Ademco 8DL5800CO User Manual

5800CO Carbon Monoxide Detector
PLEASE GO TO THE BOTTOM OF PAGE 4 FOR THE FCC / IC STATMENTS
with Built-in Wireless Transmitter
INSTALLATION AND SETUP GUIDE
GENERAL INFORMATION
The 5800CO is a 3V battery powered wireless Carbon Monoxide (CO) detector intended for use with wireless alarm systems that support 5800 series devices. Refer to control/communicator installation instructions for compatibility.
The detector consists of an electrochemical carbon monoxide sensor assembly coupled to a wireless transmitter. The transmitter can send alarm, trouble, tamper, and battery condition messages to the system’s receiver. Refer to the wireless system’s instructions for the maximum number of transmitters that can be supported.
NOTICE: This manual should be left with the owner/user of this equipment.
IMPORTANT: This detector must be tested and maintained regularly following NFPA 72 requirements.
WARNING: This product is intended for use in ordinary indoor locations of dwelling units, including homes, residential buildings, hotels, schools, dormitories, and day care centers. It is not intended for use in industrial factories or commercial parking garages.
Detector Description
• Listed to UL standard 2075 (pending)
• Supervised
• Local sounder
• Dual LED’s
• Test/Hush button
• Surface mount to wall or ceiling
• Optional drywall anchors included
The 5800CO contains a piezoelectric horn which generates the ANSI S3.41 temporal 4 pattern in an alarm condition (see note below Table 1 for temporal 4 pattern). In alarm, a message is also sent to the wireless control panel and the detector’s zone number is displayed at the console. The alarm message is transmitted every 4 seconds until the carbon monoxide condition has cleared and the detector has reset. During an alarm condition, pressing the detector’s test button will silence the piezoelectric horn for 5 minutes. Once the detector has reset, a RESTORE message is transmitted to the control panel and the transmitter’s zone number can be cleared from the panel. The mounting base installation is simplified by the incorporation of features compatible with drywall fasteners or other methods that provide a method for securing the detector in place.
During initial power-up, the red and green LEDs will blink together once every 10 seconds up to four times. It takess about 30 seconds for the detector’s CO sensor to stabilize (see Table 1).
After power-up has completed and the detector is functioning normally within its listed sensitivity range, the green LED blinks once every 10 seconds. The LED indication must not be used in place of the tests specified under TESTING THE DETECTOR. In a trouble condition, the red LED will blink once every 10 seconds (refer to Table 1). If the detector senses a low battery condition, the red LED blinks once every 45 seconds.
Two LEDs and a sounder on the detector provide local visual and audible indication of the detector’s status as listed in Table 1.
Table 1: Detector LED Modes
Normal (standby)
Alarm/Test Off
Low Battery Off
Communication Fail
Trouble Off
Detector End-of­Life
Power Up
† Temp 4 pattern is repeated pattern of four short beeps followed by a five second pause. When the detector has been in alarm for 30 minutes, the alarm signal will be given once every minute. If ambient conditions return to normal, the detector will self-restore out of alarm and into Normal (standby) mode.
†† Red and green LEDs blink a total of four times, once every 10 seconds.
Hush feature: If required, the audible alarm can be silenced for 5 minutes by pushing the button marked “Test/Hush”. The red alarm light will continue to flash in temp-4 pattern. If carbon monoxide is still present after the 5 minute hush period, the audible alarm will sound. The hush feature will not operate at levels above 350 ppm (parts per million) carbon monoxide.
Trouble feature: When the sensor supervision is in a trouble condition, the detector will send a trouble signal to the panel. Trouble conditions include an open circuit, sensor removal (tamper), and sensor end of life.
End of Life Timer feature: When the detector has reached the end of its life, the trouble contact will open. This indicates that the CO sensor inside the detector has passed the end of its life and must be replaced. This detector’s lifespan is approximately six years from the date of manufacture. Refer to Detector Replacement section
Low Battery Detection:
volt CR123A or DL123A Lithium battery (included). The detector checks for a low battery at least every 65 minutes. If a low battery is detected, the transmitter sends a low battery message to the control panel, which beeps and displays the detector’s zone number. In addition, the red LED of the detector will blink every 45 seconds and the test button will be disabled. This condition will exist for a minimum of 7 days, and then the detector’s horn will “chirp” about every 45 seconds. Pressing the test button during this time will silence the chirps for 12 hours. The battery should be replaced BEFORE the chirps begin. Be sure to replace the battery with a fresh one.
Green LED Red LED Sounder
Blinks every 10 seconds
Off
Off
Blinks every 10 secs
(w/red LED)
Off Off
Blinks every 1 second
Blinks every 45 seconds
Blinks every 5 seconds
Blinks every 5 seconds
Blinks every 10 seconds
Blinks every
††
††
10 secs
(w/green LED)
Temporal 4
Pattern
Chirp every 45 sec after LED blinks for 7 days
Off
One chirp every 45 seconds
Off
Off
The 5800CO is powered by a single 3-
BATTERY INSTALLATION AND REPLACEMENT
To replace the battery:
1. Remove the detector from its mounting base by twisting the detector counterclockwise. Remove the battery, and dispose properly.
2. To ensure proper power-down sequence, wait a minimum of 20 seconds before installing new battery.
3. Install a new 3-volt CR123A Lithium battery in the battery compartment. Follow the polarity diagram inside the compartment.
4. Reinstall the detector onto the mounting base by turning the detector clockwise.
5. Test the detector as described in the TESTING SIGNAL STRENGTH section of this manual. The green LED should blink about once every 10 seconds to indicate normal operation. If the battery is not installed correctly, the detector will not operate and the battery may be damaged. If the detector does not appear to be sending a signal during any of the tests, check for correct battery installation and for a fully charged battery.
TEST BUTTON
GREEN LED
T
N
I
A
P
T
D
O
O
N
RED LED
5800CO-001-V0
Figure 1. 5800CO Wireless Carbon Monoxide Detector
PROGRAMMING
The detector must be enrolled in the control panel before it can operate in the system. The detector’s protection zone must be enrolled as Loop 1 and “Input Type” 3 (supervised RF).
A tamper condition is transmitted as Loop 4, but does not require programming.
1. Enter the control’s Zone Programming mode.
2. Enter the zone number to be programmed.
3. Enter the applicable zone type when prompted. For
Honeywell residential controls, program loop 1 as carbon monoxide zone type 14).
4. When prompted, enter Input Type 03 (3 on some controls)
– Supervised RF Transmitter.
5. When prompted for the serial number, transmit from the
detector by activating the tamper switch. To do this, hold the base of the detector in one hand, and rotate the detector counter-clockwise on the base until it snaps open. Then return to clockwise position until the detector snaps into place.
6. When the serial number is displayed, transmit from the
detector a second time by activating the tamper switch again as described in Step 5. The current loop number (4) will begin to flash.
7. Manually change the loop number to the desired loop
number for the zone (according to the application).
WARNING: The carbon monoxide protection zone enrolled must always be Loop 1. Otherwise, annunciations will not be reported by the control.
8. Exit Programming mode when programming is complete,
and test the detector. Refer to the Testing Section.
See the control unit’s installation instructions for further details.
MOUNTING THE DETECTOR
First, determine the best location for the detector, one that provides proper gas detection (see Figure 4 for suggested detection locations) and a strong wireless transmission path.
Proper Gas Detection Location
In a wall location, the detector should be at least as high as a light switch, and at least six inches from the ceiling. In a ceiling location, the detector should be at least 12 inches from any wall.
Where to install, ideally:
• Within 10 feet of all sleeping areas
• Inside the bedroom if it contains a fuel burning appliance
• On every floor of the building
• Ideally, install in any room that contains a fuel burning appliance
• If the appliance in the room is not normally used, such as the boiler room, the detector should be placed just outside the room so the alarm can be heard more easily
Where NOT to install, ideally:
• Detectors operate best if not installed within 10 feet of any cooking appliance
• Directly above a sink, cooker, stove or oven
• Next to a door or window that would be affected by drafts i.e. extractor fan or air vent
• Outside
• Do not install in any environment that does not comply with the detector’s environmental specifications
• In or below a cupboard
• Where air flow would be obstructed by curtains or furniture
• Where dirt or dust could collect and block the sensor
• Where it could be knocked, damaged, or inadvertently removed
Good Transmission Path
A GOOD TRANSMISSION PATH MUST BE ESTABLISHED FROM THE PROPOSED MOUNTING LOCATION BEFORE PERMANENTLY INSTALLING THE DETECTOR. To check, perform the test described in the TESTING SIGNAL STRENGTH section. Prior to mounting the detector to the mounting base, you must “enroll” the detector’s serial number into the system (see the PROGRAMMING section).
Mounting Procedure
To mount the detector, perform the following steps:
1. Once a suitable location has been determined, install the
mounting base on the ceiling or on the wall (if local ordinances permit). Use the two screws and anchors provided.
2. Turn the detector in a clockwise direction in the mounting base
until it clicks into place.
3. Test the detector immediately after completing the installation
(as described in the TESTING THE DETECTOR section of this manual) and refer to the control system’s instructions for additional information concerning the use of wireless devices.
TAMPER
RELEASE TAB
Figure 2. Detector Mounting Base
DIRECT MOUNT
HOLES
SNIP OFF FOR
TAMPER LOCK
TAMPER RELEASE TAB
(CUT OFF SMALL TAB TO
ACTIVATE TAMPER RESIST FEATURE)
RE L ED
D
E
G
CK O L
LAN F
5800CO-002-V0
– 2 –
Loading...
+ 2 hidden pages