.
Is connection to connector good?
yes No
Replace the sensor
Repair connector
4.3 Operation lamp off and Timer lamp flashes
Operation lamp off and Timer lamp flashes
fter changing the main control board, check if the failure releases.
No Yes
The voltage of power supply is too low (less than 187V)?
Indoor PCB is defective
YesNo
Power supply fault Outdoor unit fault (such as the compressor)
4.4 Operation lamp on and Timer lamp flashes
EEPROM error, indoor PCB is defective.
X
On
☆
☆
2
A
5.
Failure phenomenon(heat pump)
Failure phenomenon Operation lampTimer lamp Defrosting lamp
Over current protection of the compressor occurs 4
times
Indoor fan speed has been out of control for over 1
minute
No over-zero signal
Temp. sensor on indoor evaporator is open circuit or
short circuit
Indoor room temp. sensor is open circuit or short circuitX
EEPROM error On
☆
X
☆☆☆
X X
X
☆ ☆
☆
☆
☆
☆
X
X
r Extinguish
☆ Flash at 5Hz
5.1 Operation lamp flashes ,Timer lamp off and Defrosting lamp flashes.
Operation lamp flashes ,Timer lamp off and Defrosting lamp flashes
fter changing the main control board, check if the failure releases.
No Yes
The voltage of power supply is too low (less than 187V)?
Indoor PCB is defective
YesNo
Power supply fault Outdoor unit fault (such as the compressor)
5.3 Operation lamp flashes, Timer lamp flashes and Defrosting lamp flashes .
This is alarm signal when the main chip can’t detect over-zero signal. When such
failure occurs, the main control board must have fault.
3
Operation lamp flashes and Timer lamp off.
Yes
Change the main control board
5.4 Operation lamp off ,Timer lamp off and Defrosting lamp flashes.
Is connection to connector good?
yes No
Replace the sensor
Repair connector
5.5 Operation lamp off, Timer lamp flashes and Defrosting lamp off
Is connection to connector good?
yes No
Replace the sensor
Repair connector
5.6 Operation lamp on, Timer lamp flashes and Defrosting lamp off
EEPROM error, main PCB has fault.
Temporarily turn off the power supply and turn it on again in about 1 minutes
Does the trouble occur again?
Yes
Replace the indoor PCB
4
The service rules of the R407C product
The service rules of the R410A product
1. The service rules of the new refrigerant R407C product
COOLWEX uses the green refrigerant R407C firstly in China.
Its thermal characters are similar to R22, but there is little difference between them.
1.1 The main difference between R407C and R22:
R407C R22
Component HFC32/125/134aHCFC22
The ratio of mix Wt% 23/25/52 100
The saturation liquid density Kg/m
3
1136 1191
Normal pressure kj/kg.k 0.835 0.622 Specific heat
The saturation liquid kj/kg.k1.554 1.256
Evaporating pressure kpa 499 498
Condensing pressure kpa 2112 1943
Temperature slippage ℃ 4.3-7.1 0
Heating capacity w 92-97 100
Input power w 106 100
COP 97 100
The consistent with the oil Fat oil Mineral oil
1.2 Service precautions:
1.2.1 Because R407C is a mixture composed of three kinds of matter, when vapor phase and liquid
phase coexist, the component of the vapor phase is different from the liquid phase. When we fill
the refrigerant, we must ensure to fill it in liquid phase, in order to maintain the stability of the
character.
1.2.2 The leakage of the refrigerant is from vapor side or liquid side, and the leakage from vapor side
could make the component change and impact the character seriously. So when the amount of
the leakage is up to 5%, we need discharge all refrigerant in the system, and fill liquid
refrigerant according to amount in nameplate.
1.2.3 Because the lubricant fit for refrigerant R407C is ester refrigerating engine oil (POE) or ether
refrigerating engine oil (PVE). The mineral lubricant fit for refrigerant CFC and HCFC is weak in
consistent with the HFC, and it doesn’t fit for the refrigerant HFC. So when the compressor
using new refrigerant R407C is worn out, to replace it by compressor of CFC or HCFC is
forbidden.
1.2.4 When the connection of the refrigerant pipe is finished, before the system start up we should
vacuum the indoor unit by cut-off valve or discharge the indoor unit air by refrigerant R407C
bottle. Discharged the air in system by outdoor unit refrigerant is forbidden.
1.2.5 Ester oil could adsorb the water in the air. In order to removemoisture in refrigeration system,
avoid capillary jammed by ice and the ester lubricant oil decomposed with water, we use
desiccant in system. Artificial zeolite (molecular sieve R etc.) is the effective water sorbent.
Toavoid absorb refrigerant but only absorbmoisture, we use the molecular sieve whose
aperture is smaller than the molecule of the refrigerant. For R407C we should adopt XH-11
rather than XH-9AK and 4A-NRG.
1.2.6 Because the corrosion of R407C and POE to high molecular material is different from R22 and
mineral oil, the airproof material inside high/low pressure valve and foul-way valve needs to be
changed in refrigeration system, such as R407C, polyurethane rubber etc. The high/low
pressure valve and four-way valve which are fit for R22 couldn’t be used in service.
1.2.7 When there is leakage, filling with other kind of refrigerant is forbidden.
1.2.8 When we need to vacuum the system, we should use the special quick joint, but use the quick
joint of other refrigerant is forbidden lest pollute by mixing refrigerant. The time for vacuuming is
5
about 30 minutes, and vacuity is less than 133Pa.
1.3 Precautions:
1.3.1 Regulations
Being liquefied vapor, R-407C and R-410A are high-pressure vapor , the high-pressure gas regulation is
applicable. Before use it, please refer to high-pressure gas regulation. To prevent the high-pressure
vapor from causing damage, the regulation should be followed.
1.3.2 Usage of vessel
Being high-pressure vapor, R-407C and R-410A are contained in high-pressure vessel. The
safety condition of vessel is good, but if you don’t use it carefully, you may damage the vessel
and cause accident.
1.3.3 Storage
Although R-407C and R-410A are nonflammable, when they are stored with the normal
high-pressure gas, we should place them in the good ventilation area.
In addition, there are safe devices in the high-pressure vessel. Please note that when the
temperature (fusible valve) or pressure (spring safe valve) is up to a certain value, it will eject
vapor.
1.3.4 Ventilation
Because R-407C and R-410A are heavier then air, they will go down. If room is full of the
leakage vapor, the density of oxygen will decrease, and cause people suffocated.
In addition, if you light the fire when there is R-407C in the air, it will produce the toxic gas with
pungent odor and corrosiveness.
1.3.5 Precautions about health
For R-407C, R-410A and normal liquefied high-pressure vapor, please don’t contact with skin
directly, and prevent being splashed into eyes and avoid drinking.
1.3.6 The following are the urgent disposal methods:
Splash into eyes:
Wash eyes with pure water for more than 15 minutes, and don’t knead the eyes or blink.
Please wash eyes with watery boric acid water if the ache gets heavy.
To avoid the accident, please ensure that you wear the protection glasses.
Contact with skin directly
The temperature will decrease rapidly by evaporation if R-407C and R-410A expose to air in
liquid phase. So if the liquid contacts with skin directly, it may cause frostbite. If there are freeze
burns, please go to see the doctor immediately.
2. The service rules of the R410A product
2.1 There are some differences between air conditioner of R410A s and that of R22:
2.1.1 The compressor used is different, it is a new refrigerant compressor (special);
2.1.2 The air conditioner of new refrigerant R410A has a drier, while the A/C of R22 doesn’t have.
2.1.3 There is no difference between the evaporator, condenser and system pipe of new refrigerant
R410A A/C and that of R22 A/C in appearance. The requirement of new refrigerant R410A A/C
for craft is higher , and the amount of moisture and impurity in the system is less than that of A/C
using R22. The resistance to pressure is higher.
2.1.4 The manufacture process is different, the requirement of air conditioner using R410A for craft is
high.
2.2 Refrigerant system:
2.2.1 The high pressure of refrigerant system is 3.0 Mpa, and the low pressure is 1.2 Mpa. (The
value is 1.5 times more than that of R22 under the same condition)
2.2.2 When installing the split type of new refrigerant R410A, all connecting pipes must be special
pipes of R410A. Discharging air must use refrigerant R410A, and couldn’t misuse the
connecting pipe and refrigerant of A/C using R22. Otherwise, it will destroy the stability of A/C.
2.2.3 Because the compressor of refrigerant R410A split type uses POE oil, which can react with
moisture to form water and acid. The water produced by reaction could react further, and if the
6
chain reaction proceeds continually , the water in the system will be more and more. It will cause
the capillary ice blocking; at the same time, acidity of working substance circulated in the
system will be higher and higher (the value of PH is lower and lower), and it may corrode the
components and parts in the system. The phenomenon of copperizing would happen. When
installing A/C, the action should be prompt, and after opening the plug of connecting pipe we
must tighten the nut in 5 minutes. The time of discharging air should be enough. When
installing A/C, the sweat drops into the connecting pipe is forbidden; the infusible impurity
mixed in the system is forbidden. It is better to install the A/C of refrigerant R410A split type in
fine weather, do not do it in rainy day, nor humid weather.
2.2.4 The chlorine ion could react with POE oil to form acid, and the acid corrodes the components
and parts of refrigerant system. So pollute the system with chlorine ion in installation is
forbidden, such as sweat beads and other impurities that contain chlorine ion.
2.2.5 Whatever the reason we must change the drier, if the refrigerant system is exscinded in service,
after we exscind the refrigerant system, we must use something to wrap the fracture lest the
moisture in air enters into the system. The time that refrigerant system expose to air should be
less than 5 minutes.
2.2.6 Must weld the drier into system in 5 minutes in order to isolate the air when changing it.
Otherwise it will influence the performance of the drier.
2.2.7 Must use special pump after service. The lubricant should be the grease. The pump couldn’t be
used to vacuum the A/C of refrigerant R22, otherwise it would cause the contamination of
refrigerant, and influence the performance of A/C. The time of vacuuming must be over 25
minutes, Otherwise the moisture in system will be too high, and affect the stability of A/C.
2.2.8 If need to change the components and parts, must use the special one of R410A in service.
Using the components and parts of R22 is forbidden; otherwise it would affect the stability of
A/C.
The refrigerant R410A should be placed in environment under 30℃. If the refrigerant has been
placed in environment above 30℃, it is necessary to store the refrigerant in the environment below
30℃ for more than 24 hours. Otherwise the component of refrigerant would be changed and it
affects the performance of A/C.
7
CES, CED & CEM
1. Features 66
2. Specification 67
3. Dimensions 73
4. Refrigeration cycle diagram 77
5. Operation limits 78
6. Wiring diagram 79
7. Troubleshooting 86
8. Electronic function 86
1.Features
1.1 Compact design
1.2 High efficiency and quiet operation
66
2.Specification
Model CES-05.R.....................CES-07.R.........................CES-07.RC...................CES-09.R....................CES-09.RC
Power supply Ph-V-Hz 220-240V~,50Hz220-240V~,50Hz220-240V~,50Hz 220-240V~,50Hz 220-240V~,50Hz
Capacity Btu/h 5000700070009000 9000
Cooling
Heating
Moisture Removal L/h 0.60.80.81 1
Max. input consumption W 800105010501300 1300
Max. current A 3.8557 7
Starting current A 16181825 25
Compressor
Indoor fan motor
Indoor air flow (Hi/Mi/Lo) m3/h 300/270/240380/350/320380/350/320450/420/ 390 450/420/390
Refrigerant type R22 g 480620580650 580
Design pressure MPa 2.62.62.6 2.6
Refrigerant piping
Connection wiring NoNoNo No No
Plug type 10A10A10A10A 10A
Thermostat type Electronic controlElectronic controlElectronic control Electronic control Electronic control
Operation temp ℃ 17-3017-3017-3017-30 17-30
Ambient temp ℃ 18-45-7-4518-45-7-45 18-45
Application area m2 8-1210--1410-14 14-21 14-21
Input W 5607607601000 1000
Rated current A 2.63.63.64.5 4.5
EER Btu/w.h 8.68.88.89 9
Capacity Btu/h 760010000
Input W 760980
Rated current A 3.44.4
COP w/w 2.93.0
Model KH104VFHC2P14C235ANA2P14C235ANAPH170X1C-4DZ2 PH170X1C-4DZ2
Type RotaryRotaryRotaryRotary Rotary
Brand SHANGHAI SENLINGD MatsushitaGD MatsushitaGD Toshiba GD Toshiba
Capacity Btu/h 57007500750010000 10000
Input W 590725725970 970
Rated current(RLA) A 2.73.43.44.5 4.5
Locked rotor Amp(LRA) A 13151524 24
Thermal protector BF540-KBMRA98854MRA98854UP3QE0591-T61UP3QE0591-T61(int
Over current protection of the compressor occurs 4 times ☆ X ☆
Indoor fan speed has been out of control for over 1 minute X ☆ ☆
No over-zero signal ☆ ☆ ☆
Temp. sensor on indoor evaporator is open circuit or short circuit X X ☆
Indoor room temp. sensor is open circuit or short circuit X ☆ X
EEPROM error On ☆ X
☆ On
r Extinguish
☆ Flash at 5Hz
8 Electronic function
8.1 Electric Control working environment
8.1.1 input voltage: 175~253V
8.1.2 Input power frequency:50Hz
8.1.3 Ambient temperature: -7°C~+43°C
8.1.4 Indoor fan normal working amp is less than 1A,
8.1.5 Outdoor fan. Normal working amp is less than 1.5A
8.1.6 Four-way valve normal working amp is less than 1A.
8.1.7 Swing motor: DC12V.
8.1.8 Compressor: single-phase power supply. Its normal working amp is less than 15A
8.2 Proper symbols and their meanings:
TA: Indoor ambient temperature
TE: Indoor evaporator temperature
TS: Setting temperature through the remote controller
I
: Self-protection amp of compressor, continue three seconds until turns off the compressor.
3sec
I
: Self-protection amp of compressor, continue five minutes until turns off the compressor.
5MIN
I
: Self-protection amp of outdoor fan/indoor fans when they change from higher wind to lower wind.
FAN
I
RESTORE
TH
TM
TL
TE1: Anti-cold wind, from Fan Off to Breeze temperature
87
: Amp self-protection return value
DEFROST
DEFROST
DEFROST
: High wind, defrosting temperature difference
: Middle wind, defrosting temperature difference
: Low wind, defrosting temperature difference
TE2: Anti-cold wind, from Breeze to Setting Fan Speed temperature
TE3: Anti-cold wind, from Setting Fan Speed to Breeze temperature
TE4: Anti-cold wind, from Breeze to Fan Off temperature
TE5: Evaporator low temperature protection entering temperature
TE6: Evaporator low temperature protection restoring temperature
TE7: Evaporator high temperature protection, compressor off temperature
TE8: Evaporator high temperature protection, fan off temperature
TE9: Evaporator high temperature protection, restoring temperature
8.3 Systematic functions
Remote receiving
Testing and forced run
Position set for indoor unit wind vane
LED displaying and alarm
On or off Timer
Protection for the compressor
Current protection
High temperature protection of indoor heat exchanger at heating mode
Auto defrosting and heating recovery at heating mode
Anti cold air at heating mode
Anti frozen at heating mode
8.4 Protection
8.4.1 The compressor functions protection with a delay of three minutes.
8.4.2 Sensor protection at open circuit and breaking disconnection
8.4.3 Temperature Fuse break protection
8.4.4 Fan Speed is out of control. When Indoor Fan Speed is too high(higher than High Fan+300RPM)or
too low(lower than 400RPM), the unit stops and LED displays failure information and can’t returns to
normal operation automatically.
8.4.5 Cross Zero signal error warning. If there is no Cross Zero signals in 4 minutes, the unit stops and LED
displays failure information and can’t returns to normal operation automatically.
8.4.6 The current protection of the compressor
Condition Indoor fan Compressor Outdoor fan Remark
Current up
Current down
I< I
RESTORE
I
FAN
I
5MIN
I
5MIN
I
FAN
RESTORE
I< I
On On On
RESTORE
<I< I
FAN
<I<I
Off Off After 5 Minutes
5MIN
<I< I
Off Off After 3 Seconds
3SEC
<I< I
Off Off After 3 Seconds
3SEC
<I<I
Off Off After 5 Minutes
5MIN
<I< I
FAN
On On On
RESTORE
On On Off Heating mode I
Low speed On On Cooling mode
On On Off Heating mode I
Low speed On On Cooling mode
If compressor turns off for continuously 4 times due to current protection in 5 minutes from
Compressor On, the unit stops and LED displays failure information and can’t returns to normal
operation automatically.
88
8.5 Fan-only mode
Fan speed is high/mid/low/ Auto
8.6 Cooling mode
The 4-way valve is closed at cooling mode.
The action of the compressor and the outdoor fan:
Condition Compressor Outdoor fan
T> Ts+1 On On Temp. up
T<Ts+1 Off Off
T> Ts On On Temp. down
T<Ts Off Off
Auto fan at cooling mode:
Condition
T=Indoor Temp.-Setting Temp.
Temp. up
Temp. down
T<3℃ Low
3℃<T<5℃ Med.
T>5℃ High
T> 3℃ High
1℃<T<3℃ Med.
T<1℃ Low
Indoor fan speed
Anti-freezing control to indoor evaporator at cooling mode( T: evaporator temp. )
Condition
Temp. Time
T> TE6 On On Temp. up
T< TE6 >5 Minutes Off Off
T> TE5 On On Temp. down
T< TE5 >5 Minutes Off Off
Compressor Outdoor fan
8.7 Dehumidifying mode
8.7.1 The 4-way valve is off in dehumidifying mode
8.7.2 Compressor and Indoor Fan actions in dehumidifying mode
NO Conditions Indoor Fan Compressor and Outdoor Fan
1
2
3
TA ≥ TS+2
TS ≤TA <TS+2
TA < TS
LOW
BREEZE
LOW
BREEZE
LOW
BREEZE
ON 6minutes
OFF 4minutes
ON 5minutes
OFF 5minutes
ON 4minutes
OFF 6minutes
Repeat on and off cycle.
89
8.7.3 Low room temperature protection:
When room temperature decreases to below 10℃, compressor and outdoor fan will stop(indoor fan
is Breeze). Dehumidifying operation will be resumed when room temperature restores to over 13℃.
8.7.4 At dehumidifying mode, the anti-freezing function of the indoor heat exchanger is the same as that
of cooling mode.
8.8 Heating mode
8.8.1 Generally, the 4-way valve is open in heating mode, but it is closed in defrosting mode. 4-way valve
must delay 2 minutes compared with compressor if the compressor changed into non-heating mode
or turned off. 4-way valve doesn't delay in dehumidifying mode.
8.8.2 Generally, the outdoor fan is turned off with the on-off action of compressor in heating mode, except
for the defrosting mode or the end of defrost.
8.8.3 Action of compressor and outdoor fan motor at heating mode: compressor must run for 7 minutes
after starting and then judge temperature. Meanwhile other protections are still valid.
Condition Compressor Outdoor fan
T> Ts+3 Off Off Room temp. up
T<Ts+3 On On
T< Ts+2 On On Room temp. down
T>Ts+2 Off Off
8.8.4 Indoor Fan actions at heating mode
Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, but Anti-cold wind
function prevails.
Anti-cold wind control function at heating mode
Condition
T= Indoor exchanger temp.
Indoor exchanger temp. up
Indoor exchanger temp. down
T<TE1 Off
TE1<T<TE2 Breeze
T>TE2 Setting fan speed
T> TE3 Setting fan speed
TE3<T<TE4 Breeze
T<TE4 Off
8.8.5 Auto wind at heating mode
Condition
T=Indoor Temp.-Setting Temp.
T<2℃ High Room temp. up
T>2℃ Med.
T> 0℃ Med. Room temp. down
T<0℃ High
Indoor fan speed
Indoor fan speed
90
8.8.6 Indoor evaporator high-temperature protection at heating mode
Condition
T= Indoor exchanger temp.
Indoor exchanger temp. up
T<TE8 On On
TE8<T<TE7 On Off
T>TE7 Off Off
T>TE9 Off Off Indoor exchanger temp. down
T<TE9 On On
8.9 Defrosting operation (Available for heating only).
8.9.1 Defrosting condition: Defrosting starts when either of the following ①&②: ① A and B are satisfied:
A: The compressor keeps running for 40 minutes or more.
B: The temperature difference of evaporator and room temperature meets one of the following:
℃
Fan speed is high ≤TH
Fan speed is mid ≤TM
Fan speed is low ≤TL
Breeze Meet only if it is Breeze
Temp. of evaporator---room temp.
Compressor Outdoor fan
DEFROST
DEFROST
DEFROST
② Calculate from the end of latest defrost, evaporator high temp. protection only closes outdoor fan
with the compressor still running. Add up to 90 minutes.
8.9.2 Defrosting time
If the temp. difference condition ① is satisfied for less than 40 minutes, this can be regarded as
severe frosting. The defrosting time is 10 minutes.
If the temp. difference condition ② is satisfied for more than 40 minutes, the defrosting time is 6
minutes.
If the temp. difference condition ① is satisfied out of 40 minutes, generally the defrosting time is 6
minutes, after three continuous 6-minute defrost, the fourth should be 10 minutes defrost. The
If one of following conditions is satisfied, end the defrost and turn into heating mode:
A. The defrost time has reached to 6 or 10 minutes.
B. The compressor current has reached to I
DEFROST
or above, I
DEROST
differs in different models.
91
8.9.4 Defrosting Actions:
45S 25S
Compressor
4-way Valve 23S
40S
Outdoor Fan
Indoor Fan
10S
Defrost 10or 6minutes
8.9.7 Turn into heating mode, turn off the heating mode in 7 minutes.
8.10 Automatic operation mode
8.10.1 The air conditioner automatically selects one of the following operation modes: cooling, heating or
fan only according to the temp. difference between room temp. (TA) and set temp. (TS).
TA—TS Operation mode
TA—TS>2℃ Cooling
-1℃≤TA—TS≤+2℃ Fan-only
TA—TS<-1℃Heating (air-only for cooling only type)
8.10.2 The indoor fan blows automatically in corresponding selected mode.
8.10.3 The motion of indoor fan’s blade should accord with the selected operation mode.
8.11 Forced cooling function
8.11.1 Select forced cooling function with the forced cooling button or the switch.
8.11.2 The compressor is unconditionally turned on, after 30 minutes cooling operation whose fan mode is
set as low, the A/C operates at the DRY mode with a set temp. of 24℃.
8.11.3 All protections of remote control cooling are available at forced cooling operation.
8.12 Forced Auto function
Select forced auto function with the forced auto button or the switch.
In forced auto status the A/C operates at remote control mode with a set temp. of 24℃.
8.13 Timer Function
8.14 Economic Running
8.14.1 The economic running function is available at cooling, heating or auto mode.
8.14.2 Cooling:
The set temperature rise 1℃ per hour. Two hours later, the set temperature will maintain as a
constant and the fan speed is kept at low speed.
8.14.3 Heating:
92
The set temperature decrease 1℃ per hour. Two hours later, the set temperature will maintain as a
constant and the air circulation is kept at low speed (Cold air proof function takes precedence over
all).
8.14.4 Auto:
The economic running function operates in accordance with selected running mode by auto mode.
8.15 Auto restart function
In case of a sudden power failure, this function automatically sets the unit to previous settings before
the power failure when power returns.
93
8.16 Models and Parameters
Model CES-07_RCCES-07_R CES-09_RC CES-09_R CES-12_RCCES-12_R
Note :the chart is the result from the continuous operation under constant air temperature
conditions. however, excludes the initial pull-down stage.
5.2 Heating operation
Indoor air temp.℃
30
20
10
5
-5
-15
Note :the chart is the result from the continuous operation under constant air
temperature conditions. however, excludes the initial pull-down stage.
-15 -5 5 15 25 30
Outdoor unit air temp.
℃
7
6.
Wiring Diagram
6.1 Indoor unit(CES 7 I7, CES 9 I7)
6.2 Indoor unit(CES 12 I7)
8
6.3 Outdoor unit (CES 7 I7 / CES 9 I7 / CES 12 I7)
S
NL
9
7.Troubleshooting
7.1 Indoor Unit Error Display Function
LED4 operation LED2 defrosting LED1 timer LED4 auto
LED2
defrost
X X O ☆ Mold protection
O X X ☆Compressor top protection against temperature
X O X ☆Open or short circuit of outdoor temperature sensor
X O O ☆Over load or too low voltage protection
O O O ☆
O O ☆ ☆Fan speed beyond control
☆ X O ☆ Zero-crossing examination error
☆ O X ☆ Temperature fuse protection
X X ☆ ☆ EEPROM data error
☆ O X ☆ Types doesn't match
☆ ☆ ☆ ☆ Indoor / outdoor units communication protection
LED1
Timer
LED3
Auto
LED4
LED STATUS
operation
Room temperature or evaporator temperature sensor open
or short circuit of
O (on) X (off) ☆ (flash)
7.2.Outdoor Unit Error Self-diagnosis Display
Outdoor Unit Error: if L4 flashes at 1Hz.
Outdoor unit works: L4 on
Outdoor unit Stand by: if L4 flashes at 0.5Hz
10
8 .Electronic Function
8.1 General Protection
8.1.1 Temperature Protection of Compressor Top
8.1.2 3 minutes Delayed Starting Protection of the Compressor
8.1.3 Voltage Protection
8.1.4 The frequency Up-Down speed at which the compressor starts, operates and shuts off will be
subject to the following principles (outdoor chip):
HZ
1HZ/S
92Hz 2HZ/S
57Hz 1HZ/S
1HZ/S
6HZ/S
time
50 Sec
2 min
8.1.5 Frequency Converter Mold Protection (outdoor chip):
The Frequency Converter Mold itself has a protection function against current, voltage and
temperature, if there are 4 times of above mentioned protection functioning within 1 hour (when
the compressor's consecutive operation lasts more than 10 minutes, the fore-mentioned 4
counts will be cleared), the whole machine will shut off and the mold protection gives an alarm.
8.2 Fan-only Mode Function Requirement
8.2.1 The compressor, 4 way valve and outdoor fan are off at Fan-only mode.
8.2.2 Temperature setting function is cancelled, the set temperature can not be displayed, nor
adjusted.
8.2.3 The rotational speed of indoor fan can be optionally chosen by remote control as
High/Mid/Low/Auto.
8.2.4 The indoor fan vanes at Fan-only mode perform the same as those at cooling mode.
11
8.2.5 Performance at Auto mode at Fan-only status is the same as that at Auto mode at cooling status,
provided that the set temperature is 24°c.
°C
27.5 High
27.0
25.5 Mid
25.0
Low
8.3 Cooling Mode Function Requirement
8.3.1 At cooling mode the 4 way valve is off.
8.3.2 Anti-icing Control for Indoor Evaporator
When the temperature of indoor heat exchanger drops to ≤ 4°c, the frequency will reduce one
step down (including F0) and last for 1 minute every time until the temperature is kept between 4
- 7°c. If the temperature rises to ≥ 7°c, the limitation then will be removed.
When the temperature of indoor heat exchanger drops to < 0°c, shut off the compressor and it
will resume when the temperature rises up to > 5°c.
8.3.3 Outdoor Unit Current Control When Cooling:
Shut off the compressor
(10.2A) 8.0 A
frequency down
(8.8A) 6.8 A
frequency unchanged
(7.4A) 5.4 A
resume to normal
Note: The frequency down at the diagram is in accordance with the present frequency dropping
down, to determine every 2 seconds whether the frequency is keeping going down or is
recovering.
12
8.3.4 Indoor fan operates in accordance with the following principles:
8.3.4.1 When indoor fan is in operation, it can be remote controlled to High/Mid/Low/Auto modes.
8.3.4.2 The fan speed at Auto mode in cooling status is subject to the following:
°C room temperature - set temperature
+4.0 High
+3.0
+1.5 Mid
+1.0
Low
8.3.5 Indoor fan vanes at cooling mode will swing in accordance with the following:
When just plugged in for cooling, the vanes will open to the standard angle 50°.
The vane angle can be set by remote control at any angle between 50° and 105° (every setting
can adjust 6°) or set swinging (swinging angle will be 25°).
8.4 Dehumidifying Mode Requirements
8.4.1 At dehumidifying mode, the 4 way valve is shut off
8.4.2 At dehumidifying mode, the indoor fan is fixed in Breeze status and not adjustable.
8.4.3 At dehumidifying mode, the compressor operates in accordance with the following principles:
Room temperature - set temperature
2.5 F3
2.0
1.5 F2
1.0
0.5 F1
0.0
F1
8.4.4 Too-low room temperature protection
During dehumidifying, when room temperature drops down < 10°c, the compressor will shut off,
and when the room temperature rises up than 12°c, the compressor resumes operation.
8.4.5 At dehumidifying mode, the anti-icing function of indoor heat exchanger applies.
13
8.4.6 At dehumidifying mode, the power voltage and outdoor temperature limitation to the highest
frequency when compressor starts and operates is the same as that at cooling mode.
8.5 Heating Mode Function Requirement
8.5.1 At heating mode, the 4 way valve is on, during defrosting operation, it is off.
8.5.2 Outdoor fan usually turns on or off in accordance with the action of compressor, except for
defrosting and ending of the defrost.
8.5.3 Indoor fan action:
Anti-cold air control
Temperature of heat exchanger
37°c
Set rotational speed
34°c
33°c
breeze
18°c
fan off
8.5.4 Indoor fan can be set by remote control to any mode like High/Mid/Low/Auto, however anti-cold
air function comes first.
Auto fan
Room temperature - set temperature
-0.5
Low
-1.0
-1.5 Mid
-2.0
High
14
8.5.5 Outdoor Unit current control when heating
Note:
The frequency in the table
Compressor off
goes down in accordance
(11.5A) 10.0A
with the present frequency,
frequency down
determine every 2 seconds
whether it keeps going
(10.5A) 8.8A
down or it is recovering.
frequency unchanged
(9.2A) 7.4A
8.5.6 Indoor evaporator protection against high temperature
When the temperature of indoor heat exchanger is higher than 53°c, the frequency will reduce one
step and last for 20 seconds every time until the temperature drops down lower than 53°c. If the
temperature drops down < 48°c, the limitation then will be removed (the frequency will not going
down further when reaching 35Hz).
When the temperature of indoor heat exchanger is higher than 63°c, shut off the compressor.
8.5.7 Indoor fan vanes at heating mode will swing in accordance with the following:
When just plugged in for heating, the vanes will open to the standard angle 220°.
The vane angle can be set by remote control at any angle between 0° and 220° (every setting can
adjust 6°) or set swinging (swinging angle will be 25°).
8.5.8 Defrosting operation
8.5.8.1 Defrosting precondition:
Defrosting starts when meeting one of the three conditions:
① The temperature of outdoor heat exchanger remains consecutively lower than 3°c for more than
40 minutes, and the temperature remains consecutively Ti1 for more than 3 minutes.
Model Ti1:
CES 9 I : -4°c
CES 12 I : -6°c
CES 9 I7 : -9°c
CES 9 I7 : -9°c
15
② The temperature of outdoor heat exchanger remains consecutively lower than 3°c for more than
80 minutes, and the temperature remains consecutively Ti2 for more than 3 minutes.
ModelTi2:
CES 9 I :-2°c
CES 12 I :-4°c
CES 9 I7:-7°c
CES 9 I7:-7°c
③ The temperature of outdoor heat exchanger remains consecutively lower than 3°c for more than
120 minutes, and the temperature remains consecutively Ti3 for more than 3 minutes.
ModelTi3:
CES 9 I :-0°c
CES 12 I :-2°c
CES 9 I7:-5°c
CES 9 I7:-5°c
Note: The time period starts to count when outdoor heat exchanger temperature is lower than
3°c, the defrosting operation starts when the exchanger temperature remains lower than the
starting temperatures which are Ti3, Ti2, Ti1.
8.5.8.2 Conditions of defrost ending
Defrosting ends when meeting any of the following three conditions and it turns to normal
heating operation.
① When the temperature of outdoor heat exchanger rises up to 12°c.
② When the temperature of outdoor heat exchanger rises up to 8°c and this continues for more
than 80 seconds.
③ When defrosting action continues for 10 minutes.
8.5.8.3 Defrosting Action
Max 10 mins
30 sec.
ON 10 sec. ON 30 sec
Compressor OFF
ON ON
4 way valve OFF
ON ON
Outdoor fan OFF
ON ON
Indoor fan OFF
The indoor fan operates in anti-
cold air mode when it recovers
16
8.5.9 Set Function Test
When it is detected that the outdoor temperature is between 5 - 9°c and room temperature is
between 18 - 22°c, provided that the heating operation remains consecutively more than 30
minutes, the compressor's highest operational frequency is FMAX=F8=96HZ. If any of the above
conditions is not met, it will quit from set frequency operation.
8.6 Auto Mode Function
Using remote control to choose auto mode, under which the set temperature can be adjusted in a
range of 17 - 30°c.
8.6.1 When entering auto mode, the A/C will choose cooling, heating or fan only according to the
difference between room temperature (TA) and set temperature (TS).
TA - TS Operation status
TA -TS > 1°c Cooling
-1°c ≤TA - TS ≤+1°c Fan only
TA - TS < -1°c Heating
8.6.2 At auto mode, the indoor fan will choose auto fan in corresponding mode.
8.6.3 At auto mode, the vane action of indoor fan is the same as that of chosen mode.
8.6.4 Once a mode is chose, it will take 5 minutes after shutting off the compressor to re-choose
another mode according to the difference between room temperature and set temperature, or
you can re-choose mode when set temperature is changed.
8.7 Forced Operation Function
8.7.1 Forced operation is controlled by the switch on switch board and divided into forced cooling and
forced auto. Remote control doesn't work at forced operation control.
8.7.2 At forced operation status, all protection functions in general protection fore-mentioned apply.
8.7.3 At forced cooling mode, the compressor operates at a fixed frequency of F2=42HZ, indoor fan is
Breeze, anti-icing control and general current control of cooling outdoor unit work; forced
operation will transfer to auto mode whose set temperature is 24°c automatically after 30
minutes.
8.7.4 At forced auto mode, the remote control controls in a set temperature of 24°c.
8.8 Timer Function Requirement
8.8.1 The maximum length of timer is 24 hours and the minimum resolving power is 15 minutes.
8.8.2 Timer on function: first turn off the A/C, the A/C will be automatically on at the set time.
8.8.3 Timer off function: first turn on the A/C, the A/C will be automatically off at the set time.
8.8.4 Timer on/off function( on time is earlier than off time): first turn off the A/C, it will be automatically
on at set time, and later be off at the set time.
8.8.5 Timer off/on function( off time is earlier than on time): first turn on the A/C, it will be automatically
off at set time, and later be on at the set time.
8.8.6 Timer function execution is applicable upon one operation only.
8.8.7 Timer error is less than 1 min/h.
17
INVERTER COMFORT - Multiple
1. Product features 198
2. Specification 199
3. Dimensions 203
4. Refrigeration cycle diagram 204
5. Operation limits 205
6. Capacity table 206
7. Wiring diagram 208
8. Electric control functions 210
197
1.Product Features
Both indoor units can be operated either simultaneously or separately through the utilization of the advanced
converter technique and microcomputer control.
The flowing volume of refrigerant is adjustable through the electronic expansion valve.
High Cooling and Heating capacity is facilitated through the famous-brand frequency converter compressor.
Indoor noise is minimized through the optimization of the air flow system design, a four-folded evaporator and a
big diameter Cross Flow Fan.
The system is operable under low-voltage.
Effective and prompt defrosting correlates into no cold feelings.
High heating effects under extremely low temperatures.
The systems purging function improves the quality of the air in the room.
Wireless remote controlled function:
---A Manual Switch can operate the air conditioner when the remote controller is misplaced and the batteries are
exhausted.
---Horizontal and vertical louvers can swing automatically and the customized setting flows the air as desired.
---Grounding's have been connected and are safe to use.
Outdoor air flow m3/h2500
Outdoor noise level dB(A)60
Outdoor
unit
Refrigerant type R407C g2200
Brand Welling
Input W 148
Capacitor uF3.0
Speed r/min775
Number of rows1.5
Tube pitch(a)x row pitch(b) mm25.4×22
Fin spacing mm1.7
Fin type (code)Hydrophilic aluminium
Tube outside dia.and type mmφ9.53 innergroove trube
Coil length x height x width mm776×660×22
Number of circuits2
2. Nominal heating capacities are based on the following conditions:
Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. Piping: 8m(horizontal)
Liquid side/ Gas side mmФ6.35/Ф9.53Ф6.35/Ф9.53
Max. refrigerant pipe length m101010
Max. difference in level m 5 5 5
14-18 18-24 20-30
3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an
anechoic room.
Model
Type Rotary inverter
Brand GD T oshiba
Capacity Btu/h18000
Input W1690
Rated current(RLA) A11.6
BG240X2CS-20KU
Locked rotor Amp(LRA) A60
Thermal protector Internal
Capacitor uF85UF/250V
Refrigerant oil mlRB68AF/α68TF/T-68 750 ml
Model
Indoor
fan motor
Indoor
coil
201
Brand
Input W
Capacitor uF
Speed(hi/mi/lo) r/min1050/950/7501100/1000/8001060/900/800
Number of rows22
Tube pitch(a)x row pitch(b) mm21×13.3721×13.37
Fin spacing mm1.51.5
Fin type (code)
1.2uF/≥450VAC 1.2uF/≥450VAC 1.5uF/≥450VAC
RPG13H RPG13H RPG13C
Welling Welling Matsushita
36
36
50
2
21×13.37
1.3
Hydrophilic
aluminium
Hydrophilic
aluminium
Hydr0philiC
aluminium
Indoor air flow (Hi/Mi/Lo) m3/h500/410/320520/430/330
Indoor noise level (Hi/Mi/Lo)dB(A)35/32/2636/32/26
Indoor
unit
Tube outside dia.and type mm
Coil length x height x width mm578×252×27.34578×252×27.34
Number of circuits22
Dimension (W*H*D)mm750*250*188 750*250*188 815*280*195
Packing (W*H*D)mm
Net/Gross weight Kg
Model YDK53-6M
φ7, innergroove tubeφ7, innergroove tube
830*336*280 830*336*280 915*360*275
8.5/11 8.5/11 11/14
φ7, innergroove tube
635×315×27.34
2
560/460/380
36/32/26
Outdoor
fan motor
Outdoor
coil
Outdoor air flow m3/h2500
Outdoor noise level dB(A)60
Outdoor
unit
Refrigerant type R407C g2400
Brand Welling
Input W 148
Capacitor uF3.0
Speed r/min775
Number of rows1.5
Tube pitch(a)x row pitch(b) mm25.4×22
Fin spacing mm1.7
Fin type (code)Hydrophilic aluminium
Tube outside dia.and type mmφ9.53 innergroove trube
Coil length x height x width mm776×660×22
Number of circuits2
2. Nominal heating capacities are based on the following conditions:
Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. Piping: 8m(horizontal)
202
Liquid side/ Gas side mmФ6.35/Ф9.53Ф6.35/Ф9.53
Max. refrigerant pipe length m101010
Max. difference in level m 5 5 5
14-18 18-24 20-30
Ф6.35/Ф12.7
3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an
anechoic room.
3 Dimensions
1. Indoor unit 7/9K
2. Indoor Unit 12K
3. Outdoor unit
203
4 Refrigeration Cycle Diagram
Refrigeration circuit drawing of inverter trinary type
indoor unit
heat
exchanger
heat
exchanger
heat
exchanger
filter
filter
filter
filter
capillary
2
3
Refrigeration circuit drawing of inverter binary type
capillary
outdoor unit
up part
down part
condenser
high-pressure
switch 1
4-way
valve
oil separator
inverter compressor
discharge
sensor
low-pressure
switch 2
filter
capillary
low-pressure oil tank
heat
exchanger
heat
exchanger
capillary
2
filter
filter
capillary
3
204
outdoor unit
inverter compressor
high-pressure
switch 1
up part
down part
condenser
4-way
valve
oil separator
discharge
sensor
low-pressure
switch 2
capillary
filter
low-pressure oil tank
5 Operation Limits
5.1 Cooling operation
Outdoor unit air temp.℃
60
50
40
30
20
10
Note :the chart is the result from the continuous operation under constant air temperature
conditions. however, excludes the initial pull-down stage.
10 17 25 30 35 40
Indoor air temp.
℃
5.2 Heating operation
Indoor air temp.℃
30
20
10
5
-5
-15
Note :the chart is the result from the continuous operation under constant air
205
Outdoor unit air temp.
-15 -5 5 15 25 30
℃
temperature conditions. however, excludes the initial pull-down stage.
6 Capacity Table
6.1 Capacity table of Inverter Comfort Binary type
Indoor units can be combined by
7000Btu/h+9000 Btu/h;
7000Btu/h+12000 Btu/h
9000Btu/h+9000 Btu/h
9000Btu/h+12000 Btu/h
12000Btu/h+12000 Btu/h
Cooling
Indoor unit a (W) Indoor unit b (W)
7000Btu/h 2800
6.2 Capacity table of Inverter Comfort Trinary type
Indoor units can be combined by
7000Btu/h*2+9000 Btu/h;
7000Btu/h*2+12000 Btu/h
7000Btu/h*3
9000Btu/h*2+7000 Btu/h
9000Btu/h*2+12000 Btu/h
9000Btu/h*3
12000Btu/h*2+7000 Btu/h
206
12000Btu/h*2+9000 Btu/h
7000Btu/h+9000Btu/h+12000 Btu/h
Cooling
Indoor unit a (W) Indoor unit b (W) Indoor unit c (W)
The control system adopts modular design, that is, all indoor units communicate with outdoor units, ref. to the
following figures for the control structure between indoor units and outdoor units. In the structure, the indoor control
board receives the information from users (for exam. set temp., fan speed etc.) and environment (ex, indoor coil
temp., indoor temp. etc.) ,and organize it to control the action of relevant parts, then transmits the signals to outdoor
control board through the following communication circuit. Outdoor control board can deal with the information
from indoor unit and figure out the best running mode, then transfer the instruction to indoor units to carry out it.
Indoor unit receive the user’s remote control signals.
Indoor unit Outdoor unit
T
T1、T2、Ts T3、 T4、T3
Fan Speed Pressure switch
Pressureswitch
z When AC voltage ≤ 260V for 30 seconds, Outdoor Unit resumes operation.
z When AC voltage ≥ 270V for 30 seconds, Outdoor Unit stops operation and alarms.
8.2.2 AC Amp Protection
The outdoor control board checks the compressor current and do over-current protection.
If the compressor current is over the scheduled value, the system will stop and all indoor units will display
malfunction code.
Note: 1. In order to prev ent prot ection due to too big LRA when compressor starts, the outdoor control board begins
to check the compressor current after 10 seconds.
2. If current protection happens, the compressor will stop and restart 3 minutes later.
8.2.3 High-pressure Protection and Low-pressure Protection
211
The High-pressure switch and Low-pressure switch are installed at suction pipe and discharge pipe separately. And
users can select to install. Normally, the high-pressure switch is cut down when higher than
425Psi (3.3Mpa Cut
down, 2.4Mpa Resume). While the low-pressure switch is cut down when lower than 7Psi (0.05Mpa
On, 0.15Mpa Resume).
Under high-pressure protection or low-pressure protection, the compressor will stop and restart 3
minutes later.
8.2.4 Outdoor Unit communication protection
8.2.4.1 Communication protection between indoor unit and outdoor system chip
If the outdoor unit can’t receive the indoor signal for 30 seconds, then the indoor units are judged as no starting and
there is no alarm signal. If the indoor units send signal to system chip for 2 minutes and no feedback signal is
received, then judge as communication malfunction.
8.2.4.2 Communication protection between outdoor system chip and inverter chip
If can’t receive signal or receive wrong signal for over 2 minutes, Indoor/Outdoor Unit stops operation. When the
signal is right, Indoor/Outdoor Unit restarts.
8.2.5 Outdoor condenser high temperature protection
Under cooling mode, if
T3〉65℃ for 3 minutes, the compressor will stop. When T3〈52℃, the protection
is not valid.
When protection is released, the compressor restarts 3 minutes later.
8.2.6 Temperature Sensor short/open protection
When the outdoor condenser pipe temperature T3, outdoor ambient temperature T4, indoor evaporator outlet
temperature
T2B are checked out of range 0.05~4.95V, it think temperature sensor short/open
protection. The compressor, four-way valve and outdoor fan motor will stop and send malfunction
signal to indoor units.
When the volt is resumed to the range 0.05~4.95V, then resume signal to indoor units and control
on-off of the compressor, four-way valve and outdoor fan motor by indoor size.
8.2.7 Outdoor low temperature protection
If the outdoor temperature is lower than -15℃ for 1hour, the compressor and fan motor will stop. And
any operation is not valid.
If the outdoor temperature is higher than -12℃ for 10 minutes and the compressor stops operation
for 1h, or the outdoor temperature is higher than 5℃ for 10 minutes, then restart and enter into the
prior operation mode.
If any indoor unit sends out this protection request, the outdoor unit will stop compressor until all
indoor units have not this protection request.
8.2.8 Compressor pre-heating function
When the outdoor temperature is lower than 3℃ and the compressor stops operation for more than 3
hours, or the outdoor temperature is lower than 3℃ and the power is just put on, the compressor
enters into pre-heating condition.
8.3 Display function
212
8.3.1 Checking function
The indoor and outdoor operation condition can be examined by check button.
Normal display Operation mode Capacity request Number of indoor units ambient temp.
Outdoor air flow m3/h 1500 1500 1800 1800 1900 1900
Outdoor noise level dB(A) 49 49 50 50 52 52
Outdoor unit
Refrigerant type R410A g 800 820 900 920 1160 1170
Design pressure MPa 4.2 4.2 4.2 4.2 4.2 4.2
Refrigerant piping
Connection wiring No No No No No No
Plug type 16A 16A 16A 16A 16A 16A
Thermostat type Electrolic control Electrolic control Electrolic control Electrolic control Elec trolic control Electrolic control
Operation temp
Ambient temp
Application area m2 10-14 10-14 14-21 14-21 18-26 18-26
Capacity Btu/h 7000 7000 9000 9000 12000 12000
Input W 640 640 820 820 1120 1120
Rated current A 2.8 2.8 3.6 3.6 5.0 5.0
EER
Capacity Btu/h 8500
Input W 690
Rated current A 3.0
COP W/W 3.6
Model PA82X1C-4DZ2 PA82X1C-4DZ2 PA108X1C-4FT PA108X1C-4FT PA145X2C-4FT PA145X2C-4FT
Type Rotary Rotary Rotary Rotary rotary rotary
Capacity Btu/h 6680 6680 8870 8870 12000 12000
Input W 675 675 890 890 1200 1200
Rated current(RLA) A 3.11 3.11 4.07 4.07 5.6 5.6
Locked rotor Am p(LRA) A 15.0 15.0 21.7 21.7 29.9 29.9
Thermal protector UP3QE0591-T71 UP3QE0591-T71 UP3QE0591-T61 UP3QE0591-T61 UP3RE0591-T56 UP3RE0591-T56
Capacitor uF 25 25 25 25 35 35
Refrigerant oil ml 350 350 330 330 480 480
Model RPG13H RPG13H RPG13H RPG13H RPG20D RPG20D
Input W 36.5 36.5 36.5 36.5 51.5 51.5
Capacitor uF 1.2 1.2 1.2 1.2 1.5 1.5
Speed(hi/mi/lo) r/min 1050/9200/820 1050/9200/820 1200/950/850 1200/950/850 1250/1000/800 1250/1000/800
Number of rows 2 2 2 2 2 2
Fin type (code) Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium
Tube outside dia.and type mm φ7, innergroove tube
Number of circuits 2 2 2 2 2 2
Dimension (W*H*D) mm 750*250*205 750*250*205 750*250*205 750*250*205 815*280*215 815*280*215
Packing (W*H*D) mm 830X285X 335 830X285X335 830X285X335 830X285X335 915X290X360 915X290X360
Net/Gross weight Kg 8/10 8/10 8/10 8/10 10/12 10/12
Model YDK24-6T YDK24-6T YDK24-6F YDK24-6F YDK36-6 YDK36-6
Input W 56 56 56 56 68 68
Capacitor uF 2.5 2.5 2.5 2.5 2.5 2.5
Speed r/m in 800 800 800 800 900 900
Number of rows 2 2 2 2 2 2
Fin type (code) Unhydrophilic aluminium Hydrophilic aluminium
Tube outside dia.and type mm Ф7,innergroove tube Ф7,innergroove tube Ф7,innergroove tube Ф7,innergroove tube
Coil length x height x width mm 750x508x26.74 750x508x26.74 810x508x26.74 810x508x26.74 680x550x44 680x550x 44
Number of circuits 2 2 2 2 2 2
Dimension(W*H*D) mm 700X535X235 700X535X235 780X540X250 780X540X250 760X590X285 760X590X285
Packing (W*H*D) mm 815X580X325 815X580X325 910X575X335 910X575X335 890X655X360 890X655X360
Net/Gross weight Kg 31/34 32/35 36/39 37/40 41/45 41.5/45.5
Liquid side/ Gas side mm(inch) Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф12.7 Ф6.35/Ф12.7