Ademco DD15 User Manual

Part #DD15
DD15 Daikin VRV Interface Module Installation Instructions
Table of Contents
Introduction ......................................................................................1
Specification ....................................................................................2
Safety Precautions ............................................................................3
System Overview .............................................................................4
Mounting ..........................................................................................7
Wiring ..............................................................................................9
Start-Up ..........................................................................................13
Inputs & Outputs ............................................................................14
Model & Part Numbers ..................................................................15
Regulatory Compliance .................................................................16
Introduction
Daikin North America LLC and Honeywell have jointly developed an organically integrated system which allows Honeywell’s INNCOM Integrated Room Automation system to provide direct digital control of the Daikin Variable Refrigerant Volume (VRV) heat recovery system. This is an industry first solution that provides the hotelier an intelligent integrated room automation system capable of connecting all of the guestroom devices to control room temperature, lighting drapes and amenities, in-room 3rd party integration of door locks, as well as connect to the INNcontrol 3 software on a central server over the Deep Mesh Network, with the efficiency of Daikins VRV system.
         
Part #DD15 Installation Instructions 6/30/2016
1
Specification
Part #DD15
Features
A seamless energy management solution, with integrated VRV
capability tailored specifically for hospitality
Provides a more energy efficient solution with lower operating
costs than traditional FCU systems
Maximizes dehumidification capability, and significantly reduces
mechanical noise over traditional FCU systems
In-room 2.4Ghz RF wireless network communications Software control of the field settings for the Daikin VRV in door
unit (IDU)
Error reporting from the Daikin system to the INNcontrol 3
application on the central server
Over-the-air loadable for easy installation, commissioning, and
maintenance
Ideal for new installation and retrofit Compact interface module Best-in-class offerings from Honeywell and Daikin
Parameter Specification
Input Voltage (P4) 16VDC DC Output (P3) 12V, 30mA (50mA Peak) Current Consumption
Bind Switch Recessed switch used for commissioning and binding (S1) Indicator LED’s
Communications
Dimensions 84.5mm (L) x 47mm (W) x 29mm (H) Maximum Operating Temperature (0°C to 40°C) Maximum Storage Temperature -40°C – 70°C Relative Humidity 5 – 90%RH Non-Condensing Approvals
Typical 100mA. See the DD15 Digital Output section for application
specific current consumption.
Diagnostic LED (green), Transmit activity (Yellow), Receive activity
(Red)
S5bus for wired bus communication, 2.4Ghz wireless RF Transceiver for
Deep Mesh RF communication
FCC 47CFR PT 15.247 Issued:2004/10/01 Operation within the bands
902-928MHz, 2400-2483.5MHz and 5725-5850MHz
RSS-247 Issue: 2015/05/22 Issue 1 Digital Transmission Systems
(DTSs), Frequency Hopping Systems (FHSs) and License-Exempt Local Area Network (LE-LAN) Devices
FCC 47CFR PT 15 SPT B Issued:2013/01/28 Title 47 CFR Part 15
Subpart B: Unintentional Radiators
ICES 003 Issued: 2012/08/01 Spectrum Management and
Telecommunications Interference-Causing Equipment Standard
EN 300 328:2015 V1.9.1 EMC & Radio Spectrum Matters (ERM);
Wideband Transmission Systems Data Transmission Equipment Operating in the 2.4GHz ISM Band & Using Wide Band Modulation Techniques Harmonized EN for Article 3.2- R&TTE Directive
Part #DD15 Installation Instructions 6/30/2016 2
Parameter Specification
EN 300 489-1 V1.9.2 Electromagnetic compatibility and Radio spectrum
Matters (ERM); Electromagnetic compatibility (EMC) standard for radio equipment and services; Part 1: Common technical requirements
EN 301 489-17 Electromagnetic compatibility and radio spectrum
matters (ERM); Electromagnetic Compatibility (EMC) standard for radio equipment; Part 17: Specific Conditions for broadband data transmission systems –V2.1.1
N 55022 Issue:2010/12/01 Information Technology Equipment-Radio
Disturbance Characteristics – Limits and Methods of Measurement, Includes COR 2011/10/01
EN 55024 Issue: 2010/11/01 Information Technology Equipment –
Immunity Characteristics Limits and Methods of Measurement.
Safety Precautions
The following safety precautions should be observed during the installation start-up to prevent personal injury or equipment damage:
Observe national and local electrical codes. Observe voltage and current limits marked on the DD15 Observe voltage and current limits and rating when wiring to the
Daikin VRV IDU and X18A/X35A terminal boards
Assumption is that the installer has a working knowledge of the
INNCOM system
Replacing Legacy Device
A single DD15 replaces the legacy solution of a RTD-LCINC and a PC­485, which provided the integration between Daikin VRV and the INNCOM by Honeywell system.
Shutting down power to the Daikin VRV unit will be required when disconnecting the RTD-LCINC and the PC-485. Follow the wiring instructions section when installing the DD15.
Part #DD15
NOTE:
The form factor of the DD15 allows for a different mounting
application.
Part #DD15 Installation Instructions 6/30/2016
3
System Overview
Part #DD15
Figure 1 Standard VRV Integration Overview
Honeywell’s INNCOM e528 or e527 thermostat replaces the standard Daikin VRV room controller for the heat recovery system. Daikin’s heat recovery solution provides an alternative to a chiller plant and is becoming more widely accepted in the hospitality market. The e528 or e527 thermostat is the “intelligent” device capable of linking ancillary sensors and serving as an information gateway. For example, coupled with a magnetic door switch (wired or wireless), motion detectors and other devices, the e528 or e527 thermostat becomes the center of a highly effective Energy Management System application, communicating EMS information requirements from the guestroom to the central server. When connected to the INNcontrol server over a wired or wireless backhaul network, a centrally controlled EMS package is created. Through interfaces with other devices and sensors, the solution provides the following functions:
Guestroom HVAC diagnostics Remote room occupancy indication
Part #DD15 Installation Instructions 6/30/2016 4
Deep Mesh Wireless Communication
Part #DD15
Central Electronic Lock Humidity Management Outside temperature display Peak demand load shedding Property/Building Management System (PMS/BMS) interface
The DD15 interface module is equipped with a 2.4 GHz wireless RF transceiver for Deep Mesh RF communications. This provides the capability to wirelessly communicate to Honeywell’s INNCOM e528 or e527 thermostat. This additionally provides the capability to wirelessly over-the-air load the device for software updates and configuration changes.
NOTE:
The DD15 is not intended to be used as a general purpose RF
media gateway or protocol converter.
Parameter Specification
RF Data Rate 250kbps Antenna Type SMT Indoor Range 100ft Outdoor/ RF line-of-sight
range Transmit Power 10mW (+18dBm) Receive Sensitivity -94.6dBm Frequency Band 2.4Ghz Encryption AES-128 Protocol 802.15.4 Frequency Channels 11-26
Table 1 Deep Mesh RF Radio Attributes
1000ft+
Part #DD15 Installation Instructions 6/30/2016
5
Part #DD15
Figure 2 Typical Wireless Installation
Part #DD15 Installation Instructions 6/30/2016
6