Installation must be done by a contractor qualified
in the installation and service of gas-fired heating
equipment or your gas supplier.
Improper installation, adjustment, alteration, service
or maintenance can result in death, injury or
property damage. Read the Installation, Operation
and Service Manual thoroughly before installing or
servicing this equipment.
Installer
Please take the time to read and understand
these instructions prior to any installation.
Installer must give a copy of this manual to the owner.
Owner
Keep this manual in a safe place in order to provide
your serviceman with necessary information.
If you smell gas:
1. Open windows.
2. DO NOT try to light any appliance.
3. DO NOT use electrical switches.
4. DO NOT use any telephone in
your building.
5. Extinguish any open flame.
6. Leave the building.
7. Immediately call your local gas
supplier after leaving the building.
Follow the gas supplier’s
instructions.
8. If you cannot reach your gas
supplier, call the Fire Department.
WARNING
UHA-Series
Tubular Unit Heaters
(Standard Range)
Installation, Operation
& Service Manual
Models UHA[X][S]
150, 175, 200, 225
Fire Hazard
Keep all flammable objects, liquids and
vapors the minimum required clearances to combustibles away from
heater.
Some objects will catch fire or explode
when placed close to heater.
Failure to follow these instructions can
result in death, injury or property
damage.
4. N’utilisez PAS de téléphone dans votre
bâtiment.
5. Eteignez toute flamme nue.
6. Quittez le bâtiment.
7. Après avoir quitté le bâtiment, appelez
immédiatement votre fournisseur local
de gaz.
Suivez les instructions du fournisseur
de gaz.
8. Si vous ne pouvez pas joindre votre
fournisseur de gaz, appelez le service
d’incendie.
Risque d’incendie
Garder tous les objets, liquides ou vapeurs
inflammables à la distance minimale de
l’unité de chauffage requise avec les
matériaux combustibles.
Certains objets prendront feu ou exploseront
s’ils sont placés à proximité de l’unité de
chauffage.
Le non respect de ces instructions peut
entraîner la mort, des blessures corporelles
ou des dommages matériels.
ATTENTION
Linstallation doit être effectuée par un installateur
éprouvé/contractant qualifié dans linstallation et la
maintenance du système de chauffage par infrarouge
activé au gaz.
Linstallation, lajustement, laltération, le démarrage
ou lentretien inadéquat peuvent causer la mort, des
blessures ou des dégâts matériels. Lire entièrement
le manuel dinstallation, dopération et dentretien
avant linstallation ou l'entretien de cet équipement.
Installateur
Prenez le temps de lire et comprendre ces instructions
All rights reserved. No part of this work covered by the copyrights herein may be reproduced
or copied in any form or by any means - graphic, electronic, or mechanical, including
photocopying, recording, taping or information storage and retrieval systems - without the
written permission of Addison.
Figure 12: Gas Connection .....................................................20
Figure 13: Automatic Burner Control Sequence...................... 28
Figure 14: Gas Valve for Models UHA[X][S] 150 - 400............ 29
Figure 15: LED Diagnostic Codes...........................................31
SECTION 1: HEATER SAFETY
Yo ur Safety is Important to Us!
This symbol is used throughout
the manual to notify you of
possible fire, electrical or burn
hazards. Please pay special
attention when reading and
following the warnings in these
sections.
Installation, service and, at a
minimum, annual inspection of heater must be done by a contractor qualified in the installation and
service of gas-fired heating equipment.
Read this manual carefully before installation,
operation or service of this equipment.
Heaters are not approved for residential installation.
These instructions, the layout drawing, local codes
and ordinances and applicable standards that apply
to gas piping, electrical wiring, venting, etc. must be
thoroughly understood before proceeding with the
installation.
Protective gear is to be worn during installation,
operation and service. Thin sheet metal parts have
sharp edges. To prevent injury, the use of work
gloves is recommended.
Before installation, check that the local distribution
conditions, nature of gas and pressure and
adjustment of the appliance are compatible.
The heater must be applied and operated under the
general concepts of resonable use and installed using the best building practices.
This appliance is not intended for use by persons
(including children) with reduced physical, sensory
or mental capabilities, or lack of experience and
knowledge, unless they have been given
supervision or instruction concerning use of the
appliance by a person responsible for their safety.
Children should be supervised to ensure that they
do not play with the appliance.
For additional copies of the Installation, Operation
and Service Manual, please contact Addison.
SECTION 1: HEATER SAFETY
1.3 California Proposition 65
In accordance with California Proposition 65
requirements, a warning label must be placed in a
highly visible location on the outside of the
equipment (i.e. near equipment's serial plate). See
label placement drawing on Page 2, Figure 1 through Page 4, Figure 3 for label location. Avoid
placing label on areas with extreme heat, cold,
corrosive chemicals or other elements. To order
additional labels, please contact Addison or your
®
ADDISON
independent distributor.
1. 1 M a np o w e r R e quirements
To prevent personal injury and damage to the
heater, two persons will be required for installation.
1.2 Safety Labels and Their Placement
Product safety signs or lab
els should be replaced by
the product user when they are no longer legible.
Please contact Addison or your ADDISON
independent distributor to obtain replacement signs
or labels. See Page 2, Figure 1 through Page 4, Figure 3.
®
1 of 49
UHA STANDARD UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
Do not use equipment in area containing
corrosive chemicals.
Refer to appropriate Material Safety Data
Sheets (MSDS).
Failure to follow these instructions can result
in product damage.
The installer is responsible for the following:
• To install the heater, as well as the gas and
electrical supplies, in accordance with applicable
specifications and codes. Addison recommends
the installer contact a Local Building Inspector or
Fire Marshal for guidance.
• To use the information given in a layout drawing
and in the manual together with the cited codes
and regulations to perform the installation.
• To install the heater in accordance with the
clearances to combustibles.
• To furnish all needed materials not furnished as
standard equipment.
• To plan location of supports, vents and air
intakes.
• To provide access for servicing.
• To provide the owner with a copy of this
Installation, Operation and Service Manual.
• To never use heater as support for a ladder or
other access equipment and never hang or
suspend anything from heater.
• To ensure there is adequate air circulation
around the heater and to supply air for
combustion, ventilation and distribution in
accordance with local codes.
• To ensure that the heater is placed in an
approved application.
2.1 Wall Tag
A laminated wall tag is included with the heater as a
permanent reminder of the safety instructions and
the importance of the required clearances to
combustibles. Affix the tag by peeling off the backing
of the adhesive strips on the rear surface and
position the tag on a wall near the heater.
A copy of the wall tag (P/N 91040097) is illustrated
on the back cover.
Know your model number. Model number is found
on the heater and throughout the Installation,
Operation and Service Manual.
SECTION 1: HEATER SAFETY
2.2 Corrosive Chemicals
Addison cannot be responsible for ensuring that all
appropriate safety measures are undertaken prior to
installation; this is entirely the responsibility of the
installer. It is essential that the contractor, the sub-
contractor, or the owner identifies the presence of
combustible materials, corrosive chemicals or
halogenated hydrocarbons* anywhere in the
premises.
* Halogenated Hydrocarbons are a family of chemical
compounds characterized by the presence of halogen elements (fluorine, chlorine, bromine, etc.). These compounds are
frequently used in refrigerants, cleaning agents, solvents, etc. If
these compounds enter the air supply of the burner, the life
span of the heater components will be greatly reduced. An outside air supply must be provided to the burners whenever the
presence of these compounds is suspected. Warranty will be
invalid if the heater is exposed to halogenated hydrocarbons.
2.3 National Standards and Applicable Codes
All appliances must be installed in accordance with
the latest revision of the applicable standards and
national codes. This refers also to the electric, gas
and venting installation. Note: Additional standards
for installations in public garages, aircraft hangars,
etc. may be applicable.
5 of 49
UHA STANDARD UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
SECTION 3: CRITICAL CONSIDERATIONS
3.1 Basic Information
UHA[X][S] heaters have automatic ignition burners
for ON/OFF operation only.
3.4 Minimum Required Installation Clearances
Clearances around the heater and vent must be as
indicated on Page 7, Figure 4 and Page 13, Figure 6
to ensure access for servicing and correct operation.
3.2 Manufactured Units
Gas-fired, power-vented unit heater with tubular heat
exchanger. Units shall have a minimum of 82%
thermal efficiency. The standard unit shall consist of
a non-separated combustion design with an
aluminized heat exchanger. Design and heat
exchanger alternatives shall be offered as follows:
3.5 Ventilation
It is important to ensure that there is adequate air
space around the heater to supply air for
combustion, ventilation and distribution in
accordance with local and national codes on Page 11, Section 7.
• Separated Combustion: A separated combustion
unit shall feature an enclosed, sealed burner
box. A piece of flexible air duct connects this
burner box to a flange on the cabinet.
Combustion air should be ducted from outside
the heated space, with the ductwork connecting
to the unit with the use of the flange.
3.6 Gas Supply
It is important that the gas supply pipe is sized
correctly to provide the inlet pressure as stated on
the heater data plate. The gas supply pipe and
electrical connections must not support any of the
heater's weight on Page 19, Section 9.
• Stainless Steel Heat Exchanger: A stainless
steel heat exchanger unit shall consist of heat
exchanger tubes, heat exchanger tube supports,
heat exchanger tube plates and vent box
produced of 409 stainless steel.
The use of stainless steel heat exchanger unit is
3.7 Electrical Supply
A permanent 120 V / 60 Hz / 1 Ø electrical supply is
required for the main electrical power. The heater
also requires suitable controls in accordance with See Page 21, Section 10.
recommended when air inlet temperatures are
below 40° F (4.4°C) or temperature rise is less
than 40° F (22.2° C) as condensation may form
on the heat exchanger resulting in corriosion that
may shorten its life.
3.8 Vent
Choose heater orientation to allow for the proper
location of the vent. Each heater must be fitted with
a correctly sized sealed vent system.
If vented horizontally, no other appliance may be
3.3 Location and Suspension
connected to the vent.
All models:
•Must be installed indoors.
•Must be installed in a level position with
horizontal discharge.
•May be mounted on a shelf of non-combustible
material.
•May be suspended from above (See Page 10, Figure 5) or from wall brackets of sufficient
strength to support the heater as listed in the
Te c h ni c al Da ta Ta ble on Page 48, Section 16.2.
Drop rods must be a minimum of 3/8" diameter
mild steel. Four suspension points (3/8" nuts)
are located on top of the heater.
•Must be installed in a manner which allows
access to all serviceable components.
See Page 7
, Figure 4 for details.
See Page 11, Section 7.
6 of 49
SECTION 4: CLEARANCES TO COMBUSTIBLES
WARNING
Fire Hazard
Keep all flammable objects, liquids and
vapors the required clearances to
combustibles away from heater.
Some objects can catch fire or explode
when placed close to heater.
Failure to follow these instructions can
result in death, injury or property damage.
6"
(15 cm)
31"**
(79 cm)
3"
(8 cm)
6"
(15 cm)
Clearances to Combustibles
24" for
adequate
air flow access
axial fan.
10'
(3 m)
Wall
Terminal
Roof Terminal
Top
20' (6.0 m) - 30' (9.1 m)
Max. Mounting Height*
Installation Clearances
(Optional separated
combustion concentric
venting shown.)
* Recommended mounting height varies with heater input.
Heaters may be mounted at a higher level if destratification
fans are installed.
Note: Venting directly from top of heater not applicable
on Models 150 - 400.
Clearance to Vent: 2" (5 cm)
**31" (79 cm) minimum is necessary
for servicing.
The heater must always be installed at least 6' (2 m) above the floor.
The vent pipe must have clearance from combustibles by 2" (5 cm).
If installed at low levels where individuals can come in contact with hot heat
exchanger components, adequate guarding must be provided.
4.1 Required Clearances To Combustibles
Check the clearances on the serial plate to make
sure the product is suitable for your application and
the clearances are maintained. Read and follow the
safety guidelines below:
• Keep gasoline or other combustible material
including flammable objects, liquids, dust or
vapors away from this heater or any other
appliance.
• The stated clearances to combustibles
represents a surface temperature of 90° F
(50° C) above room temperature. Building
materials with a low heat tolerance (such as
plastics, vinyl siding, canvas, tri-ply, etc) may be
subject to degradation at lower temperatures. It
is the installer’s responsibility to assure that
adjacent materials are protected from
degradation.
• Consult local Fire Marshal, Fire Insurance Carrier
Clearances are the required distances that
combustible objects must be away from the heater
to prevent serious fire hazards. Combustibles are
materials that catch on fire and include common
items such as wood, paper, rubber, fabric, etc.
Maintain clearances to combustibles at all times for
safety.
Clearances for all heater models are located on the
or other authorities for approval of proposed
installation when there is a possibility of
exposure to combustible airborne materials or
vapors.
4.2 Clearances To Combustibles
Clearances must be as indicated on Page 7, Figure
4. If clearances to combustibles are not indicated,
then installation clearances apply.
serial plate of the heater and throughout the manual.
Figure 4: Installation Clearances and Clearances to Combustibles
SECTION 4: CLEARANCES TO COMBUSTIBLES
7 of 49
UHA STANDARD UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
SECTION 5: NATIONAL STANDARDS AND APPLICABLE CODES
5.1 Gas Codes
The type of gas appearing on the name plate
must be the type of gas used. Installation must
comply with national and local codes and
requirements of the local gas company.
United States: Refer to NFPA 54/ANSI Z223.1 latest revision, National Fuel Gas Code.
Canada: Refer to CSA B149.1 Natural Gas and
Propane Installation Code.
5.2 Aircraft Hangars
Installation in aircraft hangars must be in
accordance with the following codes:
United States: Refer to Standard for Aircraft
Hangars, NFPA 409 - latest revision.
Canada: Refer to Standard CSA B149.1 Natural
Gas and Propane Installation Code.
• In aircraft storage and servicing areas, heaters
shall be installed at least 10' (3 m) above the
upper surface of wings or of engine enclosures
of the highest aircraft which may be housed in
the hangar. The measurement shall be made
from the wing or engine enclosure (whichever is
higher from the floor) to the bottom of the heater.
• In shops, offices and other sections of aircraft
hangars communicating with aircraft storage or
servicing areas, heaters shall be installed not
less than 8' (2.4 m) above the floor.
• Suspended or elevated heaters shall be so
located in all spaces of aircraft hangars that they
shall not b
e subject to injury by aircraft, cranes,
movable scaffolding or other objects. Provisions
shall be made to assure accessibility to
suspended heaters for recurrent maintenance
purposes.
5.3 Parking Structures and Repair Garages
Installation in garages must be in accordance
with the following codes:
United States: Standard for Parking Structures
NFPA 88A - latest revision or the Code for Motor
Fuel Dispensing Facilities and Repair Garages,
NFPA 30A - latest revision. Canada: Refer to
CSA B149.1 Natural Gas and Propane
Installation Code.
• In accordance with the Standard for Parking
Structures NFPA 88A, heaters must be located
a minimum of 18" (50 cm) below the floor-ceiling
assembly or 18" (50 cm) above the floor.
• In accordance with the Code for Motor Fuel
Dispensing Facilities and Repair Garages,
NFPA 30A - latest revision, heaters must not be
installed less than 8' (2.4 m) above the floor.
5.4 Electrical
The heater must be electrically grounded in
accordance with the following codes:
United States: Refer to National Electrical
®
Code
, NFPA 70 - latest revision. Wiring must
conform to the most current National Electrical
®
Code
, local ordinances and any special
diagrams furnished.
Canada: Refer to Canadian Electrical Code,
CSA C22.1 Part 1 - latest revision.
5.5 Venting
The venting must be installed in accordance
with the requirements within this manual and
the following codes:
United States: Refer to NFPA 54/ANSI Z223.1 latest revision, National Fuel Gas Code.
8 of 49
Canada: Refer to CSA B149.1 Natural Gas and
Propane Installation Code.
5.6 High Altitude
These heaters are approved (without modifications)
for installations up to 2000' (610 m) in US and
Canada. Heaters installed above 2000' (610 m)
must be de-rated. For installations above 2000' (610
m) in US, consult factory for information on burner
de-rating. For installations from 2000' (610 m) to
4500' (1370m) in Canada, high altitude conversion
kits are available. Heaters installed over 4500'
(1370 m) in Canada are not approved and must be
approved by the local or provincial authority.
SECTION 5: NATIONAL STANDARDSAND APPLICABLE CODES
9 of 49
UHA STANDARD UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
WARNING
Crush Hazard
Use 3/8" threaded rod
minimum.
Failure to follow these
instructions can result in
death, injury or property
damage.
SECTION 6: HEATER INSTALLATION
6.1 General
Heaters are designed for installation above 6'
(1.8 m). These heaters must be installed within the
heated space. Duct delivery systems are not
permitted with axial fan units. When handling or
supporting the heater from below, ensure that the weight is taken at the support points.
The gas or electrical supply lines must not be used
to support the heater.
Do not locate the gas or electrical supply lines
directly over the path of the flue products from the
heater.
The heater must be installed in a location that is
readily accessible for servicing.
The heater must be installed in accordance with
clearances to combustibles as indicated on the wall
tag and in this manual.
Figure 5: Suspension Methods
6.2 Suspension
Four suspension points (3/8" nuts) are located on
the top of the heater. Drop rods must be 3/8"
diameter mild steel minimum.
When handling or supporting the heater from below
ensure that the weight is taken at the support points.
For typical suspension, See Page 10, Figure 5.
,
10 of 49
SECTION 7: VENTING
WARNING
Carbon Monoxide Hazard
Heaters may be installed
vented or unvented.
Vented heaters must be
vented outdoors.
Unvented heaters must be
installed according to the
installation manual.
Failure to follow these
instructions can result in
death or injury.
7. 1 Ve n t i n g
This heater must be vented in accordance with the
rules contained in this manual and with the following
national codes and any state, provincial or local
codes which may apply: United States: Refer to
NFPA 54/ANSI Z223.1 - latest revision, National
Fuel Gas Code; Canada: Refer to CSA B149.1
Natural Gas and Propane Installation Code.
Any portion of vent pipe passing through a
combustible wall must have a listed thimble to
conform with the above codes.
The heater may be installed unvented in
certain circumstances according to building
ventilation codes. Refer to the above codes and Page 12, Section 7.3 for further information.
Unvented operation also requires compliance with
the clearances to combustibles given on Page 7, Figure 4.
The bottom of the vent or air intake terminal shall not
be located less than 1' (.3 m) above grade level.
The vent shall not terminate less than 7' (2.1 m)
above grade where located adjacent to pubwalkways.
Vent terminal must be installed at a height sufficient
to prevent blockage by snow and building materials
protected from degradation by flue gasses.
Vent terminal must be beyond any combustible
overhang.
Secure all joints with corrosion resistant #8 x 3/8"
sheet metal screws.
For single wall venting, pressure sensitive aluminum
tape or silicone sealant must be used to seal all
joints.
Aluminum tape shall have a minimum temperature
rating of 400° F (204° C) and meet SMACNA AFTS-
lic
SECTION 7: VENTING
100-73 standards. High temperature silicone
sealant must have a minimum temperature rating of
480° F (250° C).
7.1.1 United States Requirements
Vent must terminate at least 3' (.9 m) above any
forced air inlet located within 10' (3.1 m).
Vent must terminate at least 4' (1.2 m) below,
4' (1.2 m) horizontally from, or 1' (.3 m) above any
door, operable window, or gravity air inlet into any building.
NFPA 54/ANSI Z223.1 - latest revision, National
Fuel Gas Code specifies a 4' (1.2 m) horizontal vent
terminal clearance from gas and electric meters,
regulators and relief equipment.
7.1.2 Canadian Requirements
The vent shall not terminate within 6' (1.8 m) of a
mechanical air supply inlet to any building.
The vent shall not terminate within 3' (.9 m) of a
window or door that can be opened in any building,
any non-mechanical air supply inlet to any building,
or of the combustion air inlet of any other appliance.
7.2 Vent Installation
Maintain clearances to combustibles at all times for
safety. Clearances are the required distances that
combustible objects must be away from the heater
to prevent serious fire hazard. See Page 7, Figure 4.
For vented units, the vent must terminate outside of
the building.
Vents must be fully sealed and correctly sized for
the model. If the vent passes through a
ceiling of combustible material, it must be enclosed by a listed thimble and be separated from the
thimble by at least a 2" (5 cm) air gap.
For separated combustion models, vents and air
intakes must be a fully sealed system and correctly
sized for the model. Vent should be assembled as
detailed on Page 13, Figure 6 through Page 17, Figure 11. The joints between the vent terminal and
the roof or wall must be properly sealed. If the vent
passes through a wall or ceiling of combustible
material, it must be enclosed by a listed thimble and be separated from the thimble by at least a 2" (5 cm)
air gap.
Vents and air intakes must be adequately
supported so that the heater does not bear the
weight of the pipes.
For vent termination See Page 13, Figure 6 through
Page 17, Figure 11.
wall or
11 of 49
UHA STANDARD UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
WARNING
Carbon Monoxide Hazard
Heaters may be installed
vented or unvented.
Vented heaters must be
vented outdoors.
Unvented heaters must be
installed according to the
installation manual.
Failure to follow these
instructions can result in
death or injury.
7.2.1 Standard Vented Heaters
(Models UHA[X] 150 - 400)
The vent must be fitted with a low resistance
terminal. See Page 13, Figure 6 through Page 14, Figure 7. Standard vented heaters do not allow
outdoor air intake for combustion air.
The heaters are designed to be installed as
separated combustion heaters. The vent and air
intake are run as separate pipes to the wall or roof
terminals. See Page 16, Figure 9. As an option, the
vent and air intake are run as separate pipes to a
concentric vent box and a concentric vent/air intake
pipe penetrates the wall or roof. See Page 16, Figure 10and Page 17, Figure 11.
For separated combustion installation, the vent and
air intake must be fitted with an individual and
correctly sized sealed system and the vent and air
intake must terminate at approved wall and roof
terminals.
Separated combustion units may not be common
vented. See Page 11, Section 7.
7.3 Unvented Operation
condensation will form. Insulation is recommended
and condensation drains may be desired. For vents
pitched up toward the vent terminal, place the
condensation drain within 5' (1.5 m) of the heater.
In noncombustible walls only, vent terminal
(P/N 02537801-1P) may be used.
For 4'' (10 cm) vents in either combustible or
noncombustible walls, use vent terminal (P/N
90502100) or equivalent insulated vent terminal.
Follow the manufacturer's instructions for proper
installation.
Instead of an insulated vent terminal, a listed thimble with 2" (5 cm) air gap, may be used with a 4" (10 cm)
vent cap (P/N 90502102).
7.5 Vertical Venting
Vertically-vented standard-vented heaters can be
common vented (
For vent lengths greater than 5' (1.5 m),
condensation will form. Insulation is recommended
and condensation drains may be desired. Vent from
the rear of the heater cabinet then run the vent
vertically and use a condensate drain at the bottom
of the vertical vent.
Vent pipe must be sloped 1/4'' (.6 cm) for every
1' (.3 m).
For 4'' (10 cm), an approved vent cap
(P/N 90502102) must be used.
For 6'' (15 cm) common vent, an approved vent cap
(P/N 90502103) must be used.
For common vertical venting of more than two
heaters, See Page 15, Figure 8.
A vent shall not extend less than 2' (.6m) above the
highest point where it passes through a flat roof of a
building.
up to 4 heaters).
This heater is not approved to be installed in
residential buildings.
For unvented operation in commercial installations,
sufficient ventilation must be provided in the amo
of 4 cfm per 1000 Btu/h firing rate (United States); 3
cfm per 1000 Btu/h firing rate (Canada).
7.4 Horizontal Venting
Horizontally vented heaters must be individually
vented.
Vent pipe must be sloped ¼" (.6 cm) for every 1' (.3
m). For vent lengths greater than 5' (1.5 m),
12 of 49
7. 6 L e n gth Requirements
If using vent lengths greater than 5' (1.5 m),
condensation will form in the vent pipe. Insulation
and additional sealing measures (high temperature
silicone at all seams) are required.
The entire vent should be insulated with foil faced
fiberglass insulation (1/2" thick, 1-1/2# density
minimum).
unt
Maximum Vent Lengths Table
Model UHA[X][S]
150 - 400
40 ft (12.2 m)1
35 ft (10.7 m)2
30 ft (9.1 m)3
25 ft (7.6 m)4
20 ft (6.1 m)5
# of Elbows
7.7 Vent Material
Vent material may be single wall 26 ga. (minimum)
galvanized steel or equal thickness stainless steel.
Completely seal all joints, refer to Page 11, Section
7.2.
If penetrating a combustible wall or roof, a listed
thimble with 2" (5 cm) clearance must be used.
Where local codes permit, a single section of type
B-1 vent material may be used at the roof or wall
penetration instead of a thimble. Ensure vent
manufacturer's clearance from vent material is
maintained. Seal annular space of the type B-1 vent
as well as all joints in the remaining vent.
7. 8 Replacing an Existing Heater in a Venting
System
When replacing an existing heater in a venting
system, the venting system may not be properly
sized to vent the new heater. The following steps
must be followed with each appliance connected to
the venting system placed in operation, while any
other appliances connected to the venting system
are not in operation.
1. Seal any unused openings in the venting
system.
2. Inspect the venting system for proper size and
horizontal pitch, as required by the NFPA 54/
ANSI Z223.1 - latest revision, National Fuel
Gas Code (US) or Standard CSA B149.1
Natural Gas and Propane Installation Code
(Canada) and these instructions. Determine
that there is no blockage or restriction, leakage,
corrosion and other deficiencies which could
cause an unsafe condition.
3. Close all building doors and windows and all
doors between the space in which the
appliance(s) connected to the venting system
are located and other spaces of the building.
Turn on clothes dryers and any exhaust fans,
such as range hoods and bathroom exhausts
so that they shall operate at maximum speed.
Do not operate a summer exhaust fan. Close
fireplace dampers.
4. Follow the lighting instructions. Place the
appliance being inspected in operation. Adjust
SECTION 7: VENTING
thermostat so that the appliance will operate
continuously.
5. For any appliance having a draft hood, test for
draft hood appliance spillage at the draft hood
relief opening after five minutes of main burner
operation. Use the flame of a match or candle.
6. After it has been determined that each
appliance connected to the venting system
properly vents when tested as o
utlined above,
return doors, windows, exhaust fans, fireplace
dampers and any other gas-burning appliances
to their previous conditions of use.
7. If improper venting is observed during any of
the above tests, the venting system must be
corrected by a contractor qualified in the
installation and service of gas-fired equipment
or your local gas supplier. If the venting must be
resized, use appropriate tables in (US)
Appendix G of NFPA 54/ANSI Z223.1 - latest
revision, National Fuel Gas Code (US) or
Standard CSA B149.1 Natural Gas and
Propane Installation Code (Canada) to
determine minimum size. All vent corrections
must be in accordance with the appropriate
local codes and the NFPA 54/ANSI Z223.1 latest revision, National Fuel Gas Code (US) or
Standard CSA B149.1 Natural Gas and
Propane Installation Code (Canada).
Figure 6: Vent and Roof Detail
13 of 49
UHA STANDARD UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
Vent
Terminal
4" (10cm) Diameter Vent
Flashing
(By Others)
Listed
Thimble
(2" [5cm] Clearance)
Vent Terminal
Vertical
Option
Horizontal
Option
Vent
Listed
Thimble
(2" [5cm] Clearance)
Flashing
(By Others)
12" (31 cm)
Minimum
NOTE: Vent supports
not shown.
90°
Bend
ModelVent DiameterPart Number
UHA[X] 150 - 4004" (10 cm)90502102
Figure 7: Standard Vented Heater - Vertical and Horizontal Vent Termination
14 of 49
Figure 8: Standard Vented Heater - Common Vertical Vent Termination
SECTION 7: VENTING
Requirements:
•Maximum of four heaters can be commonly
vented through the roof.
• Heaters must be of the same BTU output.
• Heaters must be controlled by a common
thermostat.
• Connections to a common stack must be
positioned to avoid direct opposition between
streams of combustion gases.
15 of 49
UHA STANDARD UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
UHA STANDARD UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
WARNING
Explosion Hazard
Equipment must have access to
uncontaminated air at all times.
Failure to follow these instructions can result
in death, injury or property damage.
SECTION 8: AIR SUPPLY
8.1 Separated Combustion Installation
When installed as a separated combustion heater
(UHA[X]S), the air for combustion is drawn in from
outside the building. It is important to ensure that
there is adequate space around heater to provide air
for the axial air distribution fan.
8.2 Unvented Installation
It is important to ensure that there is adequate fresh
air supply at all times for both combustion and
heating requirements in accordance with local and
national codes.
8.3 Building Ventilation
Where ventilation is required, air must be taken from
an outside point where it is not likely to be
contaminated or obstructed.
8.4 Outside Combustion Air Supply
If outside combustion air supply is required,
separated combustion model (UHA[X]S) heaters
must be used.
Caution: If the building has a slight negative
pressure or corrosive contaminants su
halogenated hydrocarbons are present in the air, an
outside combustion air supply to the heater is
required. Seal all combustion air pipe joints.
The flexible air duct may have to be insulated to
prevent condensation on the outer surface. The
outside air terminal must not be more than 1' (31
cm) above the vent terminal.
ch as
8.4.1 Length Requirements
Follow the constraints listed on Page 12, Section 7.6.
18 of 49
SECTION 9: GAS PIPING
WARNING
Explosion Hazard
Leak test all components of gas piping
before operation.
Gas can leak if piping is not installed
properly.
Do not high pressure test gas piping with
heater connected.
Failure to follow these instructions can result
in death, injury or property damage.
A gas meter is connected to the service pipe by the
gas supply company. An existing meter should be
checked, preferably by the company, to ensure that
the meter is adequate for the rate of gas supply
required.
Installation pipes must be fitted in accordance with
local and national codes. Pipes of smaller size than
the heater inlet gas connection should not be used.
Gas lines must meet applicable codes:
United States: Flexible stainless steel gas hose
(US models) is certified per the standard for
connectors for gas appliances, ANSI Z21.21/CSA
6.10 - latest revision.
SECTION 9: GAS PIPING
Canada: Rubber type 1 gas hose (Canadian
models) is certified as being in compliance with the
standard for elastomeric composite hose and hose
couplings for conducting propane and natural gas,
CAN/CGA 8.1 - latest revision.
9.1 Connections
Connect the heater to the gas supply ensuring that
the final connections are as follows:
•Gas supply pipe work is run in medium or heavy
gauge tubing in compliance with local and
national codes.
• Meter and service must be large eno
handle all the burners being installed plus any
other connected load. The gas pipe which feeds
the system must be large enough to supply the
required gas with a maximum pressure drop of
1/2" wc. When gas piping is not included in the
layout drawing, contact the local gas supplier.
• An isolating valve and union connection should be used and fitted into the supply adjacent to the
heater.
•A minimum 1/8" NPT plugged tapping
accessible for test connection must be installed
immediately upstream of the gas supply
connection to the heater.
•For suspended heaters, an approved metal
flexible connection between the isolating valve
and the heater may be used. To reduce
pressure loss, use one pipe size larger than
the heater gas connection.
IMPORTANT - The complete installation must be
p
urged and tested for gas soundness in accordance
with local and national codes.
Caution: Do not high pressure (in excess of 1/2 psi
[14" wc]) test the gas piping with the burner
connected. Close manual shut-off valve during any
pressure testing equal to less than 1/2 psi (14" wc).
Check the pipe and tubing ends for leaks before
placing heating equipment into service. When
checking for gas leaks, use a soap and water
solution; never use an open flame.
ugh to
19 of 49
UHA STANDARD UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
Figure 12: Gas Connection
20 of 49
SECTION 10: WIRING
DANGER
Electrical Shock Hazard
Disconnect electric before service.
More than one disconnect switch may be
required to disconnect electric from
equipment.
Equipment must be properly grounded.
Failure to follow these instructions can result
in death or electrical shock.
SECTION 10: WIRING
Heater must be wired and electrically grounded in
accordance with local codes. In the absence of local
codes in accordance with: United States: refer to
National Electrical Code
®
NFPA 70 - latest revision
Canada: refer to Canadian Electrical Code CSA
C22.1 Part I - latest revision.
10.1 Positioning Thermostats
A room thermostat should be mounted on a
vibration-free wall or column at a height of
approximately 5' (1.5 m) from the floor to measure
the ambient temperature. It should be clear of both
cold drafts and the direct path of warm air from the
heater.
Avoid mounting thermostat on outside walls or in
areas directly exposed to radiant heat or sunlight.
Install wall tag in a visible location near thermostat.
See Page 5, Section 2.1 for wall tag details.
All heater models require constant 120 V / 1Ø / 60
Hz power supply. Check heater rating plate for
electrical rating for proper circuit sizing. For
servicing, a disconnect switch of proper electrical
rating should be installed in the vicinity of the heater.
All heaters are equipped with thermostat
connections suitable to power a 24 V thermostat.
10.2 Low Voltage Thermostat with One Heater
24 Volt
Thermostat
Heating Only
R
W
Electrical
Supply
10.1.1 Fan Control
The heater’s axial fan can be used during the offseason for air circulation. A low voltage
programmable thermostat with fan switch (P/N
90425400) must be used. See Page 21, Section
10. 2 for thermostat connection details. For the use
of multiple heaters on one thermostat, See Page 22, Section 10.3through Page 23, Section 10.4.
Terminal
Strip
R
G
W
C
Gas Supply
24 Volt
Thermostat
with Fan Control
R
G
W
C
Electrical
Supply
Terminal
Strip
R
G
W
C
Gas Supply
21 of 49
UHA STANDARD UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
ModelRelay TypeRelay Part NumberMax. Number of Heaters
UHA[X][S]150 - 250DPST904363004
10.3 Low Voltage Thermostat with Multiple Heaters (Models UHA[X][S]150 - 250)
22 of 49
10.4 Low Voltage Thermostat with Multiple Heaters (Models UHA[X][S]300 - 400)
ModelRelay TypeRelay Part NumberMax. Number of Heaters
UHA[X][S]300 - 400DPST904363002
SECTION 10: WIRING
23 of 49
UHA STANDARD UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
Blue
Black
Black
Orange
Yellow
Brown
Black
White
White
L2
L1
Black
Black
Green
White
White
Green
Green
Blue
Black
Black
Black
White
Green
Blue
Green
24 VAC
HOT
GROUND
Flame
Black
Black
Black
6
3
4
5
2
1
45
31
SENSE
ELECTRODE
LIMIT
SWITCH
PRESSURE
SWITCH
AXIAL FAN
GAS VALVE
IGNITION
MODULE
TRANSFORMER
AXIAL FAN (UHA 300,
350, 400) ONLY)
LIMIT
SWITCH
(UHA
300,350,
400 ONLY)
MANUAL RESET LIMIT SWITCH
(UHA 30 - 125 ONLY)
THERMOSTAT INPUT:
FIELD SUPPLIED
R = 24 VAC TO THERMOSTAT (RED)
G = MANUAL FAN INPUT FROM THERMOSTAT (GREEN)
W = HEAT DEMAND INPUT FROM THERMOSTAT (WHITE)
C = COMMON SIDE OF TRANSFORMER
FLUE
BLOWER
R
G
W
C
ACC
L1
CMB
Blower
Yellow
Orange
Orange
Orange
NOTE:
For field wiring into service junction box, or if any of the original wire supplied with the heater
must be replaced, it must be replaced with wiring material having a temperature rating of at least 105° C
(221° F) and 600 volts. For supply connections use No. 14 AWG or larger wires.
10.5 UHA[X][S] Series Internal Wiring Diagram
24 of 49
10.6 UHA[X][S] Series Ladder Wiring Diagram
FLAME
SENSOR
PRESSURE SWITCH
THERMOSTAT
CONNECTION
6
3
4
5
2
1
120 VAC
TRANSFORMER
FLUE BLOWER
AXIAL FAN
AXIAL FAN
UHA (300, 350, 400 Only)
GAS
VALVE
ELECTRODE
IGNITION
MODULE
Flame
Spark
Limit Switch
Limit Switch (UHA 300,
350, 400 Only)
Manual Reset Limit Switch
(UHA 30 - 125 Only)
NOTE:
For field wiring into service junction box, or if any of the original wire supplied with the heater
must be replaced, it must be replaced with wiring material having a temperature rating of at least 105° C
(221° F) and 600 volts. For supply connections use No. 14 AWG or larger wires.
SECTION 10: WIRING
25 of 49
UHA STANDARD UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
BX Connector
Junction Box
Flexible Conduit
Burner
Connect wires together
with suitable approved
wire connectors.
Green to Ground
White to L2
Black to L1
L1
L2
Ground
Black
White
Green
10.7 Electrical Connection to the Heater
Note: Junction box is not provided with heater.
Conduit can also be attached directly to heater with wire junction made within the heater cabinet.
26 of 49
SECTION 11: OPERATION AND MAINTENANCE
WARNING
Severe Injury Hazard
Turn off gas and electrical supply before
service.
Fan can start automatically at any time.
Failure to follow these instructions can
result in severe injury or product damage.
SECTION 11: OPERATIONAND MAINTENANCE
DANGER
Electrical Shock Hazard
Disconnect electric
before service.
Heater must be
connected to a properly
grounded electrical
source.
Failure to follow these instructions can result in death, electric shock, injury or property damage.
Read this manual carefully before installation,
operation, or service of this equipment. All
components are accessed via hinged door secured by tooled access. Opening the door exposes live
electrical connections and hot components.
Explosion Hazard
Turn off gas supply to
heater before service.
WARNING
Burn Hazard
Allow heater to cool
before service.
Tubing may still be hot
after operation.
11.1.2 Electrical Checks
All pre-start-up checks must be carried out before
start-up the heater.
1. Check that all site wiring is connected in
accordance with the appropriate wiring diagram on Page 24, Section 10.5.
Cut/Pinch Hazard
Wear protective gear
during installation,
operation and service.
Edges are sharp.
11.1 Pre-Start-Up Checks
All pre-start-up checks must be carried out before
lighting the heater.
Ensure that the heater and all controls are suitable
for the gas, pressure and electrical supply to which
they are to be connected.
11.1.3 Gas Supply
All aspects of the gas installation including the gas
meter must be inspected, tested for gas tightness
and purged in accordance w
codes.
Ensure that the air is fully purged from the heater
inlet pipe up to the main gas valve inlet test nipple.
11.1.4 Mechanical Checks
1. Check that the fan is free to run and
delivery louvers are turned to give required
air deflection.
2. Check that the flue (and air intake for separated
combustion units) is installed in accordance
with the instructions in this manual and local
regulations. See Page 11, Section 7.
ith local and national
11.1.1 Louvers
Where fitted, the air delivery louvers need to be set
during start-up to give the required air distribution.
27 of 49
UHA STANDARD UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
Burner Sequence for Ignition Control
Flame Signal
Start Gas Valve
Ignition Spark
Thermostat 24 V
SHUT DOWN
RUN
START
ts = 10 Seconds
Signals Output By Control
Required Incoming Signals
Flue Blower
Pressure
Switch
P
C
NO
NC
30 Seconds Purge*
*Purge time begins at pressure switch change over.
Axial Fan
30 Seconds Delay90 Seconds Delay
30 Seconds Post Purge
If at any stage the flame fails, the control will retry
for ignition. The control has four trials for ignition
before a one hour lockout.
11.2 Begin Start-Up
11.2.1 Before Operating the Heater
To e n sure that all the controls are in safe working
order, operate the heater for the first time with the
isolating gas valve turned off and power supply
turned on.
1. Turn off the isolating gas valve.
2. Turn up the thermostat above room
temperature. The automatic ignition
sequence will now begin as described on Page 28, Figure 13.
There will be no ignition of the burner and lockout will occur, which proves the controls are operating
correctly.
Figure 13: Automatic Burner Control Sequence
28 of 49
Figure 14: Gas Valve for Models UHA[X][S] 150 - 400
½PSIIN
C
ON
OFF
Regulator
Outlet
Pressure
Gas Inlet
Inlet Pressure
TOP VIEW
END VIEW
DescriptionPart Number
Gas Valve 150 - 250 NG90032505
Gas Valve 150 - 250 LP90032506
Gas Valve 300 - 400 NG90032520
Gas Valve 300 - 400 LP90032521
SECTION 11: OPERATIONAND MAINTENANCE
11.2.2 Start-Up the Gas Valve (All Gases)
11.2.2.1 Check Burner Gas Pressure
1. Re m ov e t h e p lug in the outlet (burner) pressure
test point and connect a pressure tap and a
manometer.
2. With the burner firing, measure the pressure on
the manometer. To adjust the burner pressure,
remove the regulator cover from the valve and
turn the regulator adjustment screw to set the
required burner pressure as stated in the
Te c h ni c al Da ta Ta ble for the correct gas and
model on Page 48, Section 16.3.
NOTE: If the correct burner pressure cannot be
reached, then check the inlet pressure to the valve
with the burner firing. See Technical Data Table on
Page 48, Section 16.3 for inlet pressure
requirement.
Do not continue to adjust the regulator if the
pressure is not changing.
If the inlet pressure is too low to allow correct burner
press
ure setting, then the gas inlet pressure must be
corrected before completing the start-up.
Check Gas Rate
1. A f t e r burner pressure adjustment, allow the
heater to operate for at least 15 minutes and
then re-check settings. Adjust pressure setting
if necessary.
2. Check gas flow rate at gas meter.
3. Turn off heater and electrical supply.
4. Remove the manometer and refit all covers to
the valve and tighten the screw of the outlet
pressure tap.
11.2.3 Pressure Switch
The pressure switch is factory pre-set for each
model and is not adjustable.
11.2.4 Turning Off the Heater
Set the thermostat to the "OFF" position or lowest
setting and the main burner will stop.
The fan will continue to run until it is stopped
automatically by the fan thermostat.
Do not use a disconnect switch for control of
heater. Disconnect switch will turn off the fan.
Heat exchanger could be damaged. Warranty will
not cover damage to the heat exchanger if
operated improperly. Only use the disconnect
switch for turning off heater for service or durin
off-season.
g
29 of 49
UHA STANDARD UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
11.2.5 External Controls
External controls may include time switch, interlock
switch, room thermostat and frost thermostat.
Operate each control to ensure that they function
correctly. Set the switches (if fitted) and
thermostat(s) to the users’ requirements.
11.3 Complete the Start-Up
Ensure that all covers are fitted correctly and all test
points are properly sealed.
11.3.1 Instruction to the User
Explain the controls of the heater to the user
including how to turn it on and off, using the controls
fitted on site.
Give this manual to the user.
Ensure that the user is shown and understands the
importance of maintaining clearances to
combustibles on Page 7, Figure 4, installer
responsibility on Page 6, Section 3 and user
instructions on Page 31, Section 12 and all warnings defined in this manual.
30 of 49
SECTION 12: USER INSTRUCTIONS
Cut/Pinch Hazard
Wear protective gear
during installation,
operation and service.
Edges are sharp.
WARNING
Failure to follow these instructions can result in death, electric shock, injury or property damage.
Burn Hazard
Allow heater to cool
before service.
Tubing may still be hot
after operation.
Explosion Hazard
Turn off gas supply to
heater before service.
DANGER
Electrical Shock Hazard
Disconnect electric
before service.
Heater must be
connected to a properly
grounded electrical
source.
SECTION 12: USER INSTRUCTIONS
The UHA[X][S] Series heaters are fully automatic
and operate from the external controls fitted on site.
12.1 Heater Operation
When the heater has been switched on by the
thermostat installed on site, the main burner will
automatically turn on.
The burner control box will control the safe ignition
of the flame.
All heaters require a constant gas and electricity
supply which must not be interrupted during the
normal operation of this heater.
12.2 Lighting Instructions
12.2.1 To Turn On Heater
1. E n s ure that the electrical and gas supplies to
the heater are on. Check that the on site
controls are "ON".
IMPORTANT: The thermostat setting must be above
the ambient temperature for the heater to operate.
2. The automatic firing sequence will begin as
described on Page 28, Figure 13. The heater will now operate automatically under the control
3. The time and/or temperature controls are not
"ON".
4. A limit switch may have operated. This may be
caused by an interruption of the electrical
supply, failure of the distribution fan or vent or
heat exchanger blockage.
If a temperature limit switch persistently trips, there
is a fault which must be investigated by a contractor
qualified in the installation and service of gas-fired
heating equipment.
12.3.1 Simple Troubleshooting (Burner Fault)
If the burner fails to ignite for any reason, it will retry
for ignition (four trials total). After four unsuccessful
ignition trials, the control will put the heater into
lockout for one hour.
Lockout should not occur during normal operation of
the heater and indicates there is a fault condition
which must be corrected. There is an LED light on
the ignition control that flashes codes to assist in
fault correction. See Page 31, Figure 15 for LED
indication codes.
of the on site controls.
12.2.2 To Turn the Heater Off
Set the thermostat to the "OFF" position.
The burner will turn off immediately.
The fan will continue to run for 90 seconds.
To restart, turn the thermostat above room
temperature.
12.3 Simple Troubleshooting
Some possible reasons for the heater not operating
are:
1. Ga s s upply not "ON".
2. Electricity supply not "ON".
Figure 15: LED Diagnostic Codes
LED INDICATION FAULT MODE
Slow FlashNormal Operation - No call for heat.
Fast FlashNormal Operation - Call for heat.
2 FlashesIgnition Lockout - No flame detected.
3 FlashesAirflow Fault - Pressure switch open or closed.
4 FlashesTemperature Limit Switch Open
5 FlashesFlame Sense Error - Gas valve not energized.
Steady OnInternal Control Failure
31 of 49
UHA STANDARD UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
Cut/Pinch Hazard
Wear protective gear
during installation,
operation and service.
Edges are sharp.
WARNING
Failure to follow these instructions can result in death, electric shock, injury or property damage.
Burn Hazard
Allow heater to cool
before service.
Tubing may still be hot
after operation.
Explosion Hazard
Turn off gas supply to
heater before service.
DANGER
Electrical Shock Hazard
Disconnect electric
before service.
Heater must be
connected to a properly
grounded electrical
source.
SECTION 13: SERVICING
13.1 Servicing Instructions
After start-up, the heater will require maintenance to
be carried out, at a minimum, annually. If the heater
is used in a dirty or dusty area, more frequent
maintenance may be required.
IMPORTANT: After any maintenance or repair work,
always test fire the heater in accordance with the
start-up instructions on Page 27, Section 11 through Page 30, Section 11.3.1 to ensure all safety systems
are in working order before leaving the heater to
operate. Minor faults may be traced by using the
troubleshooting charts on Page 35, Section 14 through Page 39, Section 14.5.
IMPORTANT: Check all gas pipes and pipe joints to
ensure there are no cracks or gas leaks. Any cracks
in the pipes or pipe joints must be repaired.
IMPORTANT: Inspect all suspended components
and hardware. Ensure that they are in good
condition, properly tightened, and corrosion free.
13.2 Burner Maintenance
1. Open the door and remove the burner compartment cover. See Page 41, Section 15.2
2. Clean any deposits from the main burner which
may have formed in the injectors or venturi of
the burner. See Page 41, Section 15.2.
3. Remove the ignition electrode and flame probe.
Check condition of ignition electrode and flame
probe. Clean off any deposits which may have
been formed, check condition of ceramic
32 of 49
.
insulators. Replace as necessary. See Page 42, Section 15.3.
13.3 Fan/Motor Assembly Maintenance
The main fan bearings are permanently sealed and
do not need lubrication. Before cleaning, turn off gas
and electrical supply. Remove the fan and use a
small brush or duster to clean the fan blades from
each side. Replace fan when done.
13.4 Heat Exchanger Maintenance
The heat exchanger will remain clean unless a
problem has developed with combustion. Inspect the
heat exchanger. Look for signs of overheating at the
front tubes which may indicate burner over firing or
persistently low air flows.
13.5 Gas Valve Maintenance
No regular maintenance is required on this device.
To change gas control valves, See Page 40, Section
15.1.
Do not repair or disassemble gas valve.
Replace faulty gas valves
parts sold and supplied by Addison.
13.6 Flue Blower
The flue blower should not require maintenance.
However, if the air pressure switch is causing burner
lockout, then remove the flue blower from the vent box by unscrewing the three screws at the mounting
plate. Remove the four screws attaching the
mounting plate to the fan inlet (See Page 44, Section 15.6). Ensure that the fan is free to run and
that the fan wheel is clean.
with genuine replacement
SECTION 13: SERVICING
13.7 Venting and Air Intake Pipe
Inspect all venting and air intake pipe. Ensure that
all seams are sealed and suspension points secure.
Repair suspension points if any part of the venting
or combustion air pipe is sagging. Check to make
sure any insulation is not missing or in poor
condition. Replace as necessary. Check all venting
and air intake components to ensure they are in
good condition, gas tight and corrosion-free.
must be performed by a contractor qualified in the
installation and service equipment sold and supplied
by Addison and conform to all requirements set forth
®
in the ADDISON
manuals and all applicable
governmental authorities pertaining to the
installation, service, operation and labeling of the
equipment.
To help facilitate optimum performance and safety,
Addison recommends that a qualified contractor
conduct, at a minimum, annual inspections of your
13.8 Maintenance Checklist
Installation Code and Annual Inspections: All
®
installations and service of ADDISON
equipment
ADDISON
necessary, using only replacement parts sold and
supplied by Addison.
®
equipment and perform service where
Annual Fall Start-UpFollow entire start-up procedure at this time and check control settings and
operation.
The Vicinity of the HeaterDo not store or use flammable objects, liquids or vapors near the heater.
Immediately remove these items if they are present.
See Page 6, Section 3.
Vehicles and Other
Objects
Maintain the clearances to combustibles.
Do not hang anything from, or place anything on, the heater.
Make sure nothing is lodged in between the heat exchanger or in the louvers.
Immediately remove objects in violation of the clearances to combustibles.
See Page 7, Section 4.
Vent Pipe/TerminalsVenting must be intact. Using a flashlight, look for obstructions, cracks on the
pipe, gaps in the sealed areas or corrosion.
The area must be free of dirt and dust.
Remove any carbon deposits or scale using a wire brush.
If the vent terminal has a screen built in, remove any dirt, dust or deposits
from the screen.
See Page 18, Section 8.
Cabinet ExteriorAfter installation, tou
ch up scratches. Periodic paintings should be done
thereafter as required. Warning labels and logo labels should be legible and
®
accurate. Please contact Addison or ADDISON
independent distributor if you
need replacement warning labels or logo labels See Page 2, Figure 1 through Page 4, Figure 3.
Combustion Air Intake
Pipe
Intake pipe and inlet must be intact. Look for obstructions, cracks on the pipe,
gaps in the sealed areas or corrosion.
The area must be free of dirt and dust.
Clean and reinstall as required.
See Page 18, Section 8.
33 of 49
UHA STANDARD UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
Heat ExchangerMake sure there are no cracks.
See Page 19, Section 9.
Make sure there is no sagging, bending or distortion.
Clean or replace as required.
Gas Line and Shut-off
Check for gas leaks. See Page 19, Section 9.
Valves
Burner Observation
Window
Flue Blower Scroll, Wheel
Make sure it is clean and free of cracks or holes.
Clean and replace as required.
Compressed air or a vacuum cleaner may be used to clean dust and dirt.
and Motor
Inshot Burners and
Orifices
Clear of obstructions (even spider webs will cause problems).
Carefully remove any dust and debris from the burner.
Direct-Spark IgniterReplace if there are cracked ceramics, excessive carbon residue, or erosion
of the electrode.
The electrode gap should be 1/8" (3.2 mm).
ThermostatThere should be no exposed wire or damage to the device or wiring.
See Page 21, Section 10.
Suspension PointsMake sure the heater is hanging securely.
Look for signs of w
ear on the suspension materials or ceiling.
See Page 10, Figure 5.
Silicone TubingEnsure tight, secure fit on all pressure fittings at pressure switch,
burner partition, and blower outlet.
Gas ValveVerify that cap covering pressure regulator adjustment screw is secure and
has not been tampered with.
Verify all wiring connections.
Condensate Drain
Flush drain and clear any obstructions.
(when installed)
Wall TagIf a wall tag is present, make sure it is legible and accurate. Please contact
Addison or your ADDISON
®
independent distributor if you need a wall tag.
See Page 5, Section 2.1.
34 of 49
SECTION 14: TROUBLESHOOTING
Cut/Pinch Hazard
Wear protective gear
during installation,
operation and service.
Edges are sharp.
WARNING
Failure to follow these instructions can result in death, electric shock, injury or property damage.
Burn Hazard
Allow heater to cool
before service.
Tubing may still be hot
after operation.
Explosion Hazard
Turn off gas supply to
heater before service.
DANGER
Electrical Shock Hazard
Disconnect electric
before service.
Heater must be
connected to a properly
grounded electrical
source.
SECTION 14: TROUBLESHOOTING
35 of 49
UHA STANDARD UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
14.1 General
36 of 49
14.2 Troubleshooting For Automatic Ignition Burner Systems
For your safety and optimum heater performance, use only replacement parts sold and supplied by
Addison.
Conduct start-up procedure as shown on Page 27, Section 11.
SECTION 14: TROUBLESHOOTING
37 of 49
UHA STANDARD UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
NOTE: Minimum flame probe current 1 μA DC. Typical flame probe current 3-5 μA DC.
To measure flame current, connect a 0 - 50 μA DC meter in series with the flame probe. If the meter
reads negative values, then reverse the test leads.
14.3 Troubleshooting for Flame Supervision System
START
Connect a DC ammeter in
series with the flame probe.
Is the flame present and
at least 1 μA DC flame
current?
Ye s
Is there a current flowing in
the flame probe circuit with
no flame present?
No
No
Ye s
Does “lockout” occur when
there is a flame present?
No
Heater Operating
TROUBLESHOOT ENDS.
Ye s
No
Use General
Troubleshooting section to
trace the fault.
Is the connecting lead
damaged? Is the flame probe
damaged or touching earthed
components?
Is inlet burner gas pressure
correct? Is live and neutral
polarity correct? Is
flame probe circuit correct?
No
Repair or replace as
necessary.
If problems persist, contact
Addison at
www.addison-hvac.com
Repair or replace as
Ye s
Ye s
necessary.
Replace ignition control.
38 of 49
14.4 Troubleshooting for Gas Valves
For your safety and optimum heater performance, use only genuine replacement parts sold and supplied
by Addison.
Conduct start-up procedure as shown on Page 27, Section 11.
START
SECTION 14: TROUBLESHOOTING
Is gas pressure at inlet of the
valve correct for gas type?
Note pressure found.
Does gas pressure at outlet
of the valve rise when
valve turns on?
Does gas pressure at
outlet of valve return to zero or
lower when valve turns off?
Valve Operating
TROUBLESHOOT ENDS.
14.5 Troubleshooting for Flue Blower
Ye s
Ye s
Yes
Ye s
No
No
No
No
Fault elsewhere.
Correct pressure problem.
Valve or ignition control
faulty. Replace with
one of correct type.
Valve faulty.
Replace with one of
correct type.
If problems persist, contact
Addison at
www.addison-hvac.com
START
Does flue blower run
automatically when there
is a call for heat?
Ye s
Does blower turn on and
off while burner is firing
continuously?
No
Blower Operating
TROUBLESHOOT ENDS.
Ye s
No
No
Correct power
supply problem.
Ye s
Blower motor faulty.
Replace with correct type.
Check blower motor leads
for loose connections.
If problems persist, contact
Addison at
www.addison-hvac.com
39 of 49
UHA STANDARD UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
Carbon Monoxide Hazard
WARNING
Use only genuine ADDISON® replacement parts per this installation, operation and service
manual.
Failure to follow these instructions can result in death, electric shock, injury or property damage.
Explosion Hazard
DANGER
Electrical Shock Hazard
Fire Hazard
½PSIIN
C
ON
OFF
Flexible
Air Duct
DescriptionPart Number
Gas Valve, NG (Models UHA[X][S] 150 - 250)90032505
Gas Valve, LP (Models UHA[X][S] 150 - 250)90032506
Gas Valve, NG (Models UHA[X][S] 300 - 400)90032520
Gas Valve, LP (Models UHA[X][S] 300 - 400)90032521
NOTE: Seperated combustion
model shown.
SECTION 15: REPLACEMENT PARTS
See warnings and important information on Page
32, Section 13 before removing or replacing parts.
Burner Components
All serviceable burner parts are accessed by the
door on the side of the heater. Control door opens
via tooled access.
15.1 Gas Valve
Remove the gas supply pipe at the heater inlet.
Follow steps on Page 41, Section 15.2 and See Page 41, Section 15.2.1 to remove gas valve/
manifold.
Replace in reverse order. Verify that the gas flow
direction of the valve is correct. Use a minimum
amount of gas seal on the thread joint. Check that
all the joints are leak free. Reset gas valve. See Page 29, Section 11.2.2.
IT IS IMPORTANT THAT ONLY THE CORRECT
GAS VALVE IS USED WHEN REPLACING THESE
CONTROLS.
40 of 49
15.2 Burner Compartment
Remove flexible
air duct from spigot
Remove
access plate
Remove screws and
pull off burner
compartment cover
Viewing port
for flame probe
Viewing port
for ignition electrode
Flame Probe
Burner
Compartment
Cover
Rubber Seal
Ignition Electrode
The burner compartment is
a sealed compartment.
Following any work,
re-seal the compartment
with the gas pipe rubber
seal fully in place and all
screws fitted and tight.
NOTE: Flexible duct only applies
for model UHAS.
Ensure gas tight fitting of injectors.
Ensure correct alignment with burners.
Ensure all pipe joints are gas tight.
To replace the electrode or flame probe, remove the electrical lead and screw.
Pull out from mounting. Refit in reverse ensuring that the gap to burner is as shown in the
front view of the burner compartment.
15.3 Ignition Electrode and Flame Probe
42 of 49
SECTION 15: REPLACEMENT PARTS
Push in Louver and
compress spring to
remove and replace
(opposite end first)
Horizontal Louvers
Push in Louver and
compress spring to
remove and replace
(opposite end first)
Horizontal
Louvers
Description
UHA[X][S]
150 - 175
UHA[X][S]
200 - 250
UHA[X][S]
300 - 400
Horizontal Louvers P/N110118471101184711011846
Spring P/N919012009190120091901200
Quantity7911
15.4 Heat Exchanger
The heat exchanger consists of a six-pass design with 1.5" outer diameter [aluminized steel] [409 stainless
steel] tube. The tube plates are made of [aluminized steel] [409 stainless steel]. The tube supports are
made of [aluminized steel] [409 stainless steel].
15.5 Louvers and Louver Spring
The louvers for standard range models UHA[X][S]150 - UHA[X][S]400 are only available in horizontal
configurations.
43 of 49
UHA STANDARD UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
Remove screws securing outlet
flange to the flue adapter.
Refit in reverse order.
Remove screws securing flue
blower mounting plate to vent
box.
Remove screws securing
mounting plate to blower.
Refit in reverse.
Use new gaskets.
Ensure sealed joints.
Ensure mounting plate orifice is
clear and not obstructed.
15.6 Flue Blower
UHA[X][S]
MODEL
Flue Blower P/N907104059071040390710402
150 - 175
IT IS IMPORTANT THAT ONLY THE CORRECT FLUE BLOWER SPECIFIED FOR EACH MODEL TYPE
IS USED WHEN REPLACING THESE ITEMS.
UHA[X][S]
200 - 300
UHA[X][S]
350 - 400
Carry out a start-up after working on or changing an flue blower. See Page 27, Section 11.
44 of 49
15.7 Pressure Switch
SECTION 15: REPLACEMENT PARTS
Pull off 3 way connector. Spring open plastic clips of mounting cradle. Replace with correct type of
pressure switch for model. The pressure switches are color coded for each pressure setting.
Carry out a start-up after working on or changing a pressure switch. See Page 27, Section 11.
MODEL
Pressure Switch
Kit P/N
Color Code
Set Point in. w.c.
Press ure Switch Snap
Ring P/N
UHA[X][S]
150 - 175
9043980290439808904398039043980790439808
yelloworangegraybrownorange
.32.79.41.68.79
9043985090439850904398509043985090439850
UHA[X][S]
200 - 225
UHA[X][S]
250
UHA[X][S]
300 - 350
UHA[X][S]
400
15.8 Ignition Control
The control mounts to the electrical plate. Pull out ignition cable and wiring from board, noting their
positions. Release the four mounting standoffs. Refit in reverse. Ensure correct location of ignition cable
and all other wiring.
15.9 Axial Fan/Guard/Motor Assembly
The axial fan unit for the heater is supplied completely assembled and balanced
Within 24 months from date of purchase by buyer or 27
months from date of shipment by Addison (whichever
comes first), replacement parts will be provided free of
charge for any part of the product which fails due to a
manufacturing or material defect.
Addison will require the part in question to be returned to
the factory. Addison will, at its sole discretion, repair or
replace after determining the nature of the defect and
disposition of part in question.
ADDISON
of 18 months from date of shipment from Addison or the
remaining ADDISON
®
Replacement Parts are warranted for a period
®
UHA-Series warranty.
SECTION 17: THE ADDISON® UHA-SERIES WARRANTY
READ YOUR INSTALLATION, OPERATION AND
SERVICE MANUAL
If you have questions about your controller, contact your
installing professional. Should you need Replacement
Parts or have additional questions, call or write:
Service trips, service calls and labor charges.
Shipment of replacement parts.
Claims where the total price of the goods have not
been paid.
Damage due to:
• Improper installation, operation or maintenance.
• Misuse, abuse, neglect, or modification of the
ADDISON
• Use of the ADDISON
®
UHA-Series in any way.
®
UHA-Series for other than its
intended purpose.
• Incorrect gas or electrical supply, accident, fire, floods,
acts of God, war, terrorism, or other casualty.
• Improper service, use of replacement parts or
accessories not specified by Addison.
• Failure to install or maintain the ADDISON
®
UHASeries as directed in the Installation, Operation and
Service manual.
• Relocation of the ADDISON
®
UHA-Series after initial
installation
• The use of the ADDISON
®
UHA-Series in a corrosive
atmosphere containing contaminants.
• The use of the ADDISON
®
UHA-Series in the vicinity
of a combustible or explosive material.
• Any defect in the ADDISON
®
UHA-Series arising from
a drawing, design, or specification supplied by or on
behalf of the consumer.
• Damage incurred during shipment. Claim must be
filed with carrier.
WARRANTY IS VOID IF:
The ADDISON® UHA-Series is not installed by an
electrician qualified in the installation and service of
control systems for heating equipment.
Yo u cannot prove original purchase date and required
annual maintenance history.
The data plate and/or serial number are removed,
defaced, modified or altered in any way.
Addison's liability, and your exclusive remedy, under
this warranty or any implied warranty (including the
implied warranties of merchantability and fitness for
a particular purpose) is limited to providing
replacement parts during the term of this warranty.
Some jurisdictions do not allow limitations on how long an
implied warranty lasts, so this limitation may not apply to
you. There are no rights, warranties or conditions,
expressed or implied, statutory or otherwise, other than
those contained in this warranty.
Addison shall in no event be responsible for
incidental or consequential damages or incur liability
for damages in excess of the amount paid by you for
the ADDISON
®
UHA-Series. Some jurisdictions do not
allow the exclusion or limitation of incidental or
consequential damages, so this limitation or exclusion
may not apply to you. This warranty gives you specific
legal rights, and you may also have other rights which
vary from jurisdiction to jurisdiction.
Addison shall not be responsible for failure to perform
under the terms of this warranty if caused by
circumstances out of its control, including but not limited
to war, fire, flood, strike, government or court orders, acts
of God, terrorism, unavailability of supplies, parts or
power. No person is authorized to assume for Addison
any other warranty, obligation or liability.
LIMITATIONS ON AUTHORITY OF
REPRESENTATIVES:
No representative of Addison, other than an Executive
Officer, has authority to change or extend these
provisions. Changes or extensions shall be binding only if
confirmed in writing by Addison's duly authorized
Executive Officer.
The ownership of the ADDISON
®
UHA-Series is moved
or transferred. This warranty is nontransferable.
Addison is not permitted to inspect the damaged
controller and/or component parts.
49 of 49
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.