Ademco 7720PLUS Users Manual



7777
7777
2222
0000
P
P
A
A
llll
aaaa
rrrr
m
m
N
N
eeee
AA
A
A
llll
AA
aaaa
SSyynntthheessiizzeedd SSuubbssccrriibbeerr RRaaddiio
mm
m
m
mm
NN
N
N
NN
rrrr
Installation and Setup Guide
eeee
tttt
tttt
7777
7777
2222
0000
PP
P
P
PP
LLLL
LLLL
U
U
UU
U
U
UU
S
S
SS
S
S
SS
o
N7734V3 3/06 Rev. C
•••••••••••••••••••••••••••••••••••••••••••••••••
SECTION 1.............................................................................................................................................................................. 1-1
About the 7720 PLUS.......................................................................................................................................................... 1-1
System Features ................................................................................................................................................................... 1-1
Synthesized Frequency Selection..................................................................................................................................... 1-1
Wireless Reporting........................................................................................................................................................... 1-1
Integrated Electronics ...................................................................................................................................................... 1-1
Selection of Input Interfaces ............................................................................................................................................ 1-1
Compatibility ................................................................................................................................................................... 1-1
Built-in LED Indicators ................................................................................................................................................... 1-1
Built-in Tamper Protection .............................................................................................................................................. 1-2
Antenna............................................................................................................................................................................ 1-2
Programmable Features ................................................................................................................................................... 1-3
Self -Diagnosing Transmitter........................................................................................................................................... 1-3
Power Supply................................................................................................................................................................... 1-3
Low Battery Monitoring .................................................................................................................................................. 1-3
Low Battery Shutdown .................................................................................................................................................... 1-3
General Operation................................................................................................................................................................ 1-3
Low Battery Detection and Restoral.................................................................................................................................... 1-4
Low Battery Detection..................................................................................................................................................... 1-4
SECTION 2.............................................................................................................................................................................. 2-1
Removing the Cover ............................................................................................................................................................ 2-1
Setting the Jumper Options.................................................................................................................................................. 2-1
(J2) Zone Inputs Activate on High or Low.......................................................................................................................... 2-2
(J3) Fault Output Select (Zone Mode Only) ........................................................................................................................ 2-2
Wiring at the Control Panel ................................................................................................................................................. 2-2
Wiring for ECP Communication with a Control Panel........................................................................................................ 2-2
Recommended Wiring at the 7720PLUS............................................................................................................................. 2-3
Mounting.............................................................................................................................................................................. 2-3
Powering Up ........................................................................................................................................................................ 2-4
SECTION 3.............................................................................................................................................................................. 3-1
Using a 7720P Programming Tool....................................................................................................................................... 3-1
Selecting a Mode.................................................................................................................................................................. 3-2
Zone Mode Programming.................................................................................................................................................... 3-2
Password Protection............................................................................................................................................................. 3-3
Subscriber Information .................................................................................................................................................... 3-3
AlarmNet System Users (Private system users skip to Question 6)................................................................................. 3-3
Private System Users (AlarmNet users skip to Question 8)............................................................................................. 3-3
Pulse/Delay Zone Selection ............................................................................................................................................. 3-4
Inverted Zone Selection ................................................................................................................................................... 3-5
Restoral Reporting Zone Selection .................................................................................................................................. 3-5
Open/Close, Telco and Tamper Zone Selection............................................................................................................... 3-7
Redundant Central Station Reporting .............................................................................................................................. 3-7
Exiting Program Mode, Setting Defaults and Assigning Passwords ................................................................................... 3-8
Setting Factory Defaults .................................................................................................................................................. 3-8
ECP Mode Programming..................................................................................................................................................... 3-9
SECTION 4.............................................................................................................................................................................. 4-1
Selecting a Location............................................................................................................................................................. 4-1
Antenna Mounting Options.................................................................................................................................................. 4-2
Outdoor Antenna Mounting............................................................................................................................................. 4-2
Indoor Antenna Mounting................................................................................................................................................ 4-2
Standard Wire Antenna Mounting (omnidirectional) ...................................................................................................... 4-2
Wall Mounting Using the 7825DP................................................................................................................................... 4-2
Wall Mounting with the 7625-3dB Gain and the 7720ANT Adapter.............................................................................. 4-3
Table of Contents
i
7720PLUS Installation and Setup Guide
Remote Antenna Mounting.............................................................................................................................................. 4-3
Powering Up ........................................................................................................................................................................ 4-3
Post Installation Checklist.................................................................................................................................................... 4-3
SECTION 5.............................................................................................................................................................................. 5-1
Radio Transmission Test...................................................................................................................................................... 5-1
System Test.......................................................................................................................................................................... 5-1
Status Display Interpretation for “S” Command.................................................................................................................. 5-2
ECP Status Codes ................................................................................................................................................................ 5-3
Last Detected Fault “E” Command...................................................................................................................................... 5-4
ECP Mode............................................................................................................................................................................ 5-4
Contact ID Messages ........................................................................................................................................................... 5-4
SECTION 6.............................................................................................................................................................................. 6-1
Troubleshooting................................................................................................................................................................... 6-1
Maintenance Requirements.................................................................................................................................................. 6-2
SECTION 7.............................................................................................................................................................................. 7-1
Special Notes for UL Installations....................................................................................................................................... 7-1
SECTION 8.............................................................................................................................................................................. 8-1
Specifications....................................................................................................................................................................... 8-1
SECTION 9.............................................................................................................................................................................. 9-1
FCC Statement..................................................................................................................................................................... 9-1
SECTION 10.......................................................................................................................................................................... 10-1
Limitations of the System .................................................................................................................................................. 10-1
ii
List of Figures
•••••••••••••••••••••••••••••••••••••••••••••••••
Figure 1. 7720PLUS Locking Tab Locations .......................................................................................................... 1
Figure 2. Jumper Option Location Diagram ...........................................................................................................1
Figure 3. ECP Communications Wiring Diagram ..................................................................................................3
Figure 4. 7720PLUS Wiring Connection Terminals............................................................................................... 3
iii
List of Tables
•••••••••••••••••••••••••••••••••••••••••••••••••
Table 1. LED Indications.......................................................................................................................................1-2
Table 2. Radio Fault LED Flash Patterns ...........................................................................................................1-2
Table 3. Fault Relay Sense Jumper Settings .......................................................................................................2-2
Table 4. Maximum Wire Run Lengths .................................................................................................................2-3
Table 5. 7720P Programming Tool Normal and Shift Key (shift LED lit) Functions .......................................3-1
Table 6. AlarmNet City Channels ........................................................................................................................3-4
Table 7. Antenna Kits for Remote and Outdoor Mounting .................................................................................5-2
Table 8. Post Installation Checklist .....................................................................................................................5-3
Table 9. ECP Status Code Explanations ..............................................................................................................6-3
Table 10. ECP Mode Contact ID Messages ..........................................................................................................6-4
iv
SECTION 1
System Features and Operation
•••••••••••••••••••••••••••••••••••••••••••••••••
In This Section
About the 7720PLUS
System Features
•••••••••••••••••••••••••••••••••••••••••••••••••
About the 7720 PLUS
The 7720PLUS self-contained synthesized subscriber radio is the subscriber end of a Long Range Radio alarm reporting system. As a communications link, by analogy to a telephone­based system, the 7720PLUS is comparable to a digital communicator connected by telephone line to a central monitoring station.
Installer, please read this Installation and Setup Guide all the way through and become completely familiar with it before attempting to install a 7720PLUS Synthesized Subscriber Radio.
General Operation
Low Battery Detection and Restoral
System Features
Synthesized Frequency Selection
The 7720PLUS can be programmed to operate on any authorized radio frequency. It is not necessary to stock a separate radio for each frequency the installer supports.
Wireless Reporting
All alarm and status messages are transmitted to the master station network via radio signals, which means faster and more secure reporting.
Integrated Electronics
The entire radio link equipment, except for the AC power supply unit, including interface, transmitter, battery and antenna, is housed in a single package, requiring only alarm inputs from a compatible alarm panel.
Selection of Input Interfaces
The 7720PLUS can monitor alarm inputs from the ADEMCO ECP interface, discrete 4 zone contact closures or their electrical equivalent.
NOTE: ECP features are compatible only with 685 software revision 4.7 and higher, and 685-5 software revision 8.1 and higher.
Compatibility
The 7720PLUS is compatible with existing installations using ADEMCO equipment or other control panels. The 7720PLUS can be used in conjunction with digital communicators on the same system, both acting as backup to each other (use an ADEMCO 659-EN Line Monitor connected to a zone input to report a line cut to backup a digital dialer), while connecting the radio fault output to a zone on the dialer.
Built-in LED Indicators
Three LEDs are used to indicate message transmissions, and radio faults (refer to Tables 1 and 2). A blinking yellow LED indicates normal operation.
1-1
7720PLUS Installation and Setup Guide
LED ST ATE MEANING
GREEN Blinking With YELLOW lit = Message transmission YELLOW
Lit Transmission cycle ON
Table 1. LED Indications
Rapid blink
Test or FAST message
(10 per second)
Slow blink
Normal operation
(1/second)
Slower blink
Normal, but low battery condition detected.
(1 per 3 seconds)
RED Lit Radio Fault detected. Refer to Table 2. YELLOW
and RED All lit
Blinking in unison Loss of communications between the radio and the
only
control panel. (ECP mode
)
Consecutive Power On/Reset sequence. Repeated twice before
entering normal mode. Press [ENTER] during cycle to enter Program Mode.
Slow Unison (2 per second)
Radio is not properly programmed. Will continue until [ENTER] is pressed to enter programming mode. (If in ECP mode, radio must be rebooted before entering program mode.)
Table 2. Radio Fault LED Flash Patterns
# FLASH REASON
1 5 CRC
S=Short flash (150mS); L=Long flash (600mS) #=Fault code number. See “S” command in
information.
S-L-L-L Internal radio fault
S-L-L-S Low power or high VSWR.
S-S-L-S RAM/EEPROM corruption
Section 5: Testing the 7720PLUS
for additional status
1-2
Built-in Tamper Protection
For added protection, built-in cover tamper switches trigger an alarm whenever the chassis cover is removed, thus protecting against unauthorized access to the 7720PLUS. The tamper zone number must be entered during programming to enable tamper reporting. A radio configured for ECP automatically reports the tamper status to the control panel, as well as to the central station
Antenna
The 7720PLUS can use either the supplied omni-directional wire antenna, or can use a 7825 outdoor antenna, 7625 omni-directional antenna, 7625-3DB antenna (if additional gain is required), or a 7674 (if a directional antenna is required), by using the optional 7720ANT connector kit. For wall mounting, an optional 7825DP can be used. The supplied antenna mounts directly to the7720PLUS. The antennas (other than the wire and the dipole) can be mounted remotely using the following pre-assembled coaxial cable available from ADEMCO: 5ft coax (P/N 7626-5), 12ft coax (P/N 7626-12), 25ft coax (P/N 7626-25HC), and 50ft coax (P/N 7626-50HC).
Programmable Features
The 7720PLUS utilizes EEPROM (Electrically Erasable Programmable Read Only Memory) technology that allows the 7720PLUS to be programmed with a 7720P Programming Tool. The programming options include:
radio frequency channel number (1 to 14)
Telco channel assignments for fault input
inverted trigger inputs
delayed reporting channels (1-127 seconds delay, if selected), and
open/close/restore reporting channels.
Self -Diagnosing Transmitter
Malfunctions of the transmitter, including antenna fault, radio transmitter fault, loss of external power, and low internal DC voltage can be displayed on the 7720P Programming Tool or reported on the ECP interface, as well as being transmitted to the master station, if the fault does not prevent such transmission. Faults can also trigger contact closures on a Form “C” relay to indicate radio faults.
Power Supply
The 7720PLUS is powered by an AC wall transformer, part number (1324), which provides 12VAC to the radio on pins 1 and 2 of the terminal block. An internal rechargeable battery provides power to the radio in the event of AC power outage. This battery is charged from the AC power supply during normal operation of the radio.
Section1. System Features and Operation
Low Battery Monitoring
The 7720PLUS tests its battery under 200mA load approximately every 4 hours. During this test, the 7720PLUS notifies the central station of a low battery condition if the battery voltage drops below 9.93V (± 5%). Low battery restore messages are reported during successive tests if the battery voltage reaches 10.03V (± 5%). During an AC failure condition, the periodic battery test is not performed, but the battery voltage is tested during each regular transmission, and a detected low battery condition is transmitted as described. A radio configured for ECP reports the battery status to the control panel as well as to the central station (most current controls do not annunciate this condition unless it occurs in conjunction with a more serious fault).
Low Battery Shutdown
In the absence of AC power, if battery voltage drops below 9.45 volts, the 7720PLUS will automatically shutdown and all LEDs will be off. However, so long as there is AC power, in the normal range of 102 to 138VAC at the wall outlet, the radio will operate properly, regardless of the condition of the battery.
General Operation
The 7720PLUS receives alarm and restore signals from the control panel and converts these signals to radio messages. These messages are transmitted to the master station network, which in turn relays the messages to the central station. The 7720PLUS can monitor 4 traditional zone inputs or an ECP signal line from an appropriate control panel. The first two zones may be configured by the use of a jumper, to activate on either 0 volts or 4.5-
14.2VDC; zones 3 and 4 are hard-wired to activate on 4.5-14.2VDC. Zones 1-4 can also be programmed to invert the sense of their input signals. (Zones normally are activated when the signal goes to a positive voltage. Inverting the zone trigger means that the zone is activated when the signal goes to ground. The pull-up voltage for zones 1 and 2 can be supplied by changing a jumper. Pull-up voltage for any of the zones can be supplied from the radio through external resistors or from a control panel.)
1-3
7720PLUS Installation and Setup Guide
Upon detecting an alarm or restoral, the 7720PLUS transmits the messages to the master station network. The transmissions repeat for approximately 6 minutes (total of 60 messages) to ensure that the alarm or other report is received by the central monitoring station.
The 7720PLUS periodically transmits supervisory status messages to the AlarmNet network. The supervision period (window) is a programmable feature. If no messages are received during the supervisory window, the network will generate a communication failure signal to the central station.
Radio faults that may prevent communication are indicated locally via the Radio Fault LED (refer to Table 2) and they are reported to the control panel via the fault relay in zone mode or via the ECP Status message in ECP mode. The fault relay, which is only available in zone mode, is a contact closure that can be either normally open or normally closed. In addition it can be selected to be “fail-safe” by programming the fault relay to be “on” (i.e., the relay is powered unless there is a fault). The fault output is between TB1-11 and TB1-12, which float with reference to the rest of the circuit.
When using ADEMCO's low-end control panels (VISTA-10SE, VISTA-20SE, VIA-30P), the ECP Status code is displayed on the control panel's keypad as Long Rnge Fail followed by a 4-digit code. When using ADEMCO's high-end control panels, a description of the fault is displayed in conjunction with a CHECK 8xx message where “xx” is the ECP address of the 7720PLUS.
Also available only in zone mode is the ability for the 7720PLUS to provide status information via its serial port, thus allowing radio status to be displayed on command, using either a 7720P Programming Tool or a computer terminal. Refer to Section 5: Testing the 7720PLUS for information regarding the “S command and status messages.
Low Battery Detection and Restoral
Low Battery Detection
The radio tests the condition of the battery periodically. If the radio finds that the battery is low, a low battery warning message is transmitted. When the battery voltage restores, the radio transmits a battery restore message.
The battery is under continuous float charge whenever the AC power is connected and sufficient.
1-4
SECTION 2
Wiring and Mounting
•••••••••••••••••••••••••••••••••••••••••••••••••
In This Section
Removing the Cover
Setting the Jumper Options
•••••••••••••••••••••••••••••••••••••••••••••••••
Removing the Cover
Remove the 7720PLUSs cover by inserting a screwdriver into the 4 removal points at the bottom of the unit and gently releasing the locking tabs from the cover slots as shown.
Setting the Jumper Options
The following jumper options are available:
(J2) Zone Inputs Activate on High or Low
(J3) Fault Output Select
ZONE SENSE SETUP: SHORT PINS 1 AND 2 TO HAVE CIRCUIT ENERGIZE ON HIGH INPUT; SHORT PINS 2 AND 3 TO HAVE CIRCUIT ENERGIZE ON GROUND (ZONES 1 AND 2 ONLY.) FAULT RELAY SENSE SETUP: SHORT PINS 1 AND 2 FOR A CLOSED CIRCUIT WHEN THE RELAY IS DE­ENERGIZED. SHORT PINS 2 AND 3 FOR A CLOSED CIRCUIT WHEN THE RELAY IS ENERGIZED.
Figure 1. 7720PLUS Locking Tab Locations
TAMPER SWITCH
RED LED
YELLOW LED
GREEN LED
PROGRAMMING JACK
3 2
ZONE SENSE SELECT
1
SEE
DETAIL A
3 2 1
3 2 1
3 2 1
FAULT RELAY SENSE
J2
J3
DETAIL A
Figure 2. Jumper Option Location Diagram
2-1
7720PLUS Installation and Setup Guide
(J2) Zone Inputs Activate on High or Low
NOTE: See Figure 2 when setting jumpers.
If using zone input connections, set the zone sense select jumper so that zone 1 and 2 inputs are activated either with a ground or with a positive voltage, whichever is required.
If the trigger level is set for positive voltage, +4.5 to +14.2 volts must be applied to zones 1 and 2 to trigger an alarm. If the zone is connected to a normally high voltage trigger (i.e., goes low on alarm), invert this zone when programming (Questions 13 and 14).
If ground is selected zones 1 and 2 are internally pulled up to 5 volts through a 10k-ohm resistor. This voltage should normally be pulled down (closed contact to ground) and released for alarm (opening the contact). If a normally open contact is being used, invert this zone when programming (Questions 13 and 14).
(J3) Fault Output Select (Zone Mode Only)
The radio fault output relay may be programmed for either Fail-Safe mode (relay always energized) or Low Current mode (relay normally de-energized) by selecting Yes or No to programming Question 27: FLT REL ON (Y/N). In addition, the relay can be set for either N.O. or N.C. operation (in either Fail-Safe or Low Current modes) using the fault relay sense jumper. When Fail-Safe mode is selected, the relay will change states (and trigger a dialer, if connected) in the event of power loss.
NOTE: Fail-Safe mode increases the standby current by about 10mA, which results in lower battery backup time (about 15%) in the event of power loss.
Set J1 to short pins 1-2 or short pins 2-3 as follows:
Table 3. Fault Relay Sense Jumper Settings
Programming Question 27 FLT REL ON (Y/N)
No N.C. N.O. Yes N.O. N.C.
Trigger voltage outputs: A current-limited source of approximately 12 volts DC is available at pin 3 of the terminal block, for external contacts, etc., that require a pullup voltage.
NOTE: Use color-coded wires for the power connections; it is recommended that the positive connection be red and the negative connection be black.
Fault Relay Sense Jumper Setting (relay N.O. or N.C.) Short Pins 1 -2 Short Pins 2 - 3
Wiring at the Control Panel
1. Connect ground wire to the auxiliary power ground on the control panel.
2. Run the alarm wires to the transmitter location.
Wiring for ECP Communication with a Control Panel
Only certain control panels support ECP data communication. Check the Installation and Setup Guide of your control panel to see if Long Range Radio is supported.
ECP data connections are the Data In and Data Out terminals that the keypads and other peripheral devices (RF Receiver, VIP module, etc.) use for communication with the control panel. To wire the radio for ECP communication, do the following:
1. Connect TB1-4 (Ground) of the 7720PLUS to the ground of the control panel.
2. Connect TB1-5 (ECP IN) of the 7720PLUS to data out to consoles connection on the control panel.
3. Connect TB1-6 (ECP OUT) of the 7720PLUS to data in from consoles connection on the control panel.
2-2
Figure 3. ECP Communications Wiring Diagram
Recommended Wiring at the 7720PLUS
The alarm and power wires can be brought into the transmitter through the base, or through the cover. If they are to be brought through the cover cut out the optional wire entry port. Connect the AC power wires from the transformer to TB 1-1 and TB 1-2, respectively. Install the battery into the battery holder, but do not plug in the battery cable yet.
Table 4. Maximum Wire Run Lengths
Gauge Distance
18 300 feet 20 200 feet 22 125 feet
CONTROL PANEL
DATA
DATA
IN
OUT
GND
Section 2. Wiring and Mounting
RADIO
TB1
4
5
6
Mounting
Figure 4. 7720PLUS Wiring Connection Terminals
Determine the best antenna location for strong radio communication with the Master Station network using the 7715DF Microfast Installation Tool. Mount the 7720PLUS to a horizontal or vertical surface, depending on the antenna used. Be sure to allow access to the programming port when mounting. The 7720PLUS is intended to be mounted to a horizontal surface, preferably on a ceiling, or in an attic location on top of a joist when using the supplied wire antenna. If using the 7720ANT antenna kit, the 7720PLUS can be mounted to a vertical surface such as a wall or beam.
2-3
7720PLUS Installation and Setup Guide
Powering Up
After all wiring is complete and the unit is mounted, plug the battery cable of the 7720PLUS into the connector next to the terminal block, then apply AC power to the radio. The radio will rapidly blink each LED consecutively for a total time of about 2.5 seconds. During this time, the user can configure the radio to operate in zone mode (four zone inputs) or in ECP mode, where alarm input is received from the control panel via the ECP interface. Refer to the Selecting a Mode paragraph in Section 3.
2-4
SECTION 3
Programming the 7720PLUS
•••••••••••••••••••••••••••••••••••••••••••••••••
In This Section
Using the 7720P Programming Tool
Selecting a Mode
Zone Mode Programming
•••••••••••••••••••••••••••••••••••••••••••••••••
Password Protection Exiting Program Mode, Setting Defaults and Assigning Passwords
ECP Mode Programming
Using a 7720P Programming Tool
The 7720P Programming Tool is powered by the 7720PLUS, and connects to the telephone connector on the 7720PLUS PC Board.
NOTE: The 7720P Programming Tool is not functional when the radio is running in ECP mode; it is functional only during power-up of an ECP radio.
IMPORTANT NOTE: Some older 7720P Programming Tools (shipped prior to mid-1998) will not function if the line voltage is too low. These can be modified using instructions supplied on request, or they may be returned to ADEMCO for factory modification. All 7720P Programming Tools currently shipping work without difficulty.
Each key of the 7720P Programming Tool has two possible functions; a normal function and a SHIFT function. To perform a normal key function, simply press the desired key. To perform a SHIFT key function, press the SHIFT key (the green SHIFT LED will light), then press the desired function key. Refer to Table 5 for the key functions.
Table 5. 7720P Programming Tool Normal and Shift Key (shift LED lit) Functions
KEY NORMAL KEY FUNCTION SHIFT KEY FUNCTION
BS/ESC [BS]: Press to delete entry [ESC]: Press to quit program mode; also can
reset EEPROM defaults*
/ [↓]: Scroll down programming []: Scroll up programming
N/Y [N]: Press for "NO" answer [Y]: Press SHIFT-Y for "YES" answer
SHIFT Press before pressing a SHIFT key function. Will light SHIFT LED. LED goes out
once a key is pressed. Press again for each SHIFT function desired. 1/A [1]: For entering the number 1 [A]: For entering letter A 2/B [2]: For entering the number 2 [B]: For entering letter B
3/C [3]: For entering the number 3 [C]: For entering letter C 4/D [4]: For entering the number 4 [D]: For entering letter D
5/E [5]: For entering the number 5 [E]: For entering letter E 6/F [6]: For entering the number 6 [F]: For entering letter F 7/S [7]: For entering the number 7 [S]: For entering letter S 8/T [8]: For entering the number 8 [T]: For entering letter T 9/X [9]: For entering the number 9 [X]: For entering letter X
SPACE [SPACE]: For scrolling option list No SHIFT function
0 [0]: For entering the number 0 No SHIFT function
#/ENTER [#/ENTER]: Press to accept entries No SHIFT function
* Active only when the “REVIEW?” prompt is displayed.
3-1
Loading...
+ 33 hidden pages