Failure to follow all instructions may result in equipment damage or a hazardous condition. Read all instructions
carefully before installing equipment.
Local codes and practices
Always install equipment in accordance with the National Electric Code and in a manner acceptable to the local
authority having jurisdiction.
Electrostatic sensitivity
This product and its components may be susceptible to electrostatic discharge (ESD). Use appropriate ESD
grounding techniques while handling the product. When possible, always handle the product by its non-electrical
components.
High voltage safety test
Experienced electricians, at first contact, always assume that hazardous voltages may exist in any wiring system. A
safety check using a known, reliable voltage measurement or detection device should be made immediately before
starting work and when work resumes.
Lightning and high-voltage dang er
Most electrical injuries involving low-voltage wiring result from sudden, unexpected high voltages on normally
low-voltage wiring. Low-voltage wiring can carry hazardous high voltages under unsafe conditions. Never install or
connect wiring or equipment during electrical storms. Improperly protected wiring can carry a fatal lightning surge
for many miles. All outdoor wiring must be equipped with properly grounded and listed signal circuit protectors,
which must be installed in compliance with local, applicable codes. Never install wiring or equipment while standing
in water.
Wiring and equipment separations
All wiring and controllers must be installed to minimize the possibility of accidental contact with other potentially
hazardous and disruptive power and lighting wiring. Never place 24VAC or communications wiring near other bare
power wires, lightning rods, antennas, transformers, or steam or hot water pipes. Never place wire in any conduit,
box, channel, duct or other enclosure containing power or lighting circuits of any type. Always provide adequate
separation of communications wiring and other electrical wiring according to code. Keep wiring and controllers at
least six feet from large inductive loads (power distribution panels, lighting ballasts, motors, etc.). Failure to follow
these guidelines can introduce electrical interference and cause the system to operate erratically.
Warning
This equipment (FCC ID: HS9AZWDGL) has been tested and found to comply with the limits for a class A digital
device, pursuant to part 15 of the FCC rules. These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area
is likely to cause harmful interference, in which case the user will be required to correct the interference at his own
expense.
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and (2) This device must accept any interference received,
including interference that may cause undesired operation.
FCC Caution: Any changes or modifications not expressly approved by the party responsible for compliance could
6670 185th AVE NE
Redmond, WA 98052 USA
Phone: (425)869-8400 FAX: (425)869-8445
Web Site: www.alerton.com
All information in this document is provided as is without warranty of any kind. Honeywell reserves the right to
change any information herein without prior notice. No guarantees are given as to the accuracy of information.
Trademarks and trade names may be used in this document to refer to either the entities claiming the marks and
names or their products. Alerton, BACtalk, and their logos are registered trademarks and VisualLogic is a trademark
of Honeywell. Honeywell disclaims any proprietary interest in trademarks and trade names other than its ow n.
Alerton’s AZW-5000 is a wireless communications device designed to replace
MS/TP and wall sensor cabling in instances where cabling is cost-prohibitive. It
allows you to add a small (up to 15 controllers or devices) wireless subnetwork
to a wired network.
A scenario where the AZW-5000 would be effective is a school that adds
portable class rooms that need to be tied into the existing school Building
Automation System (BAS). The cost of running cable underground to each
portable is significant. AZW-5000 is an ideal solution to this problem allowing a
wireless network to make the connection for a lower price than the labor and
materials needed to bury a cable.
It will also be useful when retrofitting wireless controllers into places where
wiring or rewiring is prohibitively expensive - buildings with concrete walls, for
example.
The AZW-5000 operates in one of three modes:.
AZW-5000
|
• Coordinator - connects to the committed MS/TP network. Sends and
receives system data to/from transceivers.
Dimensions
• Transceiver - connects to a unitary controller by an MS/TP cable. Also
supports a wireless sensor by communicating data between the unitary
controller and the wireless sensor. Sends and receives system data
to/from the coordinator.
• Repeater - Connects only to power. Repeats transmissions in areas of
weak reception. Note that the use of repeaters reduces the overall
bandwidth of the network.
Power rating
4
Figure 1 AZW-5000 dimensions
The AZW-5000 consumes <5VA power at 24VAC 50/60Hz typical.
This document provides information about installing and wiring a AZW-5000 to
equipment, power, and communication channels. It also shows how to operate
the device.
IMPORTANT Always install equipment in accordance with the National
Electric Code and in a manner acceptable to the local authority having
jurisdiction (AHJ). No guidelines, instructions, installation practices, or other
information presented in this guide may be interpreted to supersede or modify
the local codes and practices of the AHJ.
Ta bl e 1Other documentation related to AZW-5000s
Document (ID)Contains
This section provides guidance for wiring and powering Alerton controllers. For
installation instructions specific to AZW-5000, see “Installation” on page 14.
Using terminal blocks
The AZW-5000 uses header-style termination blocks to simplify field wiring of
power, communications, and I/Os. Terminal blocks accept wire gage from
12–24AWG.
To terminate wire to a AZW-5000
1. Strip approximately 1/8” of the wire jacket from the end of the wire.
2. Use a small screwdriver (1/8” max) to turn the adjustment screw fully
counter-clockwise. The clamps in the wire slot separate as you turn the
screw.
3. Insert the stripped end of the wire into it (try to get the jacket flush with
the terminal block). If using stranded wire, be sure to insert all strands
into the wire slot. If terminating multiple wires, trim wires to same
length and tightly twist exposed wire together.
General installation guidelines
|
4. Hold the wire in place and turn the adjustment screw clockwise to
tighten it until the clamps in the wire slot secure the wire.
5. Tug gently on the wire to ensure it is secure.
Power supply guidelines and requirements
AZW-5000 uses 24VAC power from a UL Listed Class 2 24VAC transformer
(not provided). The AZW-5000 uses a half-wave rectifier to convert the AC
power supply to onboard power. This enables multiple devices with half-wave
power supplies to be powered from a single, grounded transformer. When
sharing a transformer make sure the sum of the MAX loads for all connected
devices does not exceed the Load rating for the transformer. AZW-5000
maximum power consumption is <5VA.
CAUTION Half-wave devices and full-wave devices must not use the same AC
transformer. If a AZW-5000 will share its power supply with another device,
ensure that the other device uses a half-wave rectifier and that polarity of wiring
is maintained. Failure to do so can result in equipment damage.
Note All Alerton unitary controllers are half-wave devices.
Selecting a transformer
The safest way to size a transformer is to ensure that the maximum VA load
rating of the AZW-5000 is less than 85% of the Nameplate VA rating of the
transformer. Even if all outputs are not presently used, this ensures that each
AZW-5000 has sufficient power for future equipment additions.
CAUTION If an AZW-5000 will share its power supply with another device,
ensure the transformer is rated to handle the combined maximum load. Using
and undersized transformer may damage equipment.
IMPORTANT Transformer sizing should never exceed the maximum UL Class
When connecting power to the AZW-5000, ensure that one leg of the VAC
secondary circuit connects to a known earth ground. Also ensure that the GND
terminal on the AZW-5000 connects to the same known earth ground.
Supplying a high-quality ground connection to a AZW-5000 and then properly
connecting the AZW-5000 to the ground is one of the most important things you
can do to ensure a trouble-free installation.
The 24VAC secondary leads are not interchangeable. Once a lead connects to
the GND terminal on the AZW-5000, it is the grounded lead. Observe and
maintain polarity for subsequent connections. The GND terminal provides a
reference ground for the circuit board and communications wiring. Use 18 AWG
cable for best results.
WARNING Ensure that all AZW-5000 power, communications, and I/O
cabling are grounded according to these instructions. Failure to follow these
instructions may result in AZW-5000 operational and communication failures or
equipment damage.
Power supply wire selection
If you are considering long power supply wiring runs, using the right wire size is
critical. If the wire diameter is too small, the resistance may be too high,
resulting in a low voltage supply to the AZW-5000. This is known as line loss.
The wire size is based on the length of the wire run and the current draw of the
AZW-5000. Obtain additional information from the transformer manufacturer.
The AZW-5000 coordinator device communicates with the BACnet system over
the MS/TP LAN, which uses the EIA–485 signaling standard. Transceivers
communicate with their associated unitary controllers over
Note This section applies only to the coordinator device.
Ta bl e 2MS/TP LAN facts
Transmission speed9.6, 19.2, 38.4, 76.8Kbps (figured at global controller).
At startup, AZW-5000 devices operate at 76.8 Kbps.
LayoutBus.
CablingBACnet specifies the following. Shielded, twisted-pair
cabling with characteristic impedance between 100 and
130 Ohms. Distributed capacitance between conductors
must be less than 30 pF/foot (100 pF/m). Distributed
capacitance between conductor and shield must be less
than 60 pF/foot (200 pF/m). Foil or braided shield
acceptable.
Segment lengthSegments between transceivers and controllers/devices
should be kept as short as practical to reduce cable
costs. Longer segments are acceptable to improve radio
signal strength.
The segment between a coordinator and its associated
BCM can be up to 4000 ft. (1071 m.), but will typically
be much shorter.
General installation guidelines
|
Maximum devices
overall
Maximum devices
per segment
MS/TP repeatersDo not use.
Terminating
resistors
Shield groundingGround transceiver shield drain wires at single point
Terminating MS/TP LAN cabling
MS/TP terminations are located at the top of the AZW-5000. See Fig. 4 on p. 15.
Maintain polarity of the MS/TP wire run throughout the MS/TP LAN.
Note Basic information about MS/TP terminations at the AZW-5000 are
provided here. See the BACtalk System Design Guide (LTBT-TM-SYSDSGN)
for more detailed information and limitations with respect to MS/TP LANs —
distance requirements, unit loads, repeater architectures, and so on.
One coordinator and 15 transceivers/Repeaters.
One transceiver and one controller per subnet.
not applicable
earth (panel) ground, not AZW-5000 ground. Tape off
the shield drain wire at the other end.
Grounding coordinator shield wires is not necessary
unless the coordinator is located more than ten feet
from its associated BCM.