Ademco 0600906 User Manual

DT-900 Series DUAL TEC® Motion Sensor Supplemental Information
MOUNTING LOCATION
Aim the sensor toward the interior of the room, away from windows, moving machinery, and heating/ cooling sources.
Make sure the sensor has a clear line-of-sight to all areas you wish to protect. If the PIR is blocked, the unit will not alarm.
DT-906
TAMPER
The sensor covers and wall mounting are tamper protected. A screw must be installed in the wall to utilize the tamper feature.
WIRING
Reverse polarity will not damage the sensor.
Knockouts are provided to allow wire entry via 1/2 EMT or surface wiring conduit.
NOTE: For proper wiring methods, refer to the National Electrical Code NFPA 70.
INFORMER MODE
The INFORMER circuit counts the number of events registered by both the microwave and PIR technologies, and uses the resulting ratio to determine if either technology is working properly or is misapplied. Establish the INFORMER mode using switch S2. (See Step 7.)
Mode 1: Set S2 to position 1. In Mode 1, 32 PIR events without a microwave event will cause the unit to go into PIR INFORMER. 128 microwave events without a PIR event will cause the unit to go into microwave INFORMER. One LED indication does not relate to one PIR event.
Mode 2: Set S2 to position 2. In Mode 2, 16 PIR events without a microwave event will cause the unit to go into PIR INFORMER. 16 microwave events without a PIR event will cause the unit to go into microwave INFORMER. One LED indication does not relate to one microwave event.
NOTE: The Mode 2 setting is not recommended. Use only if fast INFORMER activation is required.
Disabled: To disable INFORMER function, set S2 to the open position.
When an INFORMER condition occurs, the trouble relay opens, and the LEDs display an INFORMER trouble code. The sensor performs a self-test within the hour to determine if the problem is internal.
If a self-test error is detected, the self-test LED pattern, all three LEDs flashing, replaces the INFORMER LED pattern.
If no self-test error occurs, the unit continues to display the INFORMER LED pattern and relay remains open. The problem is misapplication. Walk-test the sensor to pinpoint the cause. (Refer to Troubleshooting Table 3.)
Figure 1 DT-900 Printed Circuit Board
INPUT MODES
The DT-900 Series accommodates several international operating requirements using two operating modesStandard mode with remote LED enable and Command Input capability or European 2-Wire CENELEC mode (INPUT 1 and INPUT 2). For Standard Mode, remove jumper J4 and install jumper J6. For CENELEC mode, remove jumper J6 (See Figure 1).
Table 1 Standard ModeJ6 Installed Table 2 CENELEC ModeJ6 Removed
INPUT 1 INPUT 2
Table 4 Cenelec Functions
HIGH/Not connected
LEDs Disabled
Normal operation Self-test
Walk Test LEDs
Microwave Oscillator
Alarm Outputs
Alarm Memory Activated
Alarm Memory Reset
Alarm Memory Displayed
(Red LED flashing)
Trouble
Input Condition
LEDs Enabled
Only when Entering
LOW
Alert
Disabled
On
Enabled
Yes
Disabled
Disabled
Alert Local Test Standby Remote Test
INPUT 1 INPUT 2 high low
Operating Mode
Local Test
Enabled
On
Enabled
No No
Enabled
Enabled
high low high
Standby
Disabled
Off
Frozen
No No
Enabled
Enabled
Operating Mode
high
Remote Test
Disabled
On
Enabled
Yes
No
Disabled
Disabled
low low
Remote Test Mode causes the unit to enter a remote self-test (ongoing self-test). The Anti-Mask Output becomes a test running output and remains open for the duration of the test. If the unit passes all the self­tests, the alarm relay is activated for one second.
TROUBLESHOOTING
Vertical Adjustment
Various mounting locations may require fine vertical adjustment (e.g. uneven walls or floors, etc.). During the walk-test, if the PIR is short­ranged, turn the Vertical Adjust Screw counterclockwise. If the PIR is over-ranged, turn the Vertical Adjust Screw clockwise. (See Step 5.)
Self-Test
The sensor microcontroller automatically performs a series of self-tests in the following instances: when the unit is powered up, when the tests are installer initiated, upon Command Input, or every hour during normal operation. When a self-test error occurs, the Trouble relay opens and all 3 LEDs flash until the problem is corrected. If the problem persists and the LEDs continue to flash, the unit is defective and must be returned for repair.
DETECTION PATTERNS
Patterns for: DT-906
61 m (200) Range
TOP VIEW
Barrier LensAll Zones
DT-900
Feet
6 8 10 12 14 50 90 120 200
1.8 2.4 3 3.7 4.3 15 27 37 61
Trouble Memory
If the LED pattern disappears before you see it, you can retrieve the pattern. The trouble memory feature stores the last LED pattern from a self-test detected problem or an INFORMER condition.
To recover the LED pattern, first open the Top Cover (see Step 2). Using a small screwdriver, momentarily short circuit the two Self-Test pads located on the printed circuit board (see Supplemental Information, Figure 1). The trouble LED pattern will be re-displayed.
Short the pads with the screwdriver again to clear the LED pattern and initiate a self-test.
Anti-Mask
The DT-900 Series anti-mask feature detects attempts to block or cover the sensor by sending an active infrared beam out into the sensors field-of-view, at regular 8 second intervals. If the DT-900/DT-906 is blocked or covered (i.e. with a box or fabric) the beam is reflected back to the sensor. After two consecutive reflected beams, the sensor signals a trouble conditiongreen and red LEDs flash rapidly and the mask relay opens.
INFORMER Conditions
Table 3 describes two trouble alerts which are reported by the INFORMER circuit. To use this troubleshooting matrix:
1) Find the trouble alert that describes the condition of the walk-test LEDs (with no motion in the area).
2) Walk-test the sensor, carefully watching the reaction of the diagnostic LEDs.
3) Refer to the Possible Causes column of the matrix for an explanation of the way in which the diagnostic LEDs reacted to the walk-test.
Table 3 INFORMER Troubleshooting Matrix
Condition of LEDs
with No Motion
ALARM
PIR
(Green)
Patterns for: DT-900
MW
(Yellow)
(Red)
LED Legend: = LED is Flashing Slow =LED is OFF
27 m (90) Range
Meters
Reaction of LEDs
to Walk-Test
PIR
ALARM
(Green)
(Pattern disappears)
(Pattern disappears)
TOP VIEW
Wide Angle Lens
(Red)
MW
(Yellow)
Type of
Problem
RATIO
IMBALANCE
RATIO
IMBALANCE
RATIO
IMBALANCE
RATIO
IMBALANCE
Possible Causes
MW environmental problem MW unstable MW range too long PIR was blocked
PIR range too short PIR aimed wrong PIR not reporting
PIR environmental problem PIR unstable MW range too short
MW range too short MW not reporting
Patterns for: DT-900
15 m (50) Range
NOTE: If you enter the de-
tection pattern and the LEDs go off, you can retrieve the LED pattern to pinpoint the problem. Refer to Trouble Memory above.
TOP VIEW
Wide Angle Lens
Pattern for: DT-906
37 m (120) Range
PRODUCT SPECIFICATIONS
Range:
DT-906
37 m x 3 m / 61 m x 5 m 120' x 10' / 200' x 15'
DT-900
15 m x 12 m / 27 m x 21 m 50' x 40' / 90' x 70'
Alarm relay:
Energized Form C 25 VDC, 125 mA 22 ohm series protection resistor
Power requirements:
10 - 15 VDC 50 mA (max) at 12 VDC AC Ripple: 3V peak-to-peak at nominal 12 VDC
PIR white light immunity:
6500 Lux
RFI immunity:
30 V/m, 10 MHz - 1000 MHz
SIDE VIEW
Barrier LensAll Zones
Barrier LensAll Zones
SIDE VIEW
Barrier LensAll Zones
Trouble relay:
De-energized Form B (Normally closed) 30 VDC, 25mA
Mask relay:
De-energized Form B (Normally closed) 30 VDC, 25mA
Input 1 & 2:
Self-test initiate Active low 0 to 1.5V Inactive high 5 to V+
Sensitivity:
2 - 4 steps within field of view
Tampers:
Wall, top & bottom covers 30 VDC, 25 mA (NC)
PIR fields of view:
61 m (200) Range
2 long 6 intermediate long
TOP VIEW
4 intermediate 4 intermediate lower 8 lower 2 down
37 m (120) Range
6 long 4 intermediate long 4 intermediate 8 lower 2 down
27 m (90) Range
18 long 18 intermediate long 16 intermediate 12 intermediate lower 8 lower 2 down
15 m (50) Range
18 long 16 intermediate long 12 intermediate 8 lower 2 down
Microwave frequencies:
X band
Operating temperature:
0o to 49o C / 32o to 120o F
Relative humidity:
5% to 95% relative humidity (non-condensing)
Dimensions:
20 cm x 16.5 cm x 15.2 cm 8 x 6 1/2 x 6
Weight:
1.36 kg / 3 pounds
Packaged product:
1.6 kg / 3.5 pounds
Approvals/listings:
FCC certified Industry Canada UL listed ULC listed
Indicates Detection Area
SIDE VIEW
Wide Angle Lens
IMPORTANT: DT-900 Series sensors should be tested at least once each year to ensure proper operation.
FCC NOTICE: This equipment has been tested and found to comply with the limits for a field disturbance sensor, pursuant to
Part 15 of the FCC Rules. The user is cautioned that changes or modifications not expressly approved by IntelliSense could void the user's authority to operate this equipment.
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:  Reorient or relocate the receiving antenna.  Increase the separation between the equipment and receiver.  Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
 Consult the dealer or an experienced radio/TV technician for help.
IC Notice: Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device.
Note: The ULC label or listed marking on a product is the only evidence provided by Underwriters Laboratories of Canada to identify products that have been produced under the Listing and Follow-Up Service.
SIDE VIEW
Wide Angle Lens
Copyright 2001 IntelliSense. 5-051-344-00 Rev E
IntelliSense, DUAL TEC and INFORMER are registered trademarks of Honeywell, Inc.
DT-900 Series DUAL TEC® Motion Sensor for Commercial
and Light Industrial ApplicationsInstallation Instructions
Step 1
Select mounting height.
30 cm (12) minimum
4 m (12)
Optimal
Mounting
Height
)
6
(
m
2
Step 5
Locate correct sensor range scale and rotate Vertical Adjustment Screw until the diamond corresponds to the sensor mounting height (coarse adjust).
NOTE: Fine adjust may be needed during walk-test. See Supplemental Information.
Step 2
Carefully push screwdriver into slots to disengage latches and open top cover.
Step 6
Set switch S3 to establish the sensi­tivity best suited to your application.
SENSITIVITY
HIGH
NORMAL
LOW
*Factory default setting. **Not recommended for DT-906
S3
H
N* L**
**Not connected
Step 3
Firmly insert screwdriver into slot in arrow and rotate PIR Mirror Selector to the correct range.
DT-906
DT-900
Step 7
Select INFORMER® mode with switch S2, if desired. (See Supplemental
Information).
Step 4
Set switch S4 to establish microwave range.
MODEL
DT-906 DT-906 DT-900 DT-900
*Factory default setting.
RANGE
61 m (200) 37 m (120)
27 m (90) 15 m (50)
Switch S4
OPEN*
CLOSED 120
OPEN*
CLOSED
MIRROR Selector
200 *
90 * 50
Step 8
Carefully push screwdriver into slot to disengage latch and remove bottom cover.
Step 9
Unfasten screws and remove mount­ing plate from sensor.
Step 13
Hang the sensor on the mounting plate hooks and fasten with the two mounting plate screws.
Step 10
Attach mounting plate to wall at desired height, using four fasteners (not supplied).
Step 14
Wire the unit as shown.
Use 2.0 - 0.3 mm (14-22 AWG).
NOTE: Secure wires to mounting plate with tie wraps.
INPUTS 1 & 2
Standard or Cenelec mode
MASK DETECT (NC) 30 VDC, 25 mA
2
TROUBLE (NC) 30 VDC, 25 mA
TAMPER (NC) 30 VDC, 25 mA
END-OF-LINE
Connect terminating resistors on last unit
ALARM OUTPUTS
(NO, NC, COM) 25 VDC, 125 mA, Form C relay
POWER
10 - 15 VDC 50 mA (max) at 12 VDC
Step 11
Install M5 (#10) screw in wall 1.9 cm (3/4) below mounting screw, as shown, for tamper activation.
1.9 cm (3/4)
Step 15
Loosen horizontal locking screw in sensor support base.
Step 12
Pull about 30 cm (12) of wire from wall through the opening in the mounting plate and route wire to the terminal strip.
Step 16
Grasp housing and rotate it to the desired position (coarse adjust). If fine adjust is needed see Steps 20-
22.
NOTE: Reference marks = 5° change.
Step 17
Apply power to sensor and prepare for walk-test.
.
Wait 90 seconds for power-up self­test to run. All LEDs will flash.
PIR
(Green)
ALARM
(Red)
MW
(Yellow)
NOTE: LEDs flashing after 90 sec. = defective
Step 21
Rotate horizontal fine adjust knob to the desired position.
NOTE: Fine adjustment allows for small changes (3 degrees right or left) between coarse settings.
Step 18
Turn the microwave potentiometer counterclockwise to decrease the microwave range to minimum.
During walk-test, gradually turn the potemtiometer clockwise increasing microwave sensitivity until the desired range is obtained.
Step 22
Tighten horizontal fine locking screw on PCB.
Step 19
Walk-test the sensor to check for adequate detection coverage and to verify the sensor is fully functional. Two to four normal steps should make the LEDs light and trigger an alarm.
NOTE: If an on-going self-test problem, mask condition or an INFORMER condition occurs, the LEDs display a pattern that identifies the trouble. See Supplemental Information (Table 3).
NOTE: When there is no motion in the detection area, all three LEDs should be off.
Step 23
Tighten horizontal locking screw in sensor support base.
Step 20
For finer horizontal adjustments, loosen the PIR horizontal fine locking screw on PCB.
Step 24
Remove jumper at J5, on the PCB, to disable the LEDs after walk­testing.
Step 25
Complete installation by closing top cover and replacing bottom cover.
Loading...