Ademco 5806 User Manual

LIMITED WARRANTY
Honeywell International Inc., acting through its Security & Custom Electronics business ("Seller") 165 Eileen Way, Syosset, New York 11791, warrants its product(s) to be in conformance with its own plans and specifications and to be free from defects in materials and workmanship under normal use and service for 24 months from the date stamp control on the product(s) or, for product(s) not having a manufacturer’s date stamp, for 12 months from date of original purchase unless the installation instructions or catalog sets forth a shorter period, in which case the shorter period shall apply. Seller's obligation shall be limited to repairing or replacing, at its option, free of charge for materials or labor, any product(s) which is proved not in compliance with Seller's specifications or proves defective in materials or workmanship under normal use and service. Seller shall have no obligation under this Limited Warranty or otherwise if the product(s) is altered or improperly repaired or serviced by anyone other than Honeywell factory service. For warranty service, return product(s) transportation prepaid, to Honeywell Factory Service, 165 Eileen Way, Syosset, New York 11791.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, OF MERCHANTABILITY, OR FITNESS FOR A PARTICULAR PURPOSE OR OTHERWISE, WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. IN NO CASE SHALL SELLER BE LIABLE TO ANYONE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY, EXPRESS OR IMPLIED, OR UPON ANY OTHER BASIS OF LIABILITY WHATSOEVER, EVEN IF THE LOSS OR DAMAGE IS CAUSED BY THE SELLER'S OWN NEGLIGENCE OR FAULT.
Seller does not represent that the product(s) it sells may not be compromised or circumvented; that the product(s) will prevent any personal injury or property loss by burglary, robbery, fire or otherwise; or that the product(s) will in all cases provide adequate warning or protection. Customer understands that a properly installed and maintained alarm system may only reduce the risk of a burglary, robbery, fire, or other events occurring without providing an alarm, but it is not insurance or a guarantee that such will not occur or that there will be no personal injury or property loss as a result. CONSEQUENTLY, SELLER SHALL HAVE NO LIABILITY FOR ANY PERSONAL INJURY, PROPERTY DAMAGE OR OTHER LOSS BASED ON A CLAIM THAT THE PRODUCT(S) FAILED TO GIVE WARNING. HOWEVER, IF SELLER IS HELD LIABLE, WHETHER DIRECTLY OR INDIRECTLY, FOR ANY LOSS OR DAMAGE ARISING UNDER THIS LIMITED WARRANTY OR OTHERWISE, REGARDLESS OF CAUSE OR ORIGIN, SELLER'S MAXIMUM LIABILITY SHALL NOT IN ANY CASE EXCEED THE PURCHASE PRICE OF THE PRODUCT(S), WHICH SHALL BE THE COMPLETE AND EXCLUSIVE REMEDY AGAINST SELLER.
This warranty replaces any previous warranties and is the only warranty made by Seller on this product(s). No increase or alteration, written or verbal, of the obligations of this Limited Warranty is authorized.
FCC STATEMENT
FCC ID: CFS8DL5806-2
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference (2) This device must accept any interference received, including interference that may cause undesired operation.
IC: 573F-58062
165 Eileen Way, Syosset, New York 11791
Copyright © 2004 Honeywell International Inc.
www.honeywell.com/security
INSTALLATION INSTRUCTIONS
General Information
The ADEMCO 5806 Photoelectric Smoke Detector/Transmitter is intended for use with wireless alarm systems that support 5800 Series devices, and contains a built-in transmitter that can send alarm, supervisory and battery condition messages to the system's receiver/control unit. Refer to the wireless system's instructions for the maximum number of transmitters that can be supported.
Alarms: The smoke detector is powered by two 9-volt batteries and will sound its built-in horn when smoke reaches the detector (the LED indicator will also flash rapidly). A message will also be sent to the wireless control and the smoke detector's ID number will be displayed at the keypad. The alarm message will be transmitted every 4 seconds, until the smoke condition has cleared and the detector has reset. About 1 second after the horn has stopped, a Restore message will be transmitted to the control and it will then be possible to clear the ID number from the display. During normal or low battery conditions, the LED indicator will flash about once every 40 seconds.
Low Battery: The detector indicates a low­battery condition by emitting a "chirp" about once every 40 seconds. A low-battery message will be sent to the control unit upon any transmission following the first battery
TO REMOVE TO SECURE
INDICATOR LIGHT. FLASHES ONCE EVERY 40 SECS DURING NORMAL
SENSING CHAMBER OPENINGS
OPERATION
TEST BUTTON
ADEMCO 5806
Smoke Detector With Built-In
Wireless Transmitter
chirp (with the detector's ID number displayed at the keypad). The battery should be replaced within 30 days following the low-battery signals.
False Alarm Protection: In order to reduce the possibility of false alarms due to cigarette smoke, dust, steam, insects, etc., the detector will not transmit an alarm signal until its horn has sounded continuously for about 6 seconds. A delay also occurs when the detector is tested. Therefore, the test button must be held down for about 20 seconds before the horn will sound. The first alarm signal will be transmitted within 6 seconds after the horn sounds.
Programming: Note that the control system must “enroll” the smoke detector’s ID during installation of the system. The control should be programmed to “enroll” the 5806 as an “RF” type unit (i.e., supervised RF). See the PROGRAMMING section in this instruction book and the control unit’s Installation Instructions for further details.
Tamper Protection: The detector has provision for a tamper function if desired. When the tamper function, is enabled, the detector will cause a CHECK to be displayed if it is removed from its installed location. See TAMPER PROTECTION for detailed instructions.
Battery Installation and Replacement
The 5806 is equipped with two 9-volt batteries, which can double the time between battery replacement (compared to a single 9-volt alkaline battery). Refer to the SPECIFICATIONS section for acceptable batteries. The batteries should be changed within 30 days following the low battery beeps (about once every 40 seconds). There will also be a low-battery display on the system’s keypad. Be sure to replace BOTH batteries with fresh ones.
Important: Do not mix battery types.
ÊN6353V5mŠ
N6353V5 7/04 Rev A N6353V5 7/04 Rev A
1. Remove the smoke detector from its mounting plate by twisting the detector counterclockwise. If you are replacing batteries, remove the existing batteries from their compartments and disconnect the battery clips.
2. Install the new 9-volt alkaline batteries in their respective compartments as follows: Snap the battery contacts onto the terminals of the first battery (be sure to observe correct polarity and do not force battery clips). Holding the contacts on the battery, install the battery into its compartment. Make sure the battery is fully seated (see Figure 1).
Connect the second 9-volt alkaline
battery in a similar manner and install it in the second compartment.
3. Re-install the smoke detector onto the mounting plate by turning it clockwise, and test its operation as described in the TEST section.
4. The LED indicator should flash about once every 40 seconds, indicating normal operation. If the batteries are not installed correctly, the smoke detector will not function. If the unit appears not to be sending a signal during any of the tests, check for correct battery installation.
Note: If the detector’s ID has not been programmed into the system (i.e., this is an initial detector installation), refer to the PROGRAMMING section below and perform the ID “enrolling” procedure before mounting or testing the detector.
Programming
The control system must “enroll” the smoke detector’s ID during installation of the system. The control should be programmed to “enroll” the 5806 as an “RF” type unit (i.e., supervised RF), with a loop number of "1." With the control in the programming mode, you can either manually enter the serial number or transmit from the device (push the "Enroll" button [see Figure 1], install the battery, etc.). See the control unit’s installation instructions for further details.
Be sure to verify that the detector has been enrolled into the system by using the procedure provided in TESTING THE SMOKE DETECTOR section on page 6. If a “low battery” message is displayed and you suspect that the batteries are not actually low, remove both batteries, wait 20 seconds, re-insert them, and re-test the detector. Repeat this procedure, if necessary.
Tamper Protection
For tamper protection, cut the wire jumper indicated in Figure 1. After the detector has been mounted, a magnet must then be installed on the wall or ceiling next to the detector.
To ensure proper positioning of the magnet after the detector has been mounted, place a light pencil mark on the side of the detector near the center of the reed switch (see Fig. 1).
9 VOLT
BATTERY
COMPARTMENTS
INDEXING
MARK
LOCKING TABS ON MOUNTING PLATE SLIDE BENEATH THESE TABS (DETECTOR IS LATCHED ONTO MOUNT­ING PLATE BYTURNING CLOCKWISE)
Y
9V
BATTERY
BATTER
9V
ADEMCO
HOLDING TABS.
INDEXING MARK
“ENROLL” BUTTON
PLACE LIGHT PENCIL MARK HERE*
*
ONLY IF TAMPER MAGNET WILL BE USED
5806
No.
Model
MAGNETIC REED SWITCH
Figure 1. Bottom View of Smoke Detector (without mounting plate)
LOCATION OF “ENROLL” BUTTON
AND “TAMPER” JUMPER
“ENROLL” BUTTON (INSIDE OPENING). PUSH (WITH SMALL SCREWDRIVER) TO SEND “FAULT”.
CUT JUMPER FOR TAMPER
REED SWITCH
Mounting the Smoke Detector
First, determine the best location for the smoke detector (one that provides strong wireless transmission paths AND proper smoke detector protection). See
RECOMMENDED LOCATIONS FOR SMOKE DETECTORS (on next page).
A good RF transmission path must be established from the proposed mounting location before permanently installing the detector. To check, perform the test in TESTING THE SMOKE DETECTOR.
Mounting Locations
Detectors should be located as close to the center of the ceiling as possible. If this is not practical, detectors may be located on the ceiling up to 4 inches (10cm) from the ceiling-wall junction. Do not install near forced-air heating or air conditioning ducts (outlets or returns). For sloped, gabled, or high-peaked ceilings, detectors must be mounted between 4 and 6 inches (10 and 15cm) from the highest point in the ceiling.
Detectors may also be wall-mounted. Check with your local Fire Department about code requirements. Wall-mounted detectors should be located 4–6 inches (10–15 cm) from the ceiling.
In mobile homes, battery-operated detectors are not generally installed by the manufacturer. Mount detectors ONLY on an interior wall.
1. Once a suitable location has been determined, install the mounting plate on the ceiling or on the wall. Use the two screws and anchors provided.
SLOTTED HOLES FOR MOUNTING SCREWS
INDEXING MARK
NOTE: OTHER SIDE FACES CEILING OR WALL (THE WORDS “SINGLE GANG” MUST FACE AWAY FROM MOUNTING SURFACE)
LOCKING TABS
(USED FOR SECURING SMOKE DETECTOR TO MOUNTING PLATE)
ACE).
INDEXING MARK
Figure 2. Mounting Details
2. Latch the detector onto the mounting plate as follows: Position the detector onto the plate, mating the small center post on the detector with the "dimple" at the center of the mounting plate, and aligning the index marks on the sides of the plate and the detector. Then turn the detector in a clockwise direction so that the holding tabs on the detector engage the locking tabs on the mounting plate.
3. If the tamper has been enabled (as indicated previously), a magnet (No. 39WH-M) should be mounted on the wall or ceiling surface next to the detector (1/4” max) in the specified location (see Fig. 2).
4. Test the detector immediately after completing the installation and refer to the control system's instructions for additional information concerning the use of wireless smoke detectors.
(10 cm)
NEVER
HERE
ACCEPTABLE
HERE
4 IN.
DEAD AIR
SPACE
1/4" MAX
INDEXING MARK
4 IN.
(10 cm)
6 IN.
(15 cm)
SIDE WALL
No.39WH-M MAGNET NOTE: MAGNET IS MOUNTED NEXT TO DETECTOR ON SIDE OPPOSITE TEST BUTTON.
CEILING
BEST IN
ACCEPTABLE
CORNER
TEST BUTTON
INSTALLATION OF MAGNET (FOR TAMPER PROTECTION)
HERE
NOTE: MEASUREMENTS SHOWN ARE TO THE CLOSEST EDGE OF THE DETECTOR.
– 2 – – 3 –
Loading...
+ 2 hidden pages