Smoke detectors are not to be used with detector guards unless the combina-
TAMPER SLOT
(DEPRESS TAB TO
REMOVE DETECTOR)
TAMPER RESISTANT TAB
(CUT OFF SMALL TAB TO
ACTIVATE TAMPER-RESIST
FEATURE)
ALIGNMENT
ARROWS
tion has been evaluated and found suitable for that purpose.
DO NOT attach the detector to removable ceiling panels. Attach the detector
across panel support as shown in Figure 3.
WHAT TO DO IN CASE OF FIRE
1. DON’T PANIC — escape may depend on clear thinking.
2. Get out of the house following the planned escape routes, if possible. Do
not stop to dress or to collect anything.
3. Open doors carefully only after feeling them to see if they are hot. If a door
is hot, do not open it— follow an alternate escape route.
4. Keep close to the floor — smoke and hot gases rise. Breathe through a
cloth (wet, if possible) and take short shallow breaths.
5. Keep doors and windows closed unless it is necessary to open them for
escape.
6. Meet at your meeting place after leaving your home.
7. Call the local fire department as soon as possible from outside
the home.
8. Never re-enter a burning building.
For more information about fire safety, contact your local fire department. They
can supply more detailed information about making your home as free from fire
hazards as possible and about planning for escape in case of fire.
MOUNTING
First, determine the best location for the smoke detector; a location that provides strong wireless transmission paths and proper smoke detection. A GOOD
TRANSMISSION PATH MUST BE ESTABLISHED FROM THE PROPOSED
MOUNTING LOCATION BEFORE PERMANENTLY INSTALLING THE
DETECTOR. To check, perform the test described in the TESTING
TRANSMITTER SIGNAL section of this manual. To mount the detector:
1. Once a suitable location has been determined, install the mounting bracket
on the ceiling or on the wall (if local ordinances permit). Use the two screws
and anchors provided.
2. Prior to mounting the detector to the mounting bracket, the system must
“enroll” the detector’s ID. See the PROGRAMMING section for the steps to
follow.
3. Turn the detector in a clockwise direction in the mounting bracket until it
clicks into place.
4. Test the detector immediately after completing the installation (as described
in the TESTING section of this manual) and refer to the control system’s
instructions for additional information concerning the use of wireless smoke
detectors.
TAMPER PROTECTION
This detector has a built-in tamper switch that will cause a CHECK signal to
be displayed at the console of the detector if it is removed from its installation
bracket. The mounting bracket can also be made tamperproof by breaking off
the smaller tab at the scribed line (see Figure 2), thus preventing removal of
the detector without a tool. To remove the detector, use a small screwdriver to
depress the tamperproof tab and turn the detector counterclockwise.
TESTING
NOTE: Before testing, notify the proper authorities that the smoke detector
system is undergoing maintenance and will temporarily be out of service. Disable the zone or system undergoing maintenance to prevent
unwanted alarms.
Detectors must be tested after installation and following periodic maintenance.
The 5808LST may be tested as follows:
A. TEST SWITCH
1. A recessed test switch is located on the detector housing.
2. Push and hold the recessed test switch for a minimum of 5 seconds.
Use a small screwdriver or allen key maximum diameter of .18” (The
alarm panel will trigger and then the smoke detector will go into alarm. If
the tool is removed from the recessed switch the sounder will shut off.)
3. The LED on the detector should blink once per second and the horn
should sound within 3 seconds.
B. SMOKE ENTRY TEST
Hold a smoldering punk stick or cotton wick at the side of the detector and
gently blow smoke through the detector until the unit alarms.
C. DIRECT HEAT METHOD (Hair dryer of 1000-1500 watts)
Direct the heat toward either side thermistor. Be sure to hold the heat
source about 12 inches from the detector to avoid damage to the plastic.
The detector will reset only after it has time to cool.
Smoke detection testing is recommended for verifying system protection
capability.
A detector that fails to activate with any of these tests should first be cleaned
as outlined in this manual’s MAINTENANCE section. If the detector still fails to
activate, return for repair.
Notify the proper authorities that the system is back on line.
Figure 2. Detector Mounting Bracket
Figure 3. Mount Detector Across Ceiling Panel Support
S0158-00
S0162-00
TESTING TRANSMITTER SIGNAL
NOTE: Remove battery tab before installation.
This test should be performed before installation to determine a strong com
munication path with the control panel and after installation is complete. Also,
the owner/user should test the unit at least weekly.
1. Activate the wireless system’s TEST mode from the console.
2. Depress and hold the smoke detector’s TEST switch and the detector
should immediately transmit an alarm signal to the control panel. The builtin horn will start to sound about 2.5 seconds after depressing the button.
3. The wireless system’s console should emit at least 3 audible sounds
when the alarm transmission is received and will display the transmitting
detector’s ID number.
4. When the console has received the test signal, release the TEST switch.
The horn will immediately stop and a few seconds later the detector’s ID
number will clear from the console display.
5. If the console does not respond as noted, check the polarity of the batter
ies and be sure they are fresh. If this is an initial installation, try moving
the detector to another location that provides proper reception. Also be
sure that the detector’s ID has been “enrolled” by the control panel (see
PROGRAMMING). Then, repeat the test.
6. Turn off the system’s TEST mode from the console (security code + OFF).
-
-
AD300-00-00 3 I56-918-14R
MAINTENANCE
REMOVABLE
HOUSING
BASE
REMOVABLE
SCREEN
SENSING
CHAMBER COVER
SENSING
CHAMBER
NOTE: Before removing the detector, notify the proper authorities that the
smoke detector system is undergoing maintenance and will be temporarily out of service. Disable the zone or system undergoing maintenance to prevent unwanted alarms.
NOTE: Before removing the detector cover, note the position of the thermis
tors. Make sure the thermistors are not bent over when the housing is
replaced.
1. Remove the detector housing by gently prying the four housing tabs
on the bottom of the base with a small-bladed screwdriver and pull
the housing from the base. Use caution to avoid damaging the
thermistors.
2. Vacuum the screen carefully without removing it.
3. Remove screen assembly, pulling straight out (please see Figure 4).
4. Remove the sensing chamber cover.
5. Clean the sensing chamber by vacuuming or blowing out dust and
particles.
6. Replace the sensing chamber cover, aligning the arrow on the cover
top with the arrow on the printed circuit board.
7. Replace the screen by placing the screen assembly over the sensing
chamber cover and twisting until it snaps into place.
8. Replace the housing by aligning the two triangular slots on the
base with their counterparts on the housing. Gently press the
housing until it locks in place. Check to make sure that the ther-
mistors are in the upright position.
9. Reinstall the detector.
10. Notify the proper authorities that the system is back in operation.
-
S0163-00
Figure 4. Removal of Cover and Screen for Cleaning
Please refer to insert for the Limitations of Fire Alarm Systems
LIMITED WARRANTY
Honeywell International Inc., acting through its Security & Custom Electronics business (“Seller”) 165 Eileen Way, Syosset, New York 11791, warrants its
product(s) to be in conformance with its own plans and specifications and to be free from defects in materials and workmanship under normal use and service for
24 months from the date stamp control on the product(s) or, for product(s) not having a manufacturer’s date stamp, for 12 months from date of original purchase
unless the installation instructions or catalog sets forth a shorter period, in which case the shorter period shall apply. Seller’s obligation shall be limited to repairing
or replacing, at its option, free of charge for materials or labor, any product(s) which is proved not in compliance with Seller’s specifications or proves defective
in materials or workmanship under normal use and service. Seller shall have no obligation under this Limited Warranty or otherwise if the product(s) is altered
or improperly repaired or serviced by anyone other than Honeywell factory service. For warranty service, return product(s) transportation prepaid, to Honeywell
Factory Service, 165 Eileen Way, Syosset, New York 11791.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, OF MERCHANTABILITY, OR FITNESS FOR A PARTICULAR PURPOSE OR OTHERWISE, WHICH
EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. IN NO CASE SHALL SELLER BE LIABLE TO ANYONE FOR ANY CONSEQUENTIAL OR
INCIDENTAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY, EXPRESS OR IMPLIED, OR UPON ANY OTHER BASIS OF LIABILITY
WHATSOEVER, EVEN IF THE LOSS OR DAMAGE IS CAUSED BY THE SELLER’S OWN NEGLIGENCE OR FAULT.
Seller does not represent that the product(s) it sells may not be compromised or circumvented; that the product(s) will prevent any personal injury or property loss
by burglary, robbery, fire or otherwise; or that the product(s) will in all cases provide adequate warning or protection. Customer understands that a properly installed
and maintained alarm system may only reduce the risk of a burglary, robbery, fire, or other events occurring without providing an alarm, but it is not insurance or
a guarantee that such will not occur or that there will be no personal injury or property loss as a result.
CONSEQUENTLY, SELLER SHALL HAVE NO LIABILITY FOR ANY PERSONAL INJURY, PROPERTY DAMAGE OR OTHER LOSS BASED ON A CLAIM THAT
THE PRODUCT(S) FAILED TO GIVE WARNING. HOWEVER, IF SELLER IS HELD LIABLE, WHETHER DIRECTLY OR INDIRECTLY, FOR ANY LOSS OR
DAMAGE ARISING UNDER THIS LIMITED WARRANTY OR OTHERWISE, REGARDLESS OF CAUSE OR ORIGIN, SELLER’S MAXIMUM LIABILITY SHALL
NOT IN ANY CASE EXCEED THE PURCHASE PRICE OF THE PRODUCT(S), WHICH SHALL BE THE COMPLETE AND EXCLUSIVE REMEDY AGAINST
SELLER.
USER CAUTION: Changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate
the equipment.
.
AD300-00-00 4 I56-918-14R
This device complies with Part 15 of the FCC Rules. Operation is subject
to the following two conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation
FCC ID: CFS8DL5808AP
FCC PART 15 STATEMENT
©2005 Honeywell