ADEMCO LYNXR-ENSIA
Security Systems
Installation and Setup Guide
PREK5963-2 (bx) 7/05 Rev. A
DELETE
AUX
SELECT
STAY
ESCAPE
AWAY
ADD
OFF
LIGHTSON
7
LIGHTSOFF
STATUS
1
RECORD
4
NODELAY
CODE
0
VOLUME
5
TEST
8
ARMED
2
CHIME
#
FUNCTION
PLAY
6
BYPASS
9
READY
3
RECOMMENDATIONS FOR PROPER PROTECTION
The Following Recommendations for the Location of Fire and Burglary Detection Devices Help Provide
Proper Coverage for the Protected Premises.
Recommendations for Smoke and Heat Detectors
With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations
contained in the National Fire Protection Association's (NFPA) Standard #72 noted below.
• Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and areas of
the household as follows: For minimum protection a smoke detector should be installed outside of each separate sleeping
area, and on each additional floor of a multi-floor family living unit, including basements. The installation of smoke
detectors in kitchens, attics (finished or unfinished), or in garages is not normally recommended.
• For additional protection the NFPA recommends that you install heat
room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms, basements and attached garages.
In addition, we recommend the following:
• Install a smoke detector inside every bedroom where a smoker sleeps.
• Install a smoke detector inside every bedroom where someone sleeps with the door partly or completely closed. Smoke
could be blocked by the closed door. Also, an alarm in the hallway outside may not wake up the sleeper if the door is
closed.
• Install a smoke detector inside bedrooms where electrical appliances (such as portable heaters, air conditioners or
humidifiers) are used.
• Install a smoke detector at both ends of a hallway if the hallway is more than 40 feet (12 meters) long.
• Install smoke detectors in any room where an alarm control is located, or in any room where alarm control connections
to an AC source or phone lines are made. If detectors are not so located, a fire within the room could prevent the control
from reporting a fire or an intrusion.
THIS CONTROL COMPLIES WITH NFPA REQUIREMENTS FOR TEMPORAL PULSE
SOUNDING OF FIRE NOTIFICATION APPLIANCES.
or smoke detectors in the living room, dining
KITCHEN
DINING
LIVING ROOM
BEDROOM
BEDROOMBEDROOM
LIVING
ROOM
BEDROOM
BASEMENT
KTCHN
TO
BEDROOMBEDROOM
BEDROOM
CLOSED
.
DOOR
TV ROOM
BEDROOM
Smoke Detectors for Minimum Protection
Smoke Detectors for Additional Protection
Heat-Activated Detectors
GARAGE
KITCHEN
DINING
LIVING ROOM
BEDROOM
BEDROOM
01000-002-V0
Recommendations For Proper Intrusion Protection
• For proper intrusion coverage, sensors should be located at every possible point of entry to a home or premises. This
would include any skylights that may be present, and the upper windows in a multi-level building.
• In addition, we recommend that radio backup be used in a security system. This will ensure that alarm signals can be
sent to the alarm monitoring station in the event that the telephone lines are out of order (alarm signals are normally
sent over the phone lines, if connected to an alarm monitoring station).
–2–
Table of Contents
SYSTEM FEATURES ...............................................................................................................................................4
MOUNTING THE CONTROL..................................................................................................................................5
MECHANICS OF PROGRAMMING .....................................................................................................................14
ZONE RESPONSE TYPE DEFINITIONS ............................................................................................................15
DATA FIELD DESCRIPTIONS .............................................................................................................................17
✻56 ENHANCED ZONE PROGRAMMING MODE .............................................................................................27
✻80 DEVICE PROGRAMMING MENU MODE ...................................................................................................31
✻81 ZONE LIST MENU MODE.............................................................................................................................34
SYSTEM OPERATION ...........................................................................................................................................47
TESTING THE SYSTEM........................................................................................................................................53
SYSTEM COMMUNICATION...............................................................................................................................54
SUMMARY OF CONNECTIONS DIAGRAM .......................................................................................................71
–3–
System Features
LYNXR-ENSIA is not intended for UL985 Household Fire applications unless a 24-hour backup battery
UUUU
The LYNXR-ENSIA controls are self-contained, rechargeable wireless control/communicators that feature easy
installation and usage. A built-in speaker provides voice annunciation of system status along with voice descriptors of
each zone (if programmed). The following illustration highlights the main features of this system.
• 1 hardwire zone
• Up to 24 wireless zones
(5800 Series Transmitters)
• Up to 16 wireless button zones
• Up to 8 Powerline Carrier Devices
• Supports wireless keypads
8 USER CODES
• Installer code
• Master code
• 5 Secondary codes
• Duress code
• 3 Panic functions
(P/N LYNXRCHKIT-HC) is installed.
LLLL
Powerline Carrier Devices are not UL Listed for fire or burglary functions and are intended for home
automation.
ZONES and DEVICES
FEATURES
• Real-time Clock display and Fixed-Word display
• Message Center (for user recorded messages)
• Voice announcement of system and zone status
• Voice chime
• Alarm Clock
• Reminder
• X-10 Scheduling
• Latch Key Reports
• Automatic Stay Arming
• Remote Phone Control
• “Follow Me” Reminder and System Announcements
SYSTEM POWER
• Primary Power: Ademco
1332/1332X10 Plug-in Transformer,
110VAC to 9VAC, 15VA output
(1332CN in Canada)
• Backup battery: Six 1.2V
rechargeable nickel-metal hydride
batteries.
COMMUNICATION
• Ademco Low Speed
• Sescoa/Radionics
• Ademco Express
• Ademco Contact ID
• Paging feature
PROGRAMMING
• Options stored in EEROM
• Can be uploaded, downloaded or
controlled via IBM-compatible
computer using Compass
downloader software and specified
HAYES modem
• Voice Prompt programming mode
ARMED
READY
OFF
1
2
TEST
8
VOLUME
5
FUNCTION
CHIME
#
BYPASS
9
3
PLAY
6
ALARM OUTPUT
• Built-in sounder
AUX
SELECT
STAY
DELETE
AWAY
ADD
ESCAPE
LIGHTSON
LIGHTSOFF
STATUS
RECORD
7
4
CODE
0
NODELAY
• Piezo output
(30mA max.)
• Bell output
(120mA max.)
• Steady output for
burglary/panic
• Temporal pulse
output for fire alarms
• Alarm audio
verification
OTHER FEATURES
• Exit error feature (detects difference between an
actual alarm and exit alarm caused by leaving a door
open after the exit delay expires)
• Event log stores up to 84 events
• Macro/ 1-button paging
• RF Jam Detection
• Remote Phone Control
• Compatible with Encrypted (High-Security) Devices
• SIA Compliant
SPECIAL FEATURES
LYNXR24
• 24-hour backup
LYNXR-EN
• Two-way voice communication
• Speaker phone operation
–4–
Mounting the Control
Wall Mounting
The illustration below shows the front assembly separated from the back plate.
DO NOT disconnect the ribbon cable from the terminal strip board. Disconnect the cable only from the
front assembly board.
!
1. Separate the front assembly from the
back plate by pressing on the two
locking tabs at the top of the unit.
2. Carefully disconnect the ribbon cable
from the front assembly, leaving the
ribbon cable connected to the
terminal block PC board. The back
plate contains the terminal block for
making wiring connections.
3. Mount the back plate to a sturdy wall,
feeding the field wiring through the
appropriate openings in the back
plate.
4. After wiring connections are made,
carefully reconnect the ribbon cable to
the front assembly PC board
connector (properly aligning the red
wire).
5. Before closing the assembly, verify
which LYNXR model is being installed
by checking the model number printed
on the PC Boards. (Example:
SALYNXREN indicates the unit being
installed is a LYNXR-EN.)
6. Snap the front assembly to the back
plate so it is secured by the locking
tabs.
PC BOARD
PART NUMBER
LOCATION
1
DISCONNECT
THIS END ONLY!
LOCKING TABS
16
RED WIRE
MARKING
MXXXX
K5108
PC BOARD
PART NUMBER
LOCATION
01009-003-V0
Desktop Mounting
If desired, an optional mounting base (model LYNX-DM, purchased separately) allows the LYNXR-ENSIA controls to be
used on a desktop.
1. Slide the control panel onto the
mounting base locking tabs
2. Bring all wiring through the bottom of
the mounting base, using one of the
three wire entry locations, before
making connections to the control
panel.
3. Use tie-wraps to secure the wiring to
the built-in wire loops as needed. Use
the two supplied screws to secure the
control panel to the mounting base.
.
OFF
ESCAPE
AWAY
ADD
STAY
DELETE
AUX
SELECT
WIRE ENTRY
KNOCKOUT
(1 of 3)
01009-004-V1
–5–
)
Wiring Connections
Wiring Overview
The following summarizes the connections required. Refer to the Wiring Connections paragraph and the Summary of
Connections diagram on the inside back cover when making connections.
HARDWIRE ZONE
Supports 1 EOLR supervised zone using either closed
circuit or open circuit sensors.
The LYNXR-ENSIA supports the twoway voice feature/Alarm Audio
Use either the plug-in jacks or
the screw terminals.
TWO-WAY VOICE
PHONE LINES
POWERLINE CARRIER DEVICES
Supports up to 8 Powerline Carrier
Devices for turning on/off lights and
appliances. Requires the use of an
ADEMCO 1332X10 transformer.
MXXXX
K5108
AC TRANSFORMER
Use the supplied
ADEMCO 1332X10
9VAC, 15VA Plug-in
Transformer (1332CN in
EARTH GROUND
See Earth Ground paragraph.
LOCAL SOUNDER DISABLE JUMPER
Remove the shorting jumper (shunt) to disable local
sounder, leaving only the external sounder active.
UL NOTE: Do not remove the shorting jumper (the shunt)
for UL installations.
Canada
01009-005-V0
SOUNDERS
The system includes a built-in sounder in the master keypad. If
desired, an external bell or piezo sounder can be connected.
Bell: Use a 6-14V bell with maximum current drain of 120mA.
Piezo: Use a 6-14V piezo sounder with maximum current drain of
30mA.
This control complies with NFPA requirements for temporal pulse
sounding of fire notification appliances.
Temporal pulse sounding for a fire alarm consists of the following:
3 pulses – pause – 3 pulses – pause – 3 pulses. . .
.
Wiring Connections
1. Make Earth Ground Connection - The designated earth ground terminal (1) must be terminated in a good earth ground
for the lightning transient protective devices in this product to be effective. The following are examples of good earth
grounds available at most installations:
Metal Cold Water Pipe - Secure a non-corrosive metal strap (copper is recommended) to the pipe that is electrically
connected and secured to which the ground lead.
AC Power Outlet Ground - Available from 3-prong, 120VAC power outlets only. To test the integrity of the ground
terminal, use a three-wire circuit tester with neon lamp indicators, such as the UL Listed Ideal Model 61–035, or
equivalent, available at most electrical supply stores.
a. Connect terminal 1 to a good earth ground.
–6–
Wiring Connections
Wiring Connections
2. Make Phone Line Connections - For local or full line
seizure proceed to the appropriate steps below.
Local Seizure
a. Connect the incoming phone line to either the
8-position jack or terminals 2 (TIP) and 3 (RING) on
the Lynx.
b. Connect the handset phone lines to either the RJ11
GREY
jack or terminals 4 (TIP) and 5 (RING).
Full Line Seizure: The control must be placed in
series with the incoming phone line. Plugging the
Direct Connect Cord directly into the RJ31X jack, allows
the control to seize the phone line when an alarm
occurs and normal phone line usage by the premises
phones if the plug needs to be removed.
a. Cut the incoming RING and TIP phone lines
(typically red and green, respectively) and connect
them to RJ31X terminals 4 (red) and 5 (green).
b. Connect the premises end of the cut RING and TIP
wires to RJ31X terminals 1 (grey) and 8 (brown)
respectively.
c. Wire the flying leads of a Direct Connect Cord to the
RED
GREEN
TIP RING TIP RING
}
INCOMING
PHONE LINE
control’s phone terminals as shown in the diagram
or plug into the 8-position jack.
d. Plug the Direct Connect Cord into the RJ31X jack.
HARDWIRED ZONE: If the EOLR is not at the end of the loop, the zone will not be properly
supervised, and the system may not respond to an open circuit on the zone.
3. Make Hardwired Zone Connections - Zone 1 is an EOLR supervised zone that supports both open circuit and closed
circuit devices and has a response time of 350msec. Maximum zone resistance: 300 ohms, plus EOLR
Note: The hardwire zone cannot be used as a fire zone.
a. Connect sensors/contacts to the hardwired zone terminals 6 (+) and 7 (–). Refer to the Summary of Connections
diagram.
b. Connect closed circuit devices in series in the high (+) side of the loop. The EOL resistor must be connected in
series with the devices, following the last device.
c. Connect open circuit devices in parallel across the loop. The 2000-ohm EOLR must be connected across the loop
at the last device.
4.Make External Sounder Connections - The control panel supports either a 6-14VDC piezo sounder (30mA max.) or
6-14VDC bell (120mA max.; e.g. ADEMCO WAVE2EX).
a. Connect a piezo sounder to terminals 10 (+) and 11 (–); OR a bell to terminals 11 (–) and 12 (+).
LOCAL SOUNDER DISABLE: The Master Keypad’s built-in piezo sounder can be disabled by
removing the shorting jumper (shunt) on the terminal board. If disabled, however, no sounding
UUUU
LLLL
will occur upon AC loss, since the external sounder does not operate when AC power is lost.
Do not remove shorting jumper (the shunt) for UL installations.
5. Disable Local Sounder Option - If required the Master Keypad’s built-in piezo sounder can be disabled.
a. Remove the shorting jumper (shunt) on the terminal board.
6.Make Powerline Carrier Device Connections - The control panel supports up to 8 Powerline Carrier Devices. If using
these devices, they must be connected to the ADEMCO 1332X10 transformer, as shown in the SUMMARY OF
CONNECTIONS diagram.
a. Connect the com/data/sync/ lines from the ADEMCO 1332X10 transformer to terminals 9, 13, and 14, respectively.
Note: If not using the supplied Ademco connection cable, you may need to reverse the black and yellow wire connections. Refer to the
✻80 Device Programming Menu Mode section for details on programming Powerline Carrier Devices.
–7–
45
3
RJ31X
2
1
OR
OR
GREY
BROWN
}
TO
PREMISES
PHONES
Full Line Seizure Connections
6
7
8
DIRECT
CONNECT
CORD
8-POSITION
JACK
INCOMING
PHONE LINE
RING
TIP
GREENRED
PREMISES PHONES
RING
TIP
BROWN
TO
01000-008-V0
Wiring Connections
–8–
AC Power and Backup Battery
The system is powered by a 9VAC, 15VA Plug-in Transformer, ADEMCO 1332/1332X10 (1332CN in
Canada). Refer to the wiring table below for wire gauge and length.
Use only the provided ADEMCO
1332/1332X10 or 1332CN Transformer
Distance from Transformer
to Control
Up to 75 feet #20
Wire Gauge
75 to 150 feet #18
150 to 300 feet #16
Wiring to the AC Transformer must not exceed 300 feet using 16-gauge wire. The voltage reading between
terminals 15 and 16 of the control must not fall below 9.00VAC.
Do not plug the transformer into the AC outlet until after all wiring connections have been made.
Backup battery. In the event of an AC power loss, the system is supported by a long life backup battery
thatis supervised for connection and for low voltage conditions. If the battery is missing, or a low battery
condition is detected, a “low battery” message is displayed and a report is sent to the central station. In
addition, the system will beep once every 45 seconds to audibly indicate a low battery condition (press any
key to stop the beeping).
AC Power and Rechargeable Backup Battery
Connecting AC Power and backup battery
1. Connect wires from the 1332/1332X10 (1332CN in
Canada) AC Transformer to terminals 15 and 16 as
shown in the wiring diagram.
2. Remove battery retainer.
3. Peel the backing from tape on the back plate.
4. Insert battery pack into back plate.
5. Install battery retainer.
6. Connect battery connector to receptacle on
terminal block PC board.
7. After all wiring connections have been made, snap
the front assembly to the back plate and plug the
transformer into a 24-hour, 110VAC unswitched
outlet.
Note: Rechargeable batteries may take up to 48-hours to
fully charge. The “LOW BAT” message should clear
within four hours or by entering Test Mode.
BATTERY
PACK
BATTERY
RECEPTACLE
RETAINER
1
TAPE
16
WIRING
TERMINALS
NOTE
LYNXRCHKIT-HC
BATTERY PACK SHOWN
XXXX
M
K5108
01009-007-V0
Ensure the cover is snapped closed prior to applying AC power.
–9–
/
AC Power and Backup Battery
AC Power and Rechargeable Backup Battery
The LYNXR-ENSIA is equipped with an integral, replaceable, rechargeable battery packcomposed of six (6)
rechargeable 1.2-volt nickel-metal hydride batteries. Select the appropriate battery pack, based on the
installation’s requirement, and install the battery pack.
Model
LYNXRCHKIT-SC 4-hours (minimum) Approximately 1-hour before battery depletion
LYNXRCHKIT-HC 24-hours (minimum) At least 1-hour before battery depletion
Replacing the Rechargeable Battery
1. When battery replacement is required, unplug
the transformer from the wall outlet, and open
the control panel cover.
2. Remove the battery retainer and disconnect the
battery pack connector from the receptacle on
the terminal block PC board.
3. Remove the battery pack from the back plate.
4. If required, replace the tape that secures the
battery pack.
5. Install a replacement battery pack (P/N
LYNXRCHKIT-SC or LYNXRCHKIT-HC) into the
back plate.
6. Install the battery retainer.
7. Connect the battery connector to the
receptacle on the terminal block PC board.
8. After the wiring connection has been made,
snap the front assembly to the back plate.
9. Plug the transformer into a 24-hour, 110VAC
unswitched outlet.
10. Rechargeable batteries may take up to 48hours to fully charge. The “LOW BAT” message
should clear within four hours or by entering
Test Mode.
Part Number
Battery StandbyTime
RETAINER
BATTERY
PACK
BATTERY
RECEPTACLE
Low Battery Notification
LYNXRCHKIT-HC OR LYNXRCHKIT-SC
BATTERY
CONNECTOR
TAPE
MXXXX
K5108
01009-006-V0
Ensure the control panel assembly is snapped closed prior to applying AC power.
–10–
Installing Wireless Zones
General Information
Zones: The control supports up to 24 wireless zones using 5800 Series transmitters, and up to 16
wireless buttons.
Range: The built-in RF receiver can detect signals from wireless transmitters within a nominal
range of 200 feet.
Transmitters: 5800 Series transmitters have built-in serial numbers that must be entered into the
system using the ✻56 or ✻83 interactive mode, or input to the control via the downloader. 5800
Series transmitters (except the 5800RL, which is described separately) do not have DIP switches.
Each transmitter's zone number is programmed into the system in ✻56 mode. Some transmitters,
such as the 5816 and 5817, can support more than one "zone" (referred to as loops or inputs). On the
5816, for example, the wire connection terminal block is loop 1,the reed contact is loop 2. Each loop
must be assigned a different zone number.
The 5816 and 5817 Transmitters do not have EOL supervision of their loop wiring. Therefore, for
UL Household Burglary installations, the loop wiring may not exceed 3 feet.
UL
The 5800RL, 5802MN, 5802MN2, 5804, 5804BD, 5804BDV, 5804E, 5804WATCH, 5814, 5816TEMP,
5819, 5819S(WHS & BRS), 5828/5828V and 5850(GBD) transmitters are not intended for any UL
installations.
For button transmitters (RF "keys") such as the 5804 and 5801, you must assign a unique zone
number to each individual button used on the transmitter. Each button on the transmitter also has
a pre-designated loop or input number, which is automatically displayed.
House Identification
If you are using a 5804BD/5804BDV Wireless Keypad with the system, you must program a House
ID Code (01–31) in field ✻24 to establish proper communication, and the keypad must be set to the
same ID. House ID 00 disables all wireless keypads. An RF House ID is not necessary for other 5800
Series transmitters; the entry should be left at “00” (default) in those cases.
Transmitter Supervision
Except for some transmitters/keypads that may be carried off-premises (5804, 5804BD, 5804BDV,
5804E, and 5804WATCH), each transmitter is supervised by a check-in signal that is sent to the
receiver at 70–90 minute intervals. If at least one check-in is not received from each supervised
transmitter within a 12-hour period, the "missing" transmitter number(s) and "FAULT" will be
displayed. The supervision for a particular transmitter in the system that may also be carried off
the premises (5801, 5802MN) may be turned off by entering it as a "UR" (unsupervised RF) type, as
described in the ✻56 Enhanced Zone Programming Mode section.
5800 Series transmitters have built-in tamper protection and will annunciate as a fault condition if
covers are removed.
Transmitter Input Types
Each of the following transmitters has one or more unique factory-assigned input (loop) ID codes.
Each of the inputs requires a programming zone
Transmitters can be entered as one of the following types
input type)
Type Description
"RF" (Supervised RF) Sends periodic check-in signals, as well as fault, restore, and low battery
"UR" (Unsupervised RF) Sends all the signals that the "RF" type does, but the control does not
"BR" (Unsupervised Button RF) These only send fault signals. They do not send low battery signals until
:
(e.g., a 5804's four inputs require four button zones).
(see transmitter’s instructions for appropriate
signals. The transmitter must remain within the receiver's range.
supervise the check-in signals. The transmitter may therefore be carried
off-premises.
they are activated. The transmitter may be carried off-premises.
–11–
Installing Wireless Zones
Transmitter Battery Life
• Batteries in the wireless transmitters may last from 4–7 years, depending on the environment,
usage, and the specific wireless device being used. Factors such as humidity, high or low
temperatures, as well as large swings in temperature may all reduce the actual battery life in a
given installation. The wireless system can identify a true low battery situation, thus allowing the
dealer or user of the system time to arrange a change of battery and maintain protection for that
point within the system.
• Button-type transmitters should be periodically tested for battery life. The 5801, 5802MN,
5802MN2, 5804, 5804BD, 5804BDV, 5804E, and 5804WATCH button transmitters have
replaceable batteries.
Using the Transmitter Sniffer Mode
Use this mode after all transmitters have been entered to check that all transmitters have been
properly programmed.
1. Enter Installer code (4112) + [#] + 3.
Note: If the communicator is in the process of sending a report to the central station, the system will not go into the Sniffer mode.
If so, wait a few minutes and try again.
2. The keypad will display all zone numbers, which have a non-zero Zone Type (even if serial
numbers were not learned yet). Fault each transmitter in turn, causing each one to send a
signal. As the system receives a signal from each of the transmitters, the zone number of that
transmitter will disappear from the display. The transmitters may be checked upon
installation, or in an installed system.
3. When all transmitters have been checked, exit Sniffer mode. Enter Installer Code (4112) +
OFF.
Notes: (1) Sniffer mode does not automatically expire. You must manually exit (Installer Code + OFF) Sniffer mode to return to
(2) All BR-type units must physically be activated to clear the display, since they do not automatically send check-in
(3) When one button of a transmitter (RF, UR, or BR) is activated, all zones assigned to other buttons on that transmitter
(4) Any transmitter that is not “entered” will not turn off its zone number.
normal operation.
signals.
are cleared. This also applies to 5816 and 5817 transmitters that have multiple loops (zones).
Go/No Go Test Mode
5804E and 5804WATCH encrypted (High-Security) devices must be activated while the system is in
Go/No Go Test Mode. Refer to the transmitter’s installation instructions for complete details. The
system will confirm enrollment of the encrypted device by beeping two times.
The Go/No Go tests will verify adequate RF signal strength from the proposed transmitter location,
and allow you to reorient or relocate transmitters if necessary, before mounting the transmitters
permanently. This mode is similar to the transmitter Test mode, except that the wireless receiver
gain is reduced. This will enable you to make sure that the RF signal from each transmitter is
received with sufficient signal amplitude when the system is in the normal operating mode.
1. Enter Installer Code (4112) + [#] + 8.
2. Once you have placed transmitters in their desired locations and the approximate length of wire
to be run to sensors is connected to the transmitter's screw terminals (if used), fault each
transmitter.
Conducting this test with your hand wrapped around the transmitter will cause inaccurate results.
On button type transmitters that have been programmed to set ARM AWAY, ARM STAY, or DISARM,
pressing a button will take the system out of the Go/No Go Test mode and cause the programmed
action to occur.
Note: On button type transmitters that have been programmed to set ARM AWAY, ARM STAY, or DISARM, pressing a button will
take the system out of the Go/No Go Test mode and cause the programmed action to occur.
a. The keypad will beep three times indicating signal reception and will display the appropriate
zone number.
b. If the keypad does not beep, reorient or move the transmitter to another location. Usually a
few inches in either direction is all that is required.
–12–
Installing Wireless Zones
4. If each transmitter produces the proper keypad response when it is faulted, you can then
permanently mount each of the transmitters according to the instructions provided with them.
5. Exit the Go/No Go Test mode by entering: Installer Code (4112) + OFF.
5800 Series Transmitter Loop Numbers
The following illustration shows the compatible transmitters, their associated input types and loop
designations.
(Refer to this information when programming transmitters)
Notes: (1) Loop 4 must be enrolled on the 5801, 5804, 5804BD, 5804BDV, 5804E and 5804WATCH transmitters, whether or not the loop is
used.
(2) 5804E and 5804WATCH encrypted (High-Security) devices must be activated while the system is in Go/No Go Test Mode. Refer
to the transmitter’s installation instructions for complete details. The system will confirm enrollment of the encrypted device by
UL
beeping two times.
The 5800RL, 5802MN, 5802MN2, 5804, 5804BD, 5804BDV, 5804E, 5804WATCH, 5814, 5816TEMP, 5819, 5819S(WHS
& BRS), 5828/5828V and 5850(GBD) wireless transmitters are not intended for any UL installations.
Setting DIP Switches on the 5800RL Transmitter
Set the 5800RL Transmitters to the programmed House ID, by using the DIP switches.
(OFF position is indicated by ---)
Note: The 5800RL cannot be used in conjunction with the Auto Arm (scheduled arming) feature.
234561
SW-1 ACTIVATES
MODE SETTING
2-6 SETS HOUSE ID
SHOWN SET FOR HOUSE ID# 12
SWITCH UP FOR "ON"
SW-6 SETS
MODE
SWITCH DOWN
FOR "OFF"
01000-014-V1
Setting 5800RL DIP Switches
ID
0 --- --- --- --- --- 16 ON --- --- --- --1 --- --- --- --- ON 17 ON --- --- --- ON
2 --- --- --- ON --- 18 ON --- --- ON --3 --- --- --- ON ON 19 ON --- --- ON ON
4 --- --- ON --- --- 20 ON --- ON --- --5 --- --- ON --- ON 21 ON --- ON --- ON
6 --- --- ON ON --- 22 ON --- ON ON --7 --- --- ON ON ON 23 ON --- ON ON ON
8 --- ON --- --- --- 24 ON ON --- --- ---
9 --- ON --- --- ON 25 ON ON --- --- ON
10 --- ON --- ON --- 26 ON ON --- ON --11 --- ON --- ON ON 27 ON ON --- ON ON
12 --- ON ON --- --- 28 ON ON ON --- --13 --- ON ON --- ON 29 ON ON ON --- ON
14 --- ON ON ON --- 30 ON ON ON O N --15 --- ON ON ON ON 31 ON ON ON ON ON
DIP SWITCH POSITIONS DIP SWITCH POSITIONS House
2 3 4 5 6
5800RL DIP SWITCH TABLE
House
ID
2 3 4 5 6
–13–
Mechanics of Programming
General Programming Information
Programming options are stored in non-removable, electrically erasable, nonvolatile EEROM memory.
The system can be programmed at any time, even at the installer's premises prior to the actual
installation. Simply apply power temporarily to the Control and then program the unit as desired.
There are two programming modes:
Data field programming (used for setting various system options)
•
• Interactive menu mode programming (used for programming zone information, programming Powerline
Carrier Devices, and for entering transmitter serial numbers)
The system can also be programmed remotely, using an IBM Personal Computer, a modem, and Compass
Downloader for Windows. See the Remote Programming/Control (Downloading) section.
Note: You may find it convenient to adjust the volume setting before entering the Program Mode. This will allow you to clearly hear
the feedback announcements or system beeps in the Programming Mode, of the system’s built-in speaker. To adjust the
volume, press FUNCTION + VOLUME+ [3] or [6]. Upon exiting the Program Mode, the system will reset the volume to the
default value (mid level).
Entering Program Mode - Use one of the following methods to enter Programming Mode:
1. Press both the [✻] and [#] keys at the same time, within 50 seconds after power is applied to the Control or
from exiting Programming mode, OR
2. After power-up, enter the Installer Code (4112) + 800 (This method disabled if Program mode is exited using
✻98.) to enter Expert Programming mode or Installer Code (4112) + 888 to enter Voice Prompt
Programming mode.
Note: If a different Installer Code has been programmed, use that code to enter the Programming mode. Once you have entered the
Program mode, data field
Programming a Data Field
1. Press [✻] + Field No. (for example, ✻21), followed by the required entry.
2. When you have completely programmed a data field, the keypad will “beep” three times and then
automatically display the next data field in sequence. To go to a different field, press [
number.
3. If the number of digits that will be entered in a data field is less than the maximum number of digits available
(e.g. phone number field), enter the desired data, then press [
4. If a nonexistent field has been entered, the keypad will display “EE”. Simply re-enter [
number.
To view a data field without making changes: Enter [#] + Field No. Data will be displayed for that field.
To delete an entry in a field: Enter [
Interactive Mode Programming (
✻] + interactive mode No. (for example, ✻56). The keypad will display the first of a series of prompts.
Press [
A detailed procedure (with displays of prompts) is provided in later sections of this manual.
56 Enhanced Zone Programming Mode
✻
✻80 Device Programming Menu Mode
✻81 Zone List Menu Mode
83 Enhanced Sequential Mode
✻
✻84 Assign Zone Voice Descriptors
✻85 Record Custom Voice Descriptors
Loading Factory Defaults
To load the factory defaults, enter the Programming mode, press ✻97, then press number 1, 2, 3, or 4 to select
from default tables 1-4 at the back of this manual, or press “0” if you are not selecting a default table.
If a default table is loaded, any data that has already been programmed into the system will be changed according to
the default table selected!
!
✻96 resets all subscriber account numbers and CSID in preparation for an initial download.
Exiting Program Mode
✻
98 inhibits re-entry into the Expert or Voice Prompt Programming modes using the Installer Code.
✻99 allows re-entry into the Expert Program mode using Installer Code (4112) + 800 or into the Voice Prompt
Programming mode using Installer Code (4112) + 888.
Note: After exiting program mode (or upon power-up), the system takes up to a minute to reset. To bypass the reset delay, press
[#] + [0].
✻20 (the first data field in the system) will be displayed and both keypad LEDs will flash.
✻] to advance to the next data field.
✻] + Field No. + [✻]. (Applies only to fields ✻40–✻44, ✻88 and ✻94).
✻56, ✻80, ✻81, ✻83, ✻84, ✻85)
Interactive Mode Used to Program
Zone characteristics, report codes, and serial numbers
Powerline Carrier Devices
Zone Lists for powerline carrier activation
5800 Series transmitter serial numbers
Voice descriptors for each zone
Up to 5 custom voice descriptors for zones
✻] plus the desired field
✻] plus a valid field
–14–
Zone Response Type Definitions
General Information
During programming, you must assign a zone type to each zone, which defines the way in which the system
responds to faults in that zone. Zone types are defined below.
Type 00
Zone Not Used
Type 01
Entry/Exit Burglary #1
01000-017-V0
Type 02
Entry/Exit Burglary #2
01000-017-V0
Type 03
Perimeter
Burglary
01000-018-V0
Type 04
Interior, Follower
5890 / 5890PI
01000-019-V1
Type 05
Trouble by Day/
Alarm by Night
Type 06
24-hour
Silent Alarm
Zone type 00 is used to program a zone that is not used.
Zone type 01 is usually assigned to sensors or contacts on primary entry and exit
doors.
Zone Characteristics:
• Entry delay #1 is programmable from 30-240 seconds (field
• Exit delay is independently programmable from 45-120 seconds (field
✻35).
✻34).
• Exit and entry delays when armed in AWAY or STAY mode.
• No entry delay when armed in STAY NO DELAY or AWAY NO DELAY mode.
• Exit delay regardless of the arming mode selected.
Zone type 02 is usually assigned to sensors or contacts on which secondary entry and
exit doors that might be further from the keypad (typically used for a garage, loading
dock, or basement door).
Zone Characteristics:
• Entry delay #2 is programmable from 30-240 seconds (field
• Exit delay is independently programmable from 45-120 seconds (field
✻36).
✻34).
• Secondary entry delay, if armed in the AWAY or STAY mode.
• No entry delay when armed in the STAY NO DELAY or AWAY NO DELAY mode.
• Exit delay begins regardless of the arming mode selected.
Zone type 03 is usually assigned to all sensors or contacts on exterior doors and
windows. Zone Characteristics:
• Instant alarm, when armed in AWAY, STAY, STAY NO DELAY, or AWAY NO
DELAY mode.
Zone type 04 is usually assigned to a zone covering an entry area (i.e.: foyer, lobby, or
hallway) that one must pass upon entry (after faulting the entry/exit zone) to reach
the keypad. It provides an instant alarm if the entry/exit zone is not violated first,
and protects an area in the event an intruder has hidden on the premises before the
system is armed, or gains access to the premises through an unprotected area.
Zone Characteristics:
• Delayed alarm (using the programmed entry/exit time) if entry/exit (types 01 or
02) or interior-with-delay (type 10) zone is faulted first.
• Instant alarm in all other situations.
• Active when armed in AWAY or AWAY NO DELAY mode.
• Bypassed automatically when armed in STAY or STAY NO DELAY mode.
Zone type 05 is usually assigned to a zone that contains foil-protected doors or
windows or covers a sensitive area (i.e.: stock room, drug supply room, etc.) It can also
be used on a sensor or contact in an area where immediate notification of an entry is
desired.
Zone Characteristics:
• Instant alarm, when armed in AWAY, STAY, STAY NO DELAY, or AWAY NO
DELAY (night) mode.
• Provides a latched trouble sounding from the keypad and, if desired, a central
station report during the disarmed state (day).
Zone type 06 is usually assigned to a zone containing an Emergency
button (silent emergency).
Zone Characteristics:
• Sends a report to the central station but provides no keypad display or
sounding.
–15–
Y
Zone Response Type Definitions
Zone type 07 is usually assigned to a zone containing an Emergency
button (audible emergency).
Zone Characteristics:
• Sends a report to the central station, and provides alarm sounds
externally and at the keypad.
Zone type 08 is usually assigned to a zone containing a button for use
in personal emergencies or to a zone containing monitoring devices
(i.e.: water or temperature sensors, etc.).
Zone Characteristics:
• Sends a report to the central station and provides an alarm sound at
the keypad. (No bell output is provided and there is no keypad
timeout.)
Zone type 09 can be assigned to any wireless zone used as a
fire zone. This zone type is always active and cannot be
bypassed.
Zone Characteristics:
• Bell output will pulse when this zone type is alarmed.
Zone type 10 is bypassed when the panel is armed in the STAY or STA
NO DELAY mode.
Zone Characteristics:
• Entry delay #1 (with programmed entry time) when armed in the
AWAY mode.
• Entry delay begins whenever sensors in this zone are violated,
regardless of whether an entry/exit delay zone was tripped first.
• No entry delay when armed in the AWAY NO DELAY mode.
• Exit delay regardless of the arming mode selected.
Zone type 20 is a special-purpose zone type used with 5800 Series
wireless pushbutton units.
Zone Characteristics:
• Exit delay regardless of the arming mode selected.
• System is armed in the STAY mode when the zone is activated.
• Zone number is sent to the central station as a user number when
arming or disarming.
Zone type 21 is a special-purpose zone type used with 5800 Series
wireless pushbutton units.
Zone Characteristics:
• System is armed in the AWAY mode when the zone is activated.
• Zone number is sent to the central station as a user number when
arming or disarming.
Zone type 22 is a special-purpose zone type used with 5800 series
wireless pushbutton.
Zone Characteristics:
• Disarms the system when the zone is activated.
Zone type 23 can be used on a zone when a Powerline Carrier Device
(e.g., X-10) action is desired, but with no accompanying alarm (e.g.,
front door light).
Zone type 24 is usually assigned sensors or contacts on exterior doors
and windows where bells and/or sirens are NOT desired.
Zone Characteristics:
• Instant alarm, with NO audible indication when is armed in the
AWAY, STAY, STAY NO DELAY, or AWAY NO DELAY mode.
• Report sent to the central station.
Note: Keypad beeps if the zone is faulted when system is disarmed and Chime
mode is on.
5806/5807/5808
01000-020-V0
Type 07
24-hour
Audible
Alarm
Type 08
24-hour
Auxiliary Alarm
Type 09
Supervised
Fire
Type 10
Interior w/Delay
Type 20
Arm–Stay
Type 21
Arm–Away
Type 22
Disarm
Type 23
No Alarm Response
Type 24
Silent Burglary
–16–
Data Field Descriptions
Defaults (where applicable) are Indicated in Text.
The following pages list all data fields in this Control (in numerical order). Use the blank programming form
to record the data for this installation. Note that both keypad LEDs flash while in Programming mode.
Note: Entering a number other than the one specified will give unpredictable results.
20
✻
✻21
✻22
✻23
✻24
✻25
✻26
✻27
✻29
✻30
✻31
✻32
✻33
Installer Code
Enter 4 digits, 0-9
Quick Arm Enable
0 = do not allow quick arm
1 = allow quick arm
Keypad Backlight Timeout
0 = no timeout; always backlight keys
1 = turn backlighting off after inactivity
Forced Bypass
0 = no forced bypass
1 = provide automatic bypass of all open (faulted)
zones
RF House ID Code
00 = disable all wireless keypad usage
01-31 = House ID
Powerline Carrier Device (X-10) House ID
0 = A 4 = E 8 = I # + 12 = M
1 = B 5 = F 9 = J # + 13 = N
2 = C 6 = G # + 10 = K # + 14 = O
3 = D 7 = H # + 11 = L # + 15 = P
Chime by Zone
0 = no (chimes on fault of any entry/exit or perimeter
zone when Chime mode is activated
1 = yes (chimes on fault of those zones assigned to
Zone List 3 when Chime mode on)
Real Time Clock Display
0 = do not display the time
1 = display the time
Daylight Savings Time Start/End Month
0, 0 = no daylight saving time used
1-12 = start month and end month
Daylight Savings Time Start/End Week
0 = disable 4 = fourth weekend
1 = first weekend of month 5 = last weekend
2 = second weekend 6 = next to last
3 = third weekend 7 = 3
rd
from last
Single Alarm Sounding Per Zone
(per armed period)
0 = no limit on alarm sounding per zone
1 = limit alarm sounding to once per arming period for
a given zone
Fire Sounder Timeout
0 = yes, fire sounder timeout after time programmed in
1 = no fire sounder timeout; continue sounding until
✻33
field
manually turned off
Alarm Bell Timeout
0 = No timeout 2 = 8 min 4 = 16 min
1 = 4 min 3 = 12 min
The Installer Code is used to enter the 4-digit Master Security Code. See
"Master Code" in the System Operation section for procedure.
Note: LYNX does not allow duplication of Installer code. If a duplicate
code is entered the entry is rejected and LYNX issues single long
beep indicating rejection. The old installer code remains
unchanged.
If enabled, security code is not required to arm the system. The user
simply presses and holds down the AWAY or STAY key to arm.
This option allows the choice of either always backlighting the keypad or
turning the backlighting off after 10 seconds of keypad inactivity.
All zones bypassed by this function will be displayed after the bypass is
initiated.
Note: UL installations: must be 0 (no forced bypass)
The House ID identifies receivers and wireless keypads.
If a 5804BD/5804BDV Transmitter is to be used, a House ID Code MUST
be entered, and the keypad should be set to the same ID.
Powerline Carrier Devices require a House ID. This field identifies this
House ID to the Control. The Powerline Carrier Devices are
programmed in field ✻80.
This option allows the installer to define the specific zones intended to
chime when faulted while the system is in Chime mode. If enabled, these
zones are defined in zone list 3 (see ✻81 Zone List Menu Mode).
Refer to the User’s Manual for setting the clock time and date.
Enter # + 10 for 10, # + 11 for 11, and # + 12 for 12.
Enter the appropriate start and end weekend of the month.
UL installations: must be 0 (no limit)
This field applies only to burglary zones (zone response types 1-5, 10).
Notes: 1. This field applies only to the bell and does not affect keypad
sounds.
2. If swinger shutdown occurs (see Swinger Shutdown in Field
✻92), the number of alarm soundings on a given zone will be
limited by the setting selected in Field ✻92.
This Control complies with NFPA requirements for temporal pulse
sounding of fire notification appliances.
Temporal pulse sounding for a fire alarm consists of the following:
3 pulses – pause – 3 pulses – pause – 3 pulses. . .
This field determines whether the external sounder will shut off after
time allowed, or continue until manually turned off.
UL installations: must be set for a minimum of 4 min (option 1)
–17–
Data Field Descriptions
DELAY PROGRAMMING (✻34–✻36)
NOTE: The control validates the data entered in these fields. If the selection is not valid the control will emit a single long beep indicating that
the selection has been rejected. The control replaces the selection with the default value which is displayed on the keypad.
✻34
Exit Delay
Entries from 45-97
Entered Value Delay in Seconds
45-96 45-96
97 120
✻35
Entry Delay 01
30-99 = entry delay time in seconds.
Entered Value Delay in Seconds
30-96 30-96
97 120
98 180
99 240
✻36
Entry Delay 02
30-99 = entry delay time in seconds.
Entered Value Delay in Seconds
30-96 30-96
97 120
98 180
99 240
✻38
Confirmation of Arming Ding
0 = no arming confirmation ding after arming system
by LYNXR keypad or RF keypad
1 = arming confirmation ding after arming system by
LYNXR keypad or RF keypad
2 = arming confirmation ding after arming from RF
The system will wait the time entered before sounding an alarm if the exit
door is left open after the system has been armed.
UL installations: must be set for a maximum of 60 seconds
SIA Guidelines: must be set to a minimum of 45 seconds
Note: Entries less than 45 seconds will result in a 45 second exit delay.
The system will wait the time entered before sounding alarm upon entering
if system is not disarmed.
UL installations: must be set for a maximum of 45 seconds.
SIA Guidelines: must be set to a minimum of 30 seconds
Note: Entries less than 30 seconds will result in a 30 second exit delay.
UL/SIA The sum of entry delay 1 entered in Field ✻35 and the burglary
abort window entered in ✻50 should not exceed 1 minute.
The system will wait the time entered before sounding alarm upon
entering.
UL installations: must be set for a maximum of 45 seconds
SIA Guidelines: must be set to a minimum of 30 seconds
Note: Entries less than 30 seconds will result in a 30 second exit delay.
UL The sum of entry delay 2 entered in Field ✻36 and the burglary
abort window entered in ✻50 should not exceed 1 minute.
Confirmation of arming is provided by a 1/2 second external sounder “ding” .
The confirmation ding only sounds when LYNX is Armed Away or disarmed
after being Armed Away.
If Option 1 is selected, confirmation of arming is provided by a 1/2 second
sounder “ding” that sounds when closing report is sent, or at the end of exit
delay.
If Option 2 is selected the external sounder “ding” occurs immediately after
arming from an RF keypad.
Note: If LYNX is armed by RF button (key fob), a confirmation ding occurs
immediately after arming regardless of field *38 settings. If LYNX is
disarmed by RF button (key fob), additional disarming confirmation
ding is provided. The ding occurs immediately after disarming and is
longer than arming confirmation ding.
Sets the maximum amount of time in which two cross zones must be
tripped in an armed system to send an alarm message to the Central
Station. If only one cross zone is tripped during this time, a trouble
message (CID code 380) for that zone is sent to the Central Station.
Program Zone list 2 (using *81 Zone List Menu Mode) with the two
zones that are to be cross zoned.
Notes: (1) If option
can be used for other purposes.
(2) Cross zoning will be disabled during entry and exit delays, if
there is already an alarm in the system, if one or both of the 2
cross zones is bypassed.
If one of the 2 cross zones faults and remains faulted after the
cross zone time interval, the second cross zone can go into
alarm immediately, even after the cross zone time. This is to
detect scenarios involving multiple break-ins of a premises.
✻
39 is set to “0” (no cross zoning) then Zone List 2
UL This option is not for use in UL installations.
–18–
Data Field Descriptions
DIALER PROGRAMMING (✻40–✻50)
Fields ✻40, ✻41, ✻42: Enter up to the number of digits shown. Enter 0–9, # + 11 for ‘*’; # + 12 for ‘#’; # + 13 for a pause
(2 seconds)
NOTE: Whenever AAV is used, primary (field ✻41) and secondary (field ✻42) phone numbers should be preceded with the call waiting
disable command. Otherwise, there is the possibility of connection of the third party to LYNX during AAV mode.
✻40
✻41
✻42
PABX Access Code/Call Waiting Disable
Enter up to 6 digits if PABX is needed to access an
outside line.
or
Enter“# + 11 + 7 + 0” to program the touch-tone
sequence “*70” and cancel call waiting.
Primary Phone No.
Enter up to 20 digits.
Secondary Phone No.
Enter up to 24 digits.
If fewer than 6 digits need to be entered, exit by pressing [✻]. To clear
entries from field, press
Call Waiting: If the subscriber’s phone service has “call waiting” (and is
not using PABX), enter the touch-tone sequence“*70” (or similar depending
on the phone service). by programming “# + 11 + 7 + 0” as the PABX entry
to disable “call waiting” during control panel calls. You must also enable
the Call Waiting Cancel option in field *47.
If the subscriber does not have “call waiting” and is not using PABX, make
no entry in this field.
Important Note:
Note: PABX number and operation of the control panel with a PBX system
cannot be used if the Call Waiting Cancel Disable option has been
enabled in Field ✻47.
If fewer than 20 digits entered, exit by pressing [✻]. To clear entries from
field, press
Note: Backup reporting (8 attempts are made to the secondary phone
If fewer than 24 digits entered, exit by pressing [✻]. To clear entries from
field, press
paging feature, enter the pager phone number here.
✻41✻
number if no kissoff is received after 8 attempts to the primary
number) is automatic only if there is a secondary phone number
✻
42).
(field
✻42✻
✻40✻
.
If Call Wait Cancel is disabled in Field
Wait Disable command is entered in Field ✻40, this will
prevent successful communication to the central station
when used on a non-call waiting line.
.
. See backup reporting note for field ✻41. If using the
All four digits of the Subscriber Account number must be entered in Fields ✻43 and ✻44. If ten digit format is
!
selected in ✻48 (option 5), all ten digits of the Subscriber Account number must be entered.
✻47, and Call
Fields ✻43 and ✻44:
Enter [✻] as the fourth digit if a 3-digit account number (for 3+1 dialer reporting format) is used. Enter 0 as the first
digit of a 4-digit account number for Nos. 0000–0999. Enter [
✻
CID®) is used. Exit field by pressing [
] if only 3 digits are used. To clear entries from field, press ✻43
blank Programming Form for examples of account number entries. If using the paging feature, do not enter a leading 0
in the subscriber account number, and do not use digits A-F anywhere in the number. Some paging systems provide
voice mail capability, which is activated by a leading 0 in the message. Enter digits 0–9; # +11=B; # +12=C; # +13=D; #
+14=E; or # +15=F.
✻43
✻44
Primary Subs Account No.
Enter a four or ten digit account number.
Secondary Subs Account No.
Enter a four or ten digit account number.
Field 46: Enter up to 24 digits. Do not fill unused spaces. Enter 0-9, #+11 for ‘*’; #+12 for’#’; #+13 for a pause (2 seconds).
“Follow Me Reminder” Phone Number
✻46
Enter up to 24 digits.
✻
] as the fifth digit if a 4-digit account number (for 3+1,
Enter the primary subscriber account number.
To clear entries from field, press
Enter the secondary subscriber account number.
To clear entries from field, press
This option allows the user to schedule a time driven message. When
activated the system will dial the phone number programmed and deliver a
voice message (custom words 72, 73 and 74). This option is only supported
when the pager or follow me feature is enabled in field
10-13).
If using the Follow Me Reminder feat ure, enter the phone number here. If
fewer than 24 digits are entered, exit by pressing [
the field press
The telephone message can be terminated (acknowledged) by pressing any
key on the telephone keypad. Pressing any key on the local LYNXR-ENSIA
keypad will terminate (acknowledge) both the follow me and the local
reminder announcements.
Note: The follow me reminder announcement will be terminated if any
✻46✻
.
other event requires the system to dial out or if and audible alarm
has occurred.
5 = With
Speaker
Phone
Call Wait
Cancel
Disabled
7 = With
Speaker
Phone
Call Wait
Cancel
Disabled
13 =
With
Speaker
Phone
Call Wait
Cancel
Enabled
15 = With
Speaker
Phone
Call Wait
Cancel
Enabled
This option is used to enter the correct type of phone dialing (pulse or tone),
and to select the correct WATS line option for the Central Station. It is also
to activate the Speaker Phone option and to disable call waiting.
Call waiting warning tones can interfere with Central stations reporting.
The Call Waiting Cancel option should be selected if the reporting phone
line has call waiting service. The Call Waiting Cancel command must also
be programmed in Field *40. If the Call Waiting Cancel feature is enabled,
make sure to enter Call Waiting Cancel command in Field *40. The
command depends on a telephone service provider.
Important Note:
Notes: (1)PABX number and operation of the control panel with a PBX
system cannot be used if the Call Waiting Cancel option has
been enabled in Field ✻47.
(2) If
order to allow the pulse dialer time to operate.
Enter ✻ as the 4th digit of ✻43 through ✻44, if 3+1 dialer reporting is to be
used. (For an explanation of these formats, see the System Communication
section of this manual.)
Notes: (1) The maximum number of alarms is determined by field
(2) If Option 5 is selected a 10-digit account number must be
(3) Option 5 or 7 (ADEMCO Contact ID® Reporting) must be
If Call Wait Cancel is disabled in Field
Waiting Disable command is entered in Field ✻40, this
will prevent successful communication to the central
station when used on a non-call waiting line.
using pulse dialing, you must enter the numbers slowly in
✻47, and Call
✻
✻
entered in Fields
selected for AVM.
43 or ✻44.
92.
–20–
✻49
✻50
✻51
✻52
✻53
54
✻
Split/Dual Reporting
To Primary To Secondary
0 = All reports None, unless primary
fails, then all
1 = Alarms, Restore, Cancel* Others
2 = All except Open/Close, Test Open/Close, Test
3 = Alarms, Restore, Cancel All
4 = All except Open/Close, Test All
5 = All reports All
To Primary To Paging Number
6 = All reports except Open/Close Alarms, Open/Close ‡,
Troubles
7 = All reports Alarms, Troubles
Will report Users 0, 5-8, and, if using wireless button-type
devices, will report the zone number of the arm or disarm
button 26-33. All other zones and users are not reported.
SIA Abort Window time options: 1 = 15 secs; 2 =
30 secs; 3 = 45 secs
0 = refer to Entry delay set in field *35
Periodic Test Report
0 = no test report 2 = weekly
1 = once every 24 hrs 3 = once every 30 days
First test Report Offset
0 = 24 hrs after exit program mode or download
1 = 6 hours after exit program mode or download
2 = 12 hrs after exit program mode or download
3 = 18 hrs after exit program mode or download
0 = Disabled 4 = 90 days
1 = 1 day 5 = 180 days
2 = 7 days 6 = 365 days
3 = 27 days
Note: There will be no local annunciation indicating that
this report has been sent to the Central Station.
Data Field Descriptions
This field is used to select a reporting option as follows:
Enter: 0 - 5 when reporting to telephone receivers.
6 - 9 when reporting to a pager is desired.
10 - 13 when reporting to an auxiliary telephone receiver.
Pager Report Format
Options 6-9 send reports to the primary phone number, in a format defined
✻
in Field
entered as the secondary phone number in Field
7-digit code, with optional 16-digit prefix, in the following format:
AAAAAAAAAAAAAAAA-EEE–00NN where:
AAA = Optional 16 digits for PIN number, etc. See Field
EEE = 3-digit Event Code as follows:
911 = Alarm (NN = zone number)
101 = Open, system disarmed (NN = user no.)
102 = Close, system armed (NN = user no.)
811 = Trouble (NN = zone no.)
‡
00 = Always displayed before 2-digit user/zone no.
NN = 2-digit user number or zone number, depending on the type of
Follow Me System Report Format
Options 10-13 send reports to the primary phone number, in a format
defined in Field
number entered in Field
The message is a repeatable system status announcement. If the manual
paging option has been programmed in Field
“system, system…..”.
The message can be terminated by pressing any key on the telephone
keypad.
This provides the option for an Abort Window for Burglary zone types that
report to the central station. This feature allows time for the subscriber to
avoid a false alarm transmission. This feature does not apply to zone type 9
alarms (Supervised Fire) or to 24-hour zone types 6, 7, and 8 (silent panic,
audible alarm, auxiliary alarm), which are always sent as soon as they occur.
SIA Guidelines: must be set to a minimum of 15 seconds
UL/SIA The sum of the burglary abort window entered in ✻50 and the
Note:
Test report code entered in field ✻64 is sent.
This is the time to first report from programming or downloading.
Select 0 for all other formats.
If enabled, notifies the central station if an end user is not operating their
security system by sending a System Inactivity report 654. The report will
be sent only to the Primary phone number and only if Contact ID® format
was selected.
Note: The report will follow the
48, and send reports to a pager, which has its phone number
description of these characters.
event (EEE) that occurred.
✻
48, and sends voice message to the secondary phone
✻
42.
entry delays entered in either Field ✻35 or ✻36 should not exceed
1 minute.
The control validates the data entered in this field. If the selection is
not valid the control will emit a single long beep indicating that the
selection has been rejected. The control replaces the selection with
the default value which is displayed on the keypad.
0 = no jam detection
1 = RF jam detection with event logging, but no
central station report
2 = RF jam detection with event logging and with
central station report (if trouble/restore report is
enabled in fields ✻60, ✻71)
✻59
Exit Error Report Code
(Always enabled, a report code can be entered if
reporting formats other than Contact ID
® are used)
SYSTEM STATUS AND RESTORE REPORT CODES PROGRAMMING (✻60-✻69, ✻70-✻76, ✻89)
Program Report Codes using the interactive ✻56 Enhanced Zone Programming Mode, or codes can be entered in data
✻
fields
code digits that you enter depend upon the particular installation, and should be in agreement with you and the central
station office receiving the signals.
With a 3+1 or 4+1 Standard Format: Enter a code in the first box: 1–9, A, B, C, D, E, or F. Enter "#+10" for A
(reports a “0” on some receivers), "#+11" for B, "#+12" for C, "#+13" for D, "#+14" for E, "#+15" for F. Entering "0" in the
first box will disable a report. Entering "0" in the second box results in automatic advance to the next field.
With an Expanded or 4+2 Format: Enter codes in both boxes (1st and 2nd digits) for 1–9, or A–F, as described above.
Entering "0" in the first box will disable a report. Entering "0" in the second box will eliminate the expanded message for
that report.
With ADEMCO Contact ID® Reporting: Enter a digit in the first box to enable the zone to report. Use a different
digit for each zone until you have used up available digits. If the number of zones exceeds the number of available
digits, begin with digit 1 again. This is an "enabling" code only and is not the actual code sent to the central station
office. Entries in the second boxes will be ignored. For system status (non-alarm) codes, enter a “1” in the first box for all
the system conditions you want to send to the central station. A "0" in the first box disables the report.
60-✻69, ✻70-✻76, ✻89. The following is a set of guidelines when programming report codes. The actual report
The control validates the data entered in this field. If the selection is
Note:
not valid the control will emit a single long beep indicating that the
selection has been rejected. The control replaces the selection with
the default value which is displayed on the keypad.
Cancel Alarm Display
This option enables the display of aborted and cancelled alarms on the
LYNXR-ENSIA keypad. “CA” will be displayed.
Notes: 1. An abort occurs if the alarm panel is disarmed before it dials the
2. A cancel occurs if the alarm panel is disarmed after the alarm is
3. Zone types 5, 6 and 7 (panic zone types) and 24 (silent burglary)
Auto Stay Arming
If this feature is enabled and the control panel has been armed “Armed
Away” at the LYNX keypad or RF keypad, the system will switch to the
“Armed Stay” mode if the Exit Time has expired and no exit has been
made.
Exit Time Restart-Exit Delay Restart/Reset
This option allows the systems to restart the exit delay time
after arming in STAY mode by entering the User Code and pressing the
STAY key (if quick arming is disabled) or by pressing the STAY key (if
quick arming is enabled). This option also enables automatic exit delay
reset, which resets exit delay if the entry/exit door is re-opened and closed
before exit delay time expires after arming.
Notes: 1. This avoids the need to disarm and then re-arm the system after
2. Automatic Exit Delay Reset occurs only once during an armed
For Event Logging, Option 2 must be selected.
If the control detects an RF jam condition, a “FAULT” message appears for
zone 90. The Contact ID® code for RF Jam is 344.
If the system is armed and an entry/exit or interior zone is still open after
the exit delay time has expired, an alarm will sound at the keypad and
external sounder (the keypad will also display “EA”) , and the entry delay
begins. If the system is disarmed before the end of the entry delay that
immediately follows, the alarm sounding will stop and no message will be
sent to the central station. The keypad will display “CA “(CANCELED
ALARM) if the cancel display option was enabled in field ✻57.
If the system is not disarmed before the end of the entry delay mentioned
above, and an entry/exit or interior zone is still open, an “Exit Alarm”
message and a “Zone Alarm” message will be sent to the central station.
The keypad will display “EA (EXIT ALARM),” and the alarm sounding will
continue until the system is disarmed (or timeout occurs).
If Contact ID® format has been programmed, the message will contain the
zone number and error code 374 (Alarm–Exit Error).
alarm report to the central station.
reported.
cannot be cancelled.
allowing someone to enter or exit.
period.
–22–