Ademco 20152824, 201528100 User Manual

36-00012-01
INNCOM e7 Installation Requirements READ ME FIRST
REQUIRED TOOLS AND SOFTWARE
Required Installation Hardware:
Four #6/32, 1" Philip's Pan Head Screws
e7 Power and HVAC signal Harness
Phillips Screw driver
Wire cutters / strippers
Orange wire nuts
Optional Installation Hardware:
e7 Spacer Ring
3 wires for low voltage / S5bus in-room communications (typically CAT-5 or CAT-3 wiring)
Door, window, balcony switch and harness (wired to H2); see property specific documentation for
remote door, window and balcony switch requirements
Remote thermistor (04-1096.FL, wired to H2)
Required Installation Software
DO NOT THROW THIS UNIT AWAY: One PC-503 USB Commissioning Tool and USB cable per property / project is shipped to the site.
This tool is used in conjunction with Honeywell's engINN commissioning software when advanced commissioning of the e7 is required by a trained and certified INNCOM technician. DO NOT THROW THIS UNIT AWAY. Contact Honeywell technical support for more information.
PC-503 USB Commissioning Tool and Cable
INNCOM e7 Thermostat
CAUTION
Optional Spacer Ring
4 Junction Box
Smart Mounting Ring
Power/HVAC signal harness to thermostat
Installation Instructions
https://pages1.honeywell.com/e7_Install_Instructions.html
FOR ALL UNITS IN CAR TON. DO NOT THROW AWAY!
INSTALLATION INSTRUCTIONS
1. Position the optional spacer ring (if used) and Smart Wall Mounting Plate as shown in Fig. 1.
Disconnect the power supply before beginning installation to prevent electrical shock or equipment damage. All wiring must comply with local codes and ordinances.
• Read instructions carefully. Failure to follow them could damage the product or create a hazard.
• Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
• Installer must be a trained, experienced service technician.
• After installation is complete, check product operation as indicated in instructions.
• For variations of these systems, refer to the installation instructions of the controlled equipment.
INSTALLATION
Location
Select a location about 1.5m (5ft.) above the floor with good air circulation at average temperature. Do not mount thermostat where it may be affected by:
• Drafts or dead spots behind doors or in corners.
• Hot or cold air from ducts.
• Radiant heat from sun or appliances.
• Concealed pipes or chimneys.
• Unheated (un-cooled) areas behind the thermostat.
• If RF equipped, do not install near other RF sources/ transmitters.
• When the thermostat is equipped with PIR, consider view angle, range characteristics, and mounting position for proper coverage.
2. Ensure the optional spacer ring (if used) and Smart Mounting Plate are oriented with the raised arrow point­ing UP. Attach them to the junction box using the mount­ing screws provided.
3. Use wire nuts to connect the Power and HVAC wiring harness to the power and valve/fan control signal wires within the electrical box. See the pre-defined commission­ing document for application-specific wire connections.
4. To connect the unit to the input power and the relays to the loads, plug the pre-wired power and HVAC signal har­ness connector into the female receptacle at the back of the e7 (H1). When using mixed voltage, voltage separation must be maintained. Line voltage must reside in the left side of the gang box. Low voltage must reside in the right side of the gang box.
5. Hook the tabs at the top rear of the e7 housing into the matching depressions at the top of the Smart Mounting Plate and rotate the bottom of the housing toward the wall until it snaps into place.
6. Secure the housing to the Smart Mounting Plate with the two small captive screws at the bottom of the housing.
7. Apply power to the e7 by closing the applicable supply breaker. Verify that the e7 powers up. Values should begin appearing on the LCD display.
Mounting
The INNCOM e7 thermostat is typically mount on a standard double-gang (4 x 4) junction box. The installation kit provides a Smart Wall Mounting Plate and an optional Spacer Ring. The optional Spacer Ring is only required when a standard double­gang (4 x 4) junction box is not available, or when more space is required for wiring.
If mounted on a single-gang box, the right side (keypad side) of the e7 overlaps the wall area to the right. A low-voltage mounting plate, mud ring, or low-voltage caddy may be used for mounting 24 volt applications.
To mount the e7, complete the following steps:
Fig. 1. e7 Exploded View Assembly Reference