Addison UHD250, UHD300, UHD400, UHD350, UHDT150 Installation, Operation & Service Manual

...
FOR YOUR SAFETY If you smell gas:
1. Open windows.
2. DO NOT try to light any appliance.
3. DO NOT use electrical switches.
4. DO NOT use any telephone in your building.
5. Extinguish any open flame.
6. Leave the building.
7. Immediately call your local gas supplier after leaving the building. Follow the gas supplier’s instructions.
8. If you cannot reach your gas supplier, call the Fire Department.
UHD-Series
Tubular Duct Furnace
(Standard Range)
Installation, Operation
WARNING
Fire Hazard
Keep all flammable objects, liquids and vapors the minimum required clear­ances to combustibles away from heater.
Some objects will catch fire or explode when placed close to heater.
Failure to follow these instructions can result in death, injury or property damage.
& Service Manual
150, 175, 200, 225 250, 300, 350, 400
WARNING
Improper installation, adjustment, alteration, service or maintenance can result in death, injury or property damage. Read the Installation, Operation and Service Manual thoroughly before installing or servicing this equipment.
Installation must be done by a contractor qualified in the installation and service of gas-fired heating equipment or your gas supplier.
© 2014 Addison
Installer
Please take the time to read and understand
these instructions prior to any installation.
Installer must give a copy of this manual to the owner.
Owner
Keep this manual in a safe place in order to provide
your service technician with necessary information.
Addison
7050 Overland Road Orlando, Florida 32810 Telephone: +1.407.292.4400 Fax: +1.407.290.1329
www.addison-hvac.com
P/N AD113001NA 11/14 Rev D
POUR VOTRE SECURITE
Si vous sentez une odeur de gaz:
1. Ouvrir les fenêtres.
2. N’essayer pas d’allumer un appareil.
3. N’utiliser pas d’interrupteurs électriques.
4. N’utiliser pas de téléphone dans votre bâtiment.
5. Eteindre flamme nue.
6. Quitter le bâtiment.
7. Après avoir quitté le bâtiment, appelez immédiatement votre fournisseur local de gaz. Suivre les instructions du fournisseur de gaz.
8. Si vous ne pouvez pas joindre votre fournisseur de gaz, appeler le service d’incendie.
UHD-Series Appareil de
chauffage conduit à échangeur
tubulaire (Gamme standard)
Manuel d’installation,
AVERTISSEMENT
Risque d’incendie
Garder tous les objets, liquides ou vapeurs inflammables à la distance minimale de l’unité de chauffage requise avec les matériaux combustibles.
Certains objets prendront feu ou exploseront s’ils sont placés à proximité de l’unité de chauffage.
Le non respect de ces instructions peut entraîner la mort, des blessures corporelles ou des dommages matériels.
d’operation, et de service
Modèles UHD[T][M][X][S][R]
150, 175, 200, 225
250, 300, 350, 400
AVERTISSEMENT
L’installation, le réglage, la modification, la réparation ou la maintenance inadapté peut entraîner la mort, des blessures ou des dommages matériels. Lire attentivement le manuel d'installation, d'utilisation et d'entretien avant d’installer ou de réparer cet équipement.
L’installation doit être effectuée par un entrepreneur qualifié dans l'installation et l'entretien d'appareils de chauffage au gaz ou par votre fournisseur de gaz.
© 2014 Addison
Installateur
Vouloir prendre le temps de lire et de comprendre ces
instructions avant toute installation. L’installateur doit
donner un exemplaire de ce manuel au propriétaire.
Propriétaire
Garder ce manuel dans un endroit sûr pour fournir les
informations nécessaires au personnel d’entretien.
Addison
7050 Overland Road Orlando, FL 32810 Téléphone: +1.407.292.4400 Fax: +1.407.290.1329
www.addison-hvac.com
P/N AD113001FC 11/14 Rev D
TABLE OF CONTENTS
SECTION 1: Heater Safety...................................................... 1
1.1 Manpower Requirements ............................................. 1
1.2 Safety Labels and Their Placement..............................1
1.3 California Proposition 65 ..............................................1
SECTION 2: Installer Responsibility .....................................5
2.1 Wall Tag ....................................................................... 5
2.2 Corrosive Chemicals....................................................5
2.3 National Standards and Applicable Codes...................5
SECTION 3: Critical Considerations .....................................6
3.1 Basic Information .........................................................6
3.2 Manufactured Units......................................................6
3.3 Location and Suspension ............................................6
3.4 Minimum Required Installation Clearances .................6
3.5 Ventilation ....................................................................6
3.6 Gas Supply ..................................................................6
3.7 Electrical Supply ..........................................................6
3.8 Vent..............................................................................6
SECTION 4: Clearances to Combustibles.............................7
4.1 Required Clearances to Combustibles.........................7
4.2 Clearances to Combustibles ........................................ 7
SECTION 5: National Standards and Applicable Codes...... 8
5.1 Gas Codes................................................................... 8
5.2 Aircraft Hangars ...........................................................8
5.3 Parking Structures and Repair Garages...................... 8
5.4 Electrical ......................................................................8
5.5 Venting ......................................................................... 8
5.6 High Altitude.................................................................8
SECTION 6: Duct Heater Installation.....................................9
6.1 General ........................................................................ 9
6.2 Suspension................................................................ 10
SECTION 7: Venting.............................................................. 11
7.1 Venting........................................................................ 11
7.2 Vent Installation .......................................................... 11
7.3 Horizontal Venting....................................................... 12
7.4 Vertical Venting........................................................... 12
7.5 Maximum Vent Lengths Table .................................... 12
7.6 Vent Material............................................................... 12
7.7 Replacing an Existing Heater in a Venting System..... 12
SECTION 8: Air Supply......................................................... 17
8.1 Separated Combustion Installation ............................ 17
8.2 Building Ventilation..................................................... 17
8.3 Outside Combustion Air Supply ................................. 17
SECTION 9: Gas Piping ........................................................ 18
9.1 Connections............................................................... 18
SECTION 10: Wiring .............................................................. 20
10.1 Positioning Thermostats........................................... 20
10.2 Low Voltage Thermostat for Models
UHD[T][M][X][S][R] 150-400 ....................................20
10.3 UHD[X][S][R] Series Internal Wiring Diagram for
Single Stage Gas Valves.......................................... 21
10.4 UHD[X][S][R] Series Ladder Wiring Diagram for
Single Stage Gas Valves.......................................... 22
10.5 UHD[T][X][S][R] Series Internal Wiring Diagram for
Two Stage Gas Valves..............................................23
10.6 UHD[T][X][S][R] Series Ladder Wiring Diagram for
Two Stage Gas Valves ............................................. 24
10.7 UHD[M][X][S][R] Series Internal Wiring Diagram for
Modulating Gas Valves ............................................ 25
10.8 UHD[M][X][S][R] Series Ladder Wiring Diagram for
Modulating Gas Valves ............................................ 26
10.9 Electrical Connection to the Heater......................... 27
SECTION 11: Operation and Maintenance ......................... 28
11.1 Pre-Start-Up Checks ................................................ 28
11.2 Begin Start-Up ......................................................... 28
11.3 Pressure Switch........................................................ 32
11.4 Turning Off the Heater .............................................. 32
11.5 External Controls...................................................... 32
11.6 Complete Start-Up ................................................... 32
11.7 Instruction to the User.............................................. 32
SECTION 12: User Instructions........................................... 33
12.1 Heater Operation..................................................... 33
12.2 Lighting Instructions ................................................ 33
12.3 Simple Troubleshooting ........................................... 33
SECTION 13: Servicing ........................................................ 35
13.1 Servicing Instructions .............................................. 35
13.2 Burner Maintenance................................................ 35
13.3 Heat Exchanger Maintenance ................................. 35
13.4 Gas Valve Maintenance........................................... 35
13.5 Flue Blower ............................................................. 35
13.6 Venting and Air Intake Pipe ..................................... 36
13.7 Maintenance Checklist ............................................ 36
SECTION 14: Troubleshooting............................................. 38
14.1 General.................................................................... 39
14.2 Troubleshooting For Automatic Ignition Burner
Systems................................................................... 40
14.3 Troubleshooting for Flame Supervision System....... 41
14.4 Troubleshooting for Gas Valves ............................... 42
14.5 Troubleshooting for Flue Blower .............................. 42
SECTION 15: Replacement Parts ........................................ 43
15.1 Gas Valve ................................................................ 43
15.2 Burner Compartment for Models UHD[T][M][X][S][R]
150-400.................................................................... 44
15.3 Ignition Electrode and Flame Probe for Models
UHD[T][M][X][S][R] 150-400 .................................... 46
15.4 Heat Exchanger....................................................... 47
15.5 Flue Blower for Models UHD[T][M][X][S][R]
150-300 .................................................................. 47
15.6 Flue Blower for Models UHD[T][M][X][S][R]
350-400 ................................................................... 48
15.7 Pressure Switch....................................................... 49
15.8 Ignition Control ........................................................ 49
15.9 Limit Switches ......................................................... 49
SECTION 16: Specifications................................................ 50
16.1 Dimension Data for Models UHD[T][M][X][S][R]
150-250.................................................................... 50
16.2 General Technical Data Table .................................. 51
16.3 Technical Data Table................................................ 51
All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means - graphic, electronic, or mechanical, including photocopying, recording, taping or information storage and retrieval systems - without the written permission of Addison.
© 2014
Printed in U.S.A.
Addison
16.4 Dimension Data for Models UHD[T][M][X][S][R]
300-400 ................................................................... 52
16.5 General Technical Data Table ..................................53
16.6 Technical Data Table ................................................ 53
SECTION 17: The ADDISON
®
UHD-Series Warranty........... 55
TABLE OF FIGURES
Figure 1: UHD[T][M][X][S][R] 150-175 Label Placement........... 2
Figure 2: UHD[T][M][X][S][R] 200-250 Label Placement...........3
Figure 3: UHD[T][M][X][S][R] 300 – 400 Label Placement........4
Figure 4: Clearances to Combustibles ...................................... 7
Figure 5: Air Flow Direction.......................................................9
Figure 6: Suspension Methods ............................................... 10
Figure 7: Vent and Roof Detail ................................................ 13
Figure 8: Standard Vented Heater - Vertical and Horizontal
Vent Termination ......................................................13
Figure 9: Standard Vented Heater - Common Vertical Vent
Termination .............................................................. 14
Figure 10: Separated Combustion Heater - Vertical and
Horizontal Vent Termination ....................................15
Figure 11: Concentric Vent Box............................................... 15
Figure 12: Concentric Vertical and Horizontal Vent
Termination - Separated Combustion Heater .........16
Figure 13: Gas Connection ..................................................... 19
Figure 14: Automatic Burner Control Sequence...................... 29
Figure 15: Single Stage Gas Valve for Models UHD[X][S][R]
150 – 400 ...............................................................29
Figure 16: Two Stage Gas Valve for Models UHD[T][X][S][R]
150 - 400 ................................................................30
Figure 17: Modulating Gas Valve for Models UHD[M][X][S][R]
150 - 400 ................................................................30
Figure 18: LED Diagnostic Codes...........................................34
There are references in this manual to various trademarks. All trademarks mentioned herein, whether registered or not, are the property of their respective owners. Addison is not sponsored by or affiliated with any of the trademark or registered trademark owners, and makes no representations about them, their owners, their products or services.
SECTION 1: HEATER SAFETY
Your Safety is Important to Us! This symbol is used throughout the manual to notify you of possible fire, electrical or burn hazards. Please pay special attention when reading and following the warnings in these sections.
Installation, service and, at a minimum, annual inspection of heater must be done by a contractor qualified in the installation and service of gas-fired heating equipment. Read this manual carefully before installation, operation or service of this equipment. Heaters are not approved for residential installation.
These instructions, the layout drawing, local codes
and ordinances and applicable standards that apply to gas piping, electrical wiring, venting, etc. must be thoroughly understood before proceeding with the installation.
SECTION 1: HEATER SAFETY
1.2 Safety Labels and Their Placement
Product safety signs or labels should be replaced by the product user when they are no longer legible. Please contact Addison or your ADDISON
®
independent distributor to obtain replacement signs or labels. See Page 2, Figure 1 through Page 4, Figure 3.
1.3 California Proposition 65
In accordance with California Proposition 65 requirements, a warning label must be placed in a highly visible location on the outside of the equipment (i.e. near equipment's serial plate). See label placement drawing on Page 2, Figure 1 through Page 4, Figure 3 for label location. Avoid placing label on areas with extreme heat, cold, corrosive chemicals or other elements. To order additional labels, please contact Addison or your ADDISON
®
independent distributor.
Protective gear is to be worn during installation, operation and service in accordance to the Occupational Safety and Health Administration (OSHA). Gear must be in accordance to NFPA 70E, latest revision when working with electrical components. Thin sheet metal parts, including the various venting components, have sharp edges. To prevent injury, the use of work gloves is recommended.
Before installation, check that the local distribution conditions, nature of gas and pressure and adjustment of the equipment are compatible.
This heater must be applied and operated under the
general concepts of reasonable use and installed using the best building practices.
This equipment is not intended for use by persons
(including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the equipment by a person responsible for their safety. Children should be supervised to ensure that they do not play with the equipment. For additional copies of the Installation, Operation and Service Manual, please contact Addison.
1.1 Manpower Requirements
To prevent personal injury and damage to the
heater, two persons will be required for installation.
1 of 55
UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
Figure 1: UHD[T][M][X][S][R] 150-175 Label Placement
2 of 55
Description Part Number
Logo Label 91031107 Vent Length Label 91039505 Vent to Outdoors Label 91010427 Warning Label 91010429 Rating Plate Label 91039843 Installation Label 91010431 Instruction Location Label 91010433 Lighting Instruction Label 91010425 Venting Arrangement Label* 91010426 Proposition 65 Label 91070015 0-10VDC Modulating Label** 91040196
* For separated combustion units only ** For modulating units only
Figure 2: UHD[T][M][X][S][R] 200-250 Label Placement
SECTION 1: HEATER SAFETY
Description Part Number
Logo Label 91031107 Vent Length Label 91039505 Vent to Outdoors Label 91010427 Warning Label 91010429 Rating Plate Label 91039843 Installation Label 91010431 Instruction Location Label 91010433 Lighting Instruction Label 91010425 Venting Arrangement Label* 91010426 Proposition 65 Label 91070015 0-10VDC Modulating Label** 91040196
* For separated combustion units only ** For modulating units only
3 of 55
UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
Figure 3: UHD[T][M][X][S][R] 300 – 400 Label Placement
4 of 55
Description Part Number
Logo Label 91031107 Vent Length Label 91039505 Vent to Outdoors Label 91010427 Warning Label 91010429 Rating Plate Label 91039843 Installation Label 91010431 Instruction Location Label 91010433 Lighting Instruction Label 91010425 Venting Arrangement Label* 91010426 Proposition 65 Label 91070015 0-10VDC Modulating Label** 91040196
* For separated combustion units only ** For modulating units only
SECTION 2: INSTALLER RESPONSIBILITY
The installer is responsible for the following:
• To install the heater, as well as the gas and electrical supplies, in accordance with applicable specifications and codes. Addison recommends the installer contact a Local Building Inspector or Fire Marshal for guidance.
• To use the information given in a layout drawing and in the manual together with the cited codes and regulations to perform the installation.
• To install the heater in accordance with the clearances to combustibles.
SECTION 2: INSTALLER RESPONSIBILITY
2.2 Corrosive Chemicals
CAUTION
Product Damage Hazard
Do not use equipment in area containing corrosive chemicals.
• To furnish all needed materials not supplied as standard equipment.
• To plan location of supports, vents and air intakes.
• To provide access for servicing.
• To provide the owner with a copy of this Installation, Operation and Service Manual.
• To never use heater as support for a ladder or other access equipment and never hang or suspend anything from heater.
• To ensure there is adequate air circulation around the heater and to supply air for combustion, ventilation and distribution in accordance with local codes.
• To provide a method that ensures that the air flow through the heat exchanger is within the acceptable range indicated on the serial plate prior to energizing the heater, and that such air flow continues at least 90 seconds after the heater is de-energized.
• To ensure the heater is placed in an approved application.
2.1 Wall Tag
A laminated wall tag is included with the heater as a
permanent reminder of the safety instructions and the importance of the required clearances to combustibles. Affix the tag by peeling off the backing of the adhesive strips on the rear surface and position the tag on a wall near the heater.
A copy of the wall tag (P/N 91039848) is illustrated
on the back cover. Know your model number and installed
configuration. Model number and installed configuration are found on the heater serial plate and throughout the Installation, Operation and Service Manual.
Refer to appropriate Material Safety Data Sheets (MSDS).
Failure to follow these instructions can result in product damage.
Addison cannot be responsible for ensuring that all appropriate safety measures are undertaken prior to installation; this is entirely the responsibility of the installer. It is essential that the contractor, the sub­contractor, or the owner identifies the presence of combustible materials, corrosive chemicals or halogenated hydrocarbons* anywhere in the premises.
* Halogenated Hydrocarbons are a family of chemical compounds characterized by the presence of halogen ele­ments (fluorine, chlorine, bromine, etc.). These compounds are frequently used in refrigerants, cleaning agents, solvents, etc. If these compounds enter the air supply of the burner, the life span of the heater components will be greatly reduced. An out­side air supply must be provided to the burners whenever the presence of these compounds is suspected. Warranty will be invalid if the heater is exposed to halogenated hydrocarbons.
2.3 National Standards and Applicable Codes
All equipment must be installed in accordance with the latest revision of the applicable standards and national codes. This refers also to the electric, gas and venting installation. Note: Additional standards for installations in public garages, aircraft hangars, etc. may be applicable. See Page 8, Section 5.
5 of 55
UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
SECTION 3: CRITICAL CONSIDERATIONS
3.1 Basic Information
UHD[T][M][X][S][R] heaters have automatic ignition burners for ON/OFF, HIGH/LOW or modulate within the range of HIGH/LOW operation.
• May be mounted on a shelf of non-combustible material.
• May be suspended from above (See Page 10, Section 6.2) or from wall brackets of sufficient strength to support the heater as listed in the
3.2 Manufactured Units
Gas-fired, power-vented duct furnace with tubular heat exchanger. Units shall have a minimum of 82% thermal efficiency. The standard unit shall consist of a non-separated combustion design with an aluminized heat exchanger and a single stage gas valve. Design and heat exchanger alternatives shall be offered as follows:
Technical Data Table on Page 51, Section 16.2 and Page 53, Section 16.5.
• Drop rods must be a minimum of 3/8" diameter mild steel. Four suspension points (3/8" nuts) are located on top of the heater.
• Must be installed in a manner which allows access to all serviceable components.
• Separated Combustion: [S] A separated combustion unit shall consist of a sealed enclosure with a hinged door. Combustion air inlet on rear of heater allows for intake venting from outside of heated space to be attached. Combustion flue gases shall be ducted from
3.4 Minimum Required Installation Clearances
Clearances around the heater and vent must be as indicated on Page 7, Figure 4 and Page 11, Section 7 to ensure access for servicing and correct operation.
outside heated space by ductwork connected to unit's outlet flange.
• Stainless Steel Heat Exchanger: [X] A stainless steel heat exchanger unit shall consist of heat exchanger tubes, heat exchanger tube supports and heat exchanger tube plate produced of 409
3.5 Ventilation
It is important to ensure that there is adequate air space around the heater to supply air for combustion, ventilation and distribution in accordance with local and national code on Page 11, Section 7.
stainless steel. Air inlet temperatures below 40° F (4.4° C) are not recommended for this application.
• Two Stage Gas Valve: [T] A two stage gas valve shall allow heater to function in either high or low operation.
• Modulating Gas Valve: [M] A modulating gas
3.6 Gas Supply
It is important that the gas supply pipe is sized correctly to provide the inlet pressure as stated on the heater data plate. The gas supply pipe and electrical connections must not support any of the
heater's weight. See Page 18, Section 9. valve shall allow heater to modulate between high and low fire.
• Approved for Installation Downstream of a Refrigeration System: [R] Installation allows for unit to be installed downstream of a refrigeration system. Unit design shall include a 409 stainless
3.7 Electrical Supply
A permanent 120 V / 1 Ø / 60 Hz electrical supply is required for the main electrical power. The heater also requires suitable controls listed on Page 20, Section 10.
steel package. Stainless steel package includes heat exchanger, tube supports and drip pan.
3.8 Vent
Choose heater orientation to allow for proper
3.3 Location and Suspension
All models:
• Must be installed indoors.
• Must be installed on the positive pressure side of
location of the vent. Each heater must be fitted with a correctly sized sealed vent system.
If vented horizontally, no other equipment may be connected to the vent. See Page 11, Section 7.
the air circulation blower.
• Must be installed in a level position with horizontal discharge.
6 of 55
SECTION 4: CLEARANCES TO COMBUSTIBLES
4.1 Required Clearances to Combustibles
WARNING
Fire Hazard
Keep all flammable objects, liquids and vapors the minimum required clearances to combustibles away from heater.
SECTION 4: CLEARANCES TO COMBUSTIBLES
of exposure to combustible airborne materials or vapors.
4.2 Clearances to Combustibles
Clearances must be as indicated on Page 7, Figure
4. If clearances to combustibles are not indicated,
then installation clearances apply. All distances are minimum clearance requirements for service access, air flow and safety.
Figure 4: Clearances to Combustibles
Some objects will catch fire or explode when placed close to heater.
Failure to follow these instructions can result in death, injury or property damage.
Clearances are the required distances that combustible objects must be away from the heater to prevent a fire hazard. Combustibles are materials that may catch on fire and include common items such as wood, paper, rubber, fabric, etc. Maintain clearances to combustibles at all times for safety. Clearances for all heater models are located on the serial plate, wall tag and throughout the manual. Check the clearances on the serial plate to make sure the product is suitable for your application and the clearances are maintained. Read and follow the safety guidelines below:
• Keep gasoline or other combustible material
including flammable objects, liquids, dust or vapors away from this heater or any other equipment.
• Do not spray aerosols in the vicinity of this
heater.
• The stated clearances to combustibles
represents a surface temperature of 90° F (50° C) above room temperature. Building materials with a low heat tolerance (such as plastics, vinyl siding, canvas, tri-ply, etc.) may be subject to degradation at lower temperatures. It is the installer's and owner's responsibility to assure that adjacent materials are protected from degradation.
• Maintain clearances from heat sensitive
equipment and work stations.
• Consult local Fire Marshal, Fire Insurance
Carrier or other authorities for approval of proposed installation when there is a possibility
6"
(15 cm)
6"
(15 cm)
6"
(15 cm)
Clearance to Vent: 2" (5 cm)
*31" (79 cm) minimum is necessary for servicing.
31"*
(79 cm)
7 of 55
UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
SECTION 5: NATIONAL STANDARDS AND APPLICABLE CODES
5.1 Gas Codes
The type of gas appearing on the serial plate must be the type of gas used. Installation must comply with national and local codes and requirements of the local gas company.
United States: Refer to NFPA 54/ANSI Z223.1 ­latest revision, National Fuel Gas Code.
Canada: Refer to CSA B149.1 Natural Gas and Propane Installation Code.
5.2 Aircraft Hangars
Installation in aircraft hangars must be in accordance with the following codes:
United States: Refer to Standard for Aircraft Hangars, NFPA 409 - latest revision.
Canada: Refer to Natural Gas and Propane Installation Code, Standard CSA B149.1 - latest revision.
5.4 Electrical
The heater must be electrically grounded in accordance with the following codes:
United States: Refer to National Electrical
®
Code
, NFPA 70 - latest revision. Wiring must
conform to the most current National Electrical
®
Code
, local ordinances and any special
diagrams furnished.
Canada: Refer to Canadian Electrical Code, CSA C22.1 Part 1 - latest revision.
5.5 Venting
The venting must be installed in accordance
with the requirements within this manual and the following codes:
United States: Refer to NFPA 54/ANSI Z223.1 ­latest revision, National Fuel Gas Code.
Canada: Refer to CSA B149.1 Natural Gas and Propane Installation Code.
5.3 Parking Structures and Repair Garages
Installation in garages must be in accordance with the following codes:
United States: Refer to Standard for Parking Structures, NFPA 88A - latest revision or the Code for Motor Fuel Dispensing Facilities and Repair Garages, NFPA 30A - latest revision.
Canada: Refer to Natural Gas and Propane Installation Code, Standard CSA B149.1 - latest revision.
5.6 High Altitude
These heaters are approved (without modifications) for installations up to 2000' (610 m) in US and Canada. Heaters installed above 2000' (610 m) must be de-rated. For installations above 2000' (610 m) in US, consult factory for information on burner de-rating. For installations from 2000' (610 m) to 4500' (1370m) in Canada, high altitude conversion kits are available. Heaters installed over 4500' (1370 m) in Canada are not approved and must be approved by the local or provincial authority.
8 of 55
SECTION 6: DUCT HEATER INSTALLATION
SECTION 6: DUCT HEATER INSTALLATION
6.1 General
To connect the inlet and outlet ducts to the heater, Duct-Mate or similar flanges may be slid over the duct connector flanges supplied on the unit and secured with screws. The connection to the duct then can be made using the Duct-Mate clips. The ducts must have removable access panels upstream and downstream of the heater. These panels must be of appropriate size and placement so that smoke or reflected light could be observed to indicate the presence of leaks in the heat exchanger. Covers for these openings should be sealed to prevent leakage.
Any transition into the inlet of the heater should be smooth, with a taper of no more than 15 degrees. If elbows are required, they should be of either broad radius or fitted with properly designed turning vanes. Consult a professional to ensure turning vanes are properly designed.
The heater must be installed on the positive pressure side of the circulating air blower. Air flow through the heater must be as shown on Page 9, Figure 5 and may not be reversed. The air flow must be adjusted such that it is within the acceptable range shown on Page 9, Section 6.1.2.
The minimum inlet duct lengths shown on Page 9, Section 6.1.1 must be observed. Pressure drop through the heat exchanger at various air flows is shown on Page 9, Section 6.1.2.
Figure 5: Air Flow Direction
6.1.1 Minimum Inlet Duct Length
Model Duct Length Duct Size (W X H)
UHD[T][M][X][S][R] 150-175 52" (132 cm) 28" x 24" (71 cm x 60 cm) UHD[T][M][X][S][R] 200-250 60" (162 cm) 28" x 32 1/2" (71 cm x 83 cm) UHD[T][M][X][S][R] 300-400 75" (190 cm) 35" x 40 1/2" (89 cm x 82 cm)
6.1.2 Temperature Rise and Pressure Drop Ranges
UHD[T][M][X][S][R] 150 UHD[T][M][X][S][R] 175 UHD[T][M][X][S][R] 200 UHD[T][M][X][S][R] 225
Airflow
(CFM)
Airflow
(CFM)
Temperature
Rise (°F)
1,360 83 0.02 1,400 95 0.03 2,050 73 0.025 2,100 80 0.035 1,950 58 0.035 2,180 62 0.06 2,600 58 0.035 2,800 61 0.052 2,800 41 0.057 3,244 42 0.10 3,600 42 0.056 4,600 37 0.110 3,700 31 0.083 4,370 31 0.15 5,500 28 0.100 6,230 27 0.167 4,700 24 0.12 5,160 27 0.19 6,570 23.5 0.129 7,400 23 0.214 5,800 20 0.16 6,850 20 0.29 7,750 20 0.163 8,300 20 0.253
UHD[T][M][X][S][R] 250 UHD[T][M][X][S][R] 300 UHD[T][M][X][S][R] 350 UHD[T][M][X][S][R] 400
Temperature
Rise (°F)
2,350 80 0.05 2,700 86 0.02 3,120 86 0.03 3,420 86 0.04 3,000 63 0.07 4,735 50 0.06 4,880 56 0.07 5,200 57 0.08 4,400 43 0.13 6,813 35 0.12 6,612 41 0.123 6,700 45 0.13 5,900 32 0.19 8,000 30 0.17 9,140 30 0.23 8,850 34 0.21 7,625 25 0.28 9,300 26 0.22 10,500 26 0.30 11,600 26 0.36 8,850 22 0.35 10,200 23 0.27 13,600 22 0.48 14,200 22 0.53
Pressure
Drop
(in wc)
Pressure
Drop
(in wc)
Airflow
(CFM)
Airflow
(CFM)
Temperature
Rise (°F)
Temperature
Rise (°F)
Pressure
Drop
(in wc)
Pressure
Drop
(in wc)
Airflow
(CFM)
Airflow
(CFM)
Temperature
Rise (°F)
Temperature
Rise (°F)
Pressure
Drop
(in wc)
Pressure
Drop
(in wc)
Airflow
(CFM)
Airflow
(CFM)
Temperature
Rise (°F)
Temperature
Rise (°F)
Pressure
Pressure
Drop
(in wc)
Drop
(in wc)
9 of 55
UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
Riv
Nut
Cone Point
Set Pin
Window
Clamp
Unistrut
Unistrut
3/8"-16
Threaded
Rod
Washer
Nut
Channel Nut
6.2 Suspension
WARNING
Crush Hazard
Use 3/8" threaded rod minimum.
Failure to follow these instructions can result in death, injury or property damage.
For typical suspension, See Page 10, Figure 6.
When handling or supporting the heater from below,
ensure that the weight is taken at the support points.
Figure 6: Suspension Methods
The gas or electrical supply lines must not be used to support the heater.
Do not locate the gas or electrical supply lines directly over the path of the flue products from the heater.
The heater must be installed in a location that is readily accessible for servicing.
The heater must be installed in accordance with clearances to combustibles as indicated on the serial plate, wall tag and throughout the manual. See Page 7, Section 4.
Ensure all 3/8"-16 threaded suspension hardware is torqued to a minimum of 19 ft lbs. (25.8Nm)
NOTE:
Four suspension points located on top of heater. Duct supports not shown. Duct supports and duct are not provided by manufacturer.
3/8"-16 Threaded Rod
Washer
10 of 55
Nut
Support Points (for use in handling)
SECTION 7: VENTING
SECTION 7: VENTING
WARNING
Carbon Monoxide Hazard
Heaters must be vented outdoors.
Heaters must be installed according to the installation manual.
Failure to follow these instructions can result in death or injury.
7.1 Venting
This heater must be vented in accordance with the
rules contained in this manual and with the following national codes and any state, provincial or local codes which may apply: United States: Refer to NFPA 54/ANSI Z223.1 - latest revision, National Fuel Gas Code; Canada: Refer to CSA B149.1 Natural Gas and Propane Installation Code.
Any portion of vent pipe passing through a
combustible wall must have a listed thimble to conform with the above codes.
The bottom of the vent or air intake terminal shall not
be located less than 1' (.3 m) above grade level.
The vent shall not terminate less than 7' (2.1 m)
above grade where located adjacent to public walkways.
Vent terminal must be installed at a height sufficient
to prevent blockage by snow and building materials protected from degradation by flue gasses.
Vent terminal must be beyond any combustible
overhang. Secure all joints with corrosion resistant #8 x 3/8"
sheet metal screws. For single wall venting, pressure sensitive aluminum
tape or silicone sealant must be used to seal all joints.
Aluminum tape shall have a minimum temperature
rating of 400° F (204° C) and meet SMACNA AFTS­100-73 standards. High temperature silicone sealant must have a minimum temperature rating of 480° F (250° C).
7.1.1 United States Requirements
Vent must terminate at least 3' (.9 m) above any
forced air inlet located within 10' (3.1 m).
Vent must terminate at least 4' (1.2 m) below,
4' (1.2 m) horizontally from, or 1' (.3 m) above any door, operable window, or gravity air inlet into any
building. NFPA 54/ANSI Z223.1 - latest revision, National
Fuel Gas Code specifies a 4' (1.2 m) horizontal vent terminal clearance from gas and electric meters, regulators and relief equipment.
7.1.2 Canadian Requirements
The vent shall not terminate within 6' (1.8 m) of a mechanical air supply inlet to any building.
The vent shall not terminate within 3' (.9 m) of a window or door that can be opened in any building, any non-mechanical air supply inlet to any building, or of the combustion air inlet of any other piece of equipment.
7.2 Vent Installation
Maintain clearances to combustibles at all times for safety. Clearances are the required distances that combustible objects must be away from the heater to prevent serious fire hazard. See Page 7, Section
4. For vented units, the vent must terminate outside of the building. Vents must be fully sealed and correctly sized for the model. If the vent passes through a wall or ceiling of combustible material, it must be enclosed by a listed thimble and be separated from the thimble by at least a 2" (5 cm) air gap.
For separated combustion models, vents and air intakes must be a fully sealed system and correctly sized for the model. Vent should be assembled as detailed on Page 13, Figure 7 through Page 16, Figure 12.
The joints between the vent terminal and the roof or wall must be properly sealed.
Vents and air intakes must be adequately
supported so that the heater does not bear the weight of the pipes.
For vent termination See Page 13, Figure 7 through Page 16, Figure 12.
7.2.1 Standard Vented Heaters (Models UHD[T][M][X][R] 150 - 400)
The vent must be fitted with a low resistance
terminal. See Page 13, Figure 7 through Page 14, Figure 9. Standard vented heaters do not allow outdoor air intake for combustion air.
7.2.2 Separated Combustion Heaters (Models UHD[T][M][X]S[R] 150 - 400)
The heaters are designed to be installed as
separated combustion heaters. The vent and air intake are run as separate pipes to the wall or roof
11 of 55
UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
terminals. See Page 15, Figure 10. As an option, the vent and air intake are run as separate pipes to a concentric vent box and a concentric vent/air intake pipe penetrates the wall or roof. See Page 15, Figure 11 and Page 16, Figure 12.
For separated combustion installation, the vent and air intake must be fitted with an individual and correctly sized sealed system and the vent and air intake must terminate at approved wall and roof terminals.
Separated combustion units may not be common vented.
7.3 Horizontal Venting
Horizontally vented heaters must be individually vented, no common venting.
Vent pipe must be sloped ¼" (.6 cm) downward for
every 1' (.3 m). In noncombustible walls only, vent terminal (P/N
02537801-1P) may be used. For 4'' (10 cm) vents in either combustible or
noncombustible walls, use vent terminal (P/N
90502100) or equivalent insulated vent terminal. Follow the manufacturer's instructions for proper installation.
Instead of an insulated vent terminal, a listed thimble with 2" (5 cm) air gap may be used with a 4" (10 cm) vent cap (P/N 90502102).
7.4 Vertical Venting
Vertically vented standard vented heaters can be
common vented (up to four heaters). For 4'' (10 cm) common vent, an approved vent cap
(P/N 90502102) must be used. For 6'' (15 cm) common vent, an approved vent cap
(P/N 90502103) must be used. For common vertical venting of more than two
heaters, See Page 14, Figure 9.
A vent shall not extend less than 2' (.6 m) above the
highest point where it passes through a flat roof of a building.
7.5 Maximum Vent Lengths Table
Model UHD[T][M][X][S][R] 150 - 400 # of Elbows
30 ft (9.1 m) 1
25 ft (7.6 m) 2 20 ft (6.1 m) 3 15 ft (4.5 m) 4 10 ft (3.0 m) 5
7.6 Vent Material
Vent material may be single wall 26 ga. (minimum) galvanized steel or equal thickness stainless steel. Completely seal all joints, refer to Page 11, Section
7.2. If penetrating a combustible wall or roof, a listed thimble with 2" (5 cm) clearance must be used. Where local codes permit, a single section of type B-1 vent material may be used at the roof or wall penetration instead of a thimble. Ensure vent manufacturer's clearance from vent material is maintained. Seal annular space of the type B-1 vent as well as all joints in the remaining vent.
7.7 Replacing an Existing Heater in a Venting System
When replacing an existing heater in a venting system, the venting system may not be properly sized to vent the new heater. The following steps must be followed with each piece of equipment connected to the venting system placed in operation, while any other equipment connected to the venting system are not in operation.
1. Seal any unused openings in the venting sys­tem.
2. Inspect the venting system for proper size and horizontal pitch, as required by the NFPA 54/
ANSI Z223.1 - latest revision, National Fuel Gas Code (US) or Standard CSA B149.1 Natural Gas and Propane Installation Code (Canada) and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
3. Close all building doors and windows and all
doors between the space in which the piece(s) of equipment connected to the venting system are located and other spaces of the building. Turn on clothes dryers and any exhaust fans, such as range hoods and bathroom exhausts so that they shall operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
4. Follow the lighting instructions. Place the
equipment being inspected in operation. Adjust thermostat so that the equipment will operate continuously.
5. For any equipment having a draft hood, test for
draft hood equipment spillage at the draft hood relief opening after five minutes of main burner operation. Use the flame of a match or candle.
12 of 55
6. After it has been determined that each piece(s) of equipment connected to the venting system
Figure 7: Vent and Roof Detail
properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-burning piece(s) of equipment to their previous conditions of use.
7. If improper venting is observed during any of the above tests, the venting system must be corrected by a contractor qualified in the installation and service of gas-fired equipment or your local gas supplier. If the venting must be resized, use appropriate tables in (US) Appendix G of NFPA 54/ANSI Z223.1 - latest revision, National Fuel Gas Code (US) or Standard CSA B149.1 Natural Gas and Propane Installation Code (Canada) to determine minimum size. All vent corrections must be in accordance with the appropriate local codes and the NFPA 54/ANSI Z223.1 ­latest revision, National Fuel Gas Code (US) or Standard CSA B149.1 Natural Gas and Propane Installation Code (Canada).
Figure 8: Standard Vented Heater - Vertical and Horizontal Vent Termination
SECTION 7: VENTING
Model Vent Diameter Part Number
UHD[T][M][X][R] 150 - 400 4" (10 cm) 90502102
13 of 55
UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
Figure 9: Standard Vented Heater - Common Vertical Vent Termination
Type "B" vent cap (7" [18 cm] or 8" [20 cm]) may be
SIDE VIEW
2'(.6 m)
Minimum
used. (These are not available from the manufacurer.)
Type "B" Vent Pipe
Roof
Flashing
Roof
The last section of vent pipe passing through the roof or wall may be Type "B" vent pipe. All other vent materials in the building must be single wall vent pipe.
TOP VIEW
Requirements:
4" (10 cm)
Single Wall Pipe
"D"
Approved
Thimble
(If Applicable)
Single Wall Pipe
"D" Area must equal sum
of open area of
individual vents.
4" (10 cm)
Single Wall Pipe
• Maximum of four heaters can be commonly vented through the roof.
• Heaters must be of the same BTU output.
• Heaters must be controlled by a common thermostat.
• Connections to a common stack must be positioned to avoid direct opposition between streams of combustion gases.
14 of 55
Figure 10: Separated Combustion Heater - Vertical and Horizontal Vent Termination
SECTION 7: VENTING
Model **Vent Diameter Part Number
UHD[T][M][X]S[R] 150 - 400 4" (10 cm) 90502102
Model *Air Intake Diameter Part Number
UHD[T][M][X]S[R] 150 - 250 4" (10 cm) 90502102 UHD[T][M][X]S[R] 300 - 400 5" (13 cm) 90502105
Figure 11: Concentric Vent Box
15 of 55
UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
Figure 12: Concentric Vertical and Horizontal Vent Termination - Separated Combustion Heater
4" (10 cm)
Type B-1 Vent
UHDS 150-250: 6"
(15 cm)
Diameter Single Wall UHDS 300-400: 8"
(20 cm)
Diameter Single Wall
Concentric Vent Box
Air Intake*
Vent Terminal with Baffle Plate
6" (16 cm) Minimum 12" (31 cm) Maximum
Storm Collar (By Others) (Attach with 3 sheet metal screws.)
Combustion Air Terminal
Flashing (By Others)
12" (31 cm) Minimum from roof to combustion air terminal
NOTE: Vent supports not shown. Duct supports not shown. Duct and vent supports not provided by the manufacturer.
6" (16 cm)
Minimum
12" (31 cm)
Maximum
Vertical
Vent**
Option
10' (3 m)
Maximum
Air Intake*
Horizontal Option
Vent**
Concentric Vent Box
Description Part Number Qty. Concentric Vent Kit (150 - 250) UHVK1
Concentric Vent Box Top & Side Assembly 90504113 1 Concentric Vent Box Bottom Assembly 90504112 1 Screw #6 x 3/8 Self Drilling 91119100 14 4" (10 cm) Vent Terminal with Baffle Plate 90502102R 1 6" (15 cm) Combustion Air Terminal 90502103 1
Description Part Number Qty. Concentric Vent Kit (300 - 400) UHVK2
Concentric Vent Box Top & Side Assembly 90504013 1 Concentric Vent Box Bottom Assembly 90504012 1 Screw #6 x 3/8 Self Drilling 91119100 14 4" (10 cm) Vent Terminal with Baffle Plate 90502102R 1 8" (20 cm) Combustion Air Terminal 90502104 1
4"
(10 cm)
Type
B-1
Vent Terminal with Baffle Plate
Vent
Storm Collar (By Others)
(Attach with 3 Combustion Air Terminal
sheet metal
screws.)
12" (31 cm) Minimum from wall to combustion air terminal
Model **Vent Diameter
UHD[T][M][X]S[R] 150 - 250 4" (10 cm)
Model *Air Intake Diameter
UHD[T][M][X]S[R] 150 - 250 4" (10 cm) UHD[T][M][X]S[R] 300 - 400 5" (13 cm)
16 of 55
SECTION 8: AIR SUPPLY
WARNING
Explosion Hazard
Equipment must have access to uncontaminated air at all times.
Failure to follow these instructions can result in death, injury or property damage.
8.1 Separated Combustion Installation
When installed as a separated combustion heater
(UHD[T][M][X]S[R]), the air for combustion is drawn in from outside the building.
SECTION 8: AIR SUPPLY
8.2 Building Ventilation
Where ventilation is required, air must be taken from
an outside point where it is not likely to be contaminated or obstructed.
8.3 Outside Combustion Air Supply
If outside combustion air supply is required, separated combustion model (UHD[T][M][X]S[R]) heaters must be used.
Caution: If the building has a slight negative pressure or corrosive contaminants such as halogenated hydrocarbons are present in the air, an outside combustion air supply to the heater is required. Seal all combustion air pipe joints.
The outside air terminal must not be more than 1'
(31 cm) above the vent terminal.
8.3.1 Length Requirements
Follow the constraints listed on Page 12, Section 7.5.
17 of 55
UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
SECTION 9: GAS PIPING
Canada: Rubber type 1 gas hose (Canadian
models) is certified as being in compliance with the standard for elastomeric composite hose and hose couplings for conducting propane and natural gas, CAN/CGA 8.1 – latest revision.
9.1 Connections
Connect the heater to the gas supply ensuring that
Fire Hazard
Connect gas supply according to Figure 13.
Do not use gas supply pipe and electrical connections to support heater’s weight.
Gas can leak if not installed properly.
Failure to follow these instructions can result in death, injury or property damage.
WARNING
Explosion Hazard
Leak test all components of gas piping before operation.
Gas can leak if piping is not installed properly.
Do not high pressure test gas piping with heater connected.
Failure to follow these instructions can result in death, injury or property damage.
A gas meter is connected to the service pipe by the
gas supply company. An existing meter should be checked, preferably by the company, to ensure that the meter is adequate for the rate of gas supply required.
Installation pipes must be fitted in accordance with local and national codes. Pipes of smaller size than the heater inlet gas connection should not be used.
Gas lines must meet applicable codes: United States: Flexible stainless steel gas hose
(US models) is certified per the standard for connectors for gas equipment. ANSI Z21.21/CSA
6.10 – latest revision.
the final connections are as follows:
• Gas supply pipe work is run in medium or heavy gauge tubing in compliance with local and national codes.
• Meter and service must be large enough to handle all the burners being installed plus any other connected load. The gas pipe which feeds the system must be large enough to supply the required gas with a maximum pressure drop of 1/2 in wc. When gas piping is not included in the layout drawing, contact the local gas supplier.
• An isolating valve and union connection should be used and fitted into the supply adjacent to the heater.
• A minimum 1/8" NPT plugged tapping accessible for test connection must be installed immediately upstream of the gas supply connection to the heater.
• For suspended heaters, an approved metal flexible connection between the isolating valve and the heater may be used. To reduce
pressure loss, use one pipe size larger than the heater gas connection.
IMPORTANT - The complete installation must be
purged and tested for gas soundness in accordance with local and national codes.
Caution: Do not high pressure (in excess of 1/2 psi [14 in wc]) test the gas piping with the burner connected. Close manual shut-off valve during any pressure testing equal to or less than 1/2 psi (14 in wc).
Check the pipe and tubing ends for leaks before placing heating equipment into service. When checking for gas leaks, use a soap and water solution; never use an open flame.
18 of 55
Figure 13: Gas Connection
SECTION 9: GAS PIPING
19 of 55
UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
SECTION 10: WIRING
disconnect switch of proper electrical rating should
DANGER
Electrical Shock Hazard
Disconnect electric before service.
be installed in the vicinity of the heater. All heaters are equipped with thermostat
connections suitable to power a 24 V thermostat. Heater must be wired and electrically grounded in
accordance with local codes. In the absence of local codes in accordance with: United States: refer to
National Electrical Code Canada: refer to Canadian Electrical Code CSA C22.1 Part I - latest revision.
®
NFPA 70 - latest revision
More than one disconnect switch may be required to disconnect electric from heater.
Heater must be properly grounded.
Failure to follow these instructions can result in death or electrical shock.
All heater models require constant 120 V/1Ø/60 Hz
power supply. Check heater serial plate for electrical rating for proper circuit sizing. For servicing, a
10.2 Low Voltage Thermostat for Models UHD[T][M][X][S][R] 150-400
NOTE: Electrical supply is
located below terminal strip.
10.1 Positioning Thermostats
A room thermostat should be mounted on a vibration-free wall or column at a height of approximately 5' (1.5 m) from the floor to measure the ambient temperature. It should be clear of both cold drafts and the direct path of warm air from the heater. Avoid mounting thermostat on outside walls or in areas directly exposed to radiant heat or sunlight. Install wall tag in a visible location near thermostat. See Page 5, Section 2.1 for wall tag details.
20 of 55
10.3 UHD[X][S][R] Series Internal Wiring Diagram for Single Stage Gas Valves
SECTION 10: WIRING
IMPORTANT:
For field wiring into service junction box, or if any of the original wire supplied with the heater must be replaced, it must be replaced with wiring material having a temperature rating of at least 221° F (105° C) and 600 V. For supply connections, use No. 14 AWG or larger wires.
21 of 55
UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
10.4 UHD[X][S][R] Series Ladder Wiring Diagram for Single Stage Gas Valves
IMPORTANT:
For field wiring into service junction box, or if any of the original wire supplied with the heater must be replaced, it must be replaced with wiring material having a temperature rating of at least 221° F (105° C) and 600 V. For supply connections, use No. 14 AWG or larger wires.
22 of 55
10.5 UHD[T][X][S][R] Series Internal Wiring Diagram for Two Stage Gas Valves
HIGH/LOW CONTROL
W2
1
SECTION 10: WIRING
HIGH
COMMON
LOW
IMPORTANT:
For field wiring into service junction box, or if any of the original wire supplied with the heater must be replaced, it must be replaced with wiring material having a temperature rating of at least 221° F (105° C) and 600 V. For supply connections, use No. 14 AWG or larger wires.
23 of 55
UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
10.6 UHD[T][X][S][R] Series Ladder Wiring Diagram for Two Stage Gas Valves
HIGH
STAGE
NOTE:
For field wiring into service junction box, or if any of the original wire supplied with the heater must be replaced, it must be replaced with wiring material having a temperature rating of at least 105° C (221° F) and 600 volts. For supply connections use No. 14 AWG or larger wires.
24 of 55
10.7 UHD[M][X][S][R] Series Internal Wiring Diagram for Modulating Gas Valves
SECTION 10: WIRING
IMPORTANT:
For field wiring into service junction box, or if any of the original wire supplied with the heater must be replaced, it must be replaced with wiring material having a temperature rating of at least 221° F (105° C) and 600 V. For supply connections, use No. 14 AWG or larger wires.
25 of 55
UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
10.8 UHD[M][X][S][R] Series Ladder Wiring Diagram for Modulating Gas Valves
IMPORTANT:
For field wiring into service junction box, or if any of the original wire supplied with the heater must be replaced, it must be replaced with wiring material having a temperature rating of at least 221° F (105° C) and 600 V. For supply connections, use No. 14 AWG or larger wires.
26 of 55
10.9 Electrical Connection to the Heater
SECTION 10: WIRING
IMPORTANT: Junction box is not provided with heater.
Conduit can also be attached directly to heater with wire junction made within the heater cabinet.
27 of 55
UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
SECTION 11: OPERATION AND MAINTENANCE
DANGER
Electrical Shock Hazard
Disconnect electric before service.
Heater must be connected to a properly grounded electrical source.
Failure to follow these instructions can result in death, electric shock, injury or property damage.
Read this manual carefully before installation, operation, or service of this equipment. All components are accessed via the hinged door. Opening the door exposes live electrical connections and hot components.
Prior to any maintenance or service of the heater, shut off, lockout and tagout the electrical disconnect and gas valve that supplies the unit in accordance with OSHA regulations.
11.1 Pre-Start-Up Checks
All pre-start-up checks must be carried out before
lighting the heater. Ensure that the heater and all controls are suitable
for the gas, pressure and electrical supply to which they are to be connected.
11.1.1 Electrical Checks
1. Check that all site wiring is connected in accordance with the appropriate wiring diagram
on Page 21, Section 10.3, Page 23, Section
10.5, or Page 25, Section 10.7.
Explosion Hazard
Turn off gas supply to heater before service.
WARNING
Burn Hazard
Allow heater to cool before service.
Tubing may still be hot after operation.
11.1.3 Mechanical Checks
1. Check that the flue (and air intake for separated combustion units) is installed in accordance with the instructions in this manual and local regulations. See Page 11, Section 7.
11.2 Begin Start-Up
11.2.1 Before Operating the Heater
To ensure that all the controls are in safe working order, operate the heater for the first time with the isolating gas valve turned off and power supply turned on.
1. Turn off the isolating gas valve.
2. Turn up the thermostat above room temperature. The automatic ignition sequence will now begin as described on Page 29, Figure 14.
There will be no ignition of the burner and lockout will occur, which proves the controls are operating correctly.
Cut/Pinch Hazard
Wear protective gear during installation, operation and service.
Edges are sharp.
11.1.2 Gas Supply
All aspects of the gas installation including the gas
meter must be inspected, tested for gas tightness and purged in accordance with local and national codes.
Ensure that the air is fully purged from the heater inlet pipe up to the main gas valve inlet test nipple.
28 of 55
Figure 14: Automatic Burner Control Sequence
Burner Sequence for Ignition Control
Thermostat 24 V
SECTION 11: OPERATION AND MAINTENANCE
RUNSTART
SHUT DOWN
Flue Blower
Pressure
Switch
Ignition Spark
Start Gas Valve
Flame Signal
NO
P
C
NC
*Purge time begins at pressure switch change over.
30 Seconds Purge*
ts = 10 Seconds
Required Incoming Signals
Signals Output By Control
If at any stage the flame fails, the control will retry for ignition. The control has four trials for ignition before a one hour lockout.
Figure 15: Single Stage Gas Valve for Models UHD[X][S][R] 150 – 400
30 Seconds Post
TOP VIEW
Gas Inlet
END VIEW
Inlet Pressure
Regulator
½PSI IN
C
OFF
Description Part Number
Gas Valve 150 - 250 NG 90032505 Gas Valve 150 - 250 LP 90032506 Gas Valve 300 - 400 NG 90032520 Gas Valve 300 - 400 LP 90032521
ON
Outlet Pressure
29 of 55
UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
Figure 16: Two Stage Gas Valve for Models UHD[T][X][S][R] 150 - 400
Regulator
END VIEW
TOP VIEW
½PSI IN
HI
Gas Inlet
Description Part Number
Gas Valve 150 - 250 NG 90032530 Gas Valve 150 - 250 LP 90032531 Gas Valve 300 - 400 NG 90032532
Inlet Pressure
Gas Valve 300 - 400 LP 90032533
Figure 17: Modulating Gas Valve for Models UHD[M][X][S][R] 150 - 400
LO
C
OFF
ON
Outlet Pressure
30 of 55
Description Part Number
Gas Valve 150 - 250 NG 90032505 Gas Valve 150 - 250 LP 90032506 Gas Valve 300 - 400 NG 90032520
Gas Valve 300 - 400 LP 90032521 1/2" Exa Valve 150-250 90032550 3/4" Exa Valve 300-400 90032551
SECTION 11: OPERATION AND MAINTENANCE
11.2.2 Start-Up the Gas Valve (All Gases)
11.2.2.1 Check Burner Gas Pressure (Single Stage)
1. Remove the plug in the outlet (burner) pressure test point and connect a pressure tap and a manometer. See Page 29, Figure 15.
2. With the burner firing, measure the pressure on the manometer. To adjust the burner pressure, remove the regulator cover from the valve and turn the regulator adjustment screw to set the required burner pressure as stated in the Technical Data Table for the correct gas and model on Page 51, Section 16.3 and Page 53, Section 16.6.
11.2.2.2 Check Burner Gas Pressure (Two Stage)
1. Remove the plug in the gas valve outlet pres­sure test point and connect a pressure tap and a manometer. See Page 30, Figure 16.
2. With the unit operating in high fire or low fire, measure the outlet pressure on the manometer. Measure burner pressure in both operating modes. To adjust the burner pressure, remove plastic cover from regulators and adjust High and/or Low regulators as needed. Required burner pressures are indicated in the Technical Data Table for the correct gas and model on
Page 51, Section 16.3 and Page 53, Section
16.6
3. To set the high fire rate, adjust the high fire adjustment on the gas valve. To set the low fire rate (with the unit running in low fire), adjust the low fire adjustment on the gas valve.
11.2.2.3 Check Burner Gas Pressure (Modulating)
1. Loosen screw in outlet pressure tap shown on Page 30, Figure 17 and connect manometer. Gas pressure is NOT measured at Honeywell single stage gas valve.
2. With burner firing, measure pressure on manometer. To measure high fire burner pressure, disconnect modulating thermostat signal and apply 10 VDC to modulating input connections (polarity sensitive). To adjust high fire burner pressure, remove regulator cover from Honeywell single stage gas valve and turn regulator adjustment screw to set required burner pressure as stated in the Technical Data Table for the correct gas and model on Page
51, Section 16.3 and Page 53, Section 16.6
3. To measure low fire burner pressure disconnect 10 VDC signal to modulating valve.
NOTE: Low fire burner pressure is set at factory and not field adjustable. (modulating)
NOTE: If the correct burner pressure cannot be reached, then check the inlet pressure to the valve with the burner firing. See Technical Data Table on Page 51, Section 16.3 and Page 53, Section 16.6 for inlet pressure requirement.
Do not continue to adjust the regulator if the pressure is not changing.
If the inlet pressure is too low to allow correct burner pressure setting, then the gas inlet pressure must be corrected before completing the start-up.
11.2.2.4 Check Gas Rate (Single and Two-Stage)
1. After burner pressure adjustment, allow the heater to operate for at least 15 minutes and then re-check settings. Adjust pressure setting if necessary.
2. Check gas flow rate at gas meter. NOTE: For two stage valve, (High/Low operation) check gas flow in both operating modes.
3. Turn off heater and electrical supply.
4. Remove the manometer and refit all covers to the valve and tighten the screw of the outlet pressure tap.
11.2.2.5 Check Gas Rate (Modulating)
1. After burner pressure adjustment, allow heater to operate for at least 15 minutes and then recheck settings. Adjust pressure setting if nec­essary.
2. Check high/low fire gas flow rate at gas meter. To place heater into high fire, disconnect modulating thermostats signal and apply 10 VDC to modulating input connections.
3. To place heater into low fire, disconnect 10 VDC from modulating input connections.
4. Turn off heater and electrical supply.
5. Remove manometer, tighten outlet pressure tap screw and replace modulating thermostat signal wires.
31 of 55
UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
11.3 Pressure Switch
The pressure switch is factory pre-set for each
model and is not adjustable.
11.4 Turning Off the Heater
Set the thermostat to the
"OFF" position or lowest
setting and the main burner will stop.
11.5 External Controls
External controls may include time switch, interlock switch, room thermostat and frost thermostat. Operate each control to ensure that they function correctly. Set the switches (if fitted) and thermostat(s) to the users’ requirements.
11.6 Complete Start-Up
Ensure that all covers are fitted correctly and all test points are properly sealed.
11.7 Instruction to the User
Explain the controls of the heater to the user including how to turn it on and off, using the controls fitted on site.
Give this manual to the user. Ensure that the user is shown and understands the
importance of maintaining clearances to combustibles on Page 7, Figure 4, installer responsibility on Page 5, Section 2 and user instructions on Page 33, Section 12 and all warnings defined in this manual.
32 of 55
SECTION 12: USER INSTRUCTIONS
SECTION 12: USER INSTRUCTIONS
DANGER
Electrical Shock Hazard
Disconnect electric before service.
Heater must be connected to a properly grounded electrical source.
Failure to follow these instructions can result in death, electric shock, injury or property damage.
The UHD[T][M][X][S][R] Series heaters are fully
automatic and operate from the external controls fitted on site.
12.1 Heater Operation
When the heater has been switched on by the
thermostat installed on site, the main burner will automatically turn on.
The burner control module will control the safe
ignition of the flame. If equipped with two stage gas valve, the heater may
start in low or high fire. If equipped with a modulating gas valve, heater will
start at firing rate called for by modulating thermostat. Heater will continue to run at firing rate called for by thermostat, with 10 VDC being maximum rate and 0 VDC being minimum rate. ON/ OFF control is provided by thermostat R and W connections. See Page 20, Section 10.2.
All heaters require a constant gas and electricity
supply which must not be interrupted during the normal operation of this heater.
12.2 Lighting Instructions
12.2.1 To Turn On Heater
1. Ensure that the electrical and gas supplies to the heater are on. Check that the on site controls are
IMPORTANT: The thermostat setting must be above the ambient temperature for the heater to operate.
2. The automatic firing sequence will begin as described on Page 29, Figure 14. The heater will now operate automatically under the control of the on site controls.
12.2.2 To Turn Heater Off
Set the thermostat to the setting.
"ON".
Explosion Hazard
Turn off gas supply to heater before service.
"OFF" position or lowest
WARNING
Burn Hazard
Allow heater to cool before service.
Tubing may still be hot after operation.
The burner will turn off immediately. To restart, turn the thermostat on or above room
temperature.
12.3 Simple Troubleshooting
Some possible reasons for the heater not operating are:
1. Gas supply not
2. Electricity supply not
3. The time and/or temperature controls are not
"ON".
"ON".
4. A limit switch may have operated. This may be caused by an interruption of the electrical supply, failure of the distribution fan or vent or heat exchanger blockage.
If a temperature limit switch persistently trips, there is a fault which must be investigated by a contractor qualified in the installation and service of gas-fired heating equipment.
12.3.1 Simple Troubleshooting (Burner Faults)
If the burner fails to ignite for any reason, it will retry for ignition (four trials total). After four unsuccessful ignition trials, the control will put the heater into lockout for one hour.
Lockout should not occur during normal operation of the heater and indicates there is a fault condition which must be corrected. There is an LED light on the ignition control that flashes codes to assist in fault correction. See Page 34, Figure 18 for LED indication codes.
Cut/Pinch Hazard
Wear protective gear during installation, operation and service.
Edges are sharp.
"ON".
33 of 55
UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
Figure 18: LED Diagnostic Codes
LED INDICATION FAULT MODE
Slow Flash Normal Operation - No call for heat.
Fast Flash Normal Operation - Call for heat.
2 Flashes Ignition Lockout - No flame detected.
3 Flashes Airflow Fault - Pressure switch open or closed.
4 Flashes Temperature Limit Switch Open
5 Flashes Flame Sense Error - Gas valve not energized.
Steady On Internal Control Failure
34 of 55
SECTION 13: SERVICING
SECTION 13: SERVICING
DANGER
Electrical Shock Hazard
Disconnect electric before service.
Heater must be connected to a properly grounded electrical source.
Failure to follow these instructions can result in death, electric shock, injury or property damage.
13.1 Servicing Instructions
After start-up, the heater will require maintenance to
be carried out, at a minimum, annually. If the heater is used in a dirty or dusty area, more frequent maintenance may be required.
IMPORTANT: Prior to any maintenance or service of the heater, shut off, lockout and tagout the electrical disconnect and gas valve that supplies the unit in accordance with OSHA regulations. After any maintenance or repair work, always test fire the heater in accordance with the start-up instructions
on Page 28, Section 11 through Page 32, Section
11.7 to ensure all safety systems are in working order
before leaving the heater to operate. Minor faults may be traced by using the troubleshooting charts
on Page 38, Section 14 through Page 42, Section
14.5.
IMPORTANT: Check all gas pipes and pipe joints to ensure there are no cracks or gas leaks. Any cracks in the pipes or pipe joints must be repaired.
IMPORTANT: Inspect all suspended components and hardware. Ensure that they are in good condition, properly tightened, and corrosion free.
13.2 Burner Maintenance
13.2.1 Burner Maintenance for Models 150-400
1. Open the hinged door via tooled access and remove from the hinges. Set door aside. See Page 44, Section 15.2.
2. Remove the filler panel (10 screws) to fully access the burner assembly. See Page 44, Section 15.2.1.
3. Remove burner assembly from cabinet via screws around the burner assembly (quantity will vary). See Page 44, Section 15.2.1.
Explosion Hazard
Turn off gas supply to heater before service.
WARNING
Burn Hazard
Allow heater to cool before service.
Tubing may still be hot after operation.
Electrode and flame probe should remain attached.
4. Remove manifold from burner assembly via four screws, two on top and two on bottom. See Page 45, Section 15.2.2. Clean any deposits from the main burner which may have formed in the injectors or venturi of the burner.
5. Check condition of ignition electrode and flame probe. Clean off any deposits which may have formed, check condition of ceramic insulators. Replace as required. See Page 46, Section
15.3.
13.3 Heat Exchanger Maintenance
The heat exchanger will remain clean unless a
problem has developed with combustion. Inspect the heat exchanger. Look for signs of overheating at the front of the tubes which may indicate burner over firing or persistently low air flows.
13.4 Gas Valve Maintenance
No regular maintenance is required on this device.
To change gas control valves, See Page 43, Section
15.1.
Do not repair or disassemble gas valve.
Replace faulty gas valves with replacement parts sold and supplied by Addison.
13.5 Flue Blower
The flue blower should not require maintenance.
However, if the air pressure switch is causing burner lockout, then remove the flue blower from the vent box by unscrewing the screws at the mounting plate. Screw quantity will vary by model size. Remove the screws attaching the mounting plate to the fan inlet.
See Page 47, Section 15.5 through Page 48, Section 15.6. Ensure that the fan is free to run and
Cut/Pinch Hazard
Wear protective gear during installation, operation and service.
Edges are sharp.
35 of 55
UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
that the fan wheel is clean.
13.6 Venting and Air Intake Pipe
Inspect all venting and air intake pipe. Ensure that all seams are sealed and suspension points secure. Repair suspension points if any part of the venting or combustion air pipe is sagging. Check to make sure any insulation is not missing or in poor condition. Replace as necessary. Check all venting and air intake components to ensure they are in good condition, gas tight and corrosion-free.
13.7 Maintenance Checklist Installation Code and Annual Inspections: All
installation and service of ADDISON
®
equipment
must be performed by a contractor qualified in the installation and service equipment sold and supplied by Addison and conform to all requirements set forth in the ADDISON
®
manuals and all applicable governmental authorities pertaining to the installation, service, operation and labeling of the equipment.
To help facilitate optimum performance and safety, Addison recommends that a qualified contractor conduct, at a minimum, annual inspections of your ADDISON
®
equipment and perform service where necessary, using only replacement parts sold and supplied by Addison.
Annual Fall Start Up Follow entire start-up procedure at this time and check control settings and
operation.
The Vicinity of the Heater Do not store or use flammable objects, liquids or vapors near the heater.
Immediately remove these items if they are present.
See Page 6, Section 3.
Vehicles and Other Objects
Maintain the clearances to combustibles.
Do not hang anything from, or place anything on, the heater.
Make sure nothing is lodged in between the heat exchanger tubes.
Immediately remove objects in violation of the clearances to combustibles.
See Page 7, Section 4.
Vent Pipe/Terminals Venting must be intact. Using a flashlight, look for obstructions, cracks on the
pipe, gaps in the sealed areas or corrosion.
The area must be free of dirt and dust.
Remove any carbon deposits or scale using a wire brush.
If the vent terminal has a screen built in, remove any dirt, dust or deposits from the screen.
See Page 11, Section 7 through Page 17, Section 8.
Cabinet Exterior After installation, touch up scratches. Periodic painting should be done there-
after as required. Warning labels and logo labels should be legible and accu-
®
rate. Please contact Addison or ADDISON
independent distributor if you
need replacement warning labels or logo labels.
See Page 2, Figure 1 through Page 4, Figure 3.
Combustion Air Intake Pipe
Intake pipe and inlet must be intact. Look for obstructions, cracks on the pipe, gaps in the sealed areas or corrosion.
The area must be free of dirt and dust.
Clean and reinstall as required.
See Page 17, Section 8.
36 of 55
Heat Exchanger Make sure there are no cracks.
Make sure there is no sagging, bending or distortion.
Clean or replace as required.
SECTION 13: SERVICING
Gas Line and Shut-off Valves
Burner Observation Window
Flue Blower Scroll, Wheel
Check for gas leaks.
See Page 18, Section 9.
Make sure it is clean and free of cracks or holes.
Clean and replace as required.
Compressed air or a vacuum cleaner may be used to clean dust and dirt.
and Motor Inshot Burners and
Orifices
Clear obstructions (even spider webs will cause problems).
Carefully remove any dust and debris from the burner.
Direct-Spark Igniter Replace if there are cracked ceramics, excessive carbon residue, or erosion
of the electrode.
The electrode gap should be 1/8" (3.2 mm).
Thermostat There should be no exposed wire or damage to the device or wiring.
See Page 20, Section 10.
Suspension Points Make sure the heater is hanging securely.
Look for signs of wear on the suspension materials or ceiling.
See Page 10, Figure 6.
Silicone Tubing Ensure tight, secure fit on all pressure fittings at pressure switch and vent box.
Gas Valve Verify that cap covering pressure regulator adjustment screw is secure and
has not been tampered with.
Verify all wiring connections.
Condensate Drain
Flush drain and clear any obstructions.
(when installed) Ductwork Consult an indoor air quality professional for proper cleaning procedures
Air Circulation Blower For a complete inspection, see the manufacturer’s Installation, Operation and
Service manual.
Wall Tag If wall tag is present, make sure it is legible and accurate. Please contact
®
Addison or your ADDISON
independent distributor if you need a wall tag.
See Page 5, Section 2.1.
37 of 55
UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
SECTION 14: TROUBLESHOOTING
DANGER
Electrical Shock Hazard
Disconnect electric before service.
Heater must be connected to a properly grounded electrical source.
Failure to follow these instructions can result in death, electric shock, injury or property damage.
Explosion Hazard
Turn off gas supply to heater before service.
WARNING
Burn Hazard
Allow heater to cool before service.
Tubing may still be hot after operation.
Cut/Pinch Hazard
Wear protective gear during installation, operation and service.
Edges are sharp.
38 of 55
14.1 General
SECTION 14: TROUBLESHOOTING
39 of 55
UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
14.2 Troubleshooting For Automatic Ignition Burner Systems
For optimum heater performance, use only replacement parts sold and supplied by Addison.
Conduct start-up procedure as shown on Page 28, Section 11.
40 of 55
SECTION 14: TROUBLESHOOTING
T
14.3 Troubleshooting for Flame Supervision System
o measure flame current, connect a 0 - 50 µA DC meter in series with the flame probe. If the meter
reads negative values, then reverse the test leads.
NOTE: Minimum flame probe current 1 µA DC. Typical flame probe current 3-5 µA DC.
41 of 55
UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
14.4 Troubleshooting for Gas Valves
14.5 Troubleshooting for Flue Blower
For optimum heater performance, use only replacement parts sold and supplied by Addison.
Conduct start-up procedure as shown on Page 28, Section 11.
42 of 55
SECTION 15: REPLACEMENT PARTS
SECTION 15: REPLACEMENT PARTS
DANGER
Electrical Shock Hazard
Explosion Hazard
WARNING
Fire Hazard
Carbon Monoxide Hazard
Use only genuine ADDISON® replacement parts per this installation, operation and service manual.
Failure to follow these instructions can result in death, electric shock, injury or property damage.
See warnings and important information on Page 35, Section 13 before removing or replacing parts.
Burner Components
All serviceable burner parts are accessed by the
hinged door on the side of the heater.
Replace in reverse order. Verify that the gas flow direction of the valve is correct. Use a minimum amount of gas seal on the thread joint. Check that all the joints are leak free. Reset gas valve. See Page 31, Section 11.2.2.
IT IS IMPORTANT THAT ONLY THE CORRECT
15.1 Gas Valve
Remove the gas supply pipe at the heater inlet.
GAS VALVE IS USED WHEN REPLACING THESE CONTROLS.
Follow instructions on Page 44, Section 15.2 to remove gas valve/manifold.
Description Part Number
Single Stage Gas Valve, NG (Models UHD[X][S][R] 150 - 250) 90032505 Single Stage Gas Valve, LP (Models UHD[X][S][R] 150 - 250) 90032506 Single Stage Gas Valve, NG (Models UHD[X][S][R] 300 - 400) 90032520 Single Stage Gas Valve, LP (Models UHD[X][S][R] 300 - 400) 90032521 Two Stage Gas Valve, NG (Models UHD[T][X][S][R] 150-250) 90032530 Two Stage Gas Valve, LP (Models UHD[T][X][S][R] 150-250) 90032531 Two Stage Gas Valve, NG (Models UHD[T][X][S][R] 300 - 400) 90032532 Two Stage Gas Valve, LP (Models UHD[T][X][S][R] 300 - 400) 90032533 Exa Valve ½" (Models UHD[M][X][S][R] 150-250) NG and LP 90032550 Exa Valve ¾" (Models UHD[M][X][S][R] 300-400) NG and LP 90032551
43 of 55
UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
15.2 Burner Compartment for Models UHD[T][M][X][S][R] 150-400
Side View of Burner Compartment with Hinged Door Removed
Before burner removal, remove the 10 screws holding the filler panel on and remove the filler panel.
15.2.1 Burner Compartment without Filler Panel for Models UHD[T][M][X][S][R] 150-400
Side View of Burner Compartment with Filler Panel Removed
Burner assembly must be removed to service orifices, manifold or burners.
Following any work, refit components in reverse order.
44 of 55
15.2.2 Burner Injectors for Models UHD[T][M][X][S][R] 150-400
SECTION 15: REPLACEMENT PARTS
Remove 4 screws to remove manifold.
Ensure gas tight fitting of injectors. Ensure correct alignment with burners. Ensure all pipe joints are gas tight.
UHD
MODEL
Orifice Quantity 7 8 9 10 11 12 14 14
[T][M][X][S][R]
150
Natural Gas
Orifice Marking 43 43 2.25 mm 2.25 mm 2.25 mm 43 43 40
P/N 91930043 91930043 91930225 91930225 91930225 91930043 91930043 91930040
Propane
Orifice Marking 1.35 mm 1.35 mm 54 54 54 1.45 mm 53 53
P/N 91930135 91930135 91930054 91930054 91930054 91930145 91930053 91930053
UHD
[T][M][X][S][R]
175
UHD
[T][M][X][S][R]
200
UHD
[T][M][X][S][R]
225
UHD
[T][M][X][S][R]
250
UHD
[T][M][X][S][R]
300
UHD
[T][M][X][S][R]
350
UHD
[T][M][X][S][R]
400
45 of 55
UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
15.3 Ignition Electrode and Flame Probe for Models UHD[T][M][X][S][R] 150-400
To replace the ignition electrode or flame probe, remove the
electrical lead and screw. Pull out from mounting. Refit in reverse ensuring that the gap to burner is as shown in the front view of the burner compartment.
Description Part Number Qty.
Spark Electrode 90427411 1 Automatic Ignition Flame Probe 90439300 1 Transformer 90436900K 1 Ignition Module 90434008 1 Inshot Burners UHD[T][M][X][S][R] 150 92000001 7 Inshot Burners UHD[T][M][X][S][R] 175 92000001 8 Inshot Burners UHD[T][M][X][S][R] 200 92000000 9 Inshot Burners UHD[T][M][X][S][R] 225 92000000 10 Inshot Burners UHD[T][M][X][S][R] 250 92000000 11 Inshot Burners UHD[T][M][X][S][R] 300 92000000 12 Inshot Burners UHD[T][M][X][S][R] 350 92000000 14 Inshot Burners UHD[T][M][X][S][R] 400 92000000 14 Limit Switch (150 - 400) [300 - 400 LOWER] 90412103 1 Limit Switch (300 - 400) [UPPER] 90412105 1
46 of 55
SECTION 15: REPLACEMENT PARTS
15.4 Heat Exchanger
The heat exchanger consists of a four-pass design with 1.75" outer diameter [409 stainless steel] tube. The
tube plates are made of [aluminized steel] [409 stainless steel]. The tube supports are made of [aluminized steel] [409 stainless steel].
15.5 Flue Blower for Models UHD[T][M][X][S][R] 150-300
Remove screws securing outlet flange to the flue adapter.
Refit in reverse order.
Disconnect electrical connections at plug in tabs.
Remove screws securing flue fan mounting plate to vent box.
Remove screws securing mounting plate to fan. (Not shown)
Refit in reverse.
Use new gaskets.
Ensure sealed joints.
Ensure mounting plate orifice is clear and not obstructed.
MODEL
Flue Blower P/N 90710403
IT IS IMPORTANT THAT ONLY THE CORRECT FLUE BLOWER SPECIFIED FOR EACH MODEL TYPE IS USED WHEN REPLACING THESE ITEMS.
Carry out a start-up after working on or changing a flue blower. See Page 28, Section 11.
UHD[T][M][X][S][R]
150 - 300
47 of 55
UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
Vent Box
Outlet Gasket
Flue Blower
Vent Box
screws
Flue
Adapter
Flue Adapter
to Flue Blower
screw
Rear Panel
Hole
Disconnect
electrical connections
at plug in tabs.
Mounting Plate
to Vent Box
screws
Gasket
Gasket
Mounting Plate
to Flue Blower
screws
Vent Box
Air Plate
15.6 Flue Blower for Models UHD[T][M][X][S][R] 350-400
Remove screws securing outlet flange to the flue adapter.
Refit in reverse order.
Remove screws securing flue blower mounting plate to vent box.
Remove screws securing mounting plate to blower.
Refit in reverse.
Use new gaskets.
Ensure sealed joints.
Ensure mounting plate orifice is clear and not obstructed.
MODEL
Flue Blower P/N 90710402
IT IS IMPORTANT THAT ONLY THE CORRECT FLUE BLOWER SPECIFIED FOR EACH MODEL TYPE IS USED WHEN REPLACING THESE ITEMS.
Carry out a start-up after working on or changing a flue blower. See Page 28, Section 11.
UHD[T][M][X][S][R] 350 - 400
48 of 55
SECTION 15: REPLACEMENT PARTS
15.7 Pressure Switch
WARNING
Carbon Monoxide Hazard
Use correct pressure switch specified for each model.
Use of incorrect pressure switch or disabling pressure switch circuit could cause unsafe condition.
Failure to follow these instructions can result in death or serious injury.
Pull off 3 way connector. Spring open plastic clips of mounting cradle. Replace with correct type of pressure switch for model. The pressure switches are color coded for each pressure setting. Carry out a start-up after working on or changing a pressure switch. See Page 28, Section 11.
UHD
MODEL
Pressure Switch Kit P/N
Color Code grey orange orange grey blue grey
Set Point (in wc) 0.41 0.79 0.18 0.72 0.55 0.72
Pressure Switch Snap Ring P/N
[T][M][X][S][R]
150 - 175
90439803 90439808 90439812 90439811 90439805 90439811
90439850 90439850 90439850 90439850 90439850 90439850
UHD
[T][M][X][S][R]
200 - 225
UHD
[T][M][X][S][R]
250
UHD
[T][M][X][S][R]
300
UHD
[T][M][X][S][R]
350
UHD
[T][M][X][S][R]
400
15.8 Ignition Control
The control mounts to the electrical plate. Pull out ignition cable and wiring from board, noting their
positions. Release the four mounting standoffs. Refit in reverse. Ensure correct location of ignition cable and all other wiring.
15.9 Limit Switches
15.9.1 Removal and Replacement
1. Remove the electrical connections to the switch.
2. Unscrew the two screws securing the switch.
3. Fit a new switch with two screws.
4. Reconnect the electrical connections and test operation.
49 of 55
UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
SECTION 16: SPECIFICATIONS
16.1 Dimension Data for Models UHD[T][M][X][S][R] 150-250
Model
A in (cm) 42.4 (107.7) 42.4 (107.7) 42.4 (107.7) 42.4 (107.7) 42.4 (107.7)
B in (cm) 26.7 (67.8) 26.7 (67.8) 35.0 (88.9) 35.0 (88.9) 35.0 (88.9)
C in (cm) 25.5 (64.8) 25.5 (64.8) 25.5 (64.8) 25.5 (64.8) 25.5 (64.8)
D in (cm) 17.6 (44.7) 17.6 (44.7) 17.6 (44.7) 17.6 (44.7) 17.6 (44.7)
E in (cm) 19.4 (49.3) 19.4 (49.3) 19.4 (49.3) 19.4 (49.3) 19.4 (49.3)
G in (cm) 6.0 (15.2) 6.0 (15.2) 6.6 (16.8) 6.6 (16.8) 6.6 (16.8)
H in (cm) 8.7 (22.1) 8.7 (22.1) 8.6 (22) 8.6 (22) 8.6 (22)
J in (cm) 17.2 (43.7) 17.2 (43.7) 17.7 (45) 17.7 (45) 17.7 (45)
K in (cm) 3.1 (7.9) 3.1 (7.9) 8.1 (20.6) 8.1 (20.6) 8.1 (20.6)
L in (cm) 5.9 (15) 5.9 (15) 5.7 (14.5) 5.7 (14.5) 5.7 (14.5)
M in (cm) 10.7 (27.2) 10.7 (27.2) 10.5 (26.7) 10.5 (26.7) 10.5 (26.7)
N in (cm) 6.5 (16.5) 6.5 (16.5) 6.5 (16.5) 6.5 (16.5) 6.5 (16.5)
P in (cm) 2.0 (5.08) 2.0 (5.08) 2.0 (5.08) 2.0 (5.08) 2.0 (5.08)
UHA[T][M][X][S][R]
150
50 of 55
UHA[T][M][X][S][R]
175
UHA[T][M][X][S][R]
200
UHA[T][M][X][S][R]
225
UHA[T][M][X][S][R]
250
SECTION 16: SPECIFICATIONS
16.2 General Technical Data Table
UHD
[T][M][X][S][R]
Model
150
Full Load Amps @ 120 V A 2 2 2 2 2
Minimum Air Volume CFM 1360 1400 2050 2100 2350
Temperature Rise @ Minimum Air Volume
°F
(°C)
83
(46)
Heat Exchanger Pressure Drop @ Minimum Air Volume in wc 0.02 0.03 0.025 0.035 0.05
Maximum Air Volume CFM 5800 6850 7750 8300 8850
Temperature Rise @ Maximum Air Volume
°F
(°C)
20
(11)
Heat Exchanger Pressure Drop @ Maximum Air Volume in wc 0.16 0.29 0.163 0.253 0.35
Flue Size*
Air Intake*
Duct Size (Width)
Duct Size (Height)
Weight (Net)
in
(cm)
in
(cm)
28
(71)
24
(61)
lb
(kg)
28
(71)
24
(61)
191
(86.6)
UHD
[T][M][X][S][R]
175
95
(52)
20
(11)
28
(71)
32.5
(83)
211
(95.7)
UHD
[T][M][X][S][R]
200
73
(40)
20
(11)
4 - All Models
(10)
4 - All Models
(10)
28
(71)
32.5 (83)
239
(108.4)
UHD
[T][M][X][S][R]
225
80
(44)
20
(11)
28
(71)
32.5 (83)
249
(112.9)
UHD
[T][M][X][S][R]
250
80
(44)
22
(12)
28
(71)
32.5 (83)
254
(115.2)
* Do not exceed the maximum length of flue stated or heater may not operate properly.
16.3 Technical Data Table
Model
UHD
[T][M][X][S][R]
150
Total Input High Fire (Btu/h) x (1000) 150 175 200 225 250
Total Input Low Fire (Btu/h) x (1000) 105 122.5 140 157.5 175
Total Output High Fire (Btu/h) x (1000) 123 143.5 164 184.5 205
Total Output Low Fire (Btu/h) x (1000) 86 100 115 129 143.5
Efficiency (Max Input) % 82 82 82 82 82
Natural Gas Data - Inlet Pressure 5.0 in wc Min., 14 in wc Max.
Burner Pressure High Fire in wc 3.0 3.0 3.2 3.4 3.45
Burner Pressure Low Fire in wc 1.3 1.3 1.6 1.7 1.7
LPG / Propane Data - Inlet Pressure 12.0 in wc Min., 14 in wc Max.
Burner Pressure High Fire in wc 11.1 11.2 9.5 11.1 11.6
Burner Pressure Low Fire in wc 5.0 5.5 4.7 5.4 5.5
UHD
[T][M][X][S][R]
175
UHD
[T][M][X][S][R]
200
UHD
[T][M][X][S][R]
225
UHD
[T][M][X][S][R]
250
51 of 55
UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
16.4 Dimension Data for Models UHD[T][M][X][S][R]300-400
Model A B C D E F G H J K L M N
UHD[T][M][X][S][R] 300 UHD[T][M][X][S][R] 350 UHD[T][M][X][S][R] 400
in
(cm)
in
(cm)
in
(cm)
52.3
132.8
52.3
132.8
52.3
132.8
43.2
109.7
43.2
109.7
43.2
109.7
52 of 55
25.5
64.8
25.5
64.8
25.5
64.8
24.7
62.7
24.7
62.7
24.7
62.7
19.4
49.3
19.4
49.3
19.4
49.3
1.25
3.2
1.25
3.2
1.25
3.2
7. 0
17.8
7. 0
17.8
7. 0
17.8
11.2
28.4
11.2
28.4
11.2
28.4
13.8
35.1
13.8
35.1
13.8
35.1
4.2
6.84
4.2
6.84
4.2
6.84
8.7
22.1
8.7
22.1
8.7
22.1
12.1
30.7
12.1
30.7
12.1
30.7
6.5
16.5
6.5
16.5
6.5
16.5
SECTION 16: SPECIFICATIONS
16.5 General Technical Data Table
Model UHD[T][M][X][S][R] 300 UHD[T][M][X][S][R] 350 UHD[T][M][X][S][R] 400
Full Load Amps @ 120 V A 2 6 6
Minimum Air Volume CFM 2700 3120 3420
Temperature Rise @ Minimum Air Volume
Heat Exchanger Pressure Drop @ Minimum Air Volume in wc 0.02 0.03 0.04
Maximum Air Volume CFM 10200 13600 14200
Temperature Rise @ Maximum Air Volume
Heat Exchanger Pressure Drop @Maximum Air Volume in wc 0.27 0.48 0.53
Flue Size*
Air Intake*
Duct Size (Width)
Duct Size (Height)
Weight (Net)
°F
(°C)
°F
(°C)
in
(cm)
in
(cm)
28
(71)
24
(61)
lb
(kg)
86
(47)
23
(13)
5
(13)
35
(89)
40.5
(103)
325
(147.4)
86
(47)
22
(12)
4 - All Models
(10)
5
(13)
35
(89)
40.5
(103)
345
(156.5)
86
(47)
22
(12)
5
(13)
35
(89)
40.5
(103)
345
(156.5)
* Do not exceed the maximum length of flue stated or heater may not operate properly.
16.6 Technical Data Table
Model UHD[T][M][X][S][R] 300 UHD[T][M][X][S][R] 350 UHD[T][M][X][S][R] 400
Total Input High Fire (Btu/h) x (1000) 300 350 385
Total Input Low Fire (Btu/h) x (1000) 210 245 269.5
Total Output High Fire (Btu/h) x (1000) 246 287 315.7
Total Output Low Fire (Btu/h) x (1000) 172.2 200.9 221
Efficiency % 82 82 82
Natural Gas Data - Inlet Pressure 5.0 in wc Min., 14 in wc Max.
Burner Pressure High Fire in wc 3.9 4.0 3.3
Burner Pressure Low Fire in wc 1.8 1.8 1.4
LPG / Propane Data - Inlet Pressure 12.0 in wc Min., 14 in wc Max.
Burner Pressure High Fire in wc 10.0 8.7 10.7
Burner Pressure Low Fire in wc 4.9 4.2 5.1
53 of 55
UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
54 of 55
®
SECTION 17: THE ADDISON
UHD-SERIES WARRANTY
ADDISON WILL PAY FOR:
Within 24 months from date of purchase by buyer or 27
months from date of shipment by Addison (whichever comes first), replacement parts will be provided free of charge for any part of the product which fails due to a manufacturing or material defect.
Addison will require the part in question to be returned to the factory. Addison will, at its sole discretion, repair or replace after determining the nature of the defect and disposition of part in question.
ADDISON® Replacement Parts are warranted for a period of 18 months from date of shipment from Addison or the remaining ADDISON® UHD-Series warranty.
SECTION 17: THE ADDISON® UHD-SERIES WARRANTY
READ YOUR INSTALLATION, OPERATION AND SERVICE MANUAL
If you have questions about your controller, contact your installing professional. Should you need Replacement Parts or have additional questions, call or write Addison:
Addison
7050 Overland Road Orlando, Florida 32810
Telephone: +1.407.292.4400
Fax: +1.407.290.1329
www.addison-hvac.com
ADDISON WILL NOT PAY FOR:
Service trips, service calls and labor charges. Shipment of replacement parts. Claims where the total price of the goods have not
been paid. Damage due to:
• Improper installation, operation or maintenance.
• Misuse, abuse, neglect, or modification of the ADDISON® UHD-Series in any way.
• Use of the ADDISON® UHD-Series for other than its intended purpose.
• Incorrect gas or electrical supply, accident, fire, floods, acts of God, war, terrorism, or other casualty.
• Improper service, use of replacement parts or accessories not specified by Addison.
• Failure to install or maintain the ADDISON® UHD­Series as directed in the Installation, Operation and Service manual.
• Relocation of the ADDISON® UHD-Series after initial installation
• The use of the ADDISON® UHD-Series in a corrosive atmosphere containing contaminants.
• The use of the ADDISON® UHD-Series in the vicinity of a combustible or explosive material.
• Any defect in the ADDISON® UHD-Series arising from a drawing, design, or specification supplied by or on behalf of the consumer.
• Damage incurred during shipment. Claim must be filed with carrier.
WARRANTY IS VOID IF:
The ADDISON® UHD-Series is not installed by an
contractor qualified in the installation and service of gas­fired heating equipment.
You cannot prove original purchase date and required
annual maintenance history.
The data plate and/or serial number are removed,
defaced, modified or altered in any way.
The ownership of the ADDISON® UHD-Series is moved
or transferred. This warranty is nontransferable. Addison is not permitted to inspect the damaged
controller and/or component parts.
Addison's liability, and your exclusive remedy, under this warranty or any implied warranty (including the implied warranties of merchantability and fitness for a particular purpose) is limited to providing replacement parts during the term of this warranty.
Some jurisdictions do not allow limitations on how long an implied warranty lasts, so this limitation may not apply to you. There are no rights, warranties or conditions, expressed or implied, statutory or otherwise, other than those contained in this warranty.
Addison shall in no event be responsible for incidental or consequential damages or incur liability for damages in excess of the amount paid by you for the ADDISON® UHD-Series. Some jurisdictions do not
allow the exclusion or limitation of incidental or consequential damages, so this limitation or exclusion may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from jurisdiction to jurisdiction.
Addison shall not be responsible for failure to perform under the terms of this warranty if caused by circumstances out of its control, including but not limited to war, fire, flood, strike, government or court orders, acts of God, terrorism, unavailability of supplies, parts or power. No person is authorized to assume for Addison any other warranty, obligation or liability.
LIMITATIONS ON AUTHORITY OF REPRESENTATIVES:
No representative of Addison, other than an Executive Officer, has authority to change or extend these provisions. Changes or extensions shall be binding only if confirmed in writing by Addison's duly authorized Executive Officer.
55 of 55
Loading...