Installation, operating and
maintenance instructions
ENFRRUPLDEITESNL
EN • 1
Delta P ro S / Delta Pro Pac k : 664Y4900 • E
Page 2
INDEX
ENFRRUPLDEITESNL
IMPORTANT NOTES3
Who should read these instructions3
Symbols3
Recommendations3
Certification3
Important notes3
DESCRIPTION4
Working principle4
Standard equipment4
Optional equipment4
Construction features4
Description of the boiler4
USER GUIDE6
Use of the boiler6
Domestic hot water connection14
Heating connection15
ACV burner oil supply16
ACV burner gas supply16
OPTIONAL CONTROLS18
Installing a high or low temperature heating system with
Control Unit
BMR 31 OIL BURNER FEATURES20
Description of the BMR 31 oil burner20
BMR 31 oil burner settings20
BMV OIL BURNER FEATURES21
Description of the BMV oil burner21
BMV oil burner settings21
BG 2000S GAS BURNER FEATURES22
18
Heating circuit pressure6
Getting to know the control panel6
Oil or gas burner lockout7
TECHNICAL CHARACTERISTICS8
General8
Maximum operating conditions8
General characteristics8
Domestic hot water performance8
Burner chamber plate for oil or blown gas burner8
Dimensions9
ELECTRICAL CONNECTION10
Electrical connection of the boiler10
INSTALLATION11
Recommendations for the prevention of corrosion and scaling11
ACV BG 2000-S premix burner22
BG 2000-S gas burner settings22
Gas categories23
COMMISSIONING AND MAINTENANCE25
Filling the hot water and heating circuits25
Boiler commissioning25
Recommendation25
Boiler maintenance25
Burner maintenance25
Maintenance of safety devices25
Draining of the boiler25
Draining the heating circuit25
Draining the DHW circuit25
SPARE PARTS www.acv.com
Boiler room12
Optional balanced flue connection kit12
B23 flue connection12
Type of flue connection13
Flue connection accessories15
Delta P ro S / Delta Pro Pac k : 664Y4900 • E
EN • 2
Page 3
IMPORTANT NOTES
WHO SHOULD READ THESE INSTRUCTIONS
These instructions should be read by:
- the design engineer/consultant
- the user
- the installer
- the service engineer
SYMBOLS
Essential instruction for the correct
operation of the installation
Essential instruction for the safety of
persons and the environment
Electrocution hazard:
use a qualified technician
ENFRRUPLDEITESNL
• Before carrying out any work on the boiler, it is import ant to isolate the
electrical supply to the unit.
• The user must not attempt to gain access to the components inside the
boiler or the control panel.
• This appliance c an be used by children aged f rom 8 years and above and
persons with reduced physical, sensory or mental capabilities or lack
of experience and knowledge, only if they have been given supervision
or instruction concerning use of the appliance in a safe way and
understand the hazards involved.
• Children shall not play with the appliance.
• Cleaning and user maintenance shall not be made by children unless
they are aged from 8 years and above and supervised.
• This appliance is not intended for use by persons (including children)
with reduced physical, sensory or mental capabilities, unless used
under the super vision of a person responsible for their safety.
• Children should be supervised to ensure that they do not play with the
appliance.
CERTIFICATION
The products have received EC certification in accordance with the
standards in force in various countries (European Directives 92/42/EEC
"efficiency requirements", 2009/142/EC "appliances burning gaseous fuels").
These products have also been awarded the Belgian "H R+" (gas boiler) and
"OPTIMAZ" (oil boilers) labels.
Burn hazard
RECOMMENDATIONS
• Carefully read this manual before installing and bringing the boiler into
service.
• It is prohibited to modify the interior of the appliance in any way,
without the manufacturer’s prior written agreement.
• The boiler must be installed by a qualified engineer, in accordance with
the applicable local standards and codes.
• Failure to follow the instructions describing test operations and
procedures could result in personal injury or a risk of environmental
pollution.
• In order to ensure the appliance operates safely and correctly, it is
important to have it serviced by an approved contractor.
• If there is a problem please contact your contractor for advice.
• In spite of th e strict quality s tandards that ACV applies to i ts appliances
during production, inspection and transport, faults may occur. Please
notify your approved contractor immediately of any faults.
• Defective par ts can only be replaced with original factory parts. You
will find a list of spare parts and their ACV reference number at the end
of this manual.
IMPORTANT NOTES
IF YOU SMELL GAS:
- Isolate the gas supply immediately.
- Ventilate the room (Open the windows).
- Do not use electrical appliances and do not operate switches.
- Notif y your gas supplier and/or your installer immediately.
These instructions are an integral part of the equipment to which they relate
and must be left for the user.
The product is to be installed and serviced by qualified technicians, in
accordance with current regulations.
The manufacturer declines all liability for any damage caused as a result of
incorrect installation or in the event of the use of appliances or accessories
that are not specified by the manufacturer.
The manufacturer reserves the right to change the technical
characteristics and features of its products without prior
notice.
The availability of certain models as well as their accessories
may vary according to markets.
• BG 2000-S gas burners are pre-adjusted in the factory for natural gas
[equivalent to G20].
• Specific regulation in Belgium:
The CO2, gas flow, air flow and air/gas supply parameters are adjusted
in the factory and cannot be changed in Belgium.
EN • 3
Delta P ro S / Delta Pro Pac k : 664Y4900 • E
Page 4
DESCRIPTION
WORKING PRINCIPLE
ENFRRUPLDEITESNL
The Delta Pro boiler is a high performance hot water producer using indirect
heat transfer due to its Tank-in-Tank technology.
At the centre of the Delta Pro there is a stainless steel cylinder through
which the flue tubes pass. It is surrounded by a mild steel shell containing the
primary water (neutral fluid). The outer shell extends down to the combustion
chamber and also surrounds the flue gas tubes. The heat exchange surface is
therefore larger than that of traditional direct fired hot water boilers.
The gas or oil b urner heats the primary f luid which indirectly heat s the stainless
steel cylinder containing the hot water. As with all Tank-in-Tank systems, the
cylinder is corrugated over its full height and suspended in the boiler by its hot
and cold water connections.
The fact that the cylinder expands and contracts as it is used and that cold
water is not in contac t with the intense heat of the burner f lame prevents scale
formation. This resistance to scale, along with the anti-corrosion properties of
the stainless steel mean that sacrificial anodes are not needed.
The Delta Pro has a major advantage over other hot water boilers: it heats hot
water with a primary circuit, which allows the primary fluid to also be used
for heating.
STANDARD EQUIPMENT
DELTA PRO S MODELS 25/45/55 HAVE THE
FOLLOWING COMPONENTS AS STANDARD:
- on/off switch
- summer/winter selector
- thermostat adjustable from 60°C to 90°C
- temperature-pressure gauge
- limit thermostat (auto-reset) 95°C
- manual reset safety thermostat 103°C
- primary safety valve 3Bar
- hot water safety valve 7Bar
- drain down valve
- body fully insulated with rigid polyurethane foam
DELTA PRO PACK MODELS 25/45 HAVE THE
FOLLOWING COMPONENTS AS STANDARD:
- on/off switch
- summer/winter selector
- thermostat adjustable from 60 °C to 90 °C
- temperature-pressure gauge
- limit thermostat (auto-reset) 95 °C
- manual reset safety thermostat 103 °C
- primary safety valve 3 Bar
- hot water safety valve 7 Bar
- manual four-way valve (servomotor available as an option)
- circulator with automatic air eliminator
- primary expansion tank 12 litres
- hot water expansion tank 2 litres
- drain down valve
- body fully isolated with rigid polyurethane foam
OPTIONAL EQUIPMENT
DELTA PRO S 25/45 & PRO PACK 25/45
- Balanced flue kit (except for Delta Pro S 55)
- Control Unit kit (Delta Pro Pack only)
- Servomotor (Delta Pro Pack only)
CONSTRUCTION FEATURES
CASING
The boiler is covered by a steel casing which has been scoure d and phosphated
before being stove enamelled at 220°C.
BOILER BODY
The boiler body containing the primar y fluid is constructed with STW 22 steel.
This is tested at a pressure of 4.5bar (maximumservice pressure = 3 bar).
TANKINTANK ACCUMULATOR/HEAT EXCHANGER
The internal ring-shaped inner tank is constructed from Chrome/Nickel 18/8
stainless steel and has a large heat exchange surface area to quickly heat the
water. It is corrugated over its height by an exclusive manufacturing process
and is entirely argon arc welded using the TIG (Tungsten Inert Gas) method.
COMBUSTION GAS CIRCUIT
This includes:
• The flue tubes:
The different DE LTA Pro models include, depending on their power, 4 or 8
steel flue tubes with an internal diameter of 64mm. Each tube is equipped
with a stainless steel turbulator designed to improve thermal exchange and
reduce flue gas temperature.
• The sealed combustion chamber:
The combustion chamber of all the DELTA Pro models is entirely water
cooled.
INSULATION
The boiler body is fully insulated by rigid polyurethane foam with a high
coefficient thermal insulation, sprayed-on without the use of CFCs.
DESCRIPTION OF THE BOILER
DELTA PRO S 25/45/55 & PRO PACK 25/45 MODELS
1. Flue reduction collar with easy access for servicing
2. Rigid polyurethane foam insulation
3. PVCC dip tube with cold water diffuser
4. Control thermostat bulb
5. Burner
6. Burner chamber plate with refractory ceramic fibre
insulation
7. Cut-off thermostat and manual reset safety thermostat
bulb
8. Flue tubes
9. Turbulators
10. Stainless steel "Tank-in-Tank" hot water cylinder
11. Primary circuit (heating)
12. Combustion chamber
13. Boiler base
14. Heating flow
15. Heating return
16. Domestic hot water outlet
17. Domestic cold water supply
18. Primary hot water safety valve [7 bar]
19. Primary heating safety valve [3 bar]
20. Flue connection Ø 100mm
21. Drain down valve
DELTA PRO PACK 25/45 MODELS
22. Hot water expansion tank [2 litres]
23. Heating circulator with built-in automatic air eliminator
24. Four-way mixer valve (optional motor)
25. Heating expansion tank [12 litres]
Delta P ro S / Delta Pro Pac k : 664Y4900 • E
EN • 4
Page 5
DESCRIPTION
Delta Pro S 25/45/55 models
1
14
7
16
2
8
3
9
4
5
10
11
12
19
15
18
17
20
ENFRRUPLDEITESNL
6
22
1
2
3
4
13
Delta Pro Pack 25/45 models
23
24
7
8
9
10
14
16
19
21
15
18
17
20
25
11
5
6
12
13
EN • 5
21
Delta P ro S / Delta Pro Pac k : 664Y4900 • E
Page 6
USER GUIDE
USE OF THE BOILER
ENFRRUPLDEITESNL
Please get your system serviced every year by a qualified
technician. More frequ ent servicing may be required depending
on boiler use . If this is the case, consult your installer for advice.
Starting the burner:
In normal operation, the burner starts automatically as soon as
Also switch the general switch on the control panel to “OFF”.
the boiler drops below the temperature set point.
Before the boiler is serviced, switch of f the electrical supply
with the external isolator.
HEATING CIRCUIT PRESSURE
The heating circuit pressure must be at least 1 bar and must be regularly
checked by the end user. Always make sure that the appliance is of f when
refilling the s ystem. To do this, use the ON/OFF switch. Fo r further information,
please contact your installer.
A safety va lve is provided under the appliance. If th e pressure of the installation
exceeds 3 bars , this valve opens and water from the system is drained off. If this
happens, please contact your installer.
GETTING TO KNOW THE CONTROL PANEL
1 - Control thermostat
If the boiler is only used for producing hot water, the boiler temperature may
be adjusted between 60°C and 90°C.
If the boiler is used for hot water and heating, the boiler’s control thermostat
will generally be set to 80°C for optimum operating conditions.
2 - General switch
This switch is used for starting and shutting down the boiler.
3 - Summer/Winter selector
This is used to turn the heating circulator on and of f (if connected directly to
boiler wiring).
4 - Temperature-pressure gauge
This gauge displays the boiler temperature and the pressure inside the primary
circuit. The temperature should not exceed 90 °C. If it is higher than this,
the boiler should be shut down and the thermostat settings checked. If the
problem persists, call a technician. The pressure should not fall below 1 bar.
If it does, consult the “Heating system pressure” paragraph further on in this
section.
5 - ACV controller (optional)
Refer to the controller instructions if you have this option.
6 - Manual reset safety thermostat
If the boiler temperature exceeds 103 °C, this safety device will shut down
the boiler and the overheat warning light will come on. To restart, the boiler
temperature must fall below 60 °C. Unscrew the cover and press the restart
button using a pen or a similar pointed object, then replace the cover. If the
problem persists, turn the boiler off and call a technician.
Water from the safety valve may be extremely hot
and causevery severe burns.
15
6
Delta P ro S / Delta Pro Pac k : 664Y4900 • E
43
2
EN • 6
Page 7
USER GUIDE
OIL OR GAS BURNER LOCKOUT
The safety warning light on the burner indicates an operational fault.
Wait five minutes and then reset the burner by pressing the “RESET” button
on the burner.
If the burner does not restart, call a technician after making sure that it is not
a power cut or that the oil/gas is of f.
If the oil or gas burner is not working, turn off the power to
the boiler using the external isolator before resetting the safety
thermostat on the control panel.
PUSH
Manual reset safety thermostat
Wait until the boiler temperature is below 60 °C before
switching on.
If the problem persists, please contact your installer.
ENFRRUPLDEITESNL
ACV oil burners
Starting the burner:
In normal operation, the burner starts automatically as soon as the boiler
drops below the temperature set point.
To make sure your system works correctly, please have it
serviced every year by a qualified technician before the heating
season.
REPAIRING THE BURNER
For all burners, please refer to the servicing and repair sections in the burner
manual.
ACV premix gas burners
EN • 7
Delta P ro S / Delta Pro Pac k : 664Y4900 • E
Page 8
TECHNICAL CHARACTERISTICS
GENERAL
ENFRRUPLDEITESNL
The units are delivered fully assembled, tested and packed on a timber base
with shockproof edges; the package is protected by a heat-shrunk plastic film.
Upon receipt and af ter unpacking, check th e equipment for transport dam age.
For transport purposes, refer to the dimensions and weights given below:
MAXIMUM OPERATING CONDITIONS
Maximum Service Pressure [DHW tank full of water]
- Primary circuit : ........................................................................................................................ 3 bar
- DHW circuit : ......................................................................................................................... 8,6 bar
- Recommended safety valve (central heating) : ...................................................... 3 bar
- Recommended safety valve (DHW) : ........................................................................... 7 bar
Mains supply pressure
Max 6 bar, without a pressure reducing valve being required (to avoid discharge
of the safety pressure valve).
Maximum Operating Conditions
Maximum temperature : 90°C
Domestic Hot Water Quality
See "Recommendations for the Prevention of Corrosion and Scaling"
GENERAL CHARACTERISTICS
BURNER CHAMBER PLATE
OIL OR BLOWN GAS
The burner chamber plate has 4 threads (M 8) for attaching the burner. It is
protected from heat by a blanket insulation.
5353
5353
Ø 112
4x Ø 6,5 (M8)
Delta Pro S &
Pro Pack 25
Delta Pro S &
Pro Pack 45Delta Pro S 55
Input power [Input]kW28,349,358,7
Useful nominal power [output]kW26,044,353,9
Eciency 80/60°C [max. output]%91,989,891,8
Total capacityL158127,5151
Primary capacityL8362,568
Heating connectionØ1" [F]1" [F]1" [F]
Domestic hot water connectionØ3/4" [M]3/4" [M]3/4" [M]
DHW cylinder heat exchange surfacem1,591,992,46
Water pressure drop boiler at ∆t = 20°Cmbar152537
Flue gas circuit pressure dropmbar0,250,300,45
DOMESTIC HOT WATER PERFORMANCE
System operating at 80°C
Peak ow rate at 40°C [
Peak ow rate at 40°C [
Continuous ow rate at 40°C [
Tank rell time at 60°C
T = 30°C]L/10'268316362
T = 30°C]L/60'80612841533
T = 30°C]L/h64511611405
Delta Pro S &
Pro Pack 25
Delta Pro S &
Pro Pack 45Delta Pro S 55
Initial heating timeMinutes321616
After drawing o 140litres at 45°CMinutes1597
Delta P ro S / Delta Pro Pac k : 664Y4900 • E
EN • 8
Page 9
TECHNICAL CHARACTERISTICS
DIMENSIONS
Delta Pro S 2516155405841386360200100220144514459281400—145
Delta Pro S 4516155405841386390200100220144514459281400—168
Delta Pro S 5517605405841586390200100220164516459281600—200
Delta Pro Pack 25176054058413863606310022017231445—1400128145
Delta Pro Pack 45176054058413863906310022017231445—1400128168
(*) Empty weight without burner
A
[mm]B[mm]C[mm]D[mm]E[mm]F[mm]
Ø G
[mm]H[mm]I[mm]J[mm]K[mm]L [mm]M[mm] Kg (*)
Delta Pro Pack 25/45Delta Pro S 25/45/55
CB
CB
ENFRRUPLDEITESNL
A
D
E
F
G
I
K
H
J
L
AA
D
E
G
I
H
F
M
J
L
EN • 9
Delta P ro S / Delta Pro Pac k : 664Y4900 • E
Page 10
ELECTRICAL CONNECTION
ELECTRICAL CONNECTION
ENFRRUPLDEITESNL
SUPPLY PRINCIPLE
The boiler uses a single phase supply at 230 V - 50 Hz. A mains isolator with 6A
mcb (5A fuse) must be fitted outside the boiler to allow the power to be shut
off during servicing and before any repairs are carried out.
COMPLIANCE
The installation must comply with current regulations.
SAFETY
The hot water circuit must be connected separately to earth.
The power to the boiler must be isolated before any work is
carried out on it.
1. Boiler supply
2. On/off switch
3. Safety thermostat [103°C max.]
4. Summer/winter selector
5. Control thermostat [60/90°C]
6. Cut-off thermostat [95°C max.]
7. Connection terminal
8. Burner connection plug [7 pin]
9. Room thermostat connection (optional)
10. Connection of the heating circulator
[optional except for on Pro Pack]
B. Blue
Br. Brown
Bk. Black
G. Grey
Gr. Green
Or. Orange
V. Violet
Y/Gr. Yellow/Green
Y/Gr
Y/Gr
3
2
Or
1
Or
1
Or
Y/Gr
4
P
Bk
Bk
2
2a
Br
Y/Gr
B
1
1a
B
Y/Gr
B
Br
1 23 47101311171214 15 16
B
Br
Y/Gr
5 6
1a
V
V
B
Y/Gr
V
Y/Gr
B
Or
B
8 9
Y/Gr
B
Br
Bk
B
Br
1
t
4
C
M
109
LPEN
230 V ~ 50 Hz
6A
Br
Y/GrBBk
1
5
tt
4
6
t
4
Bk
G
Gr
G
T2 S3T1NL1B4
Bk
Or
V
Y/Gr
Y/Gr
Gr
1
C
1
C
7
8
Delta P ro S / Delta Pro Pac k : 664Y4900 • E
EN • 10
Page 11
INSTAL LATION
RECOMMENDATIONS FOR THE PREVENTION
OF CORROSION AND SCALING
HOW OXYGEN AND CARBONATES CAN AFFECT THE
HEATING SYSTEM
Oxygen and dissolved gasses in the water of the primary circuit
contribute to the oxidation and the corrosion of the system components
that are made of ordinary steel (radiators, ...). The resulting sludge is then
deposited in the boiler exchanger.
The combination of carbonates and carbon dioxide in the water results
in the formation of scale on the hot sur faces of the installation, including
those of the boiler exchanger.
These deposits in the heat exchanger reduce the water flow rate and
thermally insulate the exchange surfaces, which is likely to damage
them.
Sources of oxygen and carbonates in the heating circuit
The primary circuit is a closed circuit; the water it contains is therefore
isolated from the mains water. When maintaining the system or filling
up the circuit, water renewal results in the addition of oxygen and
carbonates in the primary circuit. The larger the water volume in the
system, the larger the addition.
Hydraulic components without an oxygen barrier (PE pipes and
connections) admit oxygen into the system.
4. Limit the carbonate concentration in the water
- T he fill water must be sof tened if its hardness is highe r than 20° fH
(11,2° dH ).
- Check regularly the water hardness and enter the values in the
service log.
- Water hardness table :
Water hardness°fH°dHmmolCa(HCO3)2 / l
Very soft0 - 70 - 3.90 - 0.7
Soft7 - 153.9 - 8.40.7 - 1.5
Fairly hard15 - 258.4 - 141.5 - 2.5
Hard25 - 4214 - 23.52.5 - 4.2
Very hard> 42> 23.5> 4.2
5. Control the heating water parameters
- In addition to the oxygen and the water hardness, other
parameters of the water must be checked.
- Treat the water if the measured values are outside the range.
Acidity6,5 < pH < 8,5
Conductivity< 400 μS/cm (à 25°C)
ENFRRUPLDEITESNL
PREVENTION PRINCIPLES
1. Clean the existing system before installing a new boiler
- Before the system is filled, it must be cleaned in accordance with
standard EN14868. Chemical cleaning agents can be used.
- If the circuit is in bad condition, or the cleaning operation was not
efficient, or the volume of water in the installation is substantial
(e.g. cascade system), it is recommended to separate the boiler
from the heating circuit using a plate-to-plate exchanger or
equivalent.
2. Limit the fill frequency
- Limit fill operations. In order to check the quantity of water that
has been added into the system, a water meter can be installed
on the filling line of the primary circuit.
- Automatic filling systems are forbidden.
- If your installation requires frequent water refilling, make sure
your system is free of water leaks.
3. Limit the presence of oxygen and sludge in the water
- A deaerator (on the boiler flow line) combined with a dirt
separator (upstream of the boiler) must be installed according to
the manufacturer's instructions.
- ACV recommends using additives that keep the oxygen in
solution in the water, such as Fernox (www.fernox.com) and
Sentinel (www.sentinel-solutions.net) products.
- The additives must be used in accordance with the instructions
issued by the manufacturer of the water treatment product.
Chlorides< 125 mg/l
Iron< 0,5 mg/l
Copper< 0,1 mg/l
EN • 11
Delta P ro S / Delta Pro Pac k : 664Y4900 • E
Page 12
INSTAL LATION
BOILER ROOM
ENFRRUPLDEITESNL
- The flue connection must be carried out in compliance with the standards
in force, for example NBN D51-003, taking account of local energy supplier
and fire regulations as well as regulations relating to “noise pollution”.
- Make sure that all air vents are unobstructed.
- Do not store flammable products in the boiler room.
- Make sure that corrosive products, such as paint, solvents, chlorine, salt,
soap and other cleaning products, are not stored near to the boiler.
- The boiler must be placed on a non-combustible surface.
Accessibility
The boiler room must be large enough to allow good access to the boiler. The
following minimum distances are required around the boiler: (500 mm in
front, 200mm to the sides, 150mm behind and 700mm above).
OPTIONAL BALANCED FLUE
CONNECTION KIT
Available only for Delta Pro S & Pro Pack 25/45 models.
(code : 10800264)
B23 FLUE CONNECTION
IM POR TANT:
The boiler is to be installed by a qualified engineer,
Boiler room ventilation
The boiler room must be fitted with top and bottom vents.
Given that regulations var y from one country to thenext, these
Each installer must ensure that boiler room ventilation
Flue diameter type B23
inaccordance with current regulations.
The diameter of the Flue must not be smaller thanthat of the
boiler’s flue reduction collar.
The tables below give the values defined according toBelgian
regulations.
tables are given for information only.
complies with current regulations.
Height
5 m10 m15 m
Delta Pro S 25
Ø mm120100100
Delta Pro Pack 25
Delta Pro S 45
Ø mm160140125
Delta Pro Pack 45
Delta Pro S 55Ø mm180150135
Delta P ro S / Delta Pro Pac k : 664Y4900 • E
EN • 12
Page 13
INSTAL LATION
TYPE OF FLUE CONNECTION
B23 : Connection to a flue with the combustion air taken directly in the
boiler room.
B23P : Connection to an exhaust system of the combustion products
designed to operate with positive pressure.
C13 : Connection by pipes with horizontal terminals that simultaneously
take in combustion air for the burner and discharge combustion
products outside through openings that are either concentric or
close enough together to be subjected to similar wind conditions.
C33 : Connection by pipes with vertical terminals that simultaneously take
in fresh air for the burner and discharge the combustion products
outside through openings that are either concentric or close enough
together to be subjected to similar wind conditions.
C43 : Connection by two ducts to a collective duct system serving more
than one appliance; this system of collec tive ducts features two ducts
connected to a terminal unit that simultaneously takes in fresh air for
the burner and discharges the combustion products outside through
openings that are either concentric or close enough together to be
subjected to similar wind conditions.
ENFRRUPLDEITESNL
C53 : Connection to separate ducts for the supply of combustion air and
for venting the combustion products; these ducts may end in zones
with different pressure levels.
C63 : Type C boiler which is intended for connection to a room sealed f lue
system which is approved and sold separately.
(Prohibited in Belgium).
Due to the high efficiency of our boilers, the flue gases are
released at low temperature. As a result, there is a risk of
condensation of the flue gases, which could damage some
chimney constructions; to avoid this risk, it is strongly
recommended to line the chimney. To prevent condensates
to flow back into the boiler, we strongly advise to install a
condensates collector. Please contact your installer for more
information.
Connection type
ModelsBurnersB23B23PC13C33C43C53C63
BMV1 / BMR-31 / BMe1
Delta Pro S 25 &
Delta Pro Pack 25
Delta Pro S 45 &
Delta Pro Pack 45
Delta Pro S 55
BMV1-FV
BG 2000-S 25
BG 2000-SV 25
BMV2
BMV2-FV
BG 2000-S 45
BG 2000-SV 45
BMV2
BG 2000-S 55
For concentric connection, the total leng th of the flue must be no more than 6 metres and no less than 1metre (including the terminal).
For double pipe connection (only with gas) :
Gas = 10 metres + 4 pipe bends
EN • 13
Delta P ro S / Delta Pro Pac k : 664Y4900 • E
Page 14
INSTAL LATION
ENFRRUPLDEITESNL
Boiler room ventilation
Delta Pro S & Pro Pack
A = Top ventcm
B = Bottom ventcm
C = Draught regulatormmØ 100
Flue connection options
2
2
150
180
B23P
B
C13
AAA
A
C43
C43
C33
AAA
B23
C53
Delta P ro S / Delta Pro Pac k : 664Y4900 • E
C
B
EN • 14
Page 15
INSTAL LATION
FLUE CONNECTION ACCESSORIES
Concentric Stainless steel - Stainless steel Ø 100/150 mm
A
TERMINALS
CodeItem SIZE
537D6197 Vertical terminal1515 mm
537D6198 Horizontal terminal with wall plates
B
DUCTS
CodeItem SIZE
537D6199 Length 250 mm210 mm
537D6200 Length 500 mm460 mm
537D6201 Length 1000 mm960 mm
C
ADJUSTABLE DUCT
CodeItem
537D6202 Length adjustable from 325 to 400
D
PIPE BENDS
CodeItem
537D6203 43°-45° bend
537D6204 87°-90° bend
795 mm
C13C33
A
255540
D
F
ENFRRUPLDEITESNL
240630
190
B
E
CONDENSATION MEASURING AND
COLLECTION DEVICE
CodeItem SIZE
537D6226 Condensate collector and measuring tube140 mm
F
ACCESSORIES
CodeItem SIZE
537D6208 Flat roof ashing (base Ø 430mm)110 mm
537D6209 Adjustable ashing
537D6210 Attachment Ø 150mm
G
ADAPTER
CodeItem SIZE
537D6207
F
BALANCED FLUE CONNECTION
CodeItem
10800264
Parallel concentric adapter
Ø 100/150 mm - 2 x Ø 100 mm205 mm
Balanced ue connection kit
F
B
C
295
270
D
E
EN • 15
Delta P ro S / Delta Pro Pac k : 664Y4900 • E
Page 16
INSTAL LATION
DOMESTIC HOT WATER CONNECTION
ENFRRUPLDEITESNL
EXAMPLE OF CONNECTION WITH
THERMOSTATIC MIXER VALVE
1. 7 bar hot water safety valve (as standard)
2. Pressure reducer
3. Temperature control valve
4. Hot water circulator (optional)
5. Non-return valve
6. Hot water expansion tank (as standard on Pro Pack, 2 litres)
7. Cold water feed valve
8. Hot water outlet
9. Drain down valve
10. Syphon valve
11. Isolating valve
4
5
6
7
2
5
3
11
10
Pressure reducer
If the water mains pressure is greater than 6 bar, a pressure reducer calibrated
to at least 4.5 bar must be fitted (UK regulations apply).
Hot water safety valve
The hot water safety valve is at 7 bar; valve discharge must be connected to
drain (UK regulations apply).
Hot water expansion tank (as standard on Pro Pack, 2 litres)
Installing a hot water expansion tank avoids any risk of pressure surges due to
water hammer or pressure variations.
Optional hot water circulation
If the tank is situated a long way from the point of use, theninstalling a closed
return circuit can provide a faster supply of hot water at all times.
IM PORTA NT
As a safety measure against burns, we strongly
recommend installing a thermostatic mixer.
8
Optional fittings available
Pressure reducerØ 3/4"
1
9
Temperature mixing valveØ 3/4"
Expansion tank5 litres
If there is a risk of low pressure in the hot water circuit
(installation of a Delta Pro S & Pro Pack on the roof of a
building), it is essential to install a vacuum breaker device onto
the cold water supply.
IM PORTANT
It is essential that the DHW cylinder is filled and pressurised
before filling the heating circuit.
Delta P ro S / Delta Pro Pac k : 664Y4900 • E
EN • 16
Page 17
INSTAL LATION
HEATING CONNECTION
EXAMPLE OF A BASIC CIRCUIT CONNECTION
1. Four-way motorisable mixer valve
2. Circulator (as standard on Pro Pack)
3. Heating isolating valve
4. System filling valve
5. 3 bar heating safety valve
(as standard)
6. Primary expansion tank (as standard on Pro Pack)
7. Control unit (optional)
8. Drain down valve (as standard)
(as standard on Pro Pack)
3
1
3
2
OIL SUPPLY FOR ACV BURNERS
Supply construction and installation must be in accordance with current
regulations.
For further information regarding the oil supply, please
consult the technical manual supplied with the burner.
If a different burner is installed, please refer to the
manufacturer’s technical manual.
GAS SUPPLY FOR ACV BG 2000S BURNERS
- The Delta Pro S & Pro Pack boilers combined with an ACV BG 2000-S
burner have a Ø 3/4” [F] gas connection for connection of a g as supply valve.
- The gas connections must comply with all applicable standards (in Belgium:
NBN D51-003).
- If there is a risk of dirt stemming from the gas network, place a gas filter
upstream of the connection.
- Purge the gas pipe and carefully check that there are no leaks on the boiler’s
internal and external pipes.
- Check the system’s gas pressure. Please refer to the technical data table.
- Check the gas pressure and consumption when commissioning the
appliance.
ENFRRUPLDEITESNL
7
5
4
6
8
DRAIN VALVE
The safety valves must be connected to the drain.
DELTA PRO PACK HYDRAULIC KIT
This hydraulic kit is factory assembled on Delta Pro Pack 25 and Delta Pro
Pack 45 models comprising:
• A circulator with automatic air eliminator built in.
• A four-way manual motorisable valve (servomotor available as an option).
• A primary 12 litres expansion tank.
• A hot water 2 litres expansion tank.
EN • 17
Delta P ro S / Delta Pro Pac k : 664Y4900 • E
Page 18
CONTROL
INSTALLATION OF A HIGH OR LOW HEATING CIRCUIT
ENFRRUPLDEITESNL
WITH CONTROL UNIT
SCHEMATIC DIAGRAM
The heating (high temperature or floor heating) is controlled by the AF200
outside temperature detector supplied with the Control Unit and by the RFF
room detector or RS Zone Unit.
The detectors are connected to a controller that can be built into the boiler.
This controller operates the four-way valve and the circulator depending on
requirements (calculated from the outside temperature) and on the start
temperature measured by a third detector.
- The system provides a high level of comfort as the start temperature is
constantly adapted to heating requirements.
- Built-in timer with setting of heating times (day) and lower temperature
times (night).
- The room detector allows the user to adjust the comfort setpoint to their
specific requirements.
Zone Unit / RFF
AF200
Control Unit
RAM
VF202
Equipment required
asoptionsCodesDescriptions
10800188
10800108
10800056
ou
10800120RTF room sensor
10800045
10510900
Control Unit :
Supplied with an AF200 outside detector and a 2 kΩ KVT bulb sensor
AF200 2 kΩ outside temperature sensor :
Included with control unit
RS Zone Unit :
Remote control + room sensor
VF202 2 kΩ contact sensor :
For outlet on controlled circuit
RAM 5409 contact thermostat :
Obligatory to protect oor heating circuits
10800199
Delta P ro S / Delta Pro Pac k : 664Y4900 • E
ARA661 servomotor :
Motor for four-way valve
EN • 18
Page 19
CONTROL
Wiring diagram for the intermediate base for connection to the Control Unit
This new generation of oil burners meets current gas performance and hygiene requirements. The burner is fitted with top quality components using the latest
technology and the oil is preheated.
For further information, please consult the technical manual supplied with the burner.
Delta Pro S &
BMR 31 OIL BURNER SETTINGS
Burner typeBMR 31
Input powerkW25
NozzleTypeSteinen
Gal/h0,65
Angle45°H
Pump pressurebar10,5
Blast tube pressurembar3,2
V = Air valve position2 - 3
X = Nozzle line2
Y = Distance between burner and angemm40
Z = Setting screw of the air valvemm20
Pro Pack 25
Y
3
1
2
7
4
6
5
10
9
8
11
Z
V
X
DIMENSIONS
BMR 31240270215280135M 8,5808115012
B
A
mm
B
mm
C
mm
D
mm
G
C
1. Control box
2. Electrical connection
3. Blast tube
4. Ignition unit
5. Oil pump
6. Motor
7. Indication lamp / reset button
8. Oil pre-heater
9. Fixing flange
10. Baffle plate
11. Motor condenser
E
mm
F G ø
mm
L ø
mm
LK ø
mmKg
L
LK
Delta P ro S / Delta Pro Pac k : 664Y4900 • E
F
EN • 20
Page 21
BMV OIL BURNER FEATURES
DESCRIPTION OF THE BMV OIL BURNER
For our DELTA Pro S & Pro Pack boilers, we have opted for the latest technology of ACVBMV1 and BMV2 boilers, which involves a third-generation transparent
flame burner. The advantages of this burner construction lie in operation saving the maximum amount of energy with very low emissions of harmful substances
(approval according to EN 267:1999-11, category 3, the German ‘Blue Angel’ environmental label, according to RAL-UZ 9, approval in accordance with the Swiss Air
Purity Act (LRV) a fan that can withstand extreme pressure and a structure that is easy to service. We draw your attention to the fact that installation, commissioning
and servicing should be carried out by a specialist company. These installation and servicing instructions contain important information on this subject. To make sure
the system operates at all times in such a way as to save energy and release few harmful substances, we recommend that you have your burner inspected every year
by a specialist company.
For further information, please consult the technical manual supplied with the burner.
The BG 2000-S air/gas premix burner has a Honeywell gas valve, a venturi
tube and an electric control relay. The gas valve has been specially designed
for low NOx air/gas premix burners with automatic ignition and ionisation
flame detection.
The output pressure of the gas valve is equal to the air pressure at the neck of
the venturi tube, less the limit of the offset adjustment. The fan takes in the
combustion air through the venturi tube into which the gas inlet opens. As it
passes through, the air creates a dif ferential across the neck of the venturi tube
and draws in the gas at the venturi tube outlet. A perfect air/gas mix passes
through the fan and is then to the burner tube.
The electric control relay attached to the gas valve ensures that the burner
flame is ignited and controlled correctly.
This principle guarantees safe and quiet operation:
• In the event of low air f low, the differential across the venturi tube falls, the
gas flow rate diminishes, the flame extinguishes and the gas valve closes: the
burner is then in lockout.
• In the event of flue blockage or restriction, the air flow rate falls, then the
same reactions as those described above causing burner lockout.
Air/gas mix control principle
A. Air
B. Gas
C. Venturi tube
D. Fan
E. Air – Gas mix
F. Offset adjustment screw
G. Gas flow rate adjustment screw
It is essential that the DHW cylinder is filled and pressurised
before filling the heating circuit.
1. Fill the DHW circuit and bring it up to pressure.
2. Fill the heating circuit taking care not to exceed the 2bar pressure limit.
3. Vent the air from the top of the boiler.
4. After venting the air from the system, bring the pressure up to the static
head plus 0.5 bar.
Head of the heating system:
• 10 m ➠ heating circuit pressure = 1.5 bar
• 15 m ➠ heating circuit pressure = 2 bar
BOILER COMMISSIONING
1. Check the gas or oil supply connection and make sure there are no leaks.
2. Check the boiler power connection, the boiler room ventilation and
ensure that there are no leaks in the combustion gas discharge pipes or
the burner chamber plate.
3. Set the boiler thermostat or potentiometer to between 60°C and 90°C.
4. Set the Summer/Winter selector to the desired position.
5. Put the ON/OFF switch to the ON position.
6. Carry out the required venting, measurement and setting procedures.
DRAINING OF THE BOILER
Water f lowing out of the drain cock is very hot and can
cause severe burns. Keep people away from discharges
of hot water.
DRAINAGE OF THE HEATING CIRCUIT
1. Turn the ON/OFF switch on the control panel to the OFF position,
isolate the boiler’s external electrical supply and close the gas or oil
supply valve.
2. Close the isolating valves (3) on the heating circuit.
3. Connect a flexible hose to the drain valve (8).
4. Open the drain valve (8) to empty the heating circuit.
DRAINAGE OF THE DHW CIRCUIT
1. Turn the ON/OFF switch on the control panel to the OFF position,
isolate the boiler’s electrical supply and close the gas or oil supply valve.
2. Lower the heating circuit pressure until the gauge indicates zero
pressure.
3. Close the valves (7 and 11).
4. Open the valves (9 and 10) (9 f irst then 10).
5. Let the hot water circuit empty into the drain.
ENFRRUPLDEITESNL
RECOMMENDATION
ACV advises that boilers should be serviced at least once a year. This service
and any boiler inspections must be carried out by a qualified technician.
BOILER MAINTENANCE
1. Switch off the power at the external isolator and shut off the gas or oil
supply.
2. Set the on/off switch on the control panel to the OFF position.
3. Remove the top cover of the boiler (A).
4. Take off the top of the Flue reduction (B).
5. Remove the turbulators (C) from the flue pipes (D) for cleaning.
6. Remove the burner chamber plate [E].
7. Brush the flue pipes (D).
8. Clean the combustion chamber (F) and the burner.
9. Check the condition of the burner chamber plate insulation [H] and
replace if necessary.
BURNER MAINTENANCE
Refer to the burner’s service and repair instructions.
MAINTENANCE OF SAFETY DEVICES
- Check that all thermostats and safety devices are working properly:
boiler thermostat, cut-off thermostat and manual reset safety
thermostat.
- Check the safety valves of the heating and DHW circuits.
The drain valve (9) must be at ground level to allow the cylinder
to drain.
Water flowing out of the safety valve or the safety unit
may be extremely hot and could cause severe burns.
EN • 25
Delta P ro S / Delta Pro Pac k : 664Y4900 • E
Page 26
COMMISSIONING AND MAINTENANCE
A
ENFRRUPLDEITESNL
B
D
C
F
H
E
4
5
6
7
2
5
1
3
8
11
10
3
3
2
1
9
Delta P ro S / Delta Pro Pac k : 664Y4900 • E
7
5
4
6
8
EN • 26
Page 27
ENFRRUPLDEITESNL
EN • 27
Delta P ro S / Delta Pro Pac k : 664Y4900 • E
Page 28
ENFRRUPLDEITESNL
Delta P ro S / Delta Pro Pac k : 664Y4900 • E
EN • 28
Page 29
ENFRRUPLDEITESNL
EN • 29
Delta P ro S / Delta Pro Pac k : 664Y4900 • E
Page 30
ENFRRUPLDEITESNL
Delta P ro S / Delta Pro Pac k : 664Y4900 • E
EN • 30
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.