Ademco 7720PLUS Draft of Installation Instructions

7720PLUS
SYNTHESIZED SUBSCRIBER RADIO
INSTALLATION INSTRUCTIONS
DRAFT
TABLE OF CONTENTS
SYSTEM FEATURES & OPERATION 2 OPEN/CLOSE TELCO & TAMPER ZONE SEL.15 Features 2 Redundant Central Station Reporting 15 General Operation 3 Exiting Program Mode/Setting Defaults 17 LED Indications 4 ECP Mode Unique Programming 18 Radio Fault Led Patterns 4 ANTENNA MOUNTING 20 Low Battery Detection 5 Selecting A Site 20 SETTING THE JUMPER OPTIONS 6 Standard Wire Antenna 21 JUMPER POSITIONS DIAGRAM 7 Optional Antennas 21 WIRING, MOUNTING & POWERING 8 POST INSTALLATION CHECKLIST 23 WIRING CONNECTIONS DIAGRAM 9 TESTING THE 7720PLUS 24 PROGRAMMING THE 7720PLUS 10 Radio Transmission Test 24 Using A 7720P Programming Tool 10 System Test 24 Choosing Mode, ECP or Zone 10 ECP Status Codes 26 Zone Mode Unique Programming 11 Last Detected Fault “E” Command 27 Password Protection 11 Unique Contact ID Messages in ECP Mode 27 Subscriber Information 12 TROUBLESHOOTING 28 PULSE/DELAY ZONE DETECTION 12 NOTES FOR UL INSTALLATIONS 29 INVERTED ZONE SELECTION 13 SPECIFICATIONS 29 RESTORAL REPORTING 14 CONNECTIONS DIAGRAM 30
N7734V1 10/96
Note to the Installer:
Please read these Installation Instructions all the way through and become completely familiar with them befo re attempting to install a 7720PLUS subscriber radio. Note to pubs: change p/n and rev date
N7734V1 10/96
SYSTEM FEATURES & OPERATION
Introduction
The 7720PLUS self-contained synthesized subscriber radio is the subscriber end of a Long Range Radio alarm reporting system. As a communications link, by analogy to a telephone-based system, the 7720PLUS is comparable to a digital communicator connected by telephone line to a central monitoring station.
Synthesized Frequency Selection
All alarm and status messages are transmitted to the master station netwo rk via radio sign als, wh ich means faster and more secure reporting.
The 7720PLUS can be programmed to oper ate on any authorized radio freque ncy. It is not
necessary to stock a separate radio for each frequency the installer supports.
Wireless Reporting
Integrated Electronics
The entire radio link equipment, except for the AC power supply unit, including interface, transmitter, battery and antenna, is housed in a single package, requiring only alarm inputs from a compatible alarm panel.
Selection of Input Interfaces
The 7720PLUS can monitor alarm inputs from the Ademco ECP interface, discrete 4 zone contact closures or their electrica l equivalent
NOTE: ECP features are compatible only with 685 software revision 4.7 and higher, and 685-5 software revision 8.1 and higher.
Compatibility
The 7720PLUS is compatible with existing installations using ADEMCO equipment or other control panels. The 7720PLUS can be used in conjunction with digital communicators on the same system, both acting as backup to one another (use an ADEMCO 659-EN Line Monitor connected to a zone input to report a line cut to backup a digital d ialer), wh ile connecting the radio fault output to a zo ne on the dialer.
Built-in LED Indicators
Three LEDs are used to indicate message transmissions, and radio faults. A blinking yellow LED indicates normal operation. (See LED Table Page 4).
Built-in Tamper Protection
For added protection, built- in cover tamp er switche s will trigge r an alarm whene ver the chassis co ver is removed, thus protecting against unauthorized access to the 7720PLUS. The tamper zone number must be entered during programming to enable tamper reporting. A radio configured for ECP will automatically report the tamper status to the control panel, as well as to the Central Station
Antenna Included
The 7720PLUS can use either the supplied omni-directional wire antenna, or can use a 7825 outdoor antenna, 7625 omni-directional antenna, 7625-3DB antenna (if add itional gain is required), a 7674, a 7674-13 YAGI antenna (if a directional antenna is required), by using the optional 7720ANT connector kit. For wall mounting, an optional 7825DP can be used. The supplied antenna mounts directly to the7720PLUS. The antennas (other than the wire and the dipole) can be mounted remotely, if desired, using the follow ing pre-assembled coaxial cable, available from ADEMCO: 5ft
– 3 –
coax (P/N 7626-5), 12ft coax (P/N 7626-12), 25ft coax (P/N 7626-25HC), and 50ft coax (P/N 7626­50HC).
Programmable Features
The 7720PLUS utilizes EEPROM (Electrically Erasable ROM) technology, which allows the 7720PLUS to be programmed with a 7720P Programming Tool. The programming options include radio frequency channel number (1 to 14), Telco channel assignments for fault input, inverted trigger inputs, delayed reporting channels (1-127 seconds delay, if selected), open/close/restore reporting channels, etc.
Self -Diagnosing Transmitter
Malfunctions of the transmitter, including antenna fault, radio transmitter fault, loss of external power, and low internal DC voltage can be displayed on the 7720P programming tool or rep orted on the ECP interface, as well as being transmitted to the master station, if the fault does no t prevent such transmission. Faults can also trigger contact closures on a Form “C” relay to indicate radio faults.
Power Supply
The 7720PLUS is powered byan AC wall transformer, part number (TBD), whichpro vides 12 volts AC to the radio on pins 1 and 2 of the terminal block. An internal rechargeable battery provides power to the radio in the event of AC power outage. This battery is charged from the AC power supply during normal operation of the radio.
Low Battery Monitoring
The 7720PLUS will notify the central station of a low battery condition whe never the battery voltage drops below 9.93V (+/- 2%). Low battery restore message s are reported “” when the battery voltage reaches 10.03V (+/-2.5%). A radio configured for ECP will report the battery status to the control panel as well as to the central station.
Low Battery Shutdown
In the absence of AC power,
automatically shutdown and ALL LEDs WILL BE OFF. However, so long as there is AC power, in the normal range of 102 to 138 VAC at the wall outle t, the radio will ope rate properly, re gardless of the condition of the battery.
if battery voltage drops below 9.45 volts, the 7720PLUS will
General Operation
The 7720PLUS receives alarm and restore signals fro m the alarm control panel and converts these signals to radio messages which are transmitted to the master station ne twork, which in turn relays the messages to the central station. The 7720PLUS can monitor 4 traditional zone inpu ts or an ECP signal line from an appropriate control panel. The first two zones may be configured by the use of a jumper, to activate on either 0 volts or 4.5-14.2VDC ; zones 3 and 4 are hard- wired to activate on 4.5-
14.2VDC. Zones 1-4 can also be programmed to invert the sense of their input signals. (Zones normally are activated when the signal go es to a positive voltage. Inverting the zo ne trigger means that the zone will be activated whe n the signal g oes to g round. The pull-up voltage for zone s 1 and 2 can be supplied by changing a jumper, if desired; pull-up voltage for any of the zones can be supplied from the radio thru external resistors, or from an alarm panel.)
Upon detecting an alarm or restor al, the 7720PLUS will transmit the message s to the master station network.The transmissions will repeat f or approximately 6 minutes (total of 60 messages) to ensure that the alarm or other report will be received by the central monitoring station.
The 7720PLUS periodically transmits superviso ry status messages to the AlarmNet ne twork. Radio faults that are indicated during transmissions may prevent communication; to prevent this, the fault output (available in zone mode only) can be p rogrammed to also indicate radio faults (programming
– 4 –
the fault output is explained later in this chapter). If no messages are received during the supervisory window, the network will generate a communication failure signal to the central station.
Available in zone mode only is a contact closure used to locally indicate a radio fault. This can be either normally open or normally closed. In addition it can be selected to be “fail-safe” by programming the fault output to be inverted (i.e. the relay is powered unless there is a fault). The fault output is between TB1-11 and TB1-12, which float with reference to the rest of the circuit.
Also available in zone mode only is the ability for the 7720PLUS to provide status inf ormation via its serial port, thus allowing radio status to be displayed on command, using either a 7720P Programming Tool or a computer terminal. Refer to the TESTING THE 7720PLUS section for information regarding the “S” command and status messages.
LED Indications
LED State Meaning
GREEN Flash With YELLOW solid = Message transmission
YELLOW Solid
Rapid Flash
Transmission cycle ON Test or FAST message
(10 per second) Slow Flash
Normal operation (1/second) Slower Flash
Normal, but low battery condition detected. (1 per 3 seconds)
RED Solid Pattern Radio Fault detected. See flash patterns table below.
YELLOW and RED
All illuminated
Flashing in unison Loss of communications between the radio and the
ECP
mode only)
Consecutive
control panel. (
Power On/Reset sequence. Repeated twice before
entering normal mode. Press [ENTER] during cycle to
enter Program Mode.
Slow Unison (
2 per second)
Radio is not properly programmed. Will continue until
[ENTER] is pressed to enter programming mode. (IF in
ECP mode, radio must be rebooted before entering program
mode)
– 5 –
Radio Fault LED Flash Patterns
# Flash Reason
1
5 CRC
S=Short flash (150mS); L=Long flash (600mS) #=Fault code number. See “S” command in the TESTING THE
7720PLUS section for additional status information.
S-L-L-L Internal radio fault
S-L-L-S Low power or high VSWR. S-S-L-S RAM/EEPROM corruptions
Low Battery Detection & Restoral
Low Battery Detection
The radio tests the condition of the batteryperiodically. If the radio finds that the battery is low, a low battery warning message will be transmitted. When the battery voltage restores, the radio will transmit a battery restore message.
Battery Charging Mode
The battery is under continuous float charge whenever the AC power is connected and sufficient.
– 6 –
SETTING THE JUMPER OPTIONS (Set Before Installing)
Removing The Cover
Remove the 7720PLUS’s cover by inse rting a screwdriver into the 4 removal points at the bottom of the unit and gently releasing the locking tabs from the cover slots as shown.
.
(J2) Zone Inputs Activate on High or Low
If using zone input connections, set the J2 jumper so that zo ne 1 & 2 inpu ts are activ ated eithe r with a ground or with a positive voltage, whichever is required.
If the trigger level is se t for positive voltage, +4.5 to +14.2 volts must be applied to zones 1 & 2 to trigger an alarm. If the zone is connected to a normally high vo ltage trigger (i.e. goes low on alarm), invert this zone when programming (questions 13 and 14).
If ground is selected, zones 1 & 2 are internally pulle d up to 5 volts throug h a 10k ohm resistor. This voltage should normally be pulled down (closed contact to ground) and released for alarm (opening the contact). If a normally open contact is being used, invert this zone when programming (que stions 13 and 14).
(J3) Fault Output Select
Refer to the diagram on the following page when setting jumpers.
– 7 –
The radio fault output relay may be programmed for either FAIL-SAFE mode (relay always energized) or LOW CURRENT mode (relay normally de-energized) by selecting Yes or No to programming question 27: FLT REL ON (Y/N). In addition, the relay can be set for either N.O. or N.C. operation (in either fail-safe or low current modes) using the J1 jumper. When fail-safe mode is selected, the relay will change state s (and trigger a dialer, if connected) in the event of power loss. Note that fail-safe mode increases the standby current by about 10mA, which results in lowe r battery backup time (about 15%) in the event of powe r loss. Set the J1 jumper to p osition A or position B, as follows:
Prog. Ques. 26 J1 Jumper Setting (relay N.O. or N.C.) Fault Relay ON
(energized)
Pos. B Pos. A NO N.C. N.O. YES N.O. N.C.
– 8 –
Trigger voltage outputs: A current-limited source of appro ximately 12 volts DC is available at p in 3 of the terminal block, for external contacts, etc., that require a pullup voltage.
NOTE:
be red and the negative connection be black.
Use color-coded wires for the power connections; it is recommended that the positive connection
Wiring At The Control Panel
’. Connect the negative wire to the system negative point, which is also the negative line from the
battery. Run the alarm wires to the transmitter location.
Wiring For ECP Communication with a Control Panel
Only certain panels support ECP data communication at this time. Check the Installation Instructions of your panel to see if Long Range Radio is supported.
ECP data connections are the Data In and Data Out te rminals that the key pad s and o ther p erip he ral devices (RF Receiver, VIP module, etc.) use for communication with the panel. To wire the radio for ECP communication, do the following:
Connect TB1-4 (Ground) of the 7720PLUS to the ground of the panel. Connect TB1-5 (ECP DATA IN) of the 7720PLUS to “data out to consoles” connection on the panel. Connect TB1-6 (ECP DATA OUT) of the 7720PLUS to “data in from consoles” connection on the panel.
Note: add ground wire to drawing below. (See page 10a)
– 9 –
– 10 –
Recommended Wiring At The 7720PLUS
The alarm and power wires can be brought into the transmitter through the base, or through the cover. If they are to be brought through the cover, cut o ut the optional w ire entry port. Con nect the AC power wires from the transf ormer to TB 1-1 and TB 1-2, respe ctively. Install the battery into the battery holder, but do not plug in the battery cable yet.
Maximum Wire Run Lengths
Gauge Distance
18 300 feet 20 200 feet 22 125 feet
—7720PLUS wiring connection TERMINALS—
Mounting
Determine the best antenna location for strong radio communication with the Master Station network using the 7715DFFAST Tool (see pages 21 - 23). Mount the 7720PLUS to a horizontal or vertical surface, depending on the antenna used. Be sure to allow access to the programming port when mounting. The 7720PLUS is intended to be mo unted to a horizontal surface, pre ferably on a ceiling, or in an attic location on top of a joist when using the supplied wire antenna. If using the 7720ANT antenna kit, the 7720PLUS can be mounted to a vertical surface such as a wall or beam.
Powering Up
After all wiring is complete and the unit is mounted, plug the the connector nex t to the terminal block, the n each LED consecutively for a total time of about 2.5 seconds. During this time, the user can configure the radio to operate in zone mode (four zone inputs) or in ECP mode, where alarm input is received from the control panel via the ECP i n terface. See “Choosing Mode” in the Programming Section.
apply power
– 11 –
battery cable
to theradio. The radio will rap idly flash
of the
7720PLUS
into
PROGRAMMING THE 7720PLUS
Using A 7720P Programming Tool
The 7720P Programming Tool is powere d by the 7720PLUS, and connects to the telephone connecto r on the 7720PLUS PC Board. Please note the the 7720P is not functional when the radio is running in ECP mode; it is functional only during power-up of an ECP radio.
IMPORTANT NOTE: Some of the older 7720P tools (those shipped prior to mid-1998) will not function if the line voltage is too low. These can be modified using instructions supplied on request, or they may be returned to Ademco for factory modification. All 7720 P tools currently shipping will work without difficulty.
Each key of the 7720P has two possible functions, a normal function and a SHIFT function. To perform a normal key function, simply press the desired key. To perform a SHIFT key function, press SHIFT key, then press desired function key.
7720P Normal & Shift Key (shift LED lit) Functions
Key Normal Key Function SHIFT Key Function
BS/ESC [BS]: Press to delete entry [ESC]: Press to quit program mode.
Also, can reset EEPROM defaults*
↓ / ↑
N/Y [N]: Press for “NO” answer. [Y]: Press SHIFT-Y for “YES” answer
SHIFT Press before pressing a SHIFT key function. Will light SHIFT LED. desired.
1/A [1]: For entering the number 1 [A]: Used for entering C.S. ID number
2/B [2]: For entering the number 2 [B]: Used for entering C.S. ID number
3/C [3]: For entering the number 3 [C]: Used for entering C.S. ID number
4/D [4]: For entering the number 4 [D]: Used for entering C.S. ID number
5/E [5]: For entering the number 5 [E]: Used for entering C.S. ID number
6/F [6]: For entering the number 6 [F]: Used for C.S. ID & FAST mode 7/S [7]: For entering the number 7 [S]: Press to display diagnostic
status 8/T [8]: For entering the number 8 [T]: Press to send TEST messages 9/X [9]: For entering the number 9 [X]: Press to reset the 7720PLUS
/SPACE [✱]: Not used with 7720PLUS [SPACE]: Not used with 7720PLUS 0 [0]: For entering the number 0 No SHIFT function #/ENTER [#/ENTER]: Press to accept entries No SHIFT function
Active only when the “REVIEW?” prompt is displayed.
[↓]: Scroll down programming [↑]: Scroll up programming
LED goes out once a key is pressed. Press again for each SHIFT function
(Zone mode only)
CHOOSING MODE: ECP OR ZONE
Using the 7720P, the user can enter the configuration set-up by pressing the enter key while the individual LEDs rapidly flash sequentially. This w ill cause the radio to d isplay the f ollowing pr ompt on the 7720P display:
ECP Radio[Y/N]
– 12 –
Loading...
+ 27 hidden pages