Ademco 8DL5808W3XT Users Manual

5808W3 Photoelectronic Smoke/Temperature
PLEASE GO TO THE BOTTOM OF PAGE 4 FOR THE FCC & IC STATEMENTS
Detector with Built-in Wireless Transmitter
INSTALLATION AND SETUP GUIDE
I56-2768-005R
General Information
Before installing detectors, please thoroughly read these installation instructions and Guide for Proper Use of System Smoke Detectors (A05-1003-002), which provides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of this manual are available from Honeywell.
NOTICE: This manual sh ould be left with the owner/user of this equipment.
IMPORTANT: This detector must be tested and maintained regularly following NFPA 72 requirements.
General Description
Two LEDs and a sounder on the detector provide local visual and audible indication of the detector’s status:
Table 1: Detector LED Modes
Green LED Red LED
Power Up
Normal (standby)
Out of Sensitivity Off
Freeze Trouble Off
Smoke Alarm Off
Thermal Alarm Off
Low Battery Off
During initial power-up, the red and green LEDs will blink synchronously once every 5 seconds. It will take approximately 20 seconds for the detector to finish the power-up cycle (see Table 1).
Blinks every
5 sec
Blinks every
10 sec
Blinks every
5 sec
Off Off
Blinks every
5 sec
Blinks every
10 sec
Blinks every
1 sec
Blinks every
4 sec
Blinks every
45 sec
Piezoelectric
Horn
Off
Off
Off
Temporal Pattern
Temporal Pattern
Chip every 45 sec after LED
blinks for 7 days
The 5808W3 contains a piezoelectric horn which generates the ANSI S3.41 temporal pattern in an alarm condition. In alarm, a message is also sent to the wireless control panel. The alarm message is transmitted every 4 seconds until the smoke or heat condition has cleared and the detector has reset. During an alarm condition, pressing the detector’s test switch will silence the piezoelectric horn for 5 minutes. Once the detector has reset, a RESTORE message is transmitted to the control panel. The built-in Drift Compensation algorithm automatically maintains the sensitivity of the detector. Once the detector reaches its limit of compensation, it transmits a maintenance signal to the panel. The mounting base installation is simplified by the incorporation of features compatible with drywall fasteners or other methods that provide a method for securing the detector in place.
After power-up has completed and the detector is functioning normally within its listed sensitivity range, the green LED blinks once every 10 seconds. If the detector is in need of maintenance because its sensitivity has shifted outside the listed limits, the red LED blinks once every 5 seconds. When alarm has been activated by smoke, the red LED blinks every 1 second. During a thermal alarm condition (>135°F) the red LED blinks once every 4 seconds. The LED indication must not be used in place of the tests specified under Testing. In a freeze trouble condition, the red LED will blink once every 10 seconds (refer to Table 1). If the detector senses a low battery condition, the red LED blinks once every 45 seconds.
To measure the detector’s sensitivity, the i3 Series Model SENS-RDR Infrared Sensitivity Reader tool (see Figure 4) should be used. Refer to instruction manual D100-98-00 for proper use of the SENS-RDR.
Low Battery Detection
The 5808W3 is powered by a single 3-volt CR123A or DL123A Lithium battery (included). The detector checks for a low battery at least every 65 minutes. If a low battery is detected, the transmitter sends a low battery message to the control panel, which beeps and displays the detector ’s zone number. In addition, the red LED of the 5808W3 will blink every 45 seconds and the test switch will be disabled. This condition will exist for a minimum of 7 days, and then the detector’s horn will “chirp” about every 45 seconds. Pressing the test switch during this time will silence the chirps for 12 hours. The battery should be replaced BEFORE the chirps begin. Be sure to replace the battery with a fresh one.
- 1 -
Battery Installation and Replacement
TEST SWTICH
RED LED
GREEN LED
DIRECT MOUNT HOLES
TAMPER RESISTANT TA B
(CUT OFF SMALL TAB TO ACTIVATE
TAMPER RESIST FEATURE)
TAMPER RELEASE TAB
To replace the battery:
1. Remove the detector from its mounting base by twisting the detector counterclockwise. Remove the battery, and dispose properly.
2. To ensure proper power-down sequence, wait a minimum of 20 seconds before installing new battery.
3. Install a new 3-volt CR123A Lithium battery in the battery compartment. Follow the polarity diagram inside the compartment.
4. Reinstall the smoke detector onto the mounting base by turning the detector clockwise.
6. When the serial number is displayed, transmit from the detector a second time by activating the tamper switch again as described in Step 5. The current loop number (4) will begin to flash.
7. Manually change the loop number to the desired loop number for the zone (according to the application).
8. When programming for this zone is complete, program other zones for the transmitter as necessary (except for Tamper Loop 4, which does not require programming).
WARNING: The fire protection zone enrolled must always be
Loop 1. Otherwise, fire annunciations will not be reported by the control.
9. Exit Programming mode when programming is complete, and test the detector. Refer to the Testing Section.
See the control unit’s installation instructions for further details.
Mounting
First, determine the best location for the smoke detector, one that provides a strong wireless transmission path and proper smoke detection. A GOOD TRANSMISSION PATH MUST BE ESTABLISHED FROM THE PROPOSED MOUNTING LOCATION BEFORE PERMANENTLY INSTALLING THE DETECTOR. To check, perform the test described in the TESTING SIGNAL STRENGTH section of this manual. Prior to mounting the detector to the mounting base, you must “enroll” the detector’s serial number into the system (see the PROGRAMMING section). To mount the detector, perform the following steps:
Programming
The smoke detector must be enrolled in the control panel before it can operate in the system. The 5808W3 smoke/heat protection zone must be enrolled as Loop 1 and “Input Type” 3 (supervised RF).
If programmed, this smoke detector is capable of monitoring the additional conditions of Maintenance (transmitted as Loop 2), and Low Temperature (transmitted as Loop 3). Tamper is transmitted as Loop 4, but does not require programming. To take advantage of the value added features of Maintenance and Low Temperature, you must program each loop as a separate zone in the 5800 series wireless compatible panel.
1. Enter the control’s Zone Programming mode.
2. Enter the zone number to be programmed.
3. Enter the applicable zone type when prompted. Program
•Loop1(Heat/Smoke)asaFirezone(type9or16),
•Loop2(High/LowMaintenance)asa24-Hr.Troublezone(type
•Loop3(FreezeWarningSensor)asa24-Hr.Aux.zone(type8).
NOTE: Loop 2 High/Low Maintenance is supported only on
4. When prompted, enter Input Type 03 (3 on some controls)
5. When prompted for the serial number, transmit from the detector
S0289-00
Figure 1. 5808W3 Wireless Smoke/Heat Detector
19), and
commercial control panels such as the Vista-128FBP.
– Supervised RF Transmitter.
by activating the tamper switch. To do this, hold the base of the detector in one hand, and rotate the detector counter-clockwise on the base until it snaps open. Then return to clockwise position until the detector snaps into place.
1. Once a suitable location has been determined, install the mounting base on the ceiling or on the wall (if local ordinances permit). Use the two screws and anchors provided.
2. Turn the detector in a clockwise direction in the mounting base until it clicks into place.
3. Test the detector immediately after completing the installation (as described in the TESTING section of this manual) and refer to the control system’s instructions for additional information concerning the use of wireless smoke detectors.
S0290-00
Figure 2. Detector Mounting Base
S0162-01
Figure 3. Mount Detector Across Ceiling Panel Support
DO NOT attach the detector to removable ceiling panels. Attach the detector across panel support as shown in Figure 3.
- 2 -
Loading...
+ 2 hidden pages