The FlexWave Prism Remote Unit has a low profile design that requires minimal real
estate for installation. The basic dimensions and weights of the Remote are listed in
Table 4-2.
Table 4-2. Remote Dimensions
Remote Configuration Depth WidthHeight Weight of Fully
Populated Units
Single- Band
10.51"12.15"22.50" <
65 lbs
Double Band
Triple Band
Quad- Band
10.51"12.15"30.50" <
10.51"12.15"38.46" <
10.51"12.15"49.60" <1
96 lbs
127 lbs
65 lbs
The Prism Remote should be mounted on a utility pole, mast, or on a flat surface. A
mounting kit is available for each unit. Installation consists of securing the bracket
to the mounting surface (wood, concrete, or steel) and then hanging the unit from the
bracket. The Remote should only be mounted in a restricted access location.
Detailed instructions for mounting the FlexWave Prism Remote are in the Remote Unit Mounting Kit Installation Instructions (ADCP-77-077).
This chapter guides you through installing a Prism Remote, which requires 63 steps
that are divided into 9 sections. Follow the steps in the order in which they are
provided.
This is restricted access equipment and only service personnel should open and operate
this equipment
Wet conditions increase the potential for receiv ing an electrical shock when installing or
using elec
electrical equipment in
Installation of the Remote may proceed separately from the installation of the
corresponding Host.
4.3.1Unpack and Inspect the Remote and Components
using appropriate tools
trically- pow ered equipment. To prev ent electrical shock, never install or use
a wet location or during a lightning storm.
This section provides instructions for opening the shipping boxes, verifying that all
parts have been received, and verifying that no shipping damage has occurred. Use
the following procedure to unpack and inspect the Host and any accessories:
Unpack and inspect the various components as follows:
11Inspect the exterior of the shipping container(s) for evidence of rough handling
that may have damaged the components in the container.
22Unpack each container while carefully checking the contents for damage and
verify with the packing slip.
33 If damage is found or parts are missing, file a claim with the commercial carrier
and notify ADC Customer Service (see “Contacting ADC” on page 335). Save the
damaged cartons for inspection by the carrier.
44Save all shipping containers for use if the equipment requires shipment at a
The RF Module cables that are pre installed in the Remote connect to the
corresponding connectors on the RF Module. The RF Module cables correlate to the
antenna connectors on the bottom of the Remote chassis. The cables and connectors
have corresponding labels as shown in Table 4-3. The RF cable and connector labels
also correspond to the RF Module slots in the Remote chassis, where MOD A is the
bottom shelf and MOD D is the top shelf.
Table 4-3. RF Antenna Labels
Remote RF
Module
Shelf
MOD AMod A TX0/RX0 Transmit RF power and primary receive to/from the antenna
MOD BMod B TX0/RX0 Transmit RF power and primary receive to/from the antenna
MOD CMod C TX0/RX0 Transmit RF power and primary receive to/from the antenna
MOD DMod D TX0/RX0 Transmit RF power and primary receive to/from the antenna
RF Module Cable,
RF Module
Connector, and
Remote Antenna
Connector Labels
Mod A RX1Diversity receive for RF power from the antenna for RF
Mod B RX1Diversity receive for RF power from the antenna for RF
Mod C RX1Diversity receive for RF power from the antenna for RF
Mod D RX1Diversity receive for RF power from the antenna for RF
In the following steps, the RF cables and connectors are referred to as
and as
where N equals A,B,C, or D.
55Unpack and inspect the RF Module as described in “Unpack and Inspect the
Remote and Components” on page 97.
Handle the RF Module with care during installation. Be especially careful to not damage
the thermal- i
the LPA can ov erheat. B
material is gouged or cracked. If the TI
contact ADC for assistance (see “Contacting ADC” on page 335 for contact informat
If the thermal- interface material is damaged, the installation and use of the RF Module
may void the
nterface material (TIM), which is attached to the LPA. If the TIM is damaged,
efore installing the RF Module, check to see if the heatsink
M is damaged, do not install the R F Module and
ion).
warranty of the RF Module.
66Open the Remote enclosure.
77Remove release liners, if present, from the thermal pads on the RF Module prior
to installing the module into the Remote chassis.
The thermal pads are very sensitive to mishandling—do not nick, scratch, or ding them.
Thermal pads are located as follows:
••one large pad on the back surface (LPA)
••up to two on the front surface (DARTs)
••two on the left side for the (RDI).
88Hold the RF Module so that the DART card(s) face away from the Remote and the
Mounting Hook is toward the Receiving flange on the Remote chassis.
Alway s install RF Modules from the bottom up and do not skip a shelf.
177 Ensure that all cable bends are below the top edge of the Connector Interface
Panel as indicated by the dashed line in the preceding figure. Failure to correctly
position the cables could inhibit closing the Remote door, which can result in
damage to the cables.
The 40W RF Modules can only be installed in the top most slots of the Remote:
•Slots A and B for a Dual-Band chassis.
•Slots B and C for a Tri-Band chassis
•Slots C and D for a Quad-Band chassis
The RF Module cables that are preinstalled in the Remote connect to the
corresponding connectors on the RF Module. The RF Module cables correlate to the
antenna connectors on the bottom of the Remote chassis. The cables and connectors
have corresponding labels as shown in Table 4-3. The RF cable and connector labels
also correspond to the RF Module slots in the Remote chassis, where MOD A is the
bottom shelf and MOD D is the top shelf.
Table 5. RF Antenna Labels for Dual-Slot Installations—From Top of Chassis Down
RF Module
Cable,
RF Module
Connector,
and Remote
Antenna
Connector
(a)
Labels
Mod D
TX0/RX0
Mod D RX1
Mod C
TX0/RX0
Mod C RX1
Mod B
TX0/RX0
Mod B RX1
Mod A
TX0/RX0
Mod A RX1
(a) For dual-slot installations, the RF cables and connectors are labeled as MOD N TX0/RX0 and MOD N TX1, where N refers to the bottom slot of the
double-slot installation. For example, for a dual-slot installation in a Quad-Band chassis, the RF cables and connectors are labeled as MOD CTX0/RX0 and MOD C TX1.
Transmit RF power and primary receive
to/from the antenna for RF Module D
Diversity receive for RF power from the
antenna for RF Module D
Transmit RF power and primary receive
to/from the antenna for RF Module C
Diversity receive for RF power from the
antenna for RF Module C
Transmit RF power and primary receive
to/from the antenna for RF Module B
Diversity receive for RF power from the
antenna for RF Module B
Transmit RF power and primary receive
to/from the antenna for RF Module A
Diversity receive for RF power from the
antenna for RF Module A
Function
Single-Slot
Remote RF
Module Shelf
Designations
MOD DN/AN/A
MOD CN/A
MOD B
MOD AMOD AMOD A
Dual-Slot Remote RF Module Shelf Designations
Dual-BandTri-BandQuad-Band
MOD C
MOD B
MOD B
MOD A
NOTE:In the following steps, the RF cables and connectors are referred to as MOD N TX0/RX0
1 Unpack and inspect the RF Module as described in “Unpack and Inspect the
Remote and Components” on page 97.
Handle the RF Module with care during installation. Be especially careful to not damage the thermal-interface
material (TIM), which is attached to the LPA. If the TIM is damaged, the LPA can overheat. Before installing the
RF Module, check to see if the heatsink material is gouged or cracked. If the TIM is damaged, do not install the
RF Module and contact ADC for assistance (see “Contacting ADC” on page 335 for contact information).
If the thermal-interface material is damaged, the installation and use of the RF Module may void the warranty
of the RF Module.
2 Open the Remote enclosure.
3 Remove release liners, if present, from the thermal pads on the RF Module prior
to installing the module into the Remote chassis.
CAUTION!The thermal pads are very sensitive to mishandling—do not nick, scratch, or ding them.
Thermal pads are located as follows:
• one large pad on the back surface (LPA)
• up to two on the front surface (DARTs)
• one on the left side for the (RDI).
4.4.2Remove Module Shelf(s)
The module shelf for the upper module as defined in Table 4-3 on page 98 must
be removed prior to installation of the dual-slot module:
In Steps 9 and 10, you engaged the right side of the RF Module with the Remote chassis.
In Step 11, you set the left edge of the RF Module into the Remote chassis.
By the end of Step 11, the front edge of the RF Module should be parallel with the shelf above it.
Now in Step 12, you are pushing the RF Module back into the chassis until it can go no further.
4Push the left edge of the RF Module back and into the Remote chassis until it
can go no further.
Make sure the RF Module is seated correctly in the Module shelf. Incorrect alignment of the RF Module can
cause the RF Module to fail due to over heating.
•The front edge of the RF Module should be parallel with the shelf above it.
•The Mounting hook on the RF Module should be fully engaged with the Receiving flange on the Remote
chassis.
•If you later cannot shut the Remote door, verify that the RF Module is installed correctly.
8Follow these rules when connecting the RF Module cables:
• At each RF Module shelf, the Power (PWR) cable and two high-speed-data
cables will always be provided.
• If you are installing a module into a Non-Diversity Chassis, only one RF
cable labeled MOD N TX0/RX0 will be populated.
• High-speed data cables labeled PRIM and DIV should always either be
connected or strain relieved to adjacent cables. This protects against the
cable getting caught in the chassis door.
• If you order a Non-Diversity RF Module and are installing it in a Diversity
chassis, connect it as if it was being installed into a Non-Diversity chassis.
• Connect both high-speed data cables (PRIM and DIV) and the RF TX0/RX0
cable.
• Adhere to a minimum bend radius of 1" for all RF cables from the integrated
cable guide to the module.
• Maintain adequate strain relief distances from connection points to the
module.
• When installing dual-slot RF modules:
–The upper RF Module shelf will either not be present (factory installed
module) or will be removed prior to installation (field installed module).
–For dual-slot modules, only the RF cable labeled MOD N TX0/RX0 on the
lower module slot will be connected to the module connector TX0/RX0.
–The MOD N RX1 cable should be secured to the cable bundle using the
provided cable tie.
–Ensure that the MOD N RX1 cable and connector are secured so that they
will not be pinched or prevent the Remote door from closing.
–The Power (PWR) cable and two high-speed-data cables of the upper RF
Module slot will not be used. Connect the RF cable labeled MOD N RX1 to
the connector labeled N/C on the upper half of the double-slot module.
Use one of the provided cable ties to secure the MOD N TX0/RX0 RF cable,
both high-speed data cables and the Power (PWR) cable to the RF cable
labeled MOD N RX1, ensuring that the cable bundle will not be pinched or
prevent the Remote door from closing.
9Working from the bottom connector up, connect the RF Module cables.
aConnect the RF cable labeled MOD N TX0/RX0 to the TX0/RX0 connector and turn
the thumbscrew to secure the cable to the chassis.
Always connect the Diversity high-speed-data cable, even for non-diversity modules. This prevents the cable
from getting caught between the chassis door and the RF Module.
b Connect the MOD N PRIM high-speed cable to the PRIM connector. This
connects the RSI to the Primary DART.
cConnect the Power cable to the PWR connector. This connects the RF Module
to the DC power connection.
d The Power (PWR) cable and two high-speed-data cables of the upper RF
Module shelf are not be used in a dual-slot installation. Connect the RF cable
labeled MOD N RX1 of the upper RF Module shelf to the connector labeled N/C
on the upper half of the dual-slot module. Use one of the provided cable
ties to secure the MOD N TX0/RX0 RF cable, both high-speed data cables and
the Power (PWR) cable to the RF cable labeled MOD N RX1, ensuring that the
cable bundle will not be pinched or prevent the Remote door from closing.
The following graphic shows cable connections for a dual-slot RF Module.
10 Ensure that all cable bends are below the top edge of the Connector Interface
Panel as indicated by the dashed line in the preceding figure. Failure to
correctly position the cables could inhibit closing the Remote door, which can
result in damage to the cables.
For Dual-Card RF Modules, use the
Power switch for the lower module.
For example, to power up a
Dual-Card RF Module in combined
slots C+D in a Quad-Band chassis,
turn ON DC Power switch for Mod C;
leave the DC Power switch for Mod D OFF.
11 Toggle the Power switch that corresponds to the RF Module to its ON position.
The Remote provides a Network port allowing communications with the internal
processor and transfer of service data to the optical protocol allowing IP servicing
between the Host and Remote(s). That is, this provides a LAN extension to the Host
network. The Network port is 10/100/1000 BASE-T/TX (802.3ab compliant) MDI and
requires a minimum of CAT 5 cable.
Although the interface might provide GigE, only 100 Mbps is provided for bandwidth
between the Host a
The network cable must be terminated with a hardened RJ-45 male connector for
connection to the Network port. The maximum cable length is 300 feet (91.4 m).
Use the following procedure to install the Network cable:
177 Remove the dust cap from the RJ-45 connector located at the bottom of the
Remote.
nd Remote.
RJ-45 Network
Connector port
RJ-45 plug
Connector nut
Network cable
NETWORK
POWER
100-240 VAC
50-60 Hz
16 AMPS
MOD D
RX1
MOD D
TX0/RX0
MOD C
RX1
Bottom View
AUX.
MOD C
TX0/RX0
MOD A
RX1
MOD B
RX1
MOD A
TX0/RX0
MOD B
TX0/RX0
FIBER 1
FIBER 2
77073-010
188 Route the network cable from the network connection to the underside of the
Remote.
199 Align the plug end of the RJ-45 cable connector with the RJ-45 port receptacle and
then insert the cable plug into the port receptacle.
200 Slide the connector nut up to the port until it engages the connector locking
mechanism.
211 Tighten the connector nut in a clockwise direction (if necessary, use a wrench or
pliers to grip the connector nut) until it snaps past the indented position and
locks into place. It may be necessary to apply 30 to 50 in-lbs (3.4 to 5.6 Nm) of
torque to the connector nut in order to turn it past the indented position.
Fiber 2 is a
ProAx connector
that comprises
4 BX5 connectors.
Bottom View
4.4.6Quad Fiber Cable Installation
The Prism Remote ships with 10 meters of environmentally hardened cable with 1
meter of exposed, un-terminated single-mode 900μm optical fiber sufficient for
splicing in an Outside Plant (OSP) splice tray. The fiber cable connector is a BX5 4-port
fiber connector.
Use the following procedure to install the fiber cables:
222 Remove ProAx connector dust cover located at the bottom of the Remote.
255 Route the fiber cable from the underside of the Remote to the OSP box. Observe
the fiber numbers and their positions in the quad cable connector as shown
below. The fibers at the other end of the fiber cable are numbered with the same
numbering scheme.
266 Secure fiber cable in place following local practices.
277 If a second fiber cable assembly is required (for example, your Prism system has
three SFPs to handle up to 280 MHz of RF bandwidth), complete Step 22 through
Step 26 to add the second fiber cable assembly, only this time, connect to the
Fiber 2 ProAx connector located at the bottom of the Remote as shown in Step 22.
4.4.7Antenna Cable Installation
Coaxial antenna cables must be routed from the antenna to the Prism Remote. The
cables must be terminated with an N-Type male connector for connection to the
Remote antenna port or the lightning surge suppressor (accessory).
To comply w ith Maximum Permissible E xposure (MPE) requirements, the maximum
composite output from the
must be permanently installed in a fixed locat
of separation from all persons.
299 If specified, connect a lightning surge suppressor (accessory) to the antenna port.
300 Connect a ground wire to the lightning surge suppressor. Connect the ground wire
to an approved earth ground.
311 Route the coaxial antenna cable from the antenna to the underside of the Remote.
322 Cut the antenna cable to the required length and terminate with an N-type male
connector.
333 Connect the antenna cable to the lightning surge suppressor or to the antenna
port; apply 15 in-lbs (1.7 Nm) of torque.
The antenna cable connections must be weather proofed (sealed) for outdoor
installations.
344 Repeat the Step 28 through Step 33 for the remaining antenna cables.
4.4.8AC Power Wiring Installation
A 15-foot, 3-wire cable with connectors is provided for the AC power connections.
The connector end of the cable connects to the AC power port located on the bottom
of the unit. The stub end of the cable must be routed to an external junction box (not
provided) for permanent connection to the AC power system wiring.
The AC power source must supply between 100 and 240 VAC, 50 or 60 Hz,
single-phase power through a circuit breaker or fuse. The AC power cable provides
three wire leads for line, neutral, and ground connections. The power cable is rated
for indoor or outdoor use and must not be placed within electrical conduit as this will
impede the cooling of the cable during usage. The electrical junction box and any
conduit, wire, and fittings required must be provided by the installer.
Use extreme caution when w orking with high voltage AC pow er. Ensure all power is
disconnected before
All electrical work must comply with local codes and requirements. A locally licensed
electrical cont
consult w ith the ADC Techn
ractor is best qualified to perform this w ork. For additional information,
working on pow er circuits.
ical Assistance Center (see “Contacting ADC” on page 335).
Use the following procedure to install the AC power wiring:
355 Locate the AC power cable that is provided separately with the Remote.
366 Route the power cable between the AC power port, located on the underside of
the Remote and the nearest AC power junction box as shown below. It may be
necessary to install a new junction box if an existing junction box is not available.
Remote enclosure
AC power cable
AC power junction box
AC power wires routed
to circuit breaker panel
77073-071
377 Secure the cable between the AC power port and the AC power junction box per
local practice. Leave sufficient slack in the cable to allow it to be easily connected
and disconnected from the AC power port.
The pow er cable is rated for indoor or outdoor use and must not be placed within
electrical conduit a
run distance to the AC power sour
s this will impede the cooling of the cable during usage. The cable
ce must not exceed 100 feet.
388 Install any AC power supply wires that may be required between the AC junction
box and the AC circuit breaker box.
It is recommended that an AC outlet be installed near the Remote for powering tools
and test equipmen
An appropriate disconnect device, as well as branch circuit protection, must be provided
as part of t
he installation.
t. This outlet must include a GFCI device for protection.
444 Remove the dust cap from the AC power port located on the bottom of the Remote
as shown below.
While trying to connect the AC power cable to the Remote AC power port, it is possible
for the line t
If the AC cable is energi
To avoid pos sible personal injury
before connecting the AC power cable to the AC po
erminal on the cable connector to contact the ground pin on the power port.
zed, this will res ult in a direct short to ground for the AC power.
and equipment damage, alw ays turn the AC pow er off
wer port.
NETWORK
MOD A
MOD C
TX0/RX0
RX1
MOD B
Green band will be
visible when coupling —
Nut is tightened
POWER
100-240 VAC
50-60 Hz
16 AMPS
MOD D
RX1
MOD D
TX0/RX0
MOD C
RX1
AUX.
Power
cable
Bottom View
455 Connect the power cable connector to the AC power port.
RX1
MOD A
TX0/RX0
MOD B
TX0/RX0
FIBER 1
FIBER 2
77073-015
466 Tighten coupling nut until the green band at the top of the connector body is
488 Enter the power consumption in the spaces provided below.
499 For the total RF Module power consumption, calculate the power consumption
from Table 4-3 on page 131 for each RF Module present in the Remote (RF Module
A - D), add the Watts, and then enter the total in the Total Power Consumption
field.
SeRF Module power consumption from Table 4-2_________Watts
Additional SFPs _____ x 1.25W_________Watts
RF Module A power consumption from Table 4-3_________Watts
RF Module B power consumption from Table 4-3_________Watts
RF Module C power consumption from Table 4-3_________Watts
RF Module D power consumption from Table 4-3_________Watts
TOTAL POWER CONSUMPTION
_________Watts
500 Divide the total Watts by the input Voltage to determine the current (Amperes)
requirements.
Watts
= Amps
Volts
511 Determine the circuit breaker or fuse size based on local codes and practices.
Circuit breaker or fuse size must be 20 Amps or less.
522 Refer to the detailed instructions for mounting the FlexWave Prism Remote in the
Remote Unit Mounting Kit Installation Instructions (ADCP-77-077) to mount the
Remote in the location selected in Section 4.2, Remote Mounting Plans, on page
96.
533 Power up the Remote by turning its AC power switch to On.
544 Close and tightly secure the Remote door and Solar Shield.
The ADC FlexWave EMS is an embedded software application that is accessed through
an internet connection using a Web browser and provides a Graphical User Interface
(GUI) for control and monitoring of a Prism system.
As shown in Figure 5-2, you access the embedded EMS through the Host, where RF
signals are converted to optical signals for distribution to the local coverage area. The
EMS is thus in a position to monitor both types of signals, and to report status,
alarms, and RF signal levels through automatic, periodic updates and in response to
user requests. User requests can include commands to set RF gain and propagation
delay.
Before you start using the EMS, familiarize yourself with its components.
You use a Web browser to access the EMS Graphical User Interface (GUI). A typical
display consists of the two frames shown in Figure 5-3.
••Function Explorer Tree—appears in the left frame. Click on a node to open the
corresponding screen.
••EMS View Frame—appears in the right frame. A typical page contains alarm
indicators, lists of parameter values, and tools such as lists and text boxes that
allow you to set parameter values.
The EMS View Frame includes the EMS Menu bar, which provides access to EMS
configuration or summary windows. For further information on the EMS Menu
bar, see “EMS Menu Bar” on page 140.
The EMS Menu bar links (Figure 5-4) perform as described in Table 5-1.
Figure 5-4. EMS Menu Bar
Table 5-1. EMS Menu Bar Links
LinkFunction
Opens the General Configuration window from which you set system Auto
refresh. See “Setting Auto Refresh” on page 179.
Opens the Activ e Alarm List window, which is a means to determine alarm
type, Host unit name, Remote name, time stamp, and other information for
active alarms. See
List window provides a link to the History Log (see “Viewing an Alarm History
Log” on page 259).
Opens the Alarm Management Table, from which you can mask and unmask
alarms. See “Masking an Alarm Type” on page 260 or “Unmasking an Alarm
Type” on page 262.
Opens the System Inventory view, which identifies the main software and
hardware components of the current, working system. See “Working with the
System Inventory” on page 180.
Opens the EMS online help system that provides a description for each node
in the Function Explorer Tree. To access a specific help topic, click on the
appropriate link. (The Help: Overview topic is the default topic.)
Opens a window that provides the software-release version of the EMS, and
copyright and trademark information.
Logs you out of the EMS.
“Viewing Active Alarms” on page 258. The Active Alarm
Some EMS parameter values are associated with alarms. When a parameter enters an
alarm state, an alarm status indicator is activated where the color of the indicates the
alarm severity (Figure 5-5):
••Red status indicator—major alarm
••Yellow status indicator—minor alarm
••Green status indicator—normal (okay) state
••White status indicator—a device or component is not communicating, but is in the
EMS database
••Grey status indicator—alarm is masked.
Figure 5-5. Example of Alarm Indicators
For further information on EMS alarms, see “Managing Alarms” on page 257.
The computer that you use to remotely access the EMS must meet the following
minimum requirements:
••Windows 2000 or Windows XP operating system
••Internet Explorer version 6.0. When a direct connection is made, an internet
connection is not needed, but the user interface still displays in a Web browser.
••Network Interface Card (NIC)
••Ethernet cable with RJ-45 connectors.
The EMS database can also be accessed remotely using an SNMP manager. In this case,
the user interface varies depending on the SNMP manager, but the underlying
parameters, parameter values, and alarms are the same as in the standard EMS
interface.
6.1 Access the EMS................................................................................................144
6.2 Discover IP Addresses.......................................................................................146
6.3 Enter a Host Name, Clock Source, and Linking Mode .............................................147
6.4 Set the Clock Priority Level................................................................................150
6.5 Provision the Host SeRF Optical Ports..................................................................151
6.6 Configure the Host DARTs .................................................................................152
6.7 Enter a Remote Name.......................................................................................156
6.8 Configure the Remote SeRF Optical Ports.............................................................158
6.9 Link the Host and Remote DARTs. ......................................................................159
6.9.1 Use of Multi Fibers ....................................................................................159
6.9.2 RF Groups in the Remote and the EMS GUI ..................................................160
6.9.3 Link a Remote DART to a Host DART ...........................................................162
6.10 Conclude Initial System Setup..........................................................................167
6.11 (Optional) Configuring Multi-Host Systems for Manual Mode .................................168
6.11.1 Set the Multi-Host System to Manual Mode.................................................168
6.11.2 Configure the Host DARTs ........................................................................168
6.11.3 Configure the Remote DARTs....................................................................173
This chapter guides you through an initial Prism system setup, which requires that
you follow the steps in the order given. There are 42 steps in this process that are
divided into 10 sections.
Only a user logged in under the admin account can complete the initial Prism setup
through the EMS.
columns provide the IP address for the Host and Remote. You can use this
view opens in the EMS View Frame. The
to display a system view.
IP address to log into the Host and Remote unit through a LAN or WAN
connection.
The
view will display all Remotes connected to the Host, so up to
eight Remotes can be listed. (The number of Remotes listed changes as Remotes
are added or removed from the FlexWave system.)
77Note the Host IP address for future use: _________________________
view in the EMS View Frame. (For information on the read-only
view, see “Viewing the Host Summary” on
page 214.)
100 In the
box, enter an identifying name for the Host. The
be between 5 and 40 characters, with no spaces. The only special character
allowed is an underscore, but it cannot be the first character of the name.
Numerals are allowed, but cannot be the first character of the name.
You may need to click in the Function Explorer Tree frame and then click Refresh before
the new name
. The new
displays in the Function Explorer Tree and the
view as part of the view title and in the
appears.
box.
122 In the
list, select
(default) or
. The SeRF
board on each Host and Remote contains the master clock for that unit. At the
Remote, the reference is a clock derived from the Host clock. The
setting allows you to frequency lock the master clock to an external
10 MHz reference.
When using the 10 MHz external reference clock, the signal must be connected to the
Host before enabl
selected for operation, but is
+ /- 5ppm, communication between the Host and
ing the clock in the software. If an external 10MHz reference clock is
not present or outside of the frequency range of 10MHz
parameter—do not change this setting during
this procedure. Refer to “Changing to Built-In Network Mode” on page 186 for
information on setting the
144 In the
list, keep the default setting of
Linking mode, the Host passes its
connected Remotes. For a Multi-Host system, you must select
you to manually set
a Multi-Host system, leave the
and
.
and
set to
In Automated
as this allows
. If you are setting up
, complete the initial
setup, and then complete “(Optional) Configuring Multi-Host Systems for Manual
There can be up to eight Host SeRF optical ports that correspond to the eight physical
ports on the Host. Labeling the Host SeRF Optical Ports provides for easier off-site
management.
199 In the Function Explorer Tree, select
x is the Host name) to open the
Frame. The default
for the Optical ports is
information on the status indicators in the
SeRF Optical Ports” on page 224.)
view for the Host in the EMS View
view, see “Viewing Host
(where
. (For
200 In the
box, enter a label for the selected Optics port. The
must be between 5 and 32 characters with no spaces. The only special character
allowed is an underscore, but it cannot be the first character of the name.
Numerals are allowed, but cannot be the first character of the name.
211 Select
management traffic. By default
unselected, the SFP cannot exchange management traffic. How you set
to configure the Small Form-Factor Pluggable (SFP) for exchange of
is not selected. If
is left
is
dependent on the system configuration:
••In a multifiber scenario, do not enable IP on both SFPs from the same Host to
the same Remote. Typically, the first SFP on the Host that goes to that Remote
is used as the IP enabled port for management communications.
••In a Multi-Host system, multiple fibers connected to a Remote come from
different Hosts. However, a Remote can accept an IP connection from only one
Host and only one Host can “own” the Remote for the purposes of provisioning
and monitoring. When a second Host attempts to establish an IP connection,
this second connection fails and an IP Conflict alarm is triggered. You
therefore select
only for the Host that manages the Remote so that
only one of the fibers connected to the Remote will have IP.
Configuring a Host DART provides information required for the DART to operate in
RF transmission. Each DART is configured in hardware to operate within a specific RF
band such as PCS or Cellular; the passband is a software-defined sub-band of the
hardware-defined band. Forward and reverse path gain, diversity status, and
operating mode may also be set when a Host DART is configured. The same settings
are applied to the Remote DART when linked to the Host DART. The Host has eight
slots for DART cards.
If you are setting up a multi- host system, go to “(Optional) Configuring Multi-Host
Systems for Manual Mode” on page 168.
233 In the Function Explorer Tree, select
the Host name) to open the
The
view displays all the Host DARTS that are present,
view in the EMS View Frame.
(where
starting from slot 1 at the top of the list and working sequentially down to last
DART, which can be slots 1-8.
box, enter a name for the DART between 5 and 32 characters
with no spaces. The only special character allowed is an underscore, but it
cannot be the first character of the name. Numerals are allowed, but cannot be
the first character of the name.
bbIn the
list, select the DART Pass Band to be
supported by this DART. The list will include only those pass bands that are
valid selections for the DART band. For example, if the DART band is
“cellular,” only cell pass bands are listed.
ccIn the
•
—forces the RF function to be muted in the Host and its linked
list, select one of the following:
Remote.
•
—allows the system to operate normally (RF function not forced to
be muted), assuming all other system components are in proper working
order. (Default setting.)
The mode
is not user selectable, and indicates that the EMS is
unaware of the current mode.
ddIn the
application, one DART will be configured
FWD/REV path signal and the other DART will be configured
selection therefore determines whether the DART card being configured will
carry the primary or secondary RF path.
For dual DART configurations, such as dual-pcs, smr800/smr900 and
dual-aws, both DARTs must have
The div ersity status of the Host DART w ill extend to the Remote DART connected to it.
For further inf
ormation, see “Link the Host and Remote DARTs.” on page 159.
set to
.
eeIn the
list, set this value (0 to 31 dB) based upon the fully
loaded forward path signal level from the Base Station. The Host DART expects
signal levels from
to
. If the fully loaded signal is +5 dBm, then the
DART forward gain should be set to 0 dB, if the fully loaded signal is -25 dBm,
then the DART Forward Gain should be set to 30 dB. The equation is:
DART Forward Gain = 5 - fullyLoadedBasestationSignal.
If you are setting up the system when no calls are going through, you must allow
headroom for a fully
unloaded to fully loaded is typically 8
fully loaded input would be - 7 dBm and the Host For
= 12 dB.
The same rules applies for GSM carriers, except that the u
determined by the equation 10*log10(# RF Channels). So if there are 4 GSM RF Cha
then the loaded forward path is 6 dB above unloaded.
If sufficient headroom is not present, the
Of Service.
When configured correctly , the Host DART Forward input can handle peaks of 14dB
above the BTS signal
peaks up to - 11 dBm can be handl
the peaks exceed the 14 dB of headroom, then Auto
to prevent over- driving the A/D Conv erter.
loaded forw ard path. For CDMA protocols, the difference from
dB, so if the unloaded signal is - 15dBm, then the
ward Gain should be set to 5- (- 7)
nloaded to loaded is
nnels,
n the LPA can be over- powered causing a Loss
level. For example, if the fully loaded CDMA carrier is - 25dBm, then
ed (CDMA peak to average is typically 10- 12 dB). If
matic Level Control (ALC) w ill occur
ffSet the
value to achieve the required gain from the input to
the Remote to the output of the Host DART. The range is:
•
to
for Cellular, SMR800, SMR900, Narrowband PCS & Narrowband
for Fullband GSM1800, UMTS, Fullband AWS, and EGSM900
Configure the Host DARTs
DART Reverse Gain
DART Reverse Gain
DART
Reverse Gain
Apply
Close
When setting the
observed:
nThe
nIf you want to match the URH noise floor to the BTS noise floor, then the
nSimulcast changes the actual REV gain level by 20log(n) where n = the
nDual PCS uplink splitting causes a 3 dB degradation in the noise figure.
266 Click
setting can be used to overcome losses from the Host
value, the following rules must be
DART to the BTS. If you want unity reverse path gain and the losses to the
BTS are 20 dB, then the Reverse Gain should be set to 20 dB.
noise floors for both the URH and the BTS must be known. Use the
to match these to optimize the reverse path. For example, if the
BTS has a noise floor of -114 dBm/30 kHz and the URH has a single Remote
noise floor of -124 dBm/30kHz, and there is 2 dB of loss from the Host
DART to the BTS, then the Reverse path gain should be set to 12 dB.
number of simulcast links. For example, if REV gain is set to 10dB in a 2:1
simulcast configuration, the actual REV gain is only 4dB (10dB - 6dB). If REV
gain is set to 20dB in a 4:1 simulcast, the actual gain is 8dB (20dB - 12dB).
The Noise Floor of the URH goes up of 10*log10(n), where n = simulcast #.
For example, the single node Remote noise floor is -124 dBm/30kHz
(Before any Reverse path gain), then the noise floor for two remotes is -121
dBm, for 4 remotes it is -118 dBm/30kHz and for 8 remotes it is -115 dBm.
A Remote becomes known to the EMS when an optical fiber is connected from the
Host to the Remote and IP has been enabled as described in “Provision the Host SeRF
Optical Ports” on page 151. The Remote appears as
the EMS Function Explorer Tree of functions and can be renamed using the following
procedure.
in the
Remotes are assigned a number from
through 8 that correspond to the physical SFP
port assignment on the Host. For example, SFP port 3 is
277 In the Function Explorer Tree, select
number and
indicates the Remote number that corresponds to a Host SFP port
n is the Remote name).
Remote name until it is user-defined.
The
shown in the
view opens in the EMS View Frame. (For information on the alarms
view, see “Monitoring a Remote Unit” on page 240.)
box, enter a name for the Remote. The Remote Name must be
between 5 and 40 characters with no spaces. The only special character allowed is
an underscore, but it cannot be the first character of the name. Numerals are
allowed, but cannot be the first character of the name.
299 Click
The new
view.
.
is shown in the in the Function Explorer Tree and the
indicates the Remote number that corresponds to a Host SFP
n is the Remote name).
The Optical Ports view for the selected Remote opens in the EMS View Frame.
For information on the optical port indicators, see “Viewing Remote SeRF Optical Ports”
on page 248.
311 In the
box, enter a label for the port that is between 5 and 32
characters with no spaces. The only special character allowed is an underscore,
but it cannot be the first character of the name. Numerals are allowed, but cannot
be the first character of the name.
The Ip Enable field is not selectable for Remotes as it is configured at the Host SeRF
SFPs. Its incl
information on Ip Enable alarms,
322 Click
usion in this view is to indicate which Remote SFP has IP on it. For
see “Viewing Host SeRF Optical Ports” on page 224.
If you are setting up a multi- host sys tem, go to “(Optional) Configuring Multi-Host
Systems for Manual Mode” on page 168.
“Linking” establishes an association in software between a particular Host DART and
a particular Remote DART, enabling the two DARTs to act as an operational unit in
providing one RF band. There are four pre-requisites to this procedure:
••The Host DART and Remote DART must be connected through the optical fiber
and be communicating with each other.
•• The Host DART card must be configured as described in “Configure the Host
DARTs” on page 152.
••The Host and Remote DARTs must be of the same type (such as, Cellular or PCS).
••There must be a sufficient number of fiber timeslots available in order to
accommodate the requested passband (for example, PCS A band requires 3
timeslots).
In the Remote DART configuration page, all Host DARTs are listed that have the same
band as the Remote DART. A link is established by selecting a Host DART to be paired
with the Remote DART.
6.9.1Use of Multi Fibers
The EMS provides the ability to install “multi fibers” between a Host and Remote. This
means that, in addition to the minimum two fibers (RX and TX) in the Host to Remote
connection, one or more additional fiber pairs are installed. This is done to increase
the bandwidth between the Host and Remote. Each fiber pair can handle
approximately 75 Mbps of RF bandwidth.
Each fiber is capable of supporting 12 TDM timeslots:
••Classic DARTs or Single SuperDARTs support up to 35 MHz of RF
When a Host DART is linked to a Remote DART in a multi-fibers configuration, the
EMS uses the first fiber (in numerical order) on which the required number of
timeslots is available for the passband being linked. The EMS will not divide up the
timeslots between two fibers. So, for example, if the passband requires eight
timeslots, and only six timeslots are available on the first fiber, the EMS will bypass
the first fiber and assign all eight timeslots to the second fiber, leaving four timeslots
unused on the second fiber.
6.9.2RF Groups in the Remote and the EMS GUI
The EMS
(whereN equals A,B,C, or D). Each rectangle represents one RF Module
view displays up to four rectangles labeled
in the Remote. Figure 6-1 shows how the FlexWave EMS maps the RF Modules in the
GUI to the physical modules and antennas.
Remote
RF Module
shelf labels
MOD D
MOD C
MOD B
EMS
RF Module
labels
MOD A
Figure 6-1. Matching Remote RF Modules to EMS Group Labels
Figure 6-2 shows the
RF Module, the slot is shown with a white indicator.
—Slot number of slot occupied by the Host DART card. The Host
table has the following columns:
has eight slots numbered from 1 to 8, read from top to bottom. If the Host
DART is a 12-Timeslot DART, then only the first of the two slots it occupies
will be shown (for example, if the Host 12-Timeslot DART occupies slots 1 and
3, only slot 1 will be shown).
•
—Port number of physical optical port where Host-Remote
optical fiber is connected on the Host.
•
—Frequency band of the Host DART. This field is not
configurable and reports the DART type (such as, cellular, pcs, and so forth).
•
•
—Passband assigned to the specified Host DART.
—System ent e red s tatu s of H o st D A RT ca rd. T h is w i ll be a cti v e,
standby, or not in service
•
—Number (1-8) indicating the physical location where this
DART card is mounted in the Remote; see “RF Groups in the Remote and the
EMS GUI” on page 160) for an explanation of how the Remote DARTs are
numbered.
•
the DARTs.
—Shows the available Remote SFPs that can be used to link
is shown in this example, so the Remote has fibers connected to
this Host using Remote SFP 1. If there are two or more sets of SFPs connected
between the same Host DART and Remote DART, this field will contain a value
such as
or
where each one-digit number represents one Remote
optical port where an SFP is connected for this Host/Remote pair. Each set of
one Host SFP and one Remote SFP supports two optical fibers (RX and TX), each
with a capacity of 12 TDM timeslots
•
or
be
•
—System entered status of Remote DART card, which can
button—used to clean out settings and information for
hardware that has been removed.
•
button—When clicked, causes the LPA to reset as described in
“Restarting an LPA” on page 236.
366 To link the Host DART to the Remote DART for this pass band, click in the radio
. The following example shows the completed link (in this case,
has been selected).
If multi fibers are connected betw een the Host and Remote, the sy stem will try the fibers
in numerica
fiber is available prov
error message is returned indicating
host.”
If adding a link to an existing simulcast con
same timeslots. If the timeslots aren't av ailable, the sy
message: “DART linking failed due to a problem on the host.”
388 Set the
As soon as you set the LPA Operating Mode to normal, RF transmission will start. Before
you set the L
connected and the sy stem is ready to
antenna, see
l sequence until a link can be established for the identified passband. If no
iding the number of TDM timeslots required for the passband, an
that “ DART linking failed due to a problem on the
nection, the system requires the use of the
stem returns the follow ing error
PA Operating Mode to normal, make sure that the antenna has been
attenuation, that will be applied to the RF forward path signal (where
=
, and so forth) The DART Forward Gain is based on the EIRP desired
list, select the dB (0 to 31), which is the actual gain, not
=
at the antenna. You therefore need to know how much cable, insertion, and any
other loss (such as splitters) exist between the Remote and the antenna. Set the
to achieve the required output power level to meet the EIRP of
your RF link budget.
The following table provides calculations you need to set the gains to achieve the
desired Output power for a single-DART configuration.
Expected Output
20W
DART
(in dBm)
6.5W
DART
DART
Input
Level
-2531314338
-25310127
+6031 4338
+600127
Host
DART
Fw d Gain
Remote
DART
Fw d Gain
For dual-DART configurations, you need to reduce each path by 3dB at the Remote
. For example, for a DART Input Level of -25dBm, the Host FWD
Gain setting would be 31dB and the Remote FWD Gain setting would be 28dB.
box, set in microseconds the actual delay that will be
applied to the RF forward path signal. The minimum delay required is calculated.
The acceptable range of delays is 88us. If you attempt to set the delay to a value
outside the allowed range, the DART uses either the minimum or maximum,
dependant on whether the DART is exceeding the set delay (too high or low).
Be aware of simulcast links. Observe the minimum delay required for the longest
link, and set the delay to the same value for all simulcast nodes in the same
connection based on this value.
Here is an example:
••Fiber has 8 usec per mile of fiber.
••Remote 1 has 5 miles of fiber (40 usec of fiber delay).
••Remote 2 has 10 miles of fiber (80 usec of fiber delay).
••Remotes are set to Cellular A"/A Band which has 8 usec of system delay. The
delay ranges will therefore be:
–Remote 1 delay (48-136)
–Remote 2 delay (88-176)
The system calculates these delay values—this is a typical example based on the fiber
lengths provided. You select a delay value that’s within the range calculated by the
system.
Set the delays to the same values for all nodes in the network in order to:
••Optimize simulcast
••Make BTS datafill changes simple (same delay offsets for all nodes)
••Simplify E-911 integration (same delay offsets for all nodes)
Delays cannot be shortened; they can only be lengthened. The recommended
approach is to normalize all Remotes to the longer minimum delay. In this
example the delay would therefore have to be 88 usec.
411 In the
box, set in microseconds the actual delay that will be
applied to the RF reverse path signal. The actual delay of the RF path will be within
1 usec. For E-911 TDOA applications, the reverse path delay must be measured to
achieve the +/- 50 nsec delay accuracy specified for DAS networks. The FWD and
REV delay values are usually the same because the fiber path between the two is
typically the same.
6.11(OPTIONAL) CONFIGURING MULTI-HOST SYSTEMS
MANUAL MODE
FOR
You can only switch between the Automated and Manual modes when there are no active
links in the syst
Linking Mode list are disable
in the Linking Mode list.
When the Prism system is set to Automated linking mode, you establish a link in the
(see “Link a Remote DART to a Host DART” on page 162). The link is then
established on both the Host and Remote ends, using the fiber and the timeslots that
are automatically selected by the FlexWave EMS. The Remote DART also automatically
adopts the Host DART's pass band and diversity setting.
Multi-Host systems must be set to Manual linking mode so each side of the link (Host
and Remote) can be established independently. The Network Administrator must also
manually specify the fiber, timeslots, pass band, and diversity status for each end.
There is no system crosscheck to validate the selections—so the setup described in
this section should be performed only by an administrator who is very familiar with
the concepts involved.
em. Once a link is established the mode is locked and selections in the
d. All active links must be unlinked to enable the selections
window by selecting the Host DART to link to and then clicking
6.11.1Set the Multi-Host System to Manual Mode
11In the Function Explorer Tree, select
the
status indicators in the
view in the EMS View Frame. (For information on the read-only
page 214.)
22In the
33Click
.
list, select
view, see “Viewing the Host Summary” on
.
6.11.2Configure the Host DARTs
44In the Function Explorer Tree, select
the Host name) to open the
The
view displays all the Host DARTS that are present,
starting from slot 1 at the top of the list and working sequentially down to last
DART, which can be slots 1-8.
window shows how many SFPs have been discovered that are available for
linking—their corresponding timeslots are blank.
aaIn the
box, enter a name for the DART between 5 and 32 characters
with no spaces. The only special character allowed is an underscore, but it
cannot be the first character of the name. Numerals are allowed, but cannot be
the first character of the name.
bbIn the
list, select the DART Pass Band to be
supported by this DART. The list will include only those pass bands that are
valid selections for the DART band. For example, if the DART band is
“cellular,” only cell pass bands are listed.
ccIn the
list, select the SFP ID for the fiber to be used to communicate
with the Remote for the DART's RF. Only the IDs of fiber with enough available
contiguous timeslots for the selected passband will be available in the
list. The table in the lower part of the screen shows which fibers are available
and which timeslots on the fibers are in use. Be careful to select a fiber to the
Remote to which you want to link.
ddIn the
list displays the range of timeslots that can be used—only unused
list, select the timeslots on the fiber that will carry the RF. The
timeslots will be available for selection. If the DART is already linked to a
Remote, the
list comprises the timeslots being used for that previous
link. If you are linking to more than one Remote, the same timeslots must be
used on all fibers for this DART.
(Optional) Configuring Multi-Host Systems for Manual Mode
DART Operating Mode
Standby
Normal
Undefined
DART Diversity Status
nonDiversity
diversity
nonDiversity
Diversity
DART Diversity Status
nonDiversity
DART Forward Gain
-25
+5 dBm
eeIn the
•
—forces the RF function to be muted in the Host and its linked
list, select one of the following:
Remote.
•
—allows the system to operate normally (RF function not forced to
be muted), assuming all other system components are in proper working
order. (Default setting.)
The mode
is not user selectable, and indicates that the EMS is
unaware of the current mode.
ffIn the
list, select
application, one DART will be configured
FWD/REV path signal and the other DART will be configured
or
. For a diversity
for the primary
. This
selection therefore determines whether the DART card being configured will
carry the primary or secondary RF path.
For dual DART configurations, such as dual-pcs, smr800/smr900 and
dual-aws, both DARTs must have
The diversity status of the Host DART will not extend to the Remote DART connected to
it. You must ex
the Host DART .
ggIn the
plicitly configure the Remote DART to hav e the same diversity status as
list, set this value (0 to 31 dB) based upon the fully
set to
.
loaded forward path signal level from the Base Station. The Host DART expects
signal levels from
to
. If the fully loaded signal is +5 dBm, then the
DART forward gain should be set to 0 dB, if the fully loaded signal is -25 dBm,
then the DART Forward Gain should be set to 30 dB. The equation is:
DART Forward Gain = 5 - fullyLoadedBasestationSignal.
If you are setting up the system when no calls are going through, you must allow
headroom for a fully
unloaded to fully loaded is typically 8
fully loaded input would be - 7 dBm and the Host For
= 12 dB.
The same rules applies for GSM carriers, except that the u
determined by the equation 10*log10(# RF Channels). So if there are 4 GSM RF Cha
then the loaded forward path is 6 dB above unloaded.
If sufficient headroom is not present, the
Of Service.
When configured correctly , the Host DART Forward input can handle peaks of 14dB
above the BTS signal
peaks up to - 11 dBm can be handl
the peaks exceed the 14 dB of headroom, then Auto
to prevent over- driving the A/D Conv erter.
loaded forw ard path. For CDMA protocols, the difference from
dB, so if the unloaded signal is - 15dBm, then the
ward Gain should be set to 5- (- 7)
nloaded to loaded is
nnels,
n the LPA can be over- powered causing a Loss
level. For example, if the fully loaded CDMA carrier is - 25dBm, then
ed (CDMA peak to average is typically 10- 12 dB). If
(Optional) Configuring Multi-Host Systems for Manual Mode
Close
System View,Remotes,Remote#-x,SERF,RF
Groups
Remote#
Alarm Summary of RF Groups
config
Configuration Details
Configuration Details of DART n on Remote
DART
Attributes
Configuration and Alarm Details of DART n
DART Name
DART Pass Band (Timeslots)
New Link
Timeslots
Timeslots
DART Operating Mode
Standby
Normal
Undefined
DART Diversity Status
nonDiversity
diversity
nonDiversity
88Click
To unlink a Host DART from a Remote, click on the checkbox in the fiber timeslot table
for the Remote
.
being unlinked, and then click Apply.
6.11.3Configure the Remote DARTs
99Login to the web server on the Host that is managing the Remote (that is, the Host
has IP enabled to the remote). This may be the Host you are currently logged into
or could be a different Host in the Multi-Host group.
100 In the Function Explorer Tree, select
(where
SFP port number and
indicates the Remote number that corresponds to a Host
n is the Remote name) to open the
view (see Figure 6-2 on page 161).
111 In the rectangle for the RF group selected, click on the
being linked to open a
selected link.
122 In the
. The table at the bottom of the
window shows how many SFPs have been discovered that are available for
linking—their corresponding timeslots are blank.
link for the band
window that corresponds to the
N window that opens, set the
aaIn the
box, enter a name for the DART between 5 and 32 characters
with no spaces. The only special character allowed is an underscore, but it
cannot be the first character of the name. Numerals are allowed, but cannot be
the first character of the name.
bbIn the
list, select the DART Pass Band to be
supported by this DART. The list will include only those pass bands that are
valid selections for the DART band. For example, if the DART band is
“cellular,” only cell pass bands are listed.
ccIn the
ddIn the
linked, the
list, select the SFP that you want to link.
list, select the timeslot for the SFP. If the DART is already
list is read-only and displays the range of timeslots
occupied by the DART.
eeIn the
•
—forces the RF function to be muted in the Host and its linked
list, select one of the following:
Remote.
•
—allows the system to operate normally (RF function not forced to
be muted), assuming all other system components are in proper working
order. (Default setting.)
The mode
is not user selectable, and indicates that the EMS is
FWD/REV path signal and the other DART will be configured
. This
selection therefore determines whether the DART card being configured will
carry the primary or secondary RF path.
For dual DART configurations, such as dual-pcs, smr800/smr900 and
dual-aws, both DARTs must have
The diversity status, fiber, and timeslots of the Host DART must match the R emote
DART linked to it.
ggIn the
list, set this value (0 to 31 dB) based upon the fully
set to
.
loaded forward path signal level from the Base Station. The Host DART expects
signal levels from
to
. If the fully loaded signal is +5 dBm, then the
DART forward gain should be set to 0 dB, if the fully loaded signal is -25 dBm,
then the DART Forward Gain should be set to 30 dB. The equation is:
DART Forward Gain = 5 - fullyLoadedBasestationSignal.
If you are setting up the system when no calls are going through, you must allow
headroom for a fully
unloaded to fully loaded is typically 8
fully loaded input would be - 7 dBm and the Host For
= 12 dB.
The same rules applies for GSM carriers, except that the u
determined by the equation 10*log10(# RF Channels). So if there are 4 GSM RF Cha
then the loaded forward path is 6 dB above unloaded.
loaded forw ard path. For CDMA protocols, the difference from
dB, so if the unloaded signal is - 15dBm, then the
ward Gain should be set to 5- (- 7)
nloaded to loaded is
nnels,
If sufficient headroom is not present, the
Of Service.
When configured correctly , the Host DART Forward input can handle peaks of 14dB
above the BTS signal
peaks up to - 11 dBm can be handl
the peaks exceed the 14 dB of headroom, then Auto
to prevent over- driving the A/D Conv erter.
hhIn the
level. For example, if the fully loaded CDMA carrier is - 25dBm, then
ed (CDMA peak to average is typically 10- 12 dB). If
box, set in microseconds the actual delay that will be
n the LPA can be over- powered causing a Loss
matic Level Control (ALC) w ill occur
applied to the RF forward path signal. The minimum delay required is
calculated. The acceptable range of delays is 88us. If you attempt to set the
delay to a value outside the allowed range, the DART uses either the minimum
or maximum, dependant on whether the DART is exceeding the set delay (too
high or low).
Be aware of simulcast links. Observe the minimum delay required for the
longest link, and set the delay to the same value for all simulcast nodes in the
same connection based on this value.
Here is an example:
••Fiber has 8 usec per mile of fiber.
••Remote 1 has 5 miles of fiber (40 usec of fiber delay).
••Remote 2 has 10 miles of fiber (80 usec of fiber delay).
(Optional) Configuring Multi-Host Systems for Manual Mode
DART Reverse Delay
Apply
••Remotes are set to Cellular A"/A Band which has 8 usec of system delay.
The delay ranges will therefore be:
–Remote 1 delay (48-136)
–Remote 2 delay (88-176)
The system calculates these delay values—this is a typical example based
on the fiber lengths provided. You select a delay value that’s within the
range calculated by the system.
Set the delays to the same values for all nodes in the network in order to:
••Optimize simulcast
••Make BTS datafill changes simple (same delay offsets for all nodes)
••Simplify E-911 integration (same delay offsets for all nodes)
Delays cannot be shortened; they can only be lengthened. The
recommended approach is to normalize all Remotes to the longer
minimum delay. In this example the delay would therefore have to be 88
usec.
iiIn the
box, set in microseconds the actual delay that will be
applied to the RF reverse path signal. The actual delay of the RF path will be
within 1 usec. For E-911 TDOA applications, the reverse path delay must be
measured to achieve the +/- 50 nsec delay accuracy specified for DAS
networks. The FWD and REV delay values are usually the same because the
fiber path between the two is typically the same.
In the Function Explorer Tree, click on
labeled as the
The
provides a top-level view of the Prism system, which identifies the
, in the EMS View Frame.
to open the system view, which is
Host and all Remotes known to the EMS by their IP addresses and provides a
summary alarm status indicator for each unit.
•
—name entered by user or
if no name has been
entered. Current summary alarm state of Host is indicated by status indicator in
same row.
•
indicator—indicates if the state of the unit:
–Green indicates a Normal state
–Yellow indicates that a Minor alarm is active, and is the highest-level active
alarm
–Red indicates that a Major alarm is active.
•
—name entered by user or
if no name has
been entered. Summary alarm state is indicated by status indicator in same row.
•
(Host/Remote)—IP Address of the Host/Remote. If logged into a Remote
that is not connected to a Host, the Host IP Address will appear as
, and the Remote IP Address will appear as
if the remote
is setup for DHCP. If a static IP address has been assigned to the Remote, the
actual IP address for the Remote will display when the Host is not connected.
Only a user logged in under the admin or a Netw ork Manager account can change Prism
settings through
Auto Refresh is intended for use after the Prism system has been configured during
initial setup and you want to monitor system performance without having to trigger
manual page refreshes.
Do not set Auto Refresh until after the initial Prism system setup described in “Initial
Prism System Setup” on page 143. If you apply Auto
You use the EMS to configure the Prism system for one of the two different modes
listed below, which affects how you configure the network interface of the Network
and Craft ports and how you access the system through the EMS. In each mode, the
Host and its subtended Remotes require the same configuration. Both modes require
a DHCP server, which assigns an IP address to the Host and its subtended Remotes.
•
mode—is the default mode. The Host and subtended Remotes are
DHCP clients and expect IP addresses to be assigned by an external DHCP server
through a network Ethernet connector. If there is no external DHCP server, the
Host will not be able to communicate with any connected Remotes.
The Host Craft port has a DHCP server that you can use to communicate with the
Host directly. The IP address for the Host Craft port is 192.168.0.1. You can access
the EMS via the Craft port, but if the Network port is not connected to an external
DHCP server, the Remotes will not be visible to you.
•
mode—
mode is best suited for when there is no
network to connect to or if the Prism network does not have a DHCP server. In
Built-In Network mode, the functionality of the Network port and the Craft port
are swapped. You connect a laptop to the Host Network port, which is assigned a
default fixed IP address of 10.0.0.1 and all subtended network interfaces obtain a
DHCP address in this same subnet. Alternatively, in Built-In Network mode you
can connect the Craft port to an external DHCP server from which the Craft port
obtains its IP address.
Static Mode—You also hav e the option of giving the devices on your Prism system static
IP addresses.
There are potential problems in switching between the External Network and Built- In
Network modes. If
addresses on a public network. Set the
it.
Contact ADC for further information (see “Contacting ADC” on page 335).
cabled incorrectly your DHCP server could provide private IP
Prism system mode once and then do not change
Table 7-1 describes how the system mode affects the IP address for the Host and
to the Host
through the EMS,
in a Web browser
enter the IP
address
192.168.0.1
(http://192.168.0.
1)
DHCP client must
be connected to a
network with a
DHCP server to
obtain an IP
address. The IP
address can then
be used by HTTP
and SNMP to
connect to the
Host.
The Host Network
port is a DHCP
client and must be
connected to a
network with a
DHCP server to
obtain an IP
address.
For direct access
to the Host
through the EMS,
in a Web browser
enter the IP
address assigned
by the DHCP
server. For
information on
discovering the IP
address, see the
DHCP server or
connect to the EMS
using the craft
port and bring up
the System View.
The Network port
is a DHCP server
with a fixed IP
address of
10.0.0.1 and
assigns IP
addresses in the
10.0.0.x range to
subtended
Remotes.
For direct access
to the Host
through the EMS,
in a Web browser
enter the IP
address
10.0.0.1
(http://10.0.0.1)
Remote Craft port
IP address is
192.168.0.1.
However, you
cannot get direct
access to the Host
or the network
from the Remote
Craft port. You get
read-only view to
Remote
configuration.
Remote Craft port
IP address is
192.168.0.1.
However, you
cannot get direct
access to the Host
or the network
from the Remote
Craft port. You get
read-only view to
Remote
configuration.
The Remote
network port
obtains its IP
address from the
external DHCP
server.
You can reach the
Remote via telnet
or ssh from the
Host.
The Remote
Network port is a
LAN/WAN
connection to the
network to which
the Host Network
port is connected.
The Remote
Network port
therefore obtains
an IP address in
the 10.0.0.x range
from the DHCP
server in the Host.
You can reach the
Remote via telnet
or ssh from the
Host.
Only a user logged in under the admin or a Netw ork Manager account can change Prism
settings through
the EMS.
mode allows all Remotes to be assigned an IP address to allow
communication without the need for an external DHCP router. You therefore set the
Prism system to
mode if there is no network to connect to or if the
network does not have a DHCP server. You would also change the Prism system to
When changing from External Netw ork mode to Built- In Netw ork mode, if the Prism
system is cabled inco
addresses on a public network. You should t
preferably during setup.
11To open the
Tree select
mode if you intend to transition to static IP addresses.
rrectly, the Prism DHCP server could broadcast private IP
herefore only change the mode once,
view in the EMS View Frame, in the Function Explorer
, and then click on the Host name node.
22Set
to
. This sets the Network port on the Host to
the IP address 10.0.0.1 and starts a DHCP server on the Host that will provide IP
addresses to connected Remotes. Built-In Network mode also causes the Host
Craft port to run a DHCP client instead of using the IP address 192.168.0.1.
66Connect the free end of the Ethernet cable to the computer’s port. Leave your
computer in DHCP mode. It will automatically receive an IP address in the
10.0.0.0/24 subnet from the Host Network port.
It can take a while for the system to update the interfaces (can be up to 30 minutes, but
typically i
from an external network an
30 minutes for the Remote to request
10.0.0.x IP address. During this transient period, ther
the Remotes.
s no more than 10 minutes). If the Remotes already have a DHCP IP address
d you change it to built- in (in a different subnet), it can take
an update from an external IP address to the
e w ill not be communication with
The Host will also take awhile to change from an externa
address, so a period of no communication with the Host can be expecte
l IP address to the 10.0.0.1 Ip
d as well.
77Open a Web browser and in its URL field, enter the Host IP address: 10.0.0.1
88When the
aaEnter the
dialog opens:
provided by ADC or by the Network Administrator. The
default is admin.
bbEnter the
provided by ADC or by the Network Administrator. The
default is adc123.
99Click
. The
page opens.
7.4.2EMS Access Methods
The FlexWave EMS has four access methods that are listed below and as shown and
numbered in Figure 7-3.
11A laptop subtended to the Craft port on the Host provides direct access to the
EMS. In this scenario the Host and the Remote can be configured and monitored
through the EMS. This is the default access scenario during initial configuration
and commissioning as described in “Access the EMS” on page 144.
22A personal computer with a Web browser connected through the internet or
intranet to the Network port on the Host. This method provides a remote user
access to the EMS through a Local Area Network (LAN) or Wide Area Network
(WAN). In this scenario the Host and subtended Remotes can be configured and
monitored through the EMS. After initial system setup, this is the default access
method.
EMS Access Methods 1 and 2 are true for the default External Network mode described
in this chapter.
definitions for EMS Access Methods 1 a
are sw itched.
If your Prism system is set to Built- in Netw ork mode, then the
nd 2 for the Host Netw ork and Craft ports are
33A personal computer with a Web browser connected to the Network port on the
Remote provides a remote user a LAN connection to the Host network interface,
which provides access to the EMS. See “Accessing the EMS Through the Remote
44A laptop subtended to the Remote Craft port provides access to the EMS. In this
scenario, Remote configuration interfaces can be viewed in Read-Only format. The
Host configuration interfaces are disabled and cannot be viewed. See “Accessing
the EMS Through the Remote Craft Port” on page 192.
2
Network
(LAN or WAN)
1
IP
Craft portNetwork port
Host Unit
with EMS
IP
IP
IP
3
Network port
Remote
Unit
Craft port
4
75356-04
Figure 7-3. Four Points of EMS Access
7.4.2.1Accessing the EMS Through the Remote Network Port
The Remote provides a Network port allowing communications with the internal
processor and transfer of service data to the optical protocol allowing IP servicing
between the Host and Remote(s). This port is customer accessible for monitoring the
interface with the subtended Host and ENET subtended devices at the Remote. The
Network port is 10/100/1000 BASE-T MDI and requires a minimum of CAT 5 cable.
Although the Netw ork port on the Remote is a GigE port, the available bandw idth is only
100Mbps (part
You cannot dedicate a full 100Mbps of band
Remote’s Network port. For example, if connecting a WiFi
Network port, you need to reduce the available bandwidth to less than 1
of this bandw idth is used for system management serv ices).
width for external ethernet services off the
access point to the Remote’s
00Mbps (such
as, 50Mbps).
The network cable must be terminated with a hardened RJ-45 male connector for
connection to the Network port. The maximum cable length is 300 feet (91.4 m).
Use the following procedure to install the Network cable and then log in to the EMS.
11Remove the dust cap from the RJ-45 connector located at the bottom of the
Remote as shown below.
NETWORK
RJ-45 Network
Connector port
RJ-45 plug
Connector nut
POWER
100-240 VAC
50-60 Hz
16 AMPS
MOD D
RX1
MOD D
TX0/RX0
MOD C
RX1
AUX.
MOD C
TX0/RX0
MOD A
RX1
MOD B
RX1
MOD A
TX0/RX0
MOD B
TX0/RX0
FIBER 1
FIBER 2
Network cable
77073-010
Bottom View
22Route the network cable from the network connection to the underside of the
Remote.
33Align the plug end of the RJ-45 cable connector with the RJ-45 port receptacle and
then insert the cable plug into the port receptacle.
44Slide the connector nut up to the port until it engages the connector locking
mechanism.
55Tighten the connector nut in a clockwise direction (if necessary, use a wrench or
pliers to grip the connector nut) until it snaps past the indented position and
locks into place. It may be necessary to apply 30 to 50 in-lbs (3.4 to 5.6 Nm) of
torque to the connector nut in order to turn it past the indented position.
It may be necessary to apply 30 to 50 lbs/ force- inches (3.4 to 5.6 Nm) of torque to the
connector nut
7.4.2.2Accessing the EMS Through the Remote Craft Port
You can use the Craft port on the SeRF Module to access the FlexWave EMS to view
system configuration and alarms. For example, if there is a problem communicating
with the Remote and you have determined that fiber is not the issue, connecting to
the Craft port helps you obtain beneficial troubleshooting information.
When you access the E MS through the Remote Craft port, the EMS GUI shows only the
Remote in its Funct
clear alarms.
11Verify that your PC network interface is configured for DHCP.
22If you have a wireless network interface, disable it. Otherwise an IP conflict may
result if the wireless network resides in the same IP subnet as the Craft port.
33Open the Prism door.
44Remove the dust cap from the Craft port located on the SeRF Module.
ion Explorer Tree. You cannot configure any system components or