Ademco 8DL5800STAT Users Manual

535
T8665A Chronotherm® IV
Deluxe Programmable
Wireless Thermostat
INSTALLATION INSTRUCTIONS

APPLICATION

The T8665 Chronotherm® IV Wireless Thermostat provides electronic control of 24 Vac heating and cooling systems. It must be used with a W8665 Receiver
Table 1. T8665A Thermostat Description.
T8665 System Changeover System Selection Fan Selection Comments
A Heat-Cool Automatic Heat-Off-Cool-Auto On-Auto System and fan
MERCURY NOTICE
If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of the old thermostat.

INSTALLATION

Accessory Required (Not Included)
Select one of the receiver modules for your application:
— W8665A Receiver Module (RM) for single zone
applications.
— W8665E RF Zone™ Panel for up to three zones.

When Installing this Product...

Read these instructions carefully. Failure to follow
1.
the instructions can damage the product or cause a hazardous condition. Check the ratings given in the instructions and on
2.
the product to make sure the product is suitable for your application. Installer must be a trained, experienced service
3.
technician. After completing installation, use these instructions
4.
to check out the product operation.
Module. Refer to Table 1 for a general description of the thermostat. The T8665A Thermostats are battery­powered.
selections are entered at keyboard.

Location

Install the thermostat about 5 ft (1.5m) above the floor in an area with good air circulation at average temperature. See Fig. 1.
Do not install the thermostat where it can be affected by: — drafts, or dead spots behind doors and in corners. — hot or cold air from ducts. — radiant heat from sun or appliances. — concealed pipes and chimneys. — unheated (uncooled) areas such as an outside wall
behind the thermostat.

Wallplate Installation

The thermostat can be mounted horizontally on the wall or on a 2 in. x 4 in. wiring box. Position wallplate horizontally on the wall or on a 2 in. x 4 in. wiring box.
Position and level the wallplate (for appearance
1.
only). The thermostat functions correctly even when not level. Use a pencil to mark the mounting holes. See Fig.
2.
2. Remove the wallplate from the wall and drill two
3.
3/16 in. holes in the wall (if drywall) as marked. For firmer material such as plaster, drill two 7/32 in. holes. Gently tap anchors (provided) into the drilled holes
4.
until flush with the wall. Position the wallplate over the holes.
5.
Loosely insert the mounting screws into the holes.
6.
Tighten the mounting screws.
7.
® U.S. Registered Trademark Copyright © 2001 Honeywell • •All Rights Reserved
69- 1
WIRELESS THERMOSTAT
M14628
PRESS LOWER EDGE OF CASE TO LATCH.
ENGAGE TABS AT TOP OF THERMOSTAT AND WALLPLATE.
A.
B.
NO
NO
[1.5 METERS]
Fig. 1. Typical thermostat location.
WIRES THROUGH WALL
YES
5 FEET
WALL

Mounting Thermostat

Engage tabs at the top of the thermostat and wall-
1.
plate. See Fig. 3. Press lower edge of case to close and latch.
2.
NOTE: To remove the thermostat from the wall, first pull
NO
M10106
out at the bottom of the thermostat; remove top last.
WALL ANCHORS (2)
Fig. 2. Mounting the wallplate.
MOUNTING HOLES
MOUNTING SCREWS
M15044
Fig. 3. Mounting thermostat on wallplate.

Using Thermostat Keys

The thermostat keys are used to:
set current day and time.
program times and setpoints for heating and cooling.
temporarily override program temperatures
display present setting,
configure Installer Setup,
check self-test,
set the system operation,
set the fan operation.
See Fig. 4 for key locations.
69-1535 2
WIRELESS THERMOSTAT
INCREASE TIME SETTING OR SCROLL FORWARD THROUGH INSTALLER SETUP AND SYSTEM TEST
SET CURRENT DAY AND TIME
RETURN TO NORMAL OPERATIONS
ENTER INDEFINITE OR TIMED HOLD MODE
SET CURRENT OR PROGRAM DAY
CHANGE BETWEEN DAYLIGHT SAVINGS AND STANDARD TIME
SET WAKE TIMES AND SETPOINTS
Set Current
Run
Day/Time
Program
Hold Temp
Day
Daylight
Time
COPY ONE PROGRAMMED DAY TO ANOTHER DAY
SET LEAVE TIMES AND SETPOINTS
Time Set Program
Heat/Cool
Settings
Copy
Fig. 4. T8665A key locations and descriptions.

Setting up T8665A to Send Signal to W8665A,E Receiver Module

The T8665A Thermostat must be set up to send signals to the W8665 Receiver Module. Use the W8665A Receiver for single-zone applications. Use the W8665E RF Zone Panel for up to three T8665A Thermostats for multizone applications.
Single Zone Applications (one T8665A/ one W8665A)
Place the Zone 1 DIP switch on the W8665A
1.
Receiver to the On position.
NOTE: Observe that the Zone 1 LED on the W8665
flashes.
Press the thermostat Fan key to the On position.
2.
The receiver accepts the message, stores identity and then stops flashing the Zone 1 LED. The ther­mostat is now set up to send signals the W8665A Receiver.
NOTE: The word On and a fan blade appear in the
thermostat display to indicate the thermostat is calling for the fan to turn on.
Set the System and Fan keys to the desired loca-
3.
tions.
NOTE: At any time, if you want to stop the thermostat
from sending signals to the W8665 Receiver, simply turn the DIP switch to the Off position. Follow the instructions in steps above to set up the thermostat again to send signals to the W8665A Receiver.
Multizone Applications (Up to three T8665A/ one W8665E)
IMPORTANT
The thermostats must be set up one zone at a time to ensure a unique address is used for each zone.
SET RETURN TIMES AND SETPOINTS
Leave
Wake
DECREASE TIME SETTING OR SCROLL BACKWARD THROUGH INSTALLER SETUP AND SYSTEM TEST
Return Sleep
System Fan
Place the Zone 1 DIP switch on the W8665E
1.
Receiver to the On position.
NOTE: Observe that the Zone 1 LED on the W8665
flashes.
Press the thermostat Fan key to the On position.
2.
The Receiver accepts the message, stores the identity of that zone, and stops flashing the Zone 1 LED. The thermostat is now set up to send signals to Zone 1 of the W8665E Receiver.
NOTE: The word On and a fan blade appear in the
thermostat display to indicate the thermostat is calling for the fan to turn on.
Set the System and Fan keys to the desired loca-
3.
tions.
NOTE: At any time, if you want to stop the thermostat
from sending signals to the W8665 Receiver, simply turn the DIP switch to the Off position. Follow the instructions in steps above to set up the thermostat again to send signals to the W8665E Receiver.
Repeat steps 1-3 for zones two and three.
4.
Attach the zone number stickers, included with the
5.
thermostat, onto the thermostat case on the inside of the thermostat cover. See Fig. 5.
Fig. 5. Zone stickers included with T8665A
INCREASE TEMPERATURE SETTING OR SCROLL FORWARD THROUGH INSTALLER SETUP OPTIONS
DECREASE TEMPERATURE SETTING OR SCROLL BACKWARD THROUGH INSTALLER SETUP OPTIONS
DISPLAY INFORMATION SUCH AS PRESENT SETTINGS
SET SLEEP TIMES AND SETPOINTS
SELECT FAN OPERATION
SELECT SYSTEM OPERATION
CHANGE BETWEEN HEATING AND COOLING SETPOINTS
Zone 2
Zone 3
Zone 1
Place one label inside each thermostat door.
Thermostat.
M13426
M20166
3 69-1535
WIRELESS THERMOSTAT

SETTINGS

System and Fan Settings

The system default setting is Heat and the fan default setting is Auto. Use the System and Fan keys to change the settings. See Fig. 6. The fan settings can be set for each program period individually. The system selection is for all the program periods.
System settings control the thermostat operation as follows:
Heat: The thermostat controls the heating.
Off: Both the heating and cooling are off.
Cool: The thermostat controls the cooling.
Auto: The thermostat automatically changes between heating and cooling operation, depending on the indoor temperature.
Fan settings control the system fan as follows:
On: Fan operates continuously.
Auto: Fan operates with equipment.
Time Set Program
Run
Set Current
Program
Day/Time
Hold Temp
Day
Daylight
Time
Fig. 6. Thermostat System and Fan key locations.
NOTE: Always press the keys with your fingertip or sim-
ilar blunt tool. Sharp instruments like a pen or pencil point can damage the keyboard.

Programmed Temperature Settings

Refer to Table 2 for the default program. If the daytime energy savings period is not used, press the period key (Leave or Return) until the time is blank. The fan setting feature is available on select thermostat models. See Owners Guide for complete instructions on changing the program.
Leave
Wake
Heat/Cool
Settings
Copy
Return
System Fan
Sleep
System
Fan
M14625
Table 2. Default Program Settings.
Period Time
Wake 6:00 AM70°F
Leave 8:00 AM62°F
Return 6:00 PM70°F
Sleep 10:00 PM62°F
Setpoint
(21°C)
(16.5°C)
(21°C)
(16.5°C)
Heat
Cool
Setpoint
78°F (25.5°C)
85°F (29.5°C)
78°F (25.5°C)
82°F (28°C)
Fan
Setting
Auto
Auto
Auto
Auto

INSTALLER SETUP

NOTE: For most applications, the thermostat factory-
settings do not need to be changed. Review the factory default settings in Table 3 and, if no changes are necessary, go to the Installer Self­Test section.
The Installer Setup is used to customize the thermostat to specific systems. Some of the options include temperature display and system changeover. Installer Setup numbers are listed in Table 3. The table includes all the configuration options and the factory-settings for the T8665.
A combination of key presses are required to use the Installer Setup feature:
To enter the Installer Setup, press and hold the
Information i key with the increase ▲ and decrease keys until the first number is displayed. All display segments appear for approximately three seconds before the number is displayed. See Fig. 7 and 8.
To advance to the next Installer Setup, press the Time
key.
To change a setting, use the increase ▲ or decrease
key.
To scroll the Installer Setup numbers backward, press
the Time ▼ key.
To exit the Installer Setup, press Run Program.
Wait Recovery
Hold for
Filter
Em Ht
Mon
TueWed Thu Fri Sat Sun
Wake Leave Return Sleep
Set Day/TimeSet Program
Aux Ht
Days
AM PM
Temporary Setting
Repl Batt
DST
Fig. 7. DIsplay of all LCD segments.
Heat
OutdoorRoom
Cool
System
Em Heat
Fan
M14559
Cool Auto
Auto
Off
On
69-1535 4