Admiral R407C, R22 Diagram

Air-Conditioning of the future
Service Manual
Residential A/Cs
CONTENTS
Please find CAS, CAD, CAM (R or I), CMP, etc.. in separate papers!
1. DIAGNOSTIC CHART 1
2. The service rules of the R407C(R410a) product 5
3. MAS 8
4. MES 45
5. CES/CED/CEM 65
6. GES 97
7. GIS 115
8. LIS 127
9. CUS 139
10. BES 157
11. CES I 178
12.
CED I & CEM I
197
Diagnostic Chart(5000Btu/h-12000Btu/h)
1. Self-diagnose the failure COOLWEX units have self-diagnose function. Note: for the following series
CES CED CEM
2. After energizing, no indicator is lighted and the air conditioner can’t be operated.
After energizing, the air conditioner can’t be operated
Check if AC220V power supply outputs to Indoor PCB.
Yes
Check if AC220V exists at the primary coil of transformer.
Yes No
Indoor PCB is defective Or current fuse is melt.
Check if AC14.5V exists at the secondary coil of transformer.
Take off the secondary plug of transformer, and then check if AC14.5V exists at the secondary coil of transformer.
No Yes
Yes
No
The transformer is defective. Indoor PCB is defective
3. Resetting phenomenon often occurs during operation. (That is automatically entering to
the status when power is on.) The reason is that the instantaneous voltage of main chip is less than 4.5V. Check according to the following procedure:
Resetting phenomenon often occurs during operation.
After changing Indoor PCB, check if the failure releases.
No Yes
After changing indoor fan motor, check if the failure releases.
Power supply circuit has problems.
No
Indoor PCB is defective
1
A
4.
Failure phenomenon for cooling only type
Failure phenomenon Operation lamp Timer lamp Indoor fan speed has been out of control for over 1 minute Indoor room temp. or evaporator sensor is open circuit or short circuit Over current protection of the compressor occurs 4 times X EEPROM error On
r Extinguish
Flash at 5Hz
☆ ☆
4.1 Operation lamp flashes and Timer lamp off.
Operation lamp flashes and Timer lamp off.
Yes
Change the main control board
4.2 Operation lamp flashes and Timer lamp on.
Is connection to connector good?
yes No
Replace the sensor
Repair connector
4.3 Operation lamp off and Timer lamp flashes
Operation lamp off and Timer lamp flashes
fter changing the main control board, check if the failure releases.
No Yes
The voltage of power supply is too low (less than 187V)?
Indoor PCB is defective
Yes No
Power supply fault Outdoor unit fault (such as the compressor)
4.4 Operation lamp on and Timer lamp flashes EEPROM error, indoor PCB is defective.
X
On
☆ ☆
2
A
5.
Failure phenomenon(heat pump)
Failure phenomenon Operation lamp Timer lamp Defrosting lamp Over current protection of the compressor occurs 4 times Indoor fan speed has been out of control for over 1 minute No over-zero signal Temp. sensor on indoor evaporator is open circuit or short circuit Indoor room temp. sensor is open circuit or short circuit X EEPROM error On
X
X X
X
☆ ☆
X X
r Extinguish
Flash at 5Hz
5.1 Operation lamp flashes ,Timer lamp off and Defrosting lamp flashes.
Operation lamp flashes ,Timer lamp off and Defrosting lamp flashes
fter changing the main control board, check if the failure releases.
No Yes
The voltage of power supply is too low (less than 187V)?
Indoor PCB is defective
Yes No
Power supply fault Outdoor unit fault (such as the compressor)
5.2 Operation lamp off, Timer lamp flashes and Defrosting lamp flashes.
Is connector connection good?
No Yes
Is voltage being applied to the fan motor?
Yes No
Repair the connector
Fan motor is defective
Indoor PCB is defective
5.3 Operation lamp flashes, Timer lamp flashes and Defrosting lamp flashes . This is alarm signal when the main chip can’t detect over-zero signal. When such failure occurs, the main control board must have fault.
3
Operation lamp flashes and Timer lamp off.
Yes
Change the main control board
5.4 Operation lamp off ,Timer lamp off and Defrosting lamp flashes.
Is connection to connector good?
yes No
Replace the sensor
Repair connector
5.5 Operation lamp off, Timer lamp flashes and Defrosting lamp off
Is connection to connector good?
yes No
Replace the sensor
Repair connector
5.6 Operation lamp on, Timer lamp flashes and Defrosting lamp off
EEPROM error, main PCB has fault.
Temporarily turn off the power supply and turn it on again in about 1 minutes
Does the trouble occur again?
Yes
Replace the indoor PCB
4
The service rules of the R407C product
The service rules of the R410A product
1. The service rules of the new refrigerant R407C product
COOLWEX uses the green refrigerant R407C firstly in China. Its thermal characters are similar to R22, but there is little difference between them.
1.1 The main difference between R407C and R22:
R407C R22 Component HFC32/125/134a HCFC22 The ratio of mix Wt 23/25/52 100 The saturation liquid density Kg/m
3
1136 1191 Normal pressure kj/kg.k 0.835 0.622 Specific heat The saturation liquid kj/kg.k 1.554 1.256
Evaporating pressure kpa 499 498 Condensing pressure kpa 2112 1943 Temperature slippage 4.3-7.1 0 Heating capacity w 92-97 100 Input power w 106 100 COP 97 100 The consistent with the oil Fat oil Mineral oil
1.2 Service precautions:
1.2.1 Because R407C is a mixture composed of three kinds of matter, when vapor phase and liquid phase coexist, the component of the vapor phase is different from the liquid phase. When we fill the refrigerant, we must ensure to fill it in liquid phase, in order to maintain the stability of the character.
1.2.2 The leakage of the refrigerant is from vapor side or liquid side, and the leakage from vapor side could make the component change and impact the character seriously. So when the amount of the leakage is up to 5%, we need discharge all refrigerant in the system, and fill liquid refrigerant according to amount in nameplate.
1.2.3 Because the lubricant fit for refrigerant R407C is ester refrigerating engine oil (POE) or ether refrigerating engine oil (PVE). The mineral lubricant fit for refrigerant CFC and HCFC is weak in consistent with the HFC, and it doesn’t fit for the refrigerant HFC. So when the compressor using new refrigerant R407C is worn out, to replace it by compressor of CFC or HCFC is forbidden.
1.2.4 When the connection of the refrigerant pipe is finished, before the system start up we should vacuum the indoor unit by cut-off valve or discharge the indoor unit air by refrigerant R407C bottle. Discharged the air in system by outdoor unit refrigerant is forbidden.
1.2.5 Ester oil could adsorb the water in the air. In order to removemoisture in refrigeration system, avoid capillary jammed by ice and the ester lubricant oil decomposed with water, we use desiccant in system. Artificial zeolite (molecular sieve R etc.) is the effective water sorbent. Toavoid absorb refrigerant but only absorbmoisture, we use the molecular sieve whose aperture is smaller than the molecule of the refrigerant. For R407C we should adopt XH-11 rather than XH-9AK and 4A-NRG.
1.2.6 Because the corrosion of R407C and POE to high molecular material is different from R22 and mineral oil, the airproof material inside high/low pressure valve and foul-way valve needs to be changed in refrigeration system, such as R407C, polyurethane rubber etc. The high/low pressure valve and four-way valve which are fit for R22 couldn’t be used in service.
1.2.7 When there is leakage, filling with other kind of refrigerant is forbidden.
1.2.8 When we need to vacuum the system, we should use the special quick joint, but use the quick joint of other refrigerant is forbidden lest pollute by mixing refrigerant. The time for vacuuming is
5
about 30 minutes, and vacuity is less than 133Pa.
1.3 Precautions:
1.3.1 Regulations
Being liquefied vapor, R-407C and R-410A are high-pressure vapor , the high-pressure gas regulation is applicable. Before use it, please refer to high-pressure gas regulation. To prevent the high-pressure vapor from causing damage, the regulation should be followed.
1.3.2 Usage of vessel Being high-pressure vapor, R-407C and R-410A are contained in high-pressure vessel. The safety condition of vessel is good, but if you don’t use it carefully, you may damage the vessel and cause accident.
1.3.3 Storage Although R-407C and R-410A are nonflammable, when they are stored with the normal high-pressure gas, we should place them in the good ventilation area. In addition, there are safe devices in the high-pressure vessel. Please note that when the temperature (fusible valve) or pressure (spring safe valve) is up to a certain value, it will eject vapor.
1.3.4 Ventilation Because R-407C and R-410A are heavier then air, they will go down. If room is full of the leakage vapor, the density of oxygen will decrease, and cause people suffocated. In addition, if you light the fire when there is R-407C in the air, it will produce the toxic gas with pungent odor and corrosiveness.
1.3.5 Precautions about health For R-407C, R-410A and normal liquefied high-pressure vapor, please don’t contact with skin directly, and prevent being splashed into eyes and avoid drinking.
1.3.6 The following are the urgent disposal methods: Splash into eyes: Wash eyes with pure water for more than 15 minutes, and don’t knead the eyes or blink. Please wash eyes with watery boric acid water if the ache gets heavy. To avoid the accident, please ensure that you wear the protection glasses. Contact with skin directly The temperature will decrease rapidly by evaporation if R-407C and R-410A expose to air in liquid phase. So if the liquid contacts with skin directly, it may cause frostbite. If there are freeze burns, please go to see the doctor immediately.
2. The service rules of the R410A product
2.1 There are some differences between air conditioner of R410A s and that of R22:
2.1.1 The compressor used is different, it is a new refrigerant compressor (special);
2.1.2 The air conditioner of new refrigerant R410A has a drier, while the A/C of R22 doesn’t have.
2.1.3 There is no difference between the evaporator, condenser and system pipe of new refrigerant R410A A/C and that of R22 A/C in appearance. The requirement of new refrigerant R410A A/C for craft is higher , and the amount of moisture and impurity in the system is less than that of A/C using R22. The resistance to pressure is higher.
2.1.4 The manufacture process is different, the requirement of air conditioner using R410A for craft is high.
2.2 Refrigerant system:
2.2.1 The high pressure of refrigerant system is 3.0 Mpa, and the low pressure is 1.2 Mpa. (The value is 1.5 times more than that of R22 under the same condition)
2.2.2 When installing the split type of new refrigerant R410A, all connecting pipes must be special pipes of R410A. Discharging air must use refrigerant R410A, and couldn’t misuse the connecting pipe and refrigerant of A/C using R22. Otherwise, it will destroy the stability of A/C.
2.2.3 Because the compressor of refrigerant R410A split type uses POE oil, which can react with moisture to form water and acid. The water produced by reaction could react further, and if the
6
chain reaction proceeds continually , the water in the system will be more and more. It will cause the capillary ice blocking; at the same time, acidity of working substance circulated in the system will be higher and higher (the value of PH is lower and lower), and it may corrode the components and parts in the system. The phenomenon of copperizing would happen. When installing A/C, the action should be prompt, and after opening the plug of connecting pipe we must tighten the nut in 5 minutes. The time of discharging air should be enough. When installing A/C, the sweat drops into the connecting pipe is forbidden; the infusible impurity mixed in the system is forbidden. It is better to install the A/C of refrigerant R410A split type in fine weather, do not do it in rainy day, nor humid weather.
2.2.4 The chlorine ion could react with POE oil to form acid, and the acid corrodes the components and parts of refrigerant system. So pollute the system with chlorine ion in installation is forbidden, such as sweat beads and other impurities that contain chlorine ion.
2.2.5 Whatever the reason we must change the drier, if the refrigerant system is exscinded in service, after we exscind the refrigerant system, we must use something to wrap the fracture lest the moisture in air enters into the system. The time that refrigerant system expose to air should be less than 5 minutes.
2.2.6 Must weld the drier into system in 5 minutes in order to isolate the air when changing it. Otherwise it will influence the performance of the drier.
2.2.7 Must use special pump after service. The lubricant should be the grease. The pump couldn’t be used to vacuum the A/C of refrigerant R22, otherwise it would cause the contamination of refrigerant, and influence the performance of A/C. The time of vacuuming must be over 25 minutes, Otherwise the moisture in system will be too high, and affect the stability of A/C.
2.2.8 If need to change the components and parts, must use the special one of R410A in service. Using the components and parts of R22 is forbidden; otherwise it would affect the stability of A/C.
The refrigerant R410A should be placed in environment under 30. If the refrigerant has been placed in environment above 30, it is necessary to store the refrigerant in the environment below 30 for more than 24 hours. Otherwise the component of refrigerant would be changed and it affects the performance of A/C.
7
CES, CED & CEM
1. Features 66
2. Specification 67
3. Dimensions 73
4. Refrigeration cycle diagram 77
5. Operation limits 78
6. Wiring diagram 79
7. Troubleshooting 86
8. Electronic function 86
1.Features
1.1 Compact design
1.2 High efficiency and quiet operation
66
2.Specification
Model CES-05.R.....................CES-07.R.........................CES-07.RC...................CES-09.R....................CES-09.RC
Power supply Ph-V-Hz 220-240V~,50Hz 220-240V~,50Hz 220-240V~,50Hz 220-240V~,50Hz 220-240V~,50Hz
Capacity Btu/h 5000 7000 7000 9000 9000
Cooling
Heating
Moisture Removal L/h 0.6 0.8 0.8 1 1
Max. input consumption W 800 1050 1050 1300 1300
Max. current A 3.8 5 5 7 7
Starting current A 16 18 18 25 25
Compressor
Indoor fan motor
Indoor air flow (Hi/Mi/Lo) m3/h 300/270/240 380/350/320 380/350/320 450/420/ 390 450/420/390
Indoor noise level (Hi/Mi/Lo) dB(A) 32/28/25 32/28/25 32/28/25 33/31/27 33/31/27
Indoor unit
Outdoor fan motor
Outdoor air flow m3/h 1400 1400 1400 1500 1500
Outdoor noise level dB(A) 49 49 49 49 49
Outdoor unit
Refrigerant type R22 g 480 620 580 650 580 Design pressure MPa 2.6 2.6 2.6 2.6
Refrigerant piping
Connection wiring No No No No No Plug type 10A 10A 10A 10A 10A Thermostat type Electronic control Electronic control Electronic control Electronic control Electronic control Operation temp 17-30 17-30 17-30 17-30 17-30 Ambient temp 18-45 -7-45 18-45 -7-45 18-45 Application area m2 8-12 10--14 10-14 14-21 14-21
Input W 560 760 760 1000 1000
Rated current A 2.6 3.6 3.6 4.5 4.5
EER Btu/w.h 8.6 8.8 8.8 9 9
Capacity Btu/h 7600 10000
Input W 760 980
Rated current A 3.4 4.4
COP w/w 2.9 3.0
Model KH104VFHC 2P14C235ANA 2P14C235ANA PH170X1C-4DZ2 PH170X1C-4DZ2 Type Rotary Rotary Rotary Rotary Rotary Brand SHANGHAI SENLIN GD Matsushita GD Matsushita GD Toshiba GD Toshiba
Capacity Btu/h 5700 7500 7500 10000 10000
Input W 590 725 725 970 970
Rated current(RLA) A 2.7 3.4 3.4 4.5 4.5
Locked rotor Amp(LRA) A 13 15 15 24 24 Thermal protector BF540-KB MRA98854 MRA98854 UP3QE0591-T61 UP3QE0591-T61(int
Capacitor uF 15 25 25 25 25
Refri
gerant oil ml MS-56 270 AT OMOS M60 270 ATOMOS M60 270 SUNISO 350 SUNISO 350
Model RPG13H RPG13H RPG13H RPG 13H RPG13H Brand WELLING WELLING WELLING W ELLING WELLING
Input W 36.5 36.5 36.5 36.5 36.5
Capacitor uF 1.2µF/450V 1.2µF/450V 1.2µF/450V 1.2µF/450V 1. 2µF/450V
peed(hi/mi/lo) r/min 1020/ 960/ 900 1020/ 960/ 900 1020/ 960/ 900 1100/1020/950 1100/1020/950
S
Dimension (W*H*D) mm 750×250×188 750×250×188 750×250×188 750×250×188 750×250×188
Packing (W*H*D) mm 830X336X280 830X336X280 830X336X280 830X336X280 830X336X280
Net/Gross wei Model YDK24-6T YDK24-6T YDK24-6T YDK24-6T YDK24-6T Brand WELLING WELLING WELLING W ELLING WELLING
Input W 70 70 70 70 70
Capacitor uF 3 3 3 3 3
peed r/min 850 850 850 850 850
S
Dimension(W*H*D) mm 700×535×235 700×535×235 700×535×235 700×535×235 700×535×235
Packing (W*H*D) mm 815×580×325 815×580×325 815×580×325 815×580×325 815×580×325
Net/Gross wei
Liquid side/ Gas side mm(inch) Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф9.53
Max. refr igerant pipe length m 10 10 10 10 10
Max. difference in level m 5 5 5 5 5
ght Kg 8/9.5 8.5/10 8.5/10 8. 5/10 8.5/10
ght Kg 26/29 28/31 27/30 30/33 29/32
1 The noise date is base on anechoic chamber, during actual operation, these values are normally somewhat different as a result of ambient condition.
67
Model CES-12.RC CES-12.R CES-18.RC CES-18.R
Power supply Ph-V-Hz 220-240V,50HZ 220-240V,50HZ 220-240V~,50Hz 220-240V~,50Hz
Capacity Btu/h 12000 12000 18000 18000
Cooling
Heating
Moisture Removal L/h 1.2 1.2 1.5 1.5
Max. input consumption W 1650 1690 2040 2080
Compressor
Indoor fan motor
Indoor air flow (Hi/Mi/Lo) m3/h 550 550 750/710/650 750/710/650
Indoor noise level (Hi/Mi/Lo) dB(A) 36/33/30 36/33/30 41/38/35 41/38/35
Indoor unit
Outdoor fan motor
Outdoor noise level dB(A) 51 51 53 53
Outdoor unit
Refrigerant type g R22/750 R22/820 1110 1370
Design pressure MPa 2.6 2.6 2.6 2.6
Refrigerant piping
Plug type 16A 16A 15 15
Application area m2 18-26 18-26 25-35 25-35
1 The noise date is base on anechoic chamber, during actual operation, these values are normally somewhat different as a result of ambient condition.
Input W 1230 1230 18000 18000
Rated current A 5.7 5.7 1820 1800
EER Btu/w.h 9.8 9.8 8.5 8.4
Capacity Btu/h 13000 10.0,2.9
Input W 1290 19000
Rated current A 6 1800
COP w/w 3.0 3.1
Model PH200X2C-8FTC PH225X2C-4FT PH290X2C-4FT1 PH290X2C-4FT1
Capacity Btu/h 11840 13610 17435 17435
Input W 1135 1305 1670 1670
Rated current(RLA) A 5.2 6.1 8.0 8.0
Locked rotor Amp(LRA) A 26 41.2 41.2
Thermal protector Internal External Internal Internal
Capacitor uF 25 35 35 35
Refrigerant oil ml 440 430 520 520
Input W 36.5 36.5 53 53
Capacitor uF 1.2 1.2 1.5uF/450V 1.5uF/450V
Speed(hi/mi/lo) r/min 1350 1350 1180 1180
Dimension (W*H*D) mm 750X250X188 750X250X188 906×286×235 906×286×235
Packing (W*H*D) mm 830X336X280 830X336X280 1020X380X328 1020X 380X328
Net/Gross weight Kg 8.5/10 8.5/10 13.5/16.5 13.5/16.5
Input W 70 70 96 96
Capacitor uF 2.5 2.5 2.5µF/450V 2.5µF/450V
Dimension(W*H*D) mm 780X540X250 780X540X250 780X540X250 780X540X250
Packing (W*H*D) mm 910X575X335 910X 575X335 910X575X335 910X575X335
Net/Gross weight Kg 34/37 36/39 43/47 44/48
Liquid side/ Vapor side mm(inch) Ф6.35/Ф12.7 Ф6.35/Ф12.7 Ф6.35/Ф12.7 Ф6. 35/Ф12.7
Max. refrigerant pipe length m 10 10 15 15
Max. difference in level m 5 5 8 8
68
Model
Power supply Ph-V-Hz 220-240V~,50Hz 220-240V~,50Hz
Capacity Btu/h 21000 21000
Cooling
Heating
Moisture Removal L/h 2.0 2.0
Max. input consumption W 2500 2600
Max. current A 11.3 14.5
Starting current A 42 42
Compressor
Indoor fan motor
Indoor air flow (Hi/Mi/Lo) m3/h 920\760\700 920\760\700
Indoor noise level (Hi/Mi/Lo) dB(A) 41/37/33 41/37/33
Indoor unit
Outdoor fan motor
Outdoor air flow m3/h 2600 2600
Outdoor noise level dB(A) 53 53
Outdoor unit
Refrigerant type R22 g 1220 1740
Design pressure MPa 2.6 2.6
Refrigerant piping
Thermostat type Electronic control Electronic control
Operation temp
Ambient temp
Application area m2 34-49 34-49
Input W 2300 2300
Rated current A 10.5 10.5
EER Btu/w.h 9.1 9.1
Capacity Btu/h 23500
Input W 2400
Rated current A 11.0
COP w/w 2.9
Model 2V36S225AUD 2V36S225AUD
Type rotary rotary
Capacity Btu/h 20600 20600
Input W 2010 2010
Rated current(RLA) A
Locked rotor Amp(LRA) A 42 42
Thermal protector INNER INNER
Capacitor uF 50 50
Refrigerant oil ml 680 680
Model RPG25 RPG25
Brand WELLING WELLING
Input W 53 53
Capacitor uF 1.5uF/450V 1.5uF/450V
Speed(hi/mi/lo) r/min 1325 1325
Dimension (W*H*D) mm 906×286×235 906×286×235
Packing (W*H*D) mm 1020X380X328 1020X380X328
Net/Gross weight Kg 13.5/16.5 13.5/16.5
Model YDK53-6 YDK53-6
Input W 100 100
Capacitor uF
Speed r/min 640 640
Dimension(W*H*D) mm 845×695×335 845×695×335
Packing (W*H*D) mm 970×770×395 970×770×395
Net/Gross weight Kg 52/57 55/60
Liquid side/ Gas side mm(inch)
Max. refrigerant pipe length m 15 15
Max. difference in level m 8 8
1 The noise date is base on anechoic chamber, during actual operation, these values are normally somewhat different as a result of ambient condition.
CES-21.RC CES-21.R
95 95
2.5μF/450V 2.5μF/450V
Ф6.35/Ф12.7 Ф6.35/Ф12.7
℃ ℃
17-30 17-30
10-43 (-5~43)
69
Comfort
Model CES-07_R7______________CES-07_R7C____________CES-09_R7_________CES-09_R7C
Power supply Ph-V-Hz 220-240V~,50Hz 220-240V~,50Hz 220-240V~,50Hz 220-240V~,50Hz
Capacity Btu/h 7000 7000 9000 9000
Cooling
Heating
Moisture Removal L/h 0.6 0.6 0.8 0.8
Max. input consumption W 1000 1000 1330 1330
Max. current A 4.4 4.4 6 6
Compressor
Indoor fan motor
Indoor air flow (Hi/Mi/Lo) m3/h 430/400/370 430/400/370 470/440/410 470/440/410
Indoor noise level (Hi/Mi/Lo) dB(A) 35/32/30 35/32/30 36/32/30 36/32/30
Indoor unit
Outdoor fan
motor
Outdoor air flow m3/h 1600 1600 1900 1600
Outdoor noise level dB(A) 49 49 49 49
Outdoor unit
Refrigerant type R407C g 740 650 840 770
Design pressure MPa 2.8 2.8 2.8 2.8
Refrigerant
piping
Operation temp 17 30 17 30 17 30 17 30 Ambient temp -7-45 18-45 -7-45 18-45 Application area m2 10-14 10-14 14-21 14-21
Input W 800 800 1050 1050
Rated current A 3.5 3.5 4.6 4.6
EER Btu/w.h 8.8 8.8 8.6 8.6
Capacity Btu/h 8500 10000
Input W 880 1050
Rated current A 4 4.6
COP w/w 2.9 2.93
Model PG135X1C-4DZ2 PG135X1C-4DZ2 PG180X1C-4DZ3 PG180X1C-4DZ3 Type Rotary Rotary Rotary Rotary Brand TOSHIBA TOSHIBA TOSHIBA TOSHIBA
Capacity Btu/h 8086/8172 8086/8172 10800 10800
Input W 765/785 765/785 1015 1015
Rated current(RLA) A 3.52/3.34 3.52/3.34 4.5 4.5 Locked rotor Amp(LRA) A Thermal protector UP3SE0591-T71 UP3SE0591-T71 UP3SE0591-T61 UP3SE0591-T61
Capacitor uF 25 25 30 30
Refrigerant oil ml 400 400 400 400 Model RPG13H RPG13H RPG13H RPG13H
Input W 36.5 37.5 38.5 39.5
Capacitor uF 1.2 1.2 1.2 1.2
Speed(hi/mi/lo) r/min 1020/960/900 1020/960/900 1100/1020/950 1100/1020/950
Dimension (W*H*D) mm 750×250×188 750×250×188 750×250×188 750×250×188
Packing (W*H*D) mm 830×336×280 830×336×280 830×336×280 830×336×280
Net/Gross weight Kg 8.5/10.5 8.5/10.5 8.5/10.5 8.5/10.5 Model YDK24-6T YDK24-6T YDK24-6T YDK24-6T
Input W 70 70 70 70
Capacitor uF 3 3 3 3
Speed r/min 850 850 850 850
Dimension(W*H*D) mm 700X535X235 700X535X235 700X535X235 700X535X235
Packing (W*H*D) mm 815X580X325 815X580X325 815X580X325 815X580X325
Net/Gross weight Kg 30/33 29/32 29/32 30/33
Liquid side/ Gas side mm(inch Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф9.53
Max. refrigerant pipe length m 10 10 10 10
Max. difference in level m 5 5 5 5
1 The noise date is base on anechoic chamber, during actual operation, these values are normally somewhat different as a result of ambient condition.
70
Model CES-12_R7C____________________________CES-12_R7
Power supply Ph-V-Hz 1, 220-240V~, 50Hz 1, 220-240V~, 50Hz
Capacity Btu/h 12000 12000
Cooling
Heating
Moisture Removal L/h 1.2 1.2
Max. input consumption W 1800 1800
Max. current A 7.8 7.8
Starting current A
Compressor
Indoor fan motor
Indoor air flow (Hi/Mi/Lo) m3/h 620/550/520 620/550/520
Indoor noise level (Hi/Mi/Lo) dB(A) 37/34/31 37/34/31
Indoor unit
Outdoor fan motor
Outdoor air flow m3/h 1900 1900
Outdoor noise level dB(A) 54 54
Outdoor unit
Refrigerant type R407C g 830 1150
Design pressure MPa 2.8 2.8
Refrigerant piping
Plug type 16A 16A
Thermostat type Electronic control Electr onic control
Operation temp
Ambient temp
Application area m2 18-26 18-26
1 The noise date is base on anechoic chamber, during actual operation, these values are normally somewhat different as a result of ambient condition.
Input W 1320 1320
Rated current A 5.8 5.8
EER Btu/w.h 9.1 9.1
Capacity Btu/h 14000
Input W 1360
Rated current A 6
COP w/w 3.02
Model 4KS225EBA 4KS225EBA
Type Rotary Rotary
Brand MATSUSHITA-WABAO MATSUSHITA-W ABAO
Capacity Btu/h 13000 13000
Input W 1260 1260
Rated current(RLA) A 5.7 5.7
Locked rotor Amp(LRA) A 30 30
Thermal protector
Capacitor uF 35 35
Refrigerant oil ml 480 480
Model RPG20D RPG20D
Input W 49.2 49. 2
Capacitor uF 1.5 1.5
Speed(hi/mi/lo) r/min 1180/1000/ 900 1180/1000/900
Dimension (W*H*D) m m 815X280X195 815X280X195
Packing (W*H*D) mm 915X360X275 915X360X275
Net/Gross weight Kg 10.5/13.5 10.5/13.5
Model YDK25-6C YDK25-6C
Input W
Capacitor uF
Speed r/min 900 900
Dimension(W*H*D) mm 780X540X250 780X540X250
Packing (W*H*D) mm 910X575X335 910X575X335
Net/Gross weight Kg 34/38 37/41
Liquid side/ Gas side mm(inch)
Max. refrigerant pipe length m 10 10
Max. difference in level m 5 5
85 85
2.5 2.5
Ф6.35/Ф12.7 Ф6.35/Ф12.7
17-30 17-30
18-45 —7-45
71
Comfort
Model CES-07_R7______________CES-07_R7C____________CES-09_R7________CES-09_R7C
Power supply Ph-V-Hz 220-240V~,50Hz 220-240V~,50Hz 220-240V~,50Hz 220-240V~,50Hz
Capacity Btu/h 7000 7000 9000 9000
Cooling
Heating
Moisture Removal L/h 0.6 0.6 0.8 0.8
Max. input consumption W 1000 1000 1330 1330
Max. current A 4.4 4.4 6 6
Compressor
Indoor fan motor
Indoor air flow (Hi/Mi/Lo) m3/h 430/400/370 430/400/370 470/440/410 470/440/410
Indoor noise level (Hi/Mi/Lo) dB(A) 35/32/30 35/32/30 36/32/30 36/32/30
Indoor unit
Outdoor fan
motor
Outdoor air flow m3/h 1600 1600 1900 1600
Outdoor noise level dB(A) 49 49 49 49
Outdoor unit
Refrigerant type R407C g 740 650 840 770
Design pressure MPa 2.8 2.8 2.8 2.8
Refrigerant
piping
Operation temp 17 30 17 30 17 30 17 30 Ambient temp -7-45 18-45 -7-45 18-45 Application area m2 10-14 10-14 14-21 14-21
Input W 800 800 1050 1050
Rated current A 3.5 3.5 4.6 4.6
EER Btu/w.h 8.8 8.8 8.6 8.6
Capacity Btu/h 8500 10000
Input W 880 1050
Rated current A 4 4.6
COP w/w 2.9 2.93
Model PG135X1C-4DZ2 PG135X1C-4DZ2 PG180X1C-4DZ3 PG180X1C-4DZ3 Type Rotary Rotary Rotary Rotary Brand TOSHIBA TOSHIBA TOSHIBA TOSHIBA
Capacity Btu/h 8086/8172 8086/8172 10800 10800
Input W 765/785 765/785 1015 1015
Rated current(RLA) A 3.52/3.34 3.52/3.34 4.5 4.5 Locked rotor Amp(LRA) A Thermal protector UP3SE0591-T71 UP3SE0591-T71 UP3SE0591-T61 UP3SE0591-T61
Capacitor uF 25 25 30 30
Refrigerant oil ml 400 400 400 400 Model RPG13H RPG13H RPG13H RPG13H
Input W 36.5 37.5 38.5 39.5
Capacitor uF 1.2 1.2 1.2 1.2
Speed(hi/mi/lo) r/min 1020/960/900 1020/960/900 1100/1020/950 1100/1020/950
Dimension (W*H*D) mm 750×250×188 750×250×188 750×250×188 750×250×188
Packing (W*H*D) mm 830×336×280 830×336×280 830×336×280 830×336×280
Net/Gross weight Kg 8.5/10.5 8.5/10.5 8.5/10.5 8.5/10.5 Model YDK24-6T YDK24-6T YDK24-6T YDK24-6T
Input W 70 70 70 70
Capacitor uF 3 3 3 3
Speed r/min 850 850 850 850
Dimension(W*H*D) mm 700X535X235 700X535X235 700X535X235 700X535X235
Packing (W*H*D) mm 815X580X325 815X580X325 815X580X325 815X580X325
Net/Gross weight Kg 30/33 29/32 29/32 30/33
Liquid side/ Gas side mm(inch Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф9.53
Max. refrigerant pipe length m 10 10 10 10
Max. difference in level m 5 5 5 5
1 The noise date is base on anechoic chamber, during actual operation, these values are normally somewhat different as a result of ambient condition.
70
3.Dimensions
3.1 Indoor unit
CES-05/07/09_R(7)(C),CES-12_R(7)(C)
3.2 Indoor unit CES-12_R(7)(C)
280
73
3.3 Indoor unit CES-18/21_R(7)(C))
3.4 Outdoor unit CES-05/07/09_R(7)(C),
74
3.5 Outdoor unit CES-12_R(7)(C) & CES-18_R(7)(C)
3.6 Outdoor unit CES-18_R(7)(C)
285
315
290
750
590
62
530
110
75
3.7 Outdoor unit CES-21_R(7)(C)
12.5
76
4.Refrigeration cycle diagram
4.1 Cooling/heating
Indoor unit outdoor unit
. 4 way valve
Sensor of room temp
Val ve
Heat exchanger Heat exchanger
Sensor of heat exchanger temp
.
Compressor
Val ve Capillary
4.2 Cooling only
Indoor unit outdoor unit
.
Sensor of room temp
Val ve
Heat exchanger Heat exchanger
Sensor of heat exchanger temp
.
Compressor
Val ve Capillary
77
5.Operation limits
5.1Cooling operation
Outdoor unit air temp.℃ DB
45
40
35
30
25
20
Indoor air temp.
Note : The chart is the result from the continuous operation under constant air temperature
conditions. However, excludes the initial pull-down stage.
5.2Heating operation
DRY COOLING
10 15 20 25 30 35 40
DB
Indoor air temp. DB
30
25
20
15
10
5
Note : The chart is the result from the continuous operation under constant air
temperature conditions. However, excludes the initial pull-down stage.
-5 5 15 25
Outdoor unit air temp.
78
DB
6.Wiring diagram
6.1 Cooling only
6.1.1 CES-05_R(7)(C) Indoor unit
POWER SUPPLY
INDOOR UNIT
OUTDOOR UNI
OVERLOAD
RELAY
COMPRESSO
Y&G
T
BLACK
BLACK
R
C
RED
R
S
BLU
E
1 2(N)
RED
COMPRESSOR CAPACITOR
Y&G
FAN
MOTOR
BLACK
BLU
Y&G
RED
RED
E
FAN CAPACITOR
79
6.1.2 CES-07_R(7)(C) & CES-09_R(7)(C)
POWER SUPPLY
INDOOR UNIT
OUTDOOR UNI
OVERLOAD
RELAY
COMPRESSO
Y&G
T
BLACK
BLACK
R
C
RED
R
S
BLU
E
1 2(N)
RED
Y&G
FAN
MOTOR
BLACK
BLU
Y&G
RED
RED
E
COMPRESSOR CAPACITOR
80
FAN CAPACITOR
6.1.3 CES-12_R(7)(C) Indoor unit (A Type)
POWER SUPPLY
INDOOR UNIT
OUTDOOR UNI
OVERLOAD
RELAY
COMPRESSO
Y&G
T
BLACK
BLACK
R
C
RED
R
S
BLU
E
1 2(N)
RED
COMPRESSOR CAPACITOR
Y&G
FAN
MOTOR
BLACK
BLU
Y&G
RED
RED
E
FAN CAPACITOR
81
6.1.4 CES-12_R(7)(C) (B Type)
INDOOR UNIT
OUTDOOR UNI
OVERLOAD
RELAY
COMPRESSO
Y&G
T
BLACK
BLACK
R
C
RED
R
S
BLU
E
1 2(N)
RED
COMPRESSOR CAPACITOR
Y&G
FAN
MOTOR
BLACK
BLU
Y&G
RED
RED
E
FAN CAPACITOR
82
6.1.5 CES-18_R7(C) & CES-21_R7(C)
DISPLAY BOARD
SWITCH BOARD
CN12
CN8
AMBIENT SENSOR
CN7
HEAT EXCHANGER
TRANSFORMER
CN9
CN10
SENSOR
CN4
CN6
LOUVER MOTOR
INDOOR MOTOR
COMPRESSOR RELAY
WHITE
CURRENT DETECTOR
CN1
CN5
LOUVER MOTOR
CN14
CN2
WHITE
BLUE
BROWN
BLACK
INDOOR UNIT
OUTDOOR UNI
OVERLOAD
RELAY
COMPRESSO
Y&G
T
1 2(N)
Y&G
BLACK
BLACK
RED
RED
BLACK
R
C
RED
R
S
BLU
E
COMPRESSOR CAPACITOR
Y&G
FAN
MOTOR
BLU
RED
E
FAN CAPACITOR
83
6.2 Heating/cooling
6.2.1 CES-07_R(7),CES-09_R(7) & CESG-09HRN2,
84
6.2.2 CES-12_R7(B TYPE) & CES-12_R7
85