ADC PRSM070A, PRSM084A, PRSM074C, PRSMAW4A, PRSM070C User Manual

...
9
MANAGING HOST UNITS
Content Page
9.1 Viewing the Host Summary................................................................................214
9.2 Resetting the Host Unit .....................................................................................215
9.3 Viewing Host SeRF Ethernet Ports.......................................................................217
9.4 Decommissioning a DART in a Host.....................................................................220
9.6 Viewing Host SeRF Optical Ports.........................................................................224
9.7 Viewing Host DART Alarms ................................................................................226
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 213 ADCP-77-073 • Issue 211/2009 ©2009 ADC Telecommunications, Inc.
Managing Host Units
Host Summary
System View
SERF
DART
Host Major Contact Alarm Output
Host Minor Contact Alarm Output
Remote Major Contact Alarm Output—
Remote Minor Contact Alarm Output—
9.1 VIEWING THE HOST SUMMARY
This section describes the read-only status indicators in the Host Summary view. For information on setting Host attributes, see “Enter a Host Name, Clock Source, and
Linking Mode” on page 147 and “Changing to Built-In Network Mode” on page 186.
To open the select
, and then click on the Host name node.
view in the EMS View Frame, in the Function Explorer Tree
The read-only status indicators are:
—Current summary alarm state of Host SeRF card. Red indicates that a major alarm exists for some component module of the SeRF. Yellow indicates a minor alarm.
—Current summary alarm state is indicated by status indicator on same row of page. Red indicates that a major alarm exists for the DART. Yellow indicates a minor alarm.
—Dry alarm NO/NC contact (labeled ALARM OUTPUTS HOST) on the Host. Current state of major alarm contacts is indicated by Alarm Summary status indicator on same row of page.
—Dry alarm NO/NC contact (labeled ALARM OUTPUTS HOST) on the Host. Current state of minor alarm contacts is indicated by Alarm Summary status indicator on same row of page.
Red indicates Host NO/NC major alarm contacts are in an alarm position. These connections are typically wired to a local alarm alert system. This status indicator is red when a major alarm is present on any Remote connected to the Host.
Red indicates that Host NO/NC minor alarm contacts are in an alarm position. These connections are typically wired to a local alarm alert system. This status indicator is red when a minor alarm is present on any Remote connected to Host.
Page 214 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
Resetting the Host Unit
System View
Host Summary
Reset Unit
9.2 RESETTING THE HOST UNIT
Only a user logged in under the admin or a Network Manager account can change Prism system settings t
Resetting the Host Unit results in a Loss of Service condition for the Host and connected Remotes unt take 5 to 20 minutes for man
hrough the EMS.
il the Host comes back up. Depending on the system configuration, it can
agement communication to be restored.
11 In the Function Explorer Tree, select
node to open the
22 Click
.
view in the EMS View Frame.
, and then click on the Host name
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 215 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
Managing Host Units
Host Summary
33 In the confirmation dialog, click OK.
Once you click OK, the confirmation dialog closes and the Host reboots. It will take some time for the Host to retrieve data from connected Remotes and to reconfigure data on the Remotes. During this time, an alert message displays in the
view and on any other page where data can be set. Any attempt to SET will fail. You cannot make configuration changes while this message is displayed. Wait until the message clears before continuing with configuration settings.
Page 216 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
Viewing Host SeRF Ethernet Ports
ENET Configurations
System View,Host-x,SERF,ENET
-
ENET Configurations
9.3 VIEWING HOST SERF ETHERNET PORTS
The Host
view is a summary of throughput and number of errors on the twelve Ethernet (ENET) ports on the Host SeRF card. These ports consist of eight ports used for connection to Remotes and four ports used for system management and maintenance functions.
11 In the Function Explorer Tree, select
Host name) to open the
view in the EMS View Frame.
(where
x is the
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 217 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
Managing Host Units
ENET Configurations
Refresh
ENET Configurations
Switch Port
Craft Port
OptEnetPort1-8
Network Port
Management Port
Rx Bytes
Rx Pkts
Rx FSC Errors
22 (Optional) To enlarge the view, click Full Screen to open a separate window that
shows only the
table.
33 To update the counters, click
The
view lists the Ethernet ports and their corresponding
.
status.
The row headers in the first column are as follows:
—on card processor's connection to the switch on the SeRF card
—on card processor's connection to the PHY port labeled Craft
—Ethernet switch interface to SFP 1-8
—Ethernet switch interface to on-card processor
—switch interface to the PHY port labeled Network
The column headers, from left to right, are as follows:
—Receive byte counter. Increments by the byte count of frames received, including those in bad packets, excluding preamble and SFD but including FCS bytes
—Receive packet counter. Increments for each frame received packet (including bad packets, all unicast, broadcast, and multicast packets)
—Receive FCS error counter. Increments for each frame received that has an integral 64 to 1518 length and contains a frame check sequence error
Page 218 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
Viewing Host SeRF Ethernet Ports
Rx BroadCast Pkts
Rx MultiCast Pkts
Rx Fragmented Frames
Rx Jabber Frames
Tx Byte Counter
Tx Pkt Counter
Tx BroadCast Pkts.
Tx MultiCast Pkts.
—Receive broadcast packet counter. Increments for each broadcast good frame of lengths 64 to 1518 (non VLAN) or 1522 (VLAN), excluding multicast frames. Does not include range/length errors
—Receive multicast packet counter. Increments for each multicast good frame of lengths 64 to 1518 (non VLAN) or 1522 (VLAN), excluding broadcast frames. This count does not include range/length errors
—Receive fragments counter. Increments for each frame received that is less than 64 bytes and contains an invalid FCS. This includes integral and non-integral lengths
—Receive jabber counter. Increments for frames received that exceed 1518 (non VLAN) or 1522 (VLAN) bytes and contain an invalid FCS. This includes alignment errors
—Transmit byte counter. Increments by the number of bytes that were put on the wire including fragments of frames that were involved with collisions. This count does not include preamble/SFD or jam bytes. This counter does not count if the frame is truncated
—Transmit packet counter. Increments for each transmitted packet (including bad packets, excessive deferred packets, excessive collision packets, late collision packets, all unicast, broadcast, and multicast packets)
—Transmit broadcast packet counter. Increments for
each broadcast frame transmitted (excluding multicast frames)
—Transmit multicast packet counter. Increments for each
multicast valid frame transmitted (excluding broadcast frames)
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 219 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
Managing Host Units
Decommission
Decommission
System View,Host-x,SERF,DARTS
-
DART’s Alarm Summary
9.4 DECOMMISSIONING A DART IN A HOST
Only a user logged in under the admin or a Network Manager account can change Prism system settings t
This procedure is for decommissioning a DART in a Host. For information on decommissioning a DART in
on page 232.
hrough the EMS.
a Remote, see “Decommissioning an RF Module in a Remote”
The removed. You use the
button is available only when a DART has already been physically
button to remove DART configuration settings and to delete DART alarms from EMS alarm summaries. Entries in the Alarm History Log, however, are preserved.
Decommission a DART only if it has been permanently removed from the Remote and will not be replaced procedure removes information about the inventory) from the EMS database.
You must delete any RF links before you can decommission a Host DART. The FlexWave system prevents a
11 In the Function Explorer Tree, select
the Host name) to open the
with another DART. When a DART is taken out of service, this
DART (such as associated alarms, links, and
decommission if RF links are in place.
view in the EMS View Frame.
(where
x is
Page 220 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
Decommissioning a DART in a Host
Information
Band-Config
Configuration and Alarm Details
Configuration and Alarm Details
Decommission
OK
22 In the
decommissioned. The
33 In the
column, click on the
window, click the
window opens.
link for the DART to be
button.
44 In the confirmation dialog, click
.
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 221 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
Managing Host Units
Host SERF
System View,Host-x,SERF
-
Prism on SERF of Host
Prism on SERF of Host
Optical Ports
SERF Fault
System Fan Fault
9.5 VIEWING THE HOST SERF SUMMARY
The
page provides a summary for the SeRF (Serial Radio Frequency) card located in the Host. The Host SeRF card contains the processor chip where the EMS software documented in this manual resides. The SeRF controls communication between the Host and the Remotes, and maintains the system configuration settings.
In the Function Explorer Tree, select name) to open the
-n view in the EMS View Frame.
(where
x is the Host
The
—alarm status indicator for Host optical ports. Red indicates that an
-n view has the following elements:
alarm exists for at least one of the eight optical ports on the SeRF card. Yellow indicates a minor alarm.
—state of the SeRF. Red indicates that either the SeRF clock source is
unacceptable or the SeRF card FPGA is not programmed.
—state of the Host chassis fan. Red indicates that the Host chassis
fan is spinning too slowly.
Page 222 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
Viewing the Host SeRF Summary
Over Temperature Fault
90° C
Primary Clock Priority Fault
Primary Clock Priority Fault
Under Temperature Fault
-40° C
Secondary Clock Priority Fault
Secondary Clock
Priority Fault
Host Temperature Measurement
• temperature of the Host is above its operating limits. Fault threshold is
—Red indicates that the current chassis-internal
.
—Indicates that there is another Host in a Multi-Host system that has the same Clock Priority Level (CPL) as this Host. All Hosts that are in conflict generate this alarm. When all Hosts with this alarm are provisioned with unique CPLs, the alarm clears. Service is disrupted on all systems when this alarm is present. The
—Yellow indicates that the current chassis-internal
temperature of the Host is below its operating limits. Fault threshold is
—In a three-Host system, indicates that the Clock
is a Major alarm.
.
Priority Level for the Host managing the Remote has been changed. All Hosts in the system generate this alarm. When all Hosts with this alarm are provisioned with unique CPLs, the alarm clears. Service is not disrupted, but could become disrupted if the host providing the clock becomes unavailable. The
is a Minor alarm.
—Gives the current chassis-internal temperature in
degrees Centigrade detected by the Host.
For corrective actions for alarm states, refer to “Troubleshooting Alarms” on
page 264. For information on setting the Clock Priority Level, see “Set the Clock Priority Level” on page 150.
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 223 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
Managing Host Units
Host Optical Ports
Host Optical Ports
Host Optical Ports
Host Optical Ports
System View
Host-x,SERF,Optical Ports
-
Optical Ports
Host
Optical Ports
9.6 VIEWING HOST SERF OPTICAL PORTS
The
view shows the current usage and alarm status of the optical ports on the Host plus the current values of some key operating parameters. The Host has eight optical ports, but the
view only shows active ports (physically connected to a Remote). Each port in the page represents one set of forward and reverse paths between a Host and Remote. Physically, this may have been accomplished with two fibers through that port or with a single fiber (if WDM is used). Each physical port contains an SFP transceiver with two connectors.
The
view provides a link that can be used to enter or edit the name for a Host optical port (see “Enter a Host Name, Clock Source, and Linking Mode” on
page 147).
For corrective actions for alarm states, refer to “Troubleshooting Alarms” on
page 264.
To access the
The
view for
(where
view, in the Function Explorer Tree, select
x is the Host name).
-n opens in the EMS View Frame, which only shows the
,
Receive power level from the Remote unit (REV path). To see the Receive power level in the FWD path (from the Host to the Remote), you must open the
view for the desired Remote as described in “Viewing Remote SeRF Optical Ports” on
page 248.
Page 224 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
Viewing Host SeRF Optical Ports
Optical Ports
Optics Number
Port
Configuration Page
Optics Name
UNKNOWN_SFPName
Optics Type
LongRange
Fwd Launch
Rev Receive
Wave Length
IpEnable Fault
RxBer Fault
0.00001
RxNoLight Fault
-34dBm
Laser Fault
OverDrive Fault
-9dBm
UnderDrive Fault
-27dBm
Remote Name
The following informational columns are provided in the
—System assigned port number. This is a link to the
for this particular port.
—user entered port name or
, which indicates that
table.
no name has been entered.
—indicates that the laser range, which is
to meet 3Gbps
optical transmission requirements.
—Launch power level in dBm of forward path signal. The minimum
FWD launch power is -2 dBm, and the maximum is 3 dBm.
—Receive power level in dBm of reverse path signal, which incorporates the launch power of the Remote Unit SFP plus all optical losses (insertion losses, fiber cable loss, and so forth). The minimum REV launch power is -27 dBm, and the maximum is -9 dBm.
—Number displayed is wave length transmitted through this port:
Non-duplex and WDM configurations: 1550 nm fwd, 1310 rev
CWDM configurations can be one of eight wavelengths: 1470, 1490, 1510,
1530, 1550, 1570, 1590, 1610.
—An attempt to enable IP on a fiber (Host) to a Remote that already has IP enabled on another fiber (Host) has been made. The alarm is cleared if IP is disabled on the fiber. It is also cleared if IP becomes enabled. This latter condition can occur if the fiber that was already carrying IP later has IP disabled, or if the fiber otherwise becomes disabled. For information on setting Ip Enable, see
“Configure the Remote SeRF Optical Ports” on page 158.
—Yellow indicates that too many errors have been received on the
receiving fiber. Fault threshold is
• threshold is below
• Fault threshold is
• Fault threshold is
—Red indicates that no light is detected on the receiving fiber. Fault
—Red indicates that the forward path laser is faulty.
—Red indicates power of signal received on the fiber is too strong.
. Threshold cannot be changed.
—Yellow indicates power of signal received on fiber is too weak.
—name of the Remote connected to this Optics port.
. Threshold cannot be changed.
.
. Threshold cannot be changed.
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 225 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
Managing Host Units
Prism Host DART’s Alarm Summary
System View,Host-x,SERF,DARTS
-
Host DART’s Alarm Summary
Information
Band-Config
Configuration and Alarm Details of DARTnon Host-
DART
Band-Config
2
9.7 VIEWING HOST DART ALARMS
A Host may support up to eight DART cards. Each DART card provides one RF band for up to eight Remotes. The DART card converts between serial (optical) and RF data in both forward and reverse directions. The all DART cards currently installed in the Host and provides an alarm summary status indicator for each card. This page also provides a link, for each DART card, to a more detailed page that can be used to configure the DART card and obtain alarm details (for more information, see “Configure the Host DARTs” on page 152).
view lists
11 In the Function Explorer Tree, select
the Host name) to open the Frame.
22 In the
to monitor. The (where
column, click on the
n corresponds to the DART whose
view in the EMS View
link for the DART that you want
x window opens
link you selected).
(where
x is
Page 226 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
Viewing Host DART Alarms
Configuration and Alarm Details of DARTnon Host-
DART Fault
DART Over Drive Fault
+20dBm
DART Hardware Mismatch Fault
DART Hardware Mismatch Fault
DART Hardware Mismatch Fault
DART UnderDrive Fault
Refresh
The
x window shows the following
Host DART alarms:
—Summary alarm state of the DART card. Red indicates a problem
with passing RF.
is too strong. Fault threshold is
—Red indicates that the RF signal received from the BTS
.
—Red indicates that the DART type doesn't match the assigned Pass Band. Examples: After assigning the Pass Band, if the DART is changed with another DART type, then the occurs. Or, if you swap DART types (such as, from GSM1800 to UMTS), the
is raised as the stored database has one DART
type configured, and the new hardware doesn't match it.
—Yellow indicates that the power of the signal received on the RF input to the DART is 20 dB below the optimal input level. For example:
Host Forward
DART Gain
30 dB -25 dBm -45 dBm
20 dB -15 dBm -35 dBm
10 dB -5 dBm -25 dBm
0 dB +5 dBm -15 dBm
Maximum RMS
Input Power
UnderDrive
Threshold
33 Click
to update the alarm summary. For corrective actions for alarm states,
refer to “Troubleshooting Alarms” on page 264.
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 227 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
Managing Host Units
Intentionally Blank Page
Page 228 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
10
MANAGING REMOTE UNITS
Content Page
10.1 Viewing Remote SeRF Ethernet Ports.................................................................230
10.2 Decommissioning an RF Module in a Remote ......................................................232
10.3 Configuring Dual-Slot LPAs ..............................................................................235
10.4 Restarting an LPA ...........................................................................................236
10.4.1 Identify the LPA Fault ..............................................................................236
10.4.2 Reset the LPA.........................................................................................238
10.5 Monitoring a Remote Unit ................................................................................240
10.6 Decommissioning a Remote Unit.......................................................................244
10.7 Resetting a Remote Unit..................................................................................246
10.8 Viewing Remote SeRF Alarms...........................................................................248
10.9 Viewing Remote SeRF Optical Ports...................................................................248
10.10 Viewing an Alarm Summary of the Remote RF Groups .......................................250
10.11 Viewing RF Band Alarm Details .......................................................................252
10.12 Viewing Remote GPS Alarms and Location Parameters .......................................255
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 229 ADCP-77-073 • Issue 211/2009 ©2009 ADC Telecommunications, Inc.
Managing Remote Units
ENET Configurations
System View,Remotes,SERF,ENET
ENET Configurations
Switch Port
Craft Port
OptEnetPort1-8
Network Port
Management Port
Rx Bytes
Rx Pkts
Rx FSC Errors
10.1 VIEWING REMOTE SERF ETHERNET PORTS
The Remote SERF ENET page is a summary of throughput and number of errors on the twelve Ethernet (ENET) ports on the Remote SeRF card. These ports, located on the front side of the SeRF card, consist of eight ports used for connection to Remotes and four ports used for system management and maintenance functions.
To open the Tree select
view in the EMS View Frame, in the Function Explorer
.
The
—on card processor's connection to the PHY port labeled Craft
—Receive byte counter. Increments by the byte count of frames received,
—on card processor's connection to the switch on the SeRF card
—Ethernet switch interface to on-card processor
view lists the Ethernet ports and their corresponding status.
—Ethernet switch interface to SFP 1-8
—switch interface to the PHY port labeled Network
including those in bad packets, excluding preamble and SFD but including FCS bytes
—Receive packet counter. Increments for each frame received packet
(including bad packets, all unicast, broadcast, and multicast packets)
—Receive FCS error counter. Increments for each frame received that
has an integral 64 to 1518 length and contains a frame check sequence error
Page 230 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
Viewing Remote SeRF Ethernet Ports
Rx BroadCast Pkts
Rx MultiCast Pkts
Rx Fragmented Frames
Rx Jabber Frames
Tx Byte Counter
Tx Pkt Counter
Tx BroadCast Pkts.
Tx MultiCast Pkts.
—Receive broadcast packet counter. Increments for each broadcast good frame of lengths 64 to 1518 (non VLAN) or 1522 (VLAN), excluding multicast frames. Does not include range/length errors
—Receive multicast packet counter. Increments for each multicast good frame of lengths 64 to 1518 (non VLAN) or 1522 (VLAN), excluding broadcast frames. This count does not include range/length errors
—Receive fragments counter. Increments for each frame received that is less than 64 bytes and contains an invalid FCS. This includes integral and non-integral lengths
—Receive jabber counter. Increments for frames received that exceed 1518 (non VLAN) or 1522 (VLAN) bytes and contain an invalid FCS. This includes alignment errors
—Transmit byte counter. Increments by the number of bytes that were put on the wire including fragments of frames that were involved with collisions. This count does not include preamble/SFD or jam bytes. This counter does not count if the frame is truncated
—Transmit packet counter. Increments for each transmitted packet (including bad packets, excessive deferred packets, excessive collision packets, late collision packets, all unicast, broadcast, and multicast packets)
—Transmit broadcast packet counter. Increments for each
broadcast frame transmitted (excluding multicast frames)
—Transmit multicast packet counter. Increments for each
multicast valid frame transmitted (excluding broadcast frames)
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 231 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
Managing Remote Units
Decommission
Decommission
System View,Remotes,Remote#-x,SERF,Optical
Ports
Remote#
Alarm Summary of RF Groups
10.2 DECOMMISSIONING AN RF MODULE IN A REMOTE
Only a user logged in under the admin or a Network Manager account can change Prism system settings t
Decommission a RF Module only if it has been permanently removed from the Remote and will not be repl
This procedure is for decommissioning a Remote’s RF Modules, which contain the Remote DARTS. For info
“Decommissioning a DART in a Host” on page 220.
hrough the EMS.
aced with another DART.
rmation on decommissioning a DART in a Host, see
The have already been physically removed. You use the
button is available only when a RF Module and hence the DART(s)
button when an RF Module and its DART(s) have taken out of service. This procedure removes all information about this RF Module (such as associated alarms, links, and inventory) from the EMS database. Entries in the Alarm History Log, however, are preserved.
11 In the Function Explorer Tree, select
(where
port number and
The
indicates the Remote number that corresponds to a Host SFP
n is the Remote name).
view opens in the EMS View Frame. For a description of the RF Groups, see “RF Groups in the Remote and the EMS GUI” on
page 160.
Page 232 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
Decommissioning an RF Module in a Remote
config
Configuration Details
Decommission
22 In the rectangle for the RF group selected, click on the
whose DART needs to be decommissioned.
link for the band
33 In the
window, click the
button.
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 233 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
Managing Remote Units
44 In the confirmation dialog, click OK.
Page 234 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
10.3 CONFIGURING DUAL-SLOT LPAS
Configuration Details
LPA Operating Mode
standby
normal
normal
standby
Configuring Dual-Slot LPAs
Both LPAs in a dual-slot 40W module can be controlled from the window, which allows you to set the
, enable/disable a LPA, or
reset a LPA, as shown below:
The following rules apply to the dual-slot LPA installation:
For the second LPA, the GUI displays it in an RF group by itself. There will be no
DART in the RF group. However, you will be able to view alarms and configuration for the RF group in case of dual LPA setup. For the “missing” DART, default values will display. You cannot configure the missing DARTs, but can set the LPA mode and reset the LPA.
User-initiated configuration of dual LPAs is simulataneous for both the LPAs. If
one of the LPAs is placed into
mode, both go into
, both go into standby. If one is placed into
mode.
User initiated LPA resets are simulataneous. If one LPA is reset, so is the other.
Alarm handling for the two LPAs occurs independently. If one alarms and goes
into
, the second LPA continues in its current state. Automatic alarm
recovery is also handled independently.
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 235 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
Managing Remote Units
LPA Reset
System View,Remotes,Remote#-x,RF Groups
Remote#
band
Alarm Details of DART-x of Group
on Remote#-
LPA Disable Fault
LPA Loop Fault,LPA Over Power Fault
10.4 RESTARTING AN LPA
Only a user logged in under the admin or a Network Manager account can change Prism system settings t
hrough the EMS.
You use the
button to bring an LPA back into service (restart) that stopped
because of an LPA alarm.
This section comprises a 6-step process that is broken into 2 sections that first identifies the fault and then resets the LPA.
10.4.1 Identify the LPA Fault
11 In the Function Explorer Tree, select
(where number and
indicates the Remote number that corresponds to a Host SFP port
n is the Remote name).
22 In the rectangle for the RF group selected, click on the
whose LPA needs to be reset. The window opens (where x is the DART, Group or Remote name).
link for the band
x
x
An LPA Reset is necessary when any of the alarms listed below have occurred.
—Red indicates that the Linear Power Amplifier is disabled because it encountered a problem. Check for a corresponding LPA fault listed in this section (such as
, and so forth), then correct
the LPA fault. If LPA Reset does not clear this alarm, the corresponding RF Module
Page 236 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
Restarting an LPA
LPA VSWR Fault
LPA DC Fault
LPA Loop Fault
LPA Over Power Fault
LPA Low Power Fault
may need to be replaced. Contact ADC Technical Assistance for further help (see
“Contacting ADC” on page 335).
—Red indicates an internal VSWR fault state of the LPA. Check the Remote’s antenna connection. If the connection is good and a subsequent LPA reset does not clear the alarm, inspect the blue cable going from the corresponding Remote Antenna port to the Duplexer—verify that the connection is tight. If this doesn't clear the fault, the Duplexer may need to be replaced. Notify ADC Technical Support (see “Contacting ADC” on page 335).
—Red indicates that the voltage level inside the LPA is outside its acceptable range. If the LPA Reset does not clear this alarm, contact ADC Technical Assistance for further help as the RF Module that contains the LPA or the Power supply within the SeRF Module may need to be replaced (see
“Contacting ADC” on page 335).
—Red indicates that the LPA is not sure of the feedback loop, so it has placed itself into a safe state. You can attempt to recover the LPA by reducing forward gain by 10dB on both DART cards, resetting the LPA, then restoring GAIN. If the reset does not work, contact ADC Technical Support (see “Contacting ADC”
on page 335).
—Red indicates that the power level inside the LPA is high enough to damage the LPA. Reduce the Remote Forward Gain (see “Link the Host
and Remote DARTs.” on page 159), then reset the LPA.
—Red indicates that the internal gain of the LPA does not meet specifications. In addition to an LPA Reset, try putting the LPA into standby and then back to enable to see if this clears this fault. If neither troubleshooting step clears this alarm, the corresponding RF Module may need to be replaced. contact ADC Technical Assistance for further help (see “Contacting ADC” on page 335).
LPA Missing Fault—Red indicates that the LPA is missing. This fault cannot be cleared
with an LPA Reset.
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 237 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
Managing Remote Units
System View,Remotes,Remote#-x,SERF,RF
Groups
Remote#
config
Configuration Details
LPA Reset
10.4.2 Reset the LPA
Once an LPA Reset is started, Loss of Service occurs. It take approximately 10 to 20 seconds before t depending on the number of Remotes Remotes the power reading could take sev eral minutes
he LPA signal recov ers. The GUI RF pow er reading w ill take longer
equipped—for a fully loaded Prism system with 8
to update.
33 In the Function Explorer Tree, select
(where
SFP port number and
indicates the Remote number that corresponds to a Host
n is the Remote name).
44 In the rectangle for the RF group selected, click on the
whose LPA needs to be reset.
55 In the
window, click the
button.
link for the band
Page 238 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
66 In the LPA Reset caution dialog, click OK.
Restarting an LPA
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 239 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
Managing Remote Units
System View,Remotes
Remote Alarm Summary
Rmt1_Hst1_Reg1
Prism Remote Unit Remote
Remote
10.5 MONITORING A REMOTE UNIT
11 In the Function Explorer Tree, select
view in the EMS View Frame.
to open the top level
22 If the Alarm Summary status indicator for any Remote is red or yellow, indicating
that an alarm exists for that Remote, in the Function Explorer Tree, select the node that corresponds to that Remote. In the preceding example, you would click on the remote node labeled
This opens the selected Remote (
-n).
.
-n summary that corresponds to the
Page 240 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
Monitoring a Remote Unit
SERF
RF Groups Alarm Summary
33 If the
or
status indicator is red or yellow, you must go another level lower in the Function Explorer Tree for this same Remote to select the page for the SeRF or RF Groups. For more information on these displays, see
“Viewing Remote SeRF Alarms” on page 248 or “Viewing Remote SeRF Optical Ports” on page 248.
The GPS alarm is not supported at present; this status indicator will be white.
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 241 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
Managing Remote Units
Major Alarms
Minor Alarms
Remote Capacity
Remote Temperature
Host Lost Fault
Remote Lost Fault
AC Power Supply Fault
Over Temperature Fault
84°C
Fan Under Speed Fault
Under Temperature Fault
-40°C
Fan Over Speed Fault
Open Door Fault
Apply
Refresh
DART ID 8
RF Slot 4
DART ID 7
DART ID 6
RF Slot 3
DART ID 5
DART ID 4
RF Slot 2
DART ID 3
DART ID 2
RF Slot 1
DART ID 1
SERF Board
44 If any status indicator in the
refer to the following list:
—Number of slots for RF Modules in the remote. Each RF Module comprises up to two Classic DARTS or Single SuperDARTs or one Dual SuperDART.
field—Currently detected internal temperature of the
Remote (measured near the SeRF board).
or
table is red or yellow,
status indicator—Red indicates Remote has lost contact with
Host.
status indicator—Red indicates that the Host is unable to
communicate with the Remote.
status indicator—Red indicates Remote power supply has
failed.
• Remote is over its functional operating limit. Fault threshold is
status indicator—Red indicates internal temperature in
.
—Red indicates that the speed of the Remote fan is not
high enough for the internal functional temperature of the Remote.
status indicator—Yellow indicates that the internal
temperature within the Remote is under the operating limit. Fault threshold is
.
—Yellow indicates that the Remote fan is not necessary for the current internal temperature of the Remote, but the fan is spinning (Minor alarm).
—Yellow status indicator for this Minor alarm, which indicates
that the door to the Remote is open.
button—When clicked, causes Remote Name entry to be applied
Page 242 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
button—When clicked, causes page to be reloaded from Host
Monitoring a Remote Unit
Reset Unit
Decommission Unit
button—When clicked, causes the Remote to reboot. This causes a Loss of Service until Remote has returned to normal operation. Typical down time is two to four minutes. See “Resetting a Remote Unit” on page 246.
The use of the Reset Unit button causes Loss of Service and should not be used unless other troublesh experienced at the Remote.
ooting processes have been follow ed and did not fix the issue being
button—When clicked, deletes any configuration settings for that Remote and removes all corresponding alarms from the EMS alarm summaries (see “Decommissioning a Remote Unit” on page 244).
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 243 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
Managing Remote Units
Decommission
Decommission
Prism Remote Unit Remote
Remote
10.6 DECOMMISSIONING A REMOTE UNIT
Only a user logged in under the admin or a Network Manager account can change Prism system settings t
hrough the EMS.
The removed from the system. You use the
button is available only when a Remote has already been physically
button to delete alarms related
to the removed Remote from the EMS alarm summaries.
Decommission a Remote only if it has been permanently removed from the Remote and will not be replace this Remote (such as associated a
d with another Remote. This procedure removes all information about
larms, links, and inventory) from the EMS database.
11 If the system is configured for manual linking mode, remove any RF links to the
DART.
22 In the Function Explorer Tree, select the node that corresponds to the Remote that
has been physically removed from the Prism system.
This opens the selected Remote (
-n). There should be a statement that communication
-n summary that corresponds to the
with the Remote has been lost.
Page 244 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
Decommissioning a Remote Unit
Decommission Unit
OK
33 Click
.
44 In the confirmation dialog, click
.
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 245 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
Managing Remote Units
Prism Remote Unit Remote
Remote
Reset Unit
10.7 RESETTING A REMOTE UNIT
Only a user logged in under the admin or a Network Manager account can change Prism system settings t
Resetting the Remote causes Loss of Service and should not be used unless other troubleshooting proce experienced at the Remote.
If communication and/or reverse-path fiber is lost to the Remote, a Remote Reset can be attempted.
11 In the Function Explorer Tree, select the node that corresponds to the Remote that
you want to reset. This opens the corresponds to the selected Remote (
hrough the EMS.
sses hav e been follow ed and did not fix the issue being
-n).
-n summary that
22 Click the
button.
Page 246 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
Resetting a Remote Unit
33 In the confirmation dialog, click OK.
The Remote reboots (resets), which causes a Loss of Service until the Remote has returned to normal operation. Typical down time is two to four minutes.
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 247 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
Managing Remote Units
Prism on SERF of Remote
System View,Remotes,Remote#-x,SERF
Remote#
Prism on SERF of Remote
Optical Ports
SERF Fault
Optical Ports On Remote
Optical
Ports On Remote
Optical Ports On Remote
System View,Remotes,Remote#-x,SERF,Optical Ports
Remote#
10.8 VIEWING REMOTE SERF ALARMS
To open the Explorer Tree select
-n view in the EMS View Frame, in the Function (where
the Remote number that corresponds to a Host SFP port number and name).
indicates
n is the Remote
The
-n view provides an alarm summary for the SeRF card on
the identified Remote.
status indicator—Summary alarm status indicator for Remote optical
ports. Red indicates no light (such as the RxNolight Fault) or a laser fault.
status indicator—Summary alarm status indicator for Remote SeRF
card. Red indicates that an alarm exists for the Remote SeRF card.
10.9 VIEWING REMOTE SERF OPTICAL PORTS
The optical ports on the Remote, plus current values of operating parameters. The
-n view only shows the ports that are in current use (that is, they have a fiber and connector plugged into them with the other end of the fiber being connected to Remote).
To open the Explorer Tree select
and
indicates the Remote number that corresponds to a Host SFP port number
n is the Remote name).
-n view shows the current usage and alarm status of the
-n view in the EMS View Frame, in the Function (where
Page 248 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
Viewing Remote SeRF Optical Ports
Optical Ports On Remote
Optics Number
Port Configuration
Page
Optics Name
UNKNOWN_SFPName
Ip Enable
Optics Type
LongRange
Fwd Launch
Rev Receive
Wave Length
RxBer Fault
0.00001
RxNoLight Fault
Laser Fault
OverDrive Fault
-9dBm
UnderDrive Fault
-27dBm
Host Name
The
-n view provides an alarm summary for the SeRF card on
the identified Remote.
• for this particular port
—System-assigned port number and link to the
—User-entered port name or
indicating no name
has been entered
—Disabled for Remotes. This parameter indicates if the link is carrying IP traffic. It can only be set on the Host as described in “Configure the Remote SeRF
Optical Ports” on page 158.
—Laser range, which is
to meet 3Gbps optical transmission
requirements.
—Launch power in dB of REV path signal, from the Remote to the Host.
—Launch power in dB of receive level of the FWD path, from the Host
to the Remote. The minimum REV launch power is -27 dBm, and the maximum is
-9 dBm.
• fiber. Fault threshold is
—Number displayed is wave length transmitted through this port
—Yellow indicates that there ware too many errors on the receiving
.
—Red indicates that no light is detected on the receiving fiber
• threshold is
• underdrive is from -28dBm to -33dBm. Fault threshold is
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 249 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
—Red indicates reverse path laser is not sending light
—Red indicates forward path optical signal is too strong. Fault
.
—Yellow indicates forward path optical signal is too weak. The
.
—Name of the Host at the other end of the fiber.
Managing Remote Units
Alarm Summary of RF Groups of Remote-
Remote-
Alarm Summary of RF Groups of Remote-
System View,Remotes,Remote#-x,RF Groups
Remote#
DART
LPA
10.10 VIEWING AN ALARM SUMMARY OF THE REMOTE RF
ROUPS
G
The four RF groups on a particular Remote (
To open the the Function Explorer Tree select
n is the Remote name).
and
indicates the Remote number that corresponds to a Host SFP port number
n view provides an alarm summary for the
n).
n view in the EMS View Frame, in
(where
To understand how the EMS maps the RF Groups in the Remote to their representation in the GUI, see “RF Groups in the Remote and the EMS GUI” on
page 160. The RF Group alarm indicators are listed below.
—Summary alarm state of the DART card upconverter, downconverter and the DART FPGA. Yellow indicates that a Minor alarm is the highest-level alarm and Red indicates that a Major alarm exists for the DART.
—Summary alarm state of Linear Power Amplifier (LPA), where both LPA indicators refer to the same LPA. Yellow indicates that a Minor alarm is the highest-level alarm and Red indicates that a Major alarm exists for the LPA.
Page 250 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
Viewing an Alarm Summary of the Remote RF Groups
LNA
Power Det
Power Det
Alarm
Summary of RF Groups on Remote
—Summary alarm state of the Low Noise Amplifier (LNA). Red indicates that
an active alarm exists for the LNA.
• configuration, the
When a new dual-slot 40W RF Module is installed in a Prism system, in the
—Red indicates that the LPA has been shut down. On initial
indicator will be red until the link is created.
window, the status of the second LPA is in the slot
below where the DART appears in the GUI.
The following figure shows:
40W RF Module, PCS 1900 Non-Diversity Enclosure for Prism Remote installed in
Slots D and C. The second LPA status is shown in Slot C.
40W RF Module AWS 2100 Non-Diversity Enclosure for Prism Remote installed in
Slots B and A. The second LPA status is shown in Slot A.
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 251 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
Managing Remote Units
Alarm Summary of RF Groups of Remote-
Alarm Summary of RF Groups of Remote-
System View,Remotes,Remote#-x,RF Groups
Remote#
10.11 VIEWING RF BAND ALARM DETAILS
The indicators and their current values.
11 To open the
in the Function Explorer Tree select (where number and
indicates the Remote number that corresponds to a Host SFP port
n is the Remote name).
n view shows band-specific alarm
n view in the EMS View Frame,
Page 252 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
Viewing RF Band Alarm Details
DART
Alarm Details
of DART-
of Group
on Remote-
Alarm Details of DART-n of Group
on Remote-
DART Major Alarms
DART Fault
DART DC Supply Fault
DART Hardware Mismatch Fault
DART Over Temperature Fault
84°C
DART Remote Ranging Fault
Power Detector Major Alarms
System VSWR Fault
RF Power Fault
0 dBm
22 Click on a
n
band in the RF Groups view (upper link) to open the
n
n window.
The
n
n window has the the following
components. For corrective actions for alarm states, refer to “Troubleshooting
Alarms” on page 264.
—Summary alarm state of the DART card upconverter downconverter and the DART FPGA. Red indicates that either the clock source for the DART card is outside the acceptable range or the DART FPGA is not programmed.
—Red indicates DART card DC supply is faulted.
—Red indicates an invalid passband
configuration for the DART.
temperature is too high. Fault threshold is
—Red indicates DART card internal
.
—Red indicates that the Host is unable to implement the signal delay entered in the RF Band Configuration Page (described in “Link the Host and Remote DARTs.” on page 159).
—Red indicates a VSWR fault at the interface to the
antenna (greater than 3:1).
output is too low. The threshold for this fault is
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 253 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
—Red indicates that the RF power measured at the antenna
.
Managing Remote Units
LNA Major Alarms
LNA Power Fault
LPA Major Alarms
LPA Disable Fault
LPA VSWR Fault
2
LPA DC Fault
LPA Loop Fault
LPA Over Power Fault
LPA Low Power Fault
LPA Missing Fault
DART Minor Alarms
DART Low Temperature Fault
-40°C
LPA Minor Alarms
LPA High Temperature Fault
error.
because it encountered a problem.
Fault threshold is
—Red indicates that the voltage level inside the LPA is outside
its acceptable range.
working.
high enough to damage the LPA.
not meet specification.
Fault threshold is
—Red indicates that the Low Noise Amplifier has an internal
—Red indicates that the Linear Power Amplifier is disabled
—Red indicates that an internal VSWR fault state of the LPA.
.
—Red indicates that the feedback loop inside the LPA is not
—Red indicates that the power level inside the LPA is
—Red indicates that the internal gain of LPA does does
—Red indicates that the LPA is missing.
—Yellow indicates DART temperature is too low.
.
temperature is too high.
—Yellow indicates that the LPA internal
Page 254 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
Viewing Remote GPS Alarms and Location Parameters
Remote GPS
System View,Remotes,Remote#-x,GPS
Remote#
10.12 VIEWING REMOTE GPS ALARMS AND LOCATION PARAMETERS
The
(Global Positioning System) page shows the alarm status and location
parameters for the Remote GPS function.
GPS is not supported in the softw are version documented in this manual so the Remote GPS page compone
nts are not described.
To open the GPS summary in the EMS View Frame, in the Function Explorer Tree select
(where
that corresponds to a Host SFP port number and
indicates the Remote number
n is the Remote name).
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 255 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
Managing Remote Units
Intentionally Blank Page
Page 256 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
11
MANAGING ALARMS
Content Page
11.1 Viewing Active Alarms .....................................................................................258
11.2 Viewing an Alarm History Log...........................................................................259
11.3 Masking an Alarm Type ...................................................................................260
11.4 Unmasking an Alarm Type ...............................................................................262
11.5 Troubleshooting Alarms...................................................................................264
Some EMS parameter values are associated with alarms. When a parameter enters an alarm state, an alarm status indicator is activated where the color of the indicates the alarm severity, where:
Red indicates a major alarm
Yellow indicates a minor alarm
Green indicates a normal (okay) state
Grey indicates that the alarm has been masked
White indicates that an associated device is unplugged or missing.
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 257 ADCP-77-073 • Issue 211/2009 ©2009 ADC Telecommunications, Inc.
Managing Alarms
Active Alarm List
System View
Active Alarm List
Active Alarm List
Active Alarm List
Alarm Type
Host No
Host Name
Remote No
Remote Name
Module Type
Module Number
Severity—Major
Minor
Time Stamp
YYYY:MM:DD:HH:MM:SS
11.1 VIEWING ACTIVE ALARMS
Viewing the
window is a means to determine alarm type, Host unit
name, Remote name, time stamp, and other information for active alarms.
11 To access the EMS Menu bar, in the Function Explorer Tree, click on
display a system view.
22 To open the
window, in the EMS Menu bar select
to
.
The
table provides the following information:
—Descriptive name of alarm. For more information, refer to
“Troubleshooting Alarms” on page 264.
—Always “1”
—User-defined Host name or system default
—System assigned number of Remote from which alarm came
—User-defined Remote name or system default
—Type of unit that is experiencing the alarm (SeRF, DART, LPA, LNA,
Power Detector, SFP)
Page 258 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
—Unit number of module experiencing the alarm condition
or
—Date and time when the alarm occurred (
)
11.2 VIEWING AN ALARM HISTORY LOG
System View
Active Alarm List
Active Alarm List
Alarm Log History
Active Alarm List
History Log
Alarm Log History
Active Alarm List
Alarm Log History
Clear
Viewing an Alarm History Log
11 To access the EMS Menu bar, in the Function Explorer Tree, click on
display a system view.
22 To open the
33 To open the
link.
window, in the EMS Menu bar select
window, in the
window click the
to
.
The window (see “Viewing Active Alarms” on page 258), except the window includes the severity of
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 259 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
window components are the same as for the
if the alarm condition has been cleared.
Managing Alarms
System View
Alarm Management
Alarm Management Tabl
11.3 MASKING AN ALARM TYPE
Only a user logged in under the admin or a Network Manager account can change Prism system settings t
Masking an alarm type causes the EMS to stop reporting alarms of that type until the alarm is unmasked. By default all alarms are unmasked. When an alarm type is masked (mask status enabled), the following is true:
The corresponding status indicator shows in gray.
The alarm state is not calculated into the higher level alarm summary
The corresponding trap is not sent to SNMP managers.
To mask an alarm:
hrough the EMS.
11 To access the EMS Menu bar, in the Function Explorer Tree, click on
display a system view.
22 In the EMS Menu bar, select
The
e window opens.
.
to
Page 260 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
Masking an Alarm Type
enable
Apply
33 Click the list in the Mask Status column for the alarm for which you want to enable
a mask, select
, and then click
.
In the following graphic, a mask has been enabled for the SeRF Secondary Clock Priority Fault.
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 261 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
Managing Alarms
System View
Alarm Management
Alarm Management Tabl
11.4 UNMASKING AN ALARM TYPE
Only a user logged in under the admin or a Network Manager account can change Prism system settings t
Unmasking an alarm type causes the EMS to report alarms of that type until the alarm is masked. By default all alarms are unmasked.
hrough the EMS.
11 To access the EMS Menu bar, in the Function Explorer Tree, click on
display a system view.
22 In the EMS Menu bar, select
The
e window opens.
.
to
Page 262 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
Unmasking an Alarm Type
disable
Apply
33 Click the list in the Mask Status column for the alarm for which you want to
disable a mask, select
, and then click
.
In the following graphic, masking has been disabled for the SeRF Secondary Clock Priority Fault.
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 263 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
Managing Alarms
HostDARTDCSupplyFault
HostDARTDwnCon1SynLockFault
HostDARTDwnCon2SynLockFault
11.5 TROUBLESHOOTING ALARMS
This section lists alarms that can be viewed in EMS alarm summaries.
Table 11-1. EMS Alarm Descriptions and Corrective Actions
Alarm Name Alarm
Sev erity Level
Major The voltage supplied
Major Lock state of the
Major Lock state of the
Description Action
Check whether the to the DART board is too low. (Host DC Power board accepts 21-60 Vdc and draws up to 427.28 Watts per Host.)
first down converter synthesizer. Causes RF mute
second downconverter synthesizer. Causes RF mute
Vdc supply is in the
range of 21-60 Vdc.
If persistent (may be
transient on
startup), contact
ADC.
When a DART is
being turned up or
after a power reset,
the DART
synthesizers may go
in and out of lock,
which may cause
this fault. Unless
this fault persists,
these transient
faults can be
ignored. If
persistent, consult
ADC, replace DART
When a DART is
being turned up or
after a power reset,
the DART
synthesizers may go
in and out of lock,
which may cause
this fault. Unless
this fault persists,
these transient
faults can be
ignored. If
persistent, consult
ADC, replace DART
Page 264 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
Troubleshooting Alarms
HostDARTFault
Active
Alarm List
HostDARTHardwareMismatchFault
HostDARTOverDriveFault
HostDARTUnderDriveFault
HostDARTUpConSynLockFault
Table 11-1. EMS Alarm Descriptions and Corrective Actions (Cont.)
Alarm Name Alarm
Sev erity Level
Major Summary status of
Major Indicates a hardware
Description Action
Inspect DART upconverter and/or downconverter and DART FPGA status. The clock source for the DART is outside an acceptable range or the DART FPGA is not programmed. may also occur with the DARTDCSupplyFault.
mismatch for the DART boards between linked Host and Remote
upconverter and/or
downconverter
alarms. If these
alarms are found
and persist, consult
ADC, replace DART.
If no
upconverter/downc
onverter alarms are
found, unplug DART
from Host, then
replug DART in Host
to reload the FPGA. If
persistent, consult
ADC, replace DART.
Check if a linked
DART of one type
was unplugged and
not decommissioned
then replaced with a
DART of another
type. Make sure
linked Host and
Remote DARTs are
of same type
for
Major the RF signal
received from BTS is greater than +5dBm. The allowed range is
-25 dBm to +5 dBm.
Minor When the Host input
level is 20 dB less than the expected Host DART Input. For example, for 30 dB of Host DART gain (-25 dBm expected input), the threshold is -45 dBm. For 0 dB of Host DART gain (+5 dBm expected input), the threshold is -15 dBm.
Major Lock state of the
upconvertor synthesizer
Lower the gain on
the Host DART. If
persistent when
gain is zero, lower
power of BTS RF
signal. Maximum
power at zero gain is
+19dBm.
Increase the gain of
the Host DART. If
persistent when
gain is at maximum,
increase power of
BTS RF signal.
If persistent, consult
ADC, replace DART
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 265 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
Managing Alarms
HostModuleMissingFault
HostOverTempFault
HostSERFFault
Active Alarm List
HostSERFOptOverDriveFault
HostSerfOptRxBerFault
HostSERFOptRxNoLightFault
HostSERFOptUnderDriveFault
HostSERFRmtLostFault
Table 11-1. EMS Alarm Descriptions and Corrective Actions (Cont.)
Alarm Name Alarm
Sev erity Level
Major One of the pluggable
Major The temperature of
Major Summary fault for
Major The power of the
Description Action
Either insert a modules is missing on the Host
the Host is Over its upper limit of 84C
SeRF combining SeRF synthesizer and SeRF FPGA status. Either the clock source is not acceptable or the SeRF board FPGA is not programmed.
signal received from the Remote exceeds the maximum level of -9dBm
replacement unit or
decommission the
unit
Check Host fan and
ambient conditions
Check for related
SeRF alarms in
and respond to
those alarms if
found. If no SeRF
alarms exists, FPGA
is faulty; consult
ADC, replace SeRF. If
SeRF is replaced, use
the same Compact
Flash to retain
system
configuration.
Externally attenuate
Remote return path
signal or replace
Remote SFP with one
of less strength
Minor Too many errors on
the receiving fiber
Major No light detected
from the receiving fiber
Minor The power of the
signal received on the fiber is below the minimum power level of -27dBm
Major Host is not receiving
messages from connected Remote or there is an IP conflict causing loss of communication
Check fiber for kink
or sharp bend. Check
for too much gain.
Make sure the fiber
is clean.
Check for broken or
disconnected fiber.
Check for out of
service Remote
Check fiber for too
much attenuation,
dirty connectors.
Check SFP type
being used (too
weak for range)
Check for optics
disconnect. Check
for Remote out of
power or out of
service
Check for IP conflict
Page 266 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
Troubleshooting Alarms
HostSERFSynthAlarmFault
HostSysCardFanFault
HostUnderTempFault
RmtAcPowerSupplyFault RmtACPowerSupplyMon1Fault
RmtDARTDCSupplyFault
RmtDARTDwnCon1SynLockFault
RmtDARTDwnCon2SynLockFault
RmtDARTFault
Table 11-1. EMS Alarm Descriptions and Corrective Actions (Cont.)
Alarm Name Alarm
,
Sev erity Level
Major The configured clock
Major The Host fan is
Minor The temperature of
Major A power supply is in
Description Action
If clock source is source is not providing an acceptable signal
spinning too slowly
the Host is under its lower operating limit (-40 degrees Fahrenheit )
a failed state
onboard and
persists, consult
ADC, replace system
card. If clock source
is external, check
clock source,
connection
Check fan for
mechanical problem.
If not fixable,
consult ADC, replace
fan
Check ambient
conditions
If persistent, consult
ADC, may have to
replace one or more
power supply
located in the SeRF
Module
Major The on-board DC
voltages are out of their valid ranges
Major Lock state of the
first downconverter synthesizer
Major Lock state of the
second downconverter synthesizer
Major Summary fault
status of DART upconvertor/ downconverter and DART FPGA status
If persistent (may be
transient on
startup), check If the
DC power switch to
the DART is in the
OFF position. If DC
power is ON, reset
set the RF Module. If
the alarm persists,
consult ADC, as you
may have to replace
RF Module
If persistent, consult
ADC, replace RF
Module
If persistent, consult
ADC, replace RF
Module
If persistent, consult
ADC, replace RF
Module
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 267 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
Managing Alarms
RmtDARTHardwareMismatchFault
RmtDARTOverTempFault
RmtDARTUnderTempFault
RmtDARTUpConSynLockFault
RmtLNAPowerFault
RmtLPADcFault
RmtLPADetectFault
RmtLPADisableFault
RmtLPAHighTempFault
Table 11-1. EMS Alarm Descriptions and Corrective Actions (Cont.)
Alarm Name Alarm
Sev erity Level
Major Indicates a hardware
Major Indicates that
Minor Indicates that
Major Lock state of the
Description Action
Check if a linked mismatch for the DART cards between linked Host and Remote
detected temperature is above the maximum ambient temperature of 50°C.
detected temperature is below the lower acceptable limit (-40 degrees Farenheit)
upconverter synthesizer
DART of one type
was unplugged and
not decommissioned
then replaced with a
DART of another
type. Make sure
linked Host and
Remote DARTs are
of same type
Check air flow
around Remote. If
persists, consult
ADC.
Check ambient
conditions
If persistent, consult
ADC, replace RF
Module
Major The low noise
amplifier has an internal error
Major The LPA voltage
level is outside its acceptable range. Causes RF mute
Major Presence fault state
of the LPA (the LPA cannot be detected)
Major Disable state of the
LPA. The LPA is disabled because it encountered a problem
Minor LPA is overheated Check ambient
If persistent, consult
ADC, replace RF
Module
Reset LPA and
recheck. If alarm
keeps coming back,
consult ADC, replace
RF Module
If persistent, consult
ADC, replace RF
Module
See “Identify the LPA
Fault” on page 236.
If fault cannot be
corrected, replace
the RF Module
temperature. Check
remote temperature.
Reset LPA. If
persistent, consult
ADC, replace RF
Module
Page 268 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
Troubleshooting Alarms
RmtLPALoopFault
RmtLPALowPowerFault
RmtLPAOverPowerFault
RmtLPAVswrFault
RmtMajorExtAlarmInputFault
RmtMinorExtAlarmInputFault
RmtModuleMissingFault
Table 11-1. EMS Alarm Descriptions and Corrective Actions (Cont.)
Alarm Name Alarm
Sev erity Level
Major The feedback loop
Major Internal low power
Description Action
Lower DART(s) inside the LPA is not working. Causes RF mute
fault state of linear power amplifier (the gain of one or more internal amplifiers does not meet specification). Causes RF mute
Internal over power fault state of linear power amplifier (power level is high enough to damage LPA)
remote gain by 10dB,
reset the LPA, then
return gain to values
previously
configured. If fault
persists, replace RF
Module.
Reset LPA. If error
persists, consult
ADC, replace RF
Module
Reduce FWD gain,
reset the LPA, and
then monitor power
levels. Adjust gain to
acceptable values.
Reset LPA. If error
persists, consult
ADC, replace RF
Module
Major Internal VSWR fault
state of linear power amplifier (greater than 3:1). Causes RF mute
Major External major alarm
contact input
ALARM­TYPE (Minor, OK)
Major One of the pluggable
External minor alarm contact input
modules is missing on the Remote
Reset LPA. If error
persists, consult
ADC, replace RF
Module
Not used
Not used
Replace or
decommission the
missing module
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 269 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
Managing Alarms
RmtNoRFPowerFault
RmtOverTempFault
RmtRangingFault
RmtSERFFault
Table 11-1. EMS Alarm Descriptions and Corrective Actions (Cont.)
Alarm Name Alarm
Sev erity Level
Major The RF power
Description Action
Verify that there is measured at the antenna output is too low. The threshold for this fault is 0 dBm.
an active Host DART
Under Drive Fault,
which indicates a
loss of BTS input. If
this fault is active,
address this
problem and the
RmtNoRFPowerFault
should clear.
If there is not an
active Host DART
Under Drive Fault,
the problem may be
the result of another
LPA fault such as
VSWR or Over Power
Faults. If there are no
other faults, then
reset the Remote RF
Module. If power is
still not, present
then replace the
module.
Major High temperature
reading from RSI card in Remote
Major The configured
delay is outside the range of what can be supplied.
Major Summary fault for
SeRF combining SeRF synthesizer and SeRF FPGA status
Check ambient
temperature. Check
remote temperature.
If not an actual over
temperature fault,
shut down Remote,
consult ADC
Enter a delay value
within the
permissible range
see “Link a Remote
DART to a Host
DART” on page 162
Check for related
SeRF alarms in active
alarms list and
respond to those
alarms if found. If no
SeRF alarm exists,
FPGA is faulty;
consult ADC, replace
SeRF
Page 270 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
Troubleshooting Alarms
RmtSERFHstLostFault
RmtSERFOptLaserFault
RmtSERFOptOverDriveFault
Table 11-1. EMS Alarm Descriptions and Corrective Actions (Cont.)
Alarm Name Alarm
Sev erity Level
Major Remote not
Description Action
There are two receiving any messages from connected Host
possible actions:
•Check for optics disconnect. Check the optical link and determine the source of lost communications. If an optical meter on the output of the SFP determines that no power is being transmitted, or meter measuring receive levels at the SFP determines the receiver is broken, replace SFP with the appropriate type for the range of signal supported.
•There may be an IP conflict. For example, if the Host is configured in External Network mode but there's not a DHCP server running on the network, the Remote will not receive an IP address, there therefore will not be communication with the Host, which would activate this alarm.
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 271 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
Major SFP reports that
laser of forward path is faulty
Major The power of the
signal received at the Remote is too strong
Replace SFP with the appropriate type for range of signal supported
Externally attenuate Host forward path signal or replace Host SFP with one of less strength
Managing Alarms
RmtSERFOptRxBERFault
RmtSERFOptRxNoLightFault
RmtSERFOptUnderDriveFault
RmtSERFSynthAlarmFault
RmtSystemVswrFault
RmtUnderTempFault
Table 11-1. EMS Alarm Descriptions and Corrective Actions (Cont.)
Alarm Name Alarm
Sev erity Level
Minor Too many errors on
Major No light detected
Minor The power of the
Major Onboard
Description Action
Check fiber for kink
the receiving fiber
from the receiving fiber
signal received on the fiber is too weak
synthesizer fault
or sharp bend. Check for too much gain. Make sure the fiber is clean.
Check for broken or disconnected fiber. Check for out of service Host
Check fiber for too much gain, dirty connectors. Check SFP type being used (too weak for range)
Check clock signal coming from Host. Host is not generating a proper signal. Possibly Host clock source is bad or Host has bad FPGA
Major LPA VSWR Fault Perform cable
sweeps on external antenna cable system. Put a load on the Remote by disconnecting the external antenna cable to determine if the source of the VSWR condition is internal or external. If it's internal, replace the RF Module. If it's external, troubleshoot and determine source of high VSWR reading.
Minor Temperature is
below lower acceptable limit (-40 degrees Farenheit)
Check ambient conditions
Page 272 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
Troubleshooting Alarms
fwuHstSERFOptIpEnableFault
fwuRmtFanOverSpeedFault
fwuRmtFanUnderSpeedFault
fwuRmtOpenDoorFault
fwuHstSysCardPrimaryCPFault
fwuHstSysCardSecondaryCPFault
Table 11-1. EMS Alarm Descriptions and Corrective Actions (Cont.)
Alarm Name Alarm
Sev erity Level
Major An attempt to enable
Minor Remote fan has an
Major Remote fan has an
Description Action
The alarm is cleared IP on a fiber (Host) to a Remote that already has IP enabled on another fiber (Host) has been made.
Over Speed fault
Under Speed fault
if IP is disabled on
the fiber. It is also
cleared if an ACK is
later received from
the Remote. This
latter condition can
occur if the fiber that
was already carrying
IP later has IP
disabled, or if the
fiber otherwise
becomes disabled.
For information on
setting Ip Enable,
see
“Configure the Remote SeRF Optical Ports” on page 158
Fan may require replacement.
Fan may require cleaning and/or replacement.
Minor Door on the Remote
is open
Major Primary Clock
Priority Fault
Minor Secondary Clock
Priority Fault
Close the Remote door
Set Primary CPL within acceptable range
Set Secondary CPL within acceptable range
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 273 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
Managing Alarms
Page 274 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
12
SNMP INTERFACE
Content Page
12.1 EMS SNMP Interface .......................................................................................276
12.2 SNMP Overview..............................................................................................277
12.2.1 Background Information on SNMP .............................................................278
12.2.2 MIB Used by FlexWave System .................................................................280
12.3 SNMP Procedures ...........................................................................................281
12.4 Accessing the FlexWave-Prism Agent MIB ..........................................................282
12.5 Configuring the Trap Viewer.............................................................................283
12.5.1 Registering the Manager for Receiving Traps
(static—non AdventNet MIB Browser) .............................................................283
12.5.2 Registering the Manager for Receiving Traps
(dynamic—AdventNet MIB Browser) ...............................................................284
12.5.3 Viewing Traps.........................................................................................287
12.5.3.1 Date and Time Stamps ....................................................................287
12.5.3.2 Variable Bindings ............................................................................288
12.5.3.3 View the Traps................................................................................290
12.6 FlexWave-URH Agent MIB................................................................................292
12.7 Traps ............................................................................................................308
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 275 ADCP-77-073 • Issue 211/2009 ©2009 ADC Telecommunications, Inc.
SNMP Interface
12.1 EMS SNMP INTERFACE
SNMP (Simple Network Management Protocol) is an international standard for remote monitoring and control of online devices. The EMS provides an interface for those wishing to access a Prism system using an SNMP manager such as the AdventNet application shown in Figure 12-1.
Figure 12-1. EMS SNMP Interface Example
The FlexWave EMS SNMP interface can manage FlexWave Prism and URH units. This document describes how
Page 276 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
to use the SNMP interface w ith a P rism system.
SNMP Overview
12.2 SNMP OVERVIEW
The FlexWave system SNMP interface, shown schematically in Figure 12-2, allows a remote user using an SNMP manager to access the same database as accessed by the standard EMS interface. The database accessed is an SNMP database called a Management Information Base (MIB).
Web
IP
GET/SETTRAP
Network port
EMS
INTERNAL
MIB
IP
Windows 2000 or Windows XP
computer running
Internet Explorer 6.0
and/or SNMP Manager
URH Host Unit
75356-05
Figure 12-2. SNMP Interface
This section describes the FlexWave system SNMP interface, and provides procedures for using the SNMP interface to “get” and “set” system parameters and receive alarms.
In SNMP terminology, the parameters in a MIB are called “objects” and alarms are called “traps.”
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 277 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
SNMP Interface
12.2.1 Background Information on SNMP
SNMP (Simple Network Management Protocol) is an international standard for remote control of online devices. A typical scenario involves the devices being controlled, remote computers (called managers) that can control them, a network connection, and SNMP software. The SNMP software includes SNMP manager software on each controlling computer and SNMP “proxy agent” software and one or more MIBs on each of the controlled devices.
A MIB is a database defined in accordance with SNMP requirements. A MIB consists of tables of objects used to exchange information between a manager and agent. Information is exchanged using three basic operations: GET, SET, and TRAP. A manager uses GET to obtain an object value from a MIB and SET to set an object to a new value. A TRAP is a notification that is sent out by an agent when the value of a trap object exceeds a threshold defining an alarm state.
In a manager browser, a MIB looks like an Explorer hierarchy of folders and files, as shown in Figure 12-3. The items at the lowest level, analogous to files in the Explorer view, are not files, however; they are objects that each represent one system parameter (object) and its current value. MIB objects are arranged in tables. Each set of objects (within a single folder) represents one such table. An object marked with a key symbol indicates that view is the key value for that table.
Page 278 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
SNMP Overview
Figure 12-3. MIB in MIB Browser
In the FlexWave system, the MIB accessed through the SNMP interface is the same database as used by the EMS graphical user interface. There is therefore a one-to-one correspondence between MIB objects and the parameters displayed in the EMS Web pages. Likewise, there is a one-to-one correspondence between the SNMP trap objects and the alarm indicator LEDs displayed on the EMS pages. The MIB object names and the EMS page names for the same items differ in a way that can be easily figured out. For example, the MIB object “fwuHstDARTPassBand” corresponds to the “Host DART Pass Band” parameter on the Host DART Configuration and Alarm Details Page.
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 279 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
SNMP Interface
12.2.2 MIB Used by FlexWave System
The FlexWave system uses a single MIB called the ADC-FLEXWAVE-URH.mib. The MIB resides on the SeRF card in the Host where the EMS software also runs. The SNMP proxy agent software required for the interface with SNMP managers also resides and runs on the Host SeRF card.
A complete list of the objects that compose the FlexWave-Prism Agent MIB are listed in this section in two tables. Table 12-2 on Page 292 lists objects that may be accessed for GET/SET operation. Table 12-3 on page 308 lists traps that are sent to SNMP managers registered to receive them whenever the respective fault condition occurs.
Page 280 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
SNMP Procedures
12.3 SNMP PROCEDURES
This topic contains procedures done at the SNMP manager to interact with the FlexWave-Prism Agent MIB. Any SNMP manager may be used. These procedures are illustrated with examples from an AdventNet MIB Browser.
Figure 12-4 shows the features of a typical MIB browser.
Figure 12-4. Typical MIB Browser
Examples show n in this chapter use the AdventNet MIB Browser. Some procedural details may vary with a
nother browser, but the basic steps are the same.
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 281 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
SNMP Interface
Host
Port number
12.4 ACCESSING THE FLEXWAVE-PRISM AGENT MIB
The FlexWave-Prism Agent MIB can be accessed using any SNMP manager with an active network connection. The IP address of the FlexWave-Prism Host must be known and entered in the MIB browser.
11 On the manager computer, open the MIB Browser.
22 Load the ADC-FLEXWAVE-URH.mib file.
33 Enter the IP address of the Host of the FlexWave-Prism system in the text box
provided next to
.
44 Enter the
as 8001.
55 Enter the Read Community as public and Write Community as private.
66 To see an overview the MIB content, expand the MIB tree.
Page 282 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
Configuring the Trap Viewer
155.226.32.101 8003 SNMP_VERSION_2c public 30 5 ACTIVE
12.5 CONFIGURING THE TRAP VIEWER
Configuring a trap viewer enables it to receive traps from the FlexWave system.
12.5.1 Registering the Manager for Receiving Traps (static—non AdventNet MIB Browser)
To receive traps, the manager must first be registered with the FlexWave-Prism Agent using the following procedure.
This procedure cannot be done with the AdventNet MIB Browser.
11 Open a telnet or ssh connection to the Host.
22 Stop the agent process with the following command: service URHagent stop
33Edit /usr/local/fwu/conf/snmp/v2managertable.txt and add a line for each
trap receiver that looks like this:
The balance of the line should be the same for all trap managers, except:
Replace “155.226.32.101” i
used by the trap manager.
8003 is the destin number is supported.
ation port used. The Default SNMP trap port is 162. Any port
n the example with the IP address of the computer being
44 Start the agent process with the following command: service URHagent start
You can't use both a static and dynamic trap agent configuration. You can only use one or the other.
If you configure static, the dynamic entries will be deleted.
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 283 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
SNMP Interface
SNMP-TARGET-MIB
Host,Port and Community
Write
Community
12.5.2 Registering the Manager for Receiving Traps (dynamic—AdventNet MIB Browser)
To receive traps, the manager must first be registered with the FlexWave-Prism Agent using the following procedure.
11 Open the MIB-browser and load the
22 Expand the MIB tree.
33 Set the common parameters such as
.
.
, and
Page 284 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
Configuring the Trap Viewer
snmpTargetAddrTable
View SNMP Data Table
View -> SNMP Table
Start
Add
44 Select the
.
55 In the window that opens, click
and then click on the
.
icon or
66 In the window that opens, click
to add the manager information.
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 285 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
SNMP Interface
snmpTargetAddrName
snmpTargetAddrDomain
snmpTargetAddrTAddress
snmpTargetAddrTimeout
snmpTargetAddrRetryCount
snmpTargetAddrTagList
public
snmpTargetAddrParams
group1
snmpTargetAddrStorageType
OK
Close
77 Set the manager information as follows:
—any unique name
—.1.3.6.1.6.1.1
—IP address of the machine where you want to receive the traps, The port number should also be provided next to IP address (for example, #8004)
• view the traps; the default community string is
You can't use both a static and dynamic trap agent configuration. You can only use one or the other.
If you configure dynamic, the static entries will be deleted.
—timeout value
—retry count
—any string that will be used as a community string to
—any string, usually
—3
88 Click
.
The information given in Step 7 displays as a new row in the SNMP Table.
99 Click
Page 286 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
to close the SNMP Table.
Configuring the Trap Viewer
EEE, MMM dd, HH:mm:ss
TUE, FEB 26, 13:30:15
12.5.3 Viewing Traps
This section describes how to view traps in the MIB Browser and how to interpret responses.
12.5.3.1 Date and Time Stamps
The FlexWave MIB imports the date and time in the format of:
Table 12-1 describes the date and time fields.
Table 12-1. MIB Date and Time Stamp Fields
Field Contents Variable
EEE Three letter abbreviation for the day of the week SUN - SAT
MMM Three letter month abbreviation JAN - DEC
dd Two-digit day of the month 01-31
HH Two-digit hour for a 24-hour clock; AM/PM will not
display
mm Two-digit minute 00 through 59
ss Two-digit second 00 through 59
00 - 23
For example, Tuesday February 26 at 1:30:15 PM would be displayed as:
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 287 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
SNMP Interface
12.5.3.2 Variable Bindings
For Host Traps, there are 9 variable bindings:
11 sysUpTime
22 snmpTrapOID
33 fwuTrapSequenceNumber
44 fwuTrapTimeStamp
55 fwuModuleNumber
66 fwuModuleType
77 fwuHstNumber
88 fwuHstName
99 fwuNotificationStatus
For Remote Traps, there are 11 variable bindings:
11 sysUpTime
22 snmpTrapOID
33 fwuTrapSequenceNumber
44 fwuTrapTimeStamp
55 fwuModuleNumber
66 fwuModuleType
77 fwuHstNumber
88 fwuHstName
99 fwuRmtNumber
100fwuRmtName
111 fwuNotificationStatus
You can therefore determine the affected module based on the module number and type (variable binding 5 and 6).
Page 288 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
The module types are represented numerically as follows:
11 Host
22 Remote
33 SeRF
44DART
55 SFP
66 RSI
77 RDI
88 Power Detector
99 LPA
100 LNA
111 Duplexer
122 GPS
Configuring the Trap Viewer
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 289 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
SNMP Interface
Trap Viewer
Trap Viewer
Port
162
Community
public
Add
Port
Community
Trap
TrapList
Load
Start
12.5.3.3 View the Traps
11 In the AdventNet MIB Browser, click the
To receive traps using the manager, you must first register the manager using the procedure in “Registering the Manager for Receiving Traps (static—non AdventNet MIB
Browser)” on page 283 o (dynamic—AdventNet MIB Browser)” on page 284.
The
r in “Registering the Manager for Receiving Traps
dialog opens.
icon on the Toolbar.
22 In the
33 (Optional) In the
traps. The default is
44 Click the
the
The Port and Community list can be deleted by clicking the Delete Entry button.
55 Click the
66 Click the
box, enter the desired port number. The default is
button to add the
box, enter the community string for the incoming
.
and
list to the
list box).
button to load the trap parser file.
button. Trap Viewer begins to receive traps from the specified port
.
list (visible in
and community.
Page 290 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
Configuring the Trap Viewer
Trap Table
Class
Type
Source
Date
Message
Enable Logging
trap.log
Show Details
View Trap Details
Stop
Delete Entry
Delete the Selected Rows
Trap Viewer
ParserEditor.Trap Viewer
ParserEditor
The traps when received are listed in the
. The trap table has the
following five columns.
—defines the severity of the trap.
—defines the type of the trap or the inform request.
—represents the IP address of the source from where the traps were
sent.
—shows the date and time when the trap was received.
—lists the VarBind list of the trap, if any.
The status of the trap is displayed in the status pane at the bottom of the dialog box. Moreover, the Trap count and the inform count is displayed in the status pane.
77 To log the received traps, select the
traps are logged to a file. The default name of the log file is
88 To view the details of the traps, click on the
right-click the trap in the trap table and select
99 Click
to stop listening to the port.
100 To delete a trap, select the trap and click the
right-click the trap in the trap table and select
check box. All the incoming
button. You can also
button. You can also
.
.
.
Another option in
is the
can filter the incoming traps according to certain criterion called the Parser Criteria. The configuration of the criterion is made possible by using the
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 291 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
.
SNMP Interface
GET/SET
GET/SET
Enable
Disable
Disable
Enable
fwuTrapSequenceNumber
fwuTrapTimeStamp
fwuHstOverTempFaultMask
fwuHstUnderTempFaultMask
fwuHstSERFFPGAStatus
fwuHstSysCardRIADCPartNumber
fwuHstSysCardRISerialNumber
fwuHstSysCardRIDateCode
fwuHstSysCardRIHWVer
12.6 FLEXWAVE-URH AGENT MIB
Objects in the FlexWave-URH Agent MIB divide into two types: trap objects. This section describes the
objects. For information on trap
objects and
objects, see “Traps” on page 308.
Table 12-2 lists all objects within the FlexWave-URH Agent MIB that are available for
GET and/or SET commands. Objects that are available for SET commands are also available for GET commands.
For each SNMP syntax, there is a range of values defined in the MIB file. These are the possible values that can be entered in a SET command and returned in a GET command.
You can also (
) or not (
or
masking, which sets whether the trap will be raised
). Thresholds dictate when a trap will be activated. Table 12-2 lists all FlexWave-URH Agent MIB objects for which traps, masks and thresholds are sent to the SNMP manager.
Table 12-2. FlexWave-URH Agent MIB GET/SET Objects
Object Name Des cription SNMP Sy ntax Get
or SET
Total number of traps raised by the agent.
Counter32 GET
Time stamp when trap was raised.
Show masking status of Over Temperature fault. Masking is disabled by default. If enabled, the trap will not be raised.
Show status of masking of Under Temperature fault. Masking is disabled by default. If enabled, the trap will not be raised.
Host SeRF Card FPGA status where 0 indicates that the SeRF can talk to the FPGA and 1 indicates that it cannot
Remote Inventory Data-ADC Part Number
Remote Inventory Data-Serial Number
Remote Inventory Data-Date Code
Remote Inventory Data-Hardware Version
DateAndTime GET
MASKType SET
MASKType SET
INTEGER GET
DisplayString GET
DisplayString GET
DisplayString GET
DisplayString GET
Page 292 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
FlexWave-URH Agent MIB
fwuHstSysCard10MhzRefClock
fwuHstSysCardCPLevel
fwuHstSysCardFanFaultMask
fwuHstSysCardPrimaryCPFaultMask
fwuHstSysCardSecondaryCPFaultMask
fwuHstOverTempThreshold
fwuHstUnderTempThreshold
fwuRmtSERFFPGAStatus
fwuRmtRSIRIADCPartNumber
fwuRmtRSIRISerialNumber
fwuRmtRSIRIDateCode
fwuRmtRSIRIHWVer
fwuRmtCapacity
fwuHstNumber
fwuHstName
Table 12-2. FlexWave-URH Agent MIB GET/SET Objects (Cont.)
Object Name Des cription SNMP Sy ntax Get
System Card Reference clock, which can be can be internal (0) or external (1)
System Card Master Clock Priority Level, which can be from 0 to 15
Host System Card Fan Fault Mask. The alarm is disabled by default. Enable the alarm by setting it to enabled (1).
Primary Clock Priority Fault Mask. The alarm is disabled by default. Enable the alarm by setting it to enabled (1).
Secondary Clock Priority Fault Mask. The alarm is disabled by default. Enable the alarm by setting it to enabled (1).
Host System Card Over Temperature threshold value. This is not user settable.
INTEGER SET
Integer SET
MASKType SET
MASKType SET
MASKType SET
Integer32 SET
or SET
Host System Card Under Temperature Threshold value. This is not user settable.
Remote SeRF Card FPGA status where 0 indicates that the SeRF can talk to the FPGA and 1 indicates that it cannot
Remote Inventory Data-ADC Part Number
Remote Inventory Data-Serial Number
Remote Inventory Data-Date Code
Remote Inventory Data-Hardware Version
The number of RF Modules that can be installed in the Remote (1 - 4)
FlexWave URH Host Number HOSTNBRType GET
User assigned name of the Host. It can be 40 characters long
Integer32 SET
INTEGER GET
DisplayString GET
DisplayString GET
DisplayString GET
DisplayString GET
Unsigned32 GET
DisplayString SET
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 293 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
SNMP Interface
fwuHstUnitReset
fwuHstBackPlaneRev
fwuHstAlarmStatusSummary
fwuHstTempMeas
fwuSystemAlarmStatusSummary
fwuHstLinkingMode
fwuHstMajorContactAlarmOutput
fwuHstMinorContactAlarmOutput
fwuRmtMajorContactAlarmOutput
fwuRmtMinorContactAlarmOutput
fwuSystemAlarmSequenceNumber
fwuSystemAlarmAgentUpTime
fwuSystemAlarmType
fwuSystemAlarmHstNumber
fwuSystemAlarmHstName
fwuSystemAlarmRmtNumber
Table 12-2. FlexWave-URH Agent MIB GET/SET Objects (Cont.)
Object Name Des cription SNMP Sy ntax Get
Host SeRF card can be reset by setting a value of 1
Revision of Host back plane. DisplayString GET
Host Alarm Status Summary, where the severity of the alarm is:
•Normal = 1
•Minor = 2
•Major = 3
• Not Present = 0
Host system temperature value in Celsius
System Alarm Status Summary, where the severity of the alarm is:
•Normal = 1
•Minor = 2
•Major = 3
• Not Present = 0
INTEGER SET
ALARMType GET
DisplayString GET
ALARMType GET
or SET
System Linking mode for DART linking
Host Major contact output port state
Host Minor contact output port state
Remote Major contact output port state
Remote Minor contact output port state
Defines the index of the Alarm Table
Agent up time TimeTicks GET
Trap OID of the Alarm OBJECT
Host number from which the alarm has been raised
Name of the Host from which the alarm has been raised
Remote number from which the alarm has been raised
Integer SET
CONTACTTypeGET
CONTACTTypeGET
CONTACTTypeGET
CONTACTTypeGET
Unsigned32 GET
GET
IDENTIFIER
HOSTNBRType GET
DisplayString GET
REMOTENBRT ype
GET
Page 294 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
FlexWave-URH Agent MIB
fwuSystemAlarmRmtName
fwuSystemAlarmModuleType
fwuSystemAlarmModuleNumber
fwuSystemAlarmSeverity
fwuSystemAlarmTimeStamp
fwuHstSERFLinuxKernelVer
fwuHstSERFLinuxBootLoaderVer
fwuHstSERFCompactFlashSWVer
fwuHstSERFFPGAVer
fwuHstSERFPPCSNMPHTTPAgentSWVer
fwuHstSERFPPCHWMonSWVer
fwuHstSERFPPCAPPMonSWVer
fwuHstSERFPPCMATEMonSWVer
fwuHstSERFPPCENETMonSWVer
fwuHstSERFPPCFPGAMonSWVer
fwuHstSERFRIDateCode
Table 12-2. FlexWave-URH Agent MIB GET/SET Objects (Cont.)
Object Name Des cription SNMP Sy ntax Get
Remote name from which the alarm has been raised
Type of module raising the alarm
Identifier of the module raising the alarm.
This object gives the severity of this Alarm notification.
•Normal = 1
•Minor = 2
•Major = 3
• Not Present = 0
Time stamp of the Alarm DateAndTime GET
Linux Kernel Version of the Host system
Boot Loader Version of the Host system
DisplayString GET
MODULEType GET
Integer32 GET
ALARMType GET
DisplayString GET
DisplayString GET
or SET
Compact Flash Version of the Host system
Version of FPGA image loaded on SeRF
Software Version of the HTTP/SNMP agent running on Host
Software Version of the Hardware Monitor process running on the Host
Software Version of the Application Monitor process running on the Host
Software Version of the Mate Monitor process running on the Host
Software Version of the Ethernet Monitor process running on the Host
Software Version of the FPGA Monitor process running on the Host
DisplayString GET
DisplayString GET
DisplayString GET
DisplayString GET
DisplayString GET
DisplayString GET
DisplayString GET
DisplayString GET
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 295 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
Host SeRF Inventory-Date Code
DisplayString GET
SNMP Interface
fwuHstSERFRIHWVer
fwuHstSERFRISerialNumber
fwuHstSERFRIADCPartNumber
fwuHstSERFOptSFPNumber
fwuHstSERFOptSFPName
fwuHstSERFOptSFPType
fwuHstSERFOptSFPTxColor
fwuHstSERFOptRevLaunchPowerMeas
fwuHstSERFOptFwdLaunchPowerMeas
fwuHstSERFOptMateName
fwuHstSERFIPEnable
fwuHstSERFOptRxBERFaultThreshold
fwuHstSERFOptOverDriveFaultThreshld
fwuHstSERFOptUnderDriveFaultThreshld
fwuHstSERFOptRxBERFaultMask
fwuHstSERFOptOverDriveFaultMask
Table 12-2. FlexWave-URH Agent MIB GET/SET Objects (Cont.)
Object Name Des cription SNMP Sy ntax Get
Host SeRF Inventory-Hardware Version
Host SeRF Inventory-Serial Number
Host SeRF Inventory-ADC Part Number
SFP Number-Optical Port number (from 1 to 8)
User defined name of the SFP Optical Port that can be up to 32 characters long
SFP Type-Optical Port Type OPTICSType GET
SFP wavelength in nanometer Integer32 GET
Value of Host Receive measured optical power in dBm
Value of Host Transmit measured optical power in dBm
DisplayString GET
DisplayString GET
DisplayString GET
INTEGER GET
DisplayString SET
DisplayString GET
DisplayString GET
or SET
Name of Host Mates DisplayString GET
IP Enable mode for Host carrying RF, where 1 equals enable
Threshold Value for declaring a Decoded word error state of the primary wavelength optical receiver (too many errors)
Threshold value for declaring SFP over drive fault. This is not user settable.
Threshold value for declaring SFP under drive fault. This is not user settable.
Shows the masking status of primary wavelength optical receiver; masking is disabled by default; if enabled, the trap will not be raised.
Shows the masking status of SFP Over Drive Fault; masking is disabled by default; if enabled, the trap will not be raised.
Integer SET
DisplayString SET
Integer32 SET
Integer32 SET
MASKType SET
MASKType SET
Page 296 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
FlexWave-URH Agent MIB
fwuHstSERFOptUnderDriveFaultMask
fwuHstSERFOptIpEnableFaultMask
fwuHstSERFEthPortNumber
fwuHstSERFEthPortType
fwuHstSERFEthPortRxBytes
fwuHstSERFEthPortRxPkts
fwuHstSERFEthPortRxFcsErrors
fwuHstSERFEthPortRxBroadcastPkts
fwuHstSERFEthPortRxMulticastPkts
fwuHstSERFEthPortRxFragmtdFrames
fwuHstSERFEthPortRxJabbersFrames
fwuHstSERFEthPortTxByteCounter
fwuHstSERFEthPortTxPkts
fwuHstSERFEthPortTxBroadcastPkts
fwuHstSERFEthPortTxMulticastPkts
fwuHstSERFEthPortSFPId
fwuHstDARTNumber
fwuHstDARTName
fwuHstDARTBandType
fwuHstDARTPassBand
Table 12-2. FlexWave-URH Agent MIB GET/SET Objects (Cont.)
Object Name Des cription SNMP Sy ntax Get
Shows the masking status of Under Drive Fault. Masked is disabled by default. If enabled, the trap will not be raised.
Shows the masking status of the IP Enable Fault. Masked is disabled by default. If enabled, the trap will not be raised.
A unique identifier for each Ethernet port (from 1 to 12)
Identifies the type of Ethernet port
Receive byte counter Counter64 GET
Receive packet counter Counter64 GET
Receive FCS error counter Counter64 GET
Receive Broadcast packet counter
MASKType SET
MASKType SET
Unsigned32 GET
ENETType GET
Counter64 GET
or SET
Receive Multicast packet counter
Receive fragments counter Counter64 GET
Receive jabber counter Counter64 GET
Transmit byte counter Counter64 GET
Transmit packet counter Counter64 GET
Transmit broadcast packet counter
Transmit multicast packet counter
Identifier of SFP to which this Ethernet port connects
A unique identifier for each DART Card Object (from 1 to
8)
A user defined name for each DART Card object that can be up to 32 characters long
Band type of Host DART card BANDType GET
Counter64 GET
Counter64 GET
Counter64 GET
Unsigned32 GET
Integer32 GET
DisplayString SET
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 297 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
Pass-band type of host DART card.
PASSBANDTypeSET
SNMP Interface
fwuHstDARTOperatingMode
fwuHstDARTDiversityStatus
fwuHstDARTForwardGain
fwuHstDARTReverseGain
fwuHstDARTFPGAStatus
fwuHstDARTFPGAProgramVer
fwuHstDARTRIADCPartNumber
fwuHstDARTRISerialNumber
fwuHstDARTRIDateCode
fwuHstDARTRIHWVer
fwuHstDARTRowStatus
fwuHstDARTOverDriveFaultThreshold
fwuHstDARTUnderDriveFaultThreshold
fwuRmtNumber
fwuRmtCatalogState
fwuRmtName
Table 12-2. FlexWave-URH Agent MIB GET/SET Objects (Cont.)
Object Name Des cription SNMP Sy ntax Get
Operating mode of Host DART card
Diversity Status of Host DART card, where diversity is 1 and no diversity is 0
Primary Gain in forward path of Host DART card
Primary Gain in reverse path of Host DART card
Indicates if the Host SeRF FPGA can talk to the DART FPGA where 0 indicates that the SeRF can talk to the FPGA and 1 indicates that it cannot
FPGA Version on the Host DART card
Host DART Inventory Data-ADC Part Number
Host DART Inventory Data-Serial Number
MODEType SET
INTEGER SET
GAINType SET
GAINType SET
INTEGER GET
DisplayString GET
DisplayString GET
DisplayString GET
or SET
Host DART Inventory Data ­Date Code
Host DART Inventory Data-Hardware Version
Status of this conceptual row RowStatus SET
Threshold value for Host DART Card Over Drive. This is not user settable.
Threshold value for Host DART Card Under Drive. This is not user settable.
The Remote number of Remote connected (from 1 to
8)
Catalog state of Remote. If fwuRmtCatalogState is commission (2) state, commission Remote. If it is in normal (1) state, do not commission Remote
User defined name of the Remote, which can be up to 40 characters long
DisplayString GET
DisplayString GET
DisplayString SET
DisplayString SET
INTEGER GET
CATALOGTypeGET
DisplayString SET
Page 298 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
FlexWave-URH Agent MIB
fwuRmtAlarmStatusSummary
fwuRmtTempMeasurement
fwuRmtGeneralTableRowStatus
fwuRmtType
fwuRmtSERFLinuxKernelVer
fwuRmtSERFLinuxBootLoaderVer
fwuRmtSERFCompactFlashSWVer
fwuRmtSERFFPGAVer
fwuRmtSERFPPCHWMonSWVer
fwuRmtSERFPPCAPPMonSWVer
fwuRmtSERFPPCGPSMonSWVer
fwuRmtSERFPPCSNMPHTTPAgentSWVer
fwuRmtSERFPPCMATEMonSWVer
fwuRmtSERFPPCENETMonSWVer
fwuRmtSERFPPCFPGAMonSWVer
fwuRmtSERFRIDateCode
Table 12-2. FlexWave-URH Agent MIB GET/SET Objects (Cont.)
Object Name Des cription SNMP Sy ntax Get
Summary of alarm status of all connected remote units where:
•Normal = 1
•Minor = 2
•Major = 3
• Not Present = 0
Temperature of each Remote in Celsius. This value comes from the RSI
Status of this conceptual row RowStatus SET
Type of Remote: Prism or URH REMOTEType GET
Linux Kernel Version of the Remote system
Linux Boot loader Version of the Remote system
Compact Flash Software Version of the Remote system
ALARMType GET
DisplayString GET
DisplayString GET
DisplayString GET
DisplayString GET
or SET
Version of FPGA loaded on SeRF
Hardware monitor process Software Version of the Remote system
Application monitor process Software Version of the Remote system
GPS monitor process Software Version of the Remote system
SNMP agent Software Version of the Remote system
Mate monitor process Software Version of the remote system.
ENET monitor process Software Version of the Remote system
FPGA monitor process Software Version of the Remote system
DisplayString GET
DisplayString GET
DisplayString GET
DisplayString GET
DisplayString GET
DisplayString GET
DisplayString GET
DisplayString GET
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 299 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
Remote SeRF Inventory-Date Code of the Remote system
DisplayString GET
SNMP Interface
fwuRmtSERFRIHWRev
fwuRmtSERFRISerialNumber
fwuRmtSERFRIADCPartNumber
fwuRmtSERFOptSFPNumber
fwuRmtSERFOptSFPName
fwuRmtSERFOptSFPType
fwuRmtSERFOptSFPColor
fwuRmtSERFOptRevLaunchPowerMeas
fwuRmtSERFOptFwdLaunchPowerMeas
fwuRmtSERFOptMateName
fwuRmtSERFIPEnable
fwuRmtSERFOptRxBERFaultThreshold
fwuRmtSerfOptOverDriveFaultThreshld
fwuRmtSerfOptUnderDriveFaultThreshld
fwuRmtSERFOptRxBERFaultMask
Table 12-2. FlexWave-URH Agent MIB GET/SET Objects (Cont.)
Object Name Des cription SNMP Sy ntax Get
Remote SeRF Inventory ­Hardware Version of the Remote system
Remote SeRF Inventory-Serial Number
Remote SeRF Inventory-ADC Part Number
A unique identifier of each SFP (from 1 to 8)
User defined name of each Remote SFP.It can be 32 character long.
SFP Type-Optical Port Type OPTICSType GET
SFP wavelength in nanometer. Integer32 GET
Value of Remote Receive measured optical power in dbm
Value of Remote Transmit measured optical power in dbm
DisplayString GET
DisplayString GET
DisplayString GET
INTEGER GET
DisplayString SET
DisplayString GET
DisplayString GET
or SET
Name of Remote mate DisplayString GET
IP Enable mode for Host connected to the Remote that is carrying RF, where 1 equals enable
Threshold Value for declaring a Decoded word error state of the primary wavelength optical receiver (too many errors). This is not user settable.
Threshold value for declaring SFP over drive fault. This is not user settable.
Threshold value for declaring SFP under drive fault. This is not user settable.
Trap enable/disable for primary wavelength optical receiver; trap is enabled by default; if disabled, the trap will not be raised
Integer GET
DisplayString SET
Integer32 SET
Integer32 SET
MASKType SET
Page 300 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
FlexWave-URH Agent MIB
fwuRmtSERFOptOverDriveFaultMask
fwuRmtSERFOptUnderDriveFaultMask
fwuRmtSERFEthPortNumber
fwuRmtSERFEthPortType
fwuRmtSERFEthPortRxBytes
fwuRmtSERFEthPortRxPkts
fwuRmtSERFEthPortRxFscErrors
fwuRmtSERFEthPortRxBroadcastPkts
fwuRmtSERFEthPortRxMulticastPkts
fwuRmtSERFEthPortRxFragmtdFrames
fwuRmtSERFEthPortRxJabbersFrames
fwuRmtSERFEthPortTxByteCounter
fwuRmtSERFEthPortTxPkts
fwuRmtSERFEthPortTxBroadcastPkts
fwuRmtSERFEthPortTxMulticastPkts
fwuRmtSERFEthSFPID
fwuRmtDARTNumber
fwuRmtDARTName
fwuRmtDARTBandType
Table 12-2. FlexWave-URH Agent MIB GET/SET Objects (Cont.)
Object Name Des cription SNMP Sy ntax Get
Trap enable/disable for SFP Over Drive Fault. Trap is enabled by default. If disabled, the trap will not be raised.
Trap enable/disable for SFP Under Drive Fault; trap is enabled by default; if disabled, the trap will not be raised
A unique identifier for each Ethernet port (from 1 to 12)
An identifier for the type of Ethernet port
Receive byte counter Counter64 GET
Receive packet counter Counter64 GET
Receive FCS error counter Counter64 GET
Receive broadcast packet counter
MASKType SET
MASKType SET
Unsigned32 GET
ENETType GET
Counter64 GET
or SET
Receive multicast packet counter
Receive fragments counter Counter64 GET
Receive jabber counter Counter64 GET
Transmit byte counter Counter64 GET
Transmit packet counter Counter64 GET
Transmit multicast packet counter
Transmit broadcast packet counter
Identifier of SFP to which this Ethernet port connects to
A unique identifier for each DART Card Object of Remote (from 1 to 8)
A user defined name for each DART Card object of Remote, which can be up to 32 characters
Band type of Remote DART card
Counter64 GET
Counter64 GET
Counter64 GET
Unsigned32 GET
Integer32 GET
DisplayString SET
BANDType GET
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 301 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
SNMP Interface
fwuRmtDARTPassBand
fwuRmtDARTOperatingMode
fwuRmtDARTDiversityStatus
fwuRmtDARTForwardGain
fwuRmtDARTReverseGain
fwuRmtDARTForwardDelay
fwuRmtDARTReverseDelay
fwuRmtDARTTempMeas
fwuRmtDARTFPGAStatus
fwuRmtDARTFPGAProgramVer
fwuRmtDARTRIADCPartNumber
fwuRmtDARTRISerialNumber
fwuRmtDARTRIDateCode
fwuRmtDARTRIHWVer
fwuRmtDARTGeneralTableRowStatus
Table 12-2. FlexWave-URH Agent MIB GET/SET Objects (Cont.)
Object Name Des cription SNMP Sy ntax Get
Pass-band type of remote DART card.
Operating mode of Remote DART card
Diversity Status of Remote DART card, where diversity is 1 and no diversity is 0
Primary Gain in forward path of Remote DART card
Primary Gain in reverse path of Remote DART card
Forward Delay for Remote DART card Micro Seconds (from 1 to 500). If the Forward Delay value is not equal to Actual Forward Delay value then, then a Ranging fault will be raised if the Remote DART is Linked
Reverse Delay for Remote DART card Micro Seconds (from 1 to 500). If the Reverse Delay value is not equal to the Actual Reverse Delay value then, then a Ranging fault will be raised if the Remote DART is linked
PASSBANDTypeSET
MODEType SET
INTEGER SET
GAINType SET
GAINType GET
DELAYType SET
DELAYType SET
or SET
Page 302 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
Temperature value of Remote DART card
Indicates if the Remote SeRF FPGA can talk to DART FPGA where 0 indicates that the SeRF can talk to the DART and 1 indicates that it cannot
FPGA Version on the Remote DART card
Remote DART Inventory Data-ADC Part Number
Remote DART Inventory Data-Serial Number
Remote DART Inventory Data
- Date Code
Remote DART Inventory Data-Hardware Version
Status of a row in the DART General table
DisplayString GET
INTEGER GET
DisplayString GET
DisplayString GET
DisplayString GET
DisplayString GET
DisplayString GET
RowStatus SET
FlexWave-URH Agent MIB
fwuRmtDARTActualForwardDelay
fwuRmtDARTForwardLowerboundDelay
fwuRmtDARTForwardUpperboundDelay
fwuRmtDARTActualReverseDelay
fwuRmtDARTReverseLowerboundDelay
fwuRmtDARTReverseUpperboundDelay
fwuRmtDARTOverTempFaultMask
fwuRmtDARTUnderTempFaultMask
fwuRmtDARTOverTempThreshold
fwuRmtDARTUnderTempThreshold
fwuRmtGPSLongitudeDegrees
fwuRmtGPSLongitudeMinutes
fwuRmtGPSLongitudeSeconds
fwuRmtGPSLatitudeDegrees
fwuRmtGPSLatitudeMinutes
fwuRmtGPSLatitudeSeconds
fwuRmtGPSAltitudeMeters
fwuRmtGPSNumberOfSatellite
Table 12-2. FlexWave-URH Agent MIB GET/SET Objects (Cont.)
Object Name Des cription SNMP Sy ntax Get
Forward Delay for Remote DART
Lower bound forward delay value
Upper bound delay value Integer32 GET
Reverse Delay for Remote DART
Lower bound Reverse delay value
Upper bound Reverse delay value
Masking status of DART over Temp fault; masking is disabled by default.If enabled trap will not raised
Masking status of DART under Temp fault. Masking is disabled by default.If enabled trap will not raised
Integer32 GET
Integer32 GET
Integer32 GET
Integer32 GET
Integer32 GET
MASKType SET
MASKType SET
or SET
Threshold value for remote DART over temperature. This is not user settable.
Threshold value for remote DART under temperature. This is not user settable.
The GPS Longitude in Degrees (from -180 to 180)
The GPS Longitude in Minutes (from -59 to 59)
The GPS Longitude in milliseconds (from -5999 to
5999)
The GPS Latitude in Degrees (from -180 to 180)
The GPS Latitude in Minutes (from -59 to 59)
The GPS Latitude in milliseconds (from -5999 to
5999)
The GPS Altitude in Meters (from -180 to 180)
MASKType SET
MASKType SET
INTEGER GET
INTEGER GET
INTEGER GET
INTEGER GET
INTEGER GET
INTEGER GET
INTEGER GET
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 303 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
The Number of satellites discovered (from -180 to 180)
INTEGER GET
SNMP Interface
fwuRmtGPSFaultMask
fwuRmtLPANumber
fwuRmtLPAReset
fwuRmtLPAOpState
fwuRmtPowerDetectorNumber
fwuRmtSystemVSWRMeas
fwuRmtRFPowerOutputMeas
fwuRmtPwrDetectorBoardRIADCPartNum
fwuRmtPwrDetectorBoardRISerialNum
fwuRmtPwrDetectorBoardRIDateCode
fwuRmtPwrDetectorBoardRIHWVer
fwuRmtSystemVSWRFaultMask
fwuRmtNoRFPowerFaultMask
fwuRmtSystemVSWRFaultThreshold
fwuRmtLNANumber
fwuRmtLNAType
fwuRmtLNARIADCPartNumber
fwuRmtLNARISerialNumber
fwuRmtLNARIDateCode
Table 12-2. FlexWave-URH Agent MIB GET/SET Objects (Cont.)
Object Name Des cription SNMP Sy ntax Get
Shows masking status of GPS Fault; masking is disabled by default; if enabled, the trap will not be raised
A unique identifier for an LPA (from 1 to 4)
Set this object to a value of 1 to cause LPA to reset itself. Normal value is 0
Operating mode of Remote LPA, where normal is 0 and standby is 1
A unique identifier for each power detector (from 1 to 4)
VSWR (Voltage Standing Wave Ratio) measurement
The value of Remote RF Power Output in dBm
Power Detector Inventory-ADC Part Number
MASKType SET
Integer32 GET
INTEGER SET
INTEGER SET
Integer32 GET
DisplayString GET
DisplayString GET
DisplayString GET
or SET
Power Detector Inventory-Serial Number
Power Detector Inventory-Date Code
Power Detector Inventory-Hardware Version
System VSWR (Voltage Standing Wave Ratio) Fault
No RF Power Fault MASKType SET
Threshold value for System VSWR (Voltage Standing Wave Ratio) Fault. This is not user settable.
A unique identifier for LNA Objects (from 1 to 8)
Remote LNA card type BANDType GET
LNA Inventory Data-ADC Part Number
LNA Inventory Data-Serial Number
DisplayString GET
DisplayString GET
DisplayString GET
MASKType SET
Integer32 SET
Integer32 GET
DisplayString GET
DisplayString GET
Page 304 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
LNA Inventory Data-Date Code
DisplayString GET
FlexWave-URH Agent MIB
fwuRmtLNARIHWVer
fwuRmtLNAPowerFaultMask
fwuRmtRDINumber
fwuRmtRDIRIADCPartNumber
fwuRmtRDIRISerialNumber
fwuRmtRDIRIDateCode
fwuRmtRDIRIHWVer
fwuHstDARTOverDriveFaultMask
fwuHstDARTUnderDriveFaultMask
fwuRmtOverTempFaultMask
fwuRmtUnderTempFaultMask
fwuRmtOpenDoorFaultMask
fwuRmtFanOverSpeedFaultMask
Table 12-2. FlexWave-URH Agent MIB GET/SET Objects (Cont.)
Object Name Des cription SNMP Sy ntax Get
LNA Inventory Data-Hardware Version.
Shows masking status of Remote LNA Power Fault; masking is disabled by default; if enabled, the trap will not be raised
A unique identifier for each RDI (from 1 to 4)
RDI Inventory Data-ADC Part Number
RDI Inventory Data-Serial Number
RDI Inventory Data-Date Code DisplayString GET
RDI Inventory Data-Hardware Version
Shows masking status of Host DART Over Drive Fault; masking is disabled by default; if enabled, the trap will not be raised
DisplayString GET
MASKType SET
Integer32 GET
DisplayString GET
DisplayString GET
DisplayString GET
MASKType SET
or SET
Shows masking status of Host DART Under Drive Fault; masking is disabled by default; if enabled, the trap will not be raised
Show status of masking of Remote over temperature Fault; masking is disabled by default; if enabled, the trap will not be raised
Show status of masking of Remote Under Temperature Fault; masking is disabled by default; if enabled, the trap will not be raised
Show status of masking of Remote Open Door Fault; masking is disabled by default; if enabled, the trap will not be raised
Show status of masking of Remote Fan Over Speed Fault; masking is disabled by default; if enabled, the trap will not be raised
MASKType SET
MASKType SET
MASKType SET
MASKType SET
MASKType SET
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 305 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
SNMP Interface
fwuRmtFanUnderSpeedFaultMask
fwuRmtOverTempFaultThreshold
fwuRmtUnderTempFaultThreshold
fwuHMmonIndex
fwuHMmonRmtLocation
fwuHMmonRmtIPAddress
fwuHMmonRmtID
fwuHMmonHstSideSFPID
fwuHMmonRmtSideSFPID
fwuRMmonIndex
fwuRMmonHstIPAddress
fwuRMmonHstID
fwuRMmonRmtID
fwuRMmonHstSideSFPID
fwuRMmonRmtSideSFPID
fwuGeoHeartbeatTimer
fwuGeoIndex
fwuGeoLatitude
fwuGeoLongitude
fwuGeoRmtName
Table 12-2. FlexWave-URH Agent MIB GET/SET Objects (Cont.)
Object Name Des cription SNMP Sy ntax Get
Show status of masking of Remote Fan Under Speed Fault; masking is disabled by default; if enabled, the trap will not be raised
Threshold value for remote over temperature Fault. This is not user settable.
Threshold value for remote under temperature Fault. This is not user settable.
Index of mate monitor table. Integer32 GET
Location of Remote connected to Host
IP addresses of Remote IpAddress GET
ID of connected Remote REMOTENBRT
Slot ID of the SFP at Host end. Integer32 GET
MASKType SET
MASKType SET
MASKType SET
DisplayString GET
ype
or SET
GET
Slot ID of the SFP used at Remote end
Index of mate monitor table Integer32 GET
IP addresses of Host connected to the Remote
ID of Host connected to the Remote
ID of companion remote unit. REMOTENBRT
Slot ID of the SFP at Host end Integer32 GET
Slot ID of the SFP used at Remote end.
Specifies Heartbeat can be sent at the timer specified here, from 1 to 30
Geo objects Table Index. Unsigned32 SET
Identifies the Latitude of Remote
Identifies the Longitude of Remote
Integer32 GET
IpAddress GET
HOSTNBRType GET
GET
ype
Integer32 GET
INTEGER SET
DisplayString SET
DisplayString SET
Page 306 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
Identifies the Latitude of Remote
DisplayString GET
FlexWave-URH Agent MIB
fwuGeoStatus
fwuDARTMappingIndex
fwuHstID
fwuHstDARTID
fwuHstSFPID
fwuHstDARTPassBand
fwuRmtID
fwuRmtDARTID
fwuRmtSFPID
fwuRmtDARTPassband
fwuHstSFPStartTimeSlot
fwuHstSFPEndTimeSlot
fwuMappingStatus
fwuRmtUnitReset
Table 12-2. FlexWave-URH Agent MIB GET/SET Objects (Cont.)
Object Name Des cription SNMP Sy ntax Get
Identifies the Latitude of Remote
Index of the DART table. Unsigned32 GET
ID of the Host HOSTNBRType SET
ID of DART at Host to which the Remote DART is to be connected (from 1 to 8)
ID of host side SFP ID connected toward the remote DART. (from 1 to 8)
Pass-band type of Host DART card
ID of the Remote from which DART is to be connected
ID of Remote DART to which the Host DART will connect (from 1 to 8)
ID of Remote side SFP ID connected toward the Host DART (from 1 to 8)
INTEGER GET
INTEGER SET
INTEGER SET
PASSBANDTypeGET
REMOTENBRT ype
INTEGER SET
INTEGER SET
or SET
SET
Remote side Band-PassBand information of the linked darts
Start timeslot on the fiber that is carrying the DART traffic. This is a read-write object but it is not available for user to do a RW operation.
End timeslot on the fiber that is carrying the RF traffic from Host to Remote DART card. This is a Read-Write object, but is not available for user as a Read-Write operation.
Status of row RowStatus SET
Provides a way to reset the Remote SeRF card. Set to 1 to trigger a Remote reset
PASSBANDTypeGET
Integer32 SET
Integer32 SET
INTEGER SET
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 307 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
SNMP Interface
GET/SET
fwuHstSysCardFanFault
fwuHstModuleMissingFault
fwuHstOverTempFault
fwuHstUnderTempFault
fwuRmtModuleMissingFault
fwuRmtOverTempFault
fwuRmtUnderTempFault
fwuRmtOpenDoorFault
fwuRmtFanOverSpeedFault
fwuRmtFanUnderSpeedFault
fwuHstSERFSynthAlarmFault
fwuHstSERFFault
fwuHstSERFRmtLostFault
fwuHstSERFOptRxBERFault
fwuHstSERFOptRxNoLightFault
fwuHstSERFOptLaserFault
fwuHstSERFOptOverDriveFault
fwuHstSERFOptUnderDriveFault
fwuHstSERFOptIpEnableFault
fwuHstDARTDwnCon1SynLockFault
fwuHstDARTDwnCon2SynLockFault
fwuHstDARTUpConSynLockFault
fwuHstDARTOverDriveFault
12.7 TRAPS
The EMS receives traps from SNMP agents and converts them to alarms and non-alarmed events for further processing and reporting.
For information on
objects, see “FlexWave-URH Agent MIB” on page 292.
Table 12-3. FlexWave-URH Agent MIB Traps
Trap Object Description
Host System Card Fan fault
Host Module missing fault
Host Over Temperature fault
Host Under Temperature fault
Remote Module missing fault
Remote Over Temperature fault
Remote Under Temperature fault
Door on the Remote is open
Remote fan has an Over Speed fault
Remote fan has an Under Speed fault
Onboard synthesizer fault
Consolidation of SeRF Onboard synthesizer fault and SeRF FPGA Status
Remote Lost fault-Host not receiving any messages from connected Remote
Decoded word error state of the primary wavelength optical receiver (too many errors)
Receiving light state of the primary wavelength optical receiver (no light)
Error state of laser forward path
Host SFP Over Drive fault
Host SFP Under Drive fault
Host SFP IP Enable fault
Lock State of the first Down Converter synthesizer
Lock State of the second Down Converter synthesizer
Lock State of the Up Converter synthesizer
Host DART Card Over Drive fault. RF signal received from BTS is too high
Page 308 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
fwuHstDARTUnderDriveFault
fwuHstDARTFault
fwuHstDARTDCSupplyFault
fwuHstDARTHardwareMismatchFault
fwuRmtAcPowerSupplyFault
fwuRmtMajorExtAlarmInputFault
fwuRmtMinorExtAlarmInputFault
fwuRmtSERFHstLostFault
fwuRmtSERFOptRxBERFault
fwuRmtSERFOptRxNoLightFault
fwuRmtSERFOptLaserFault
fwuRmtSERFOptOverDriveFault
fwuRmtSERFOptUnderDriveFault
fwuRmtSERFSynthAlarmFault
fwuRmtSERFFault
fwuRmtDARTDwnCon1SynLockFault
fwuRmtDARTDwnCon2SynLockFault
fwuRmtDARTUpConSynLockFault
fwuRmtDARTDCSupplyFault
fwuRmtDARTFault
fwuRmtDARTHardwareMismatchFault
fwuRmtRangingFault
Table 12-3. FlexWave-URH Agent MIB Traps (Cont.)
Trap Object Description
Traps
Host DART Card Under Drive fault. RF Signal received from the BTS is too low
This fault is a consolidated fault of
fw uHstDARTDwnCon1SynLockFault, fw uHstDARTDwnCon2SynLockFault, fw uHstDARTUpConSynLockFault, fw uHstDARTFP
Host DART Card DC Supply fault
Indicates a hardware mismatch for the RF and optical cards between Host and Remotes
Remote AC Power Supply fault. This is an aggregation of
ACPowerSupplyMonitor1, ACP owerSupplyMonitor2, ACPowerSupplyMonitor3, ACP owerSupplyMonitor4
The remote Major Ext Alarm Input Fault
The remote Minor Ext Alarm Input Fault
Host Lost fault-Remote not receiving any messages from connected Host
Decoded word error state of the primary wavelength optical receiver (too many errors)
Receiving light state of the primary wavelength optical receiver (no light)
GAStatus and fwuHstDARTDCSupplyFault
Error state of laser forward path
Remote SFP Over Drive fault
Remote SFP Under Drive Fault
Onboard synthesizer fault
Consolidation of SeRF Onboard synthesizer fault and SeRF FPGA Status
Lock state of the first down converter synthesizer
Lock state of the second down converter synthesizer
Lock state of the Upconverter synthesizer
Remote DART Card DC Supply fault
Consolidated fault for
fw uRmtDARTDwnCon1SynLockFault, fw uRmtDARTDwnCon2SynLockFault, fw uRmtDARTUpConSynLockFault, fw uRmtDARTDCS
Indicate the hardware mismatch for the RF DART card between Host and Remotes
Host cannot auto-range a connected Remote anymore
upplyFault and DARTFPGAStatus
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 309 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
SNMP Interface
fwuRmtDARTOverTempFault
fwuRmtDARTUnderTempFault
fwuRmtGPSFault
fwuRmtLPADisableFault
fwuRmtLPAOverPowerFault
fwuRmtLPAHighTempFault
fwuRmtLPAVswrFault
fwuRmtLPADcFault
fwuRmtLPALoopFault
fwuRmtLPALowPowerFault
fwuRmtLPADetectFault
fwuRmtSystemVswrFault
fwuRmtNoRFPowerFault
fwuRmtLNAPowerFault
fwuRmtFanFault
fwuRmtACPowerSupplyMon4Fault
fwuRmtACPowerSupplyMon1Fault
fwuRmtACPowerSupplyMon2Fault
fwuRmtACPowerSupplyMon3Fault
fwuHstSysCardPrimaryCPFault
fwuHstSysCardSecondaryCPFault
Table 12-3. FlexWave-URH Agent MIB Traps (Cont.)
Trap Object Description
indicates a Remote DART Card Over Temperature Fault
Indicate the Remote DART Card Under Temperature Fault
Remote GPS fault
Disable state of the linear power amplifier
Internal over power fault state of linear power amplifier (power level is high enough to damage LPA)
Remote LPA High Temperature fault
Internal VSWR fault state of linear power amplifier (greater than 3:1)
Remote LPA DC fault
Remote LPA Loop fault
Internal low power fault state of linear power amplifier (the gain of one or more internal amplifiers does not meet specification)
Presence fault state of linear power amplifier (the LPA is missing)
Remote system Vswr fault
Remote No RF Power fault
Remote LNA power fault
Remote system VSWR fault. This object hasn't been implemented in this release
AC Power monitor 4 Fault
AC Power monitor 1 Fault
AC Power monitor 2 Fault
AC Power monitor 3 Fault
Primary Clock Priority Fault
Secondary Clock Priority Fault
Page 310 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
PART IV
APPENDICES
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 311 ADCP-77-073 • Issue 211/2009 © 2009 ADC Telecommunications, Inc.
Intentionally Blank Page
Page 312 FlexWave Prism Host, Remote and EMS 5.1 System Reference © 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
Loading...