7. ELECTRICAL SPECIFICATIONS AND CABLING DIAGRAMS 17
8. PUFFER RANGE 24
9. DOMESTIC HOT WATER STORAGE RANGE 25
10. SINGLE COIL RANGE 26
11. HEAT PUMP COIL RANGE 27
12. DOUBLE COIL RANGE 28
13. INSTALLATION OF HYDRAULIC ACCESSORIES 29
14. INSTALLATION OF THE INSULATION 30
15. COMMISSIONING 31
16. SHUTDOWN OF THE SYSTEM 31
17. USER RECOMMENDATIONS 32
18. MAINTENANCE AND CLEANING 33
19. TROUBLESHOOTING 34
20. WARRANTY 35
EN 5 Document ref.: 42801603
EN 6 Document ref.: 42801603
1. RECOMMENDATIONS
1-1 General recommendations
1. This very important manual is an indispensable part of
the appliance.
The manual must be kept in a safe place and must be
passed onto any subsequent owners or users of the
appliance and/or in the event that the boiler is
transferred to another site.
2. Read the instructions and advice provided carefully, as
this will help you to ensure your appliance is safely
installed, used and maintained.
3. The purchaser is responsible for installation, which
must be carried out by an industry professional in
accordance with the instructions in the manual.
4. Any use of the appliance other than that stipulated
herein is prohibited.
The manufacturer shall in no way be held liable for any
damages arising from the improper, incorrect or
unreasonable use of the appliance or failure to follow
the instructions contained in this manual.
5. Installation, maintenance and all other operations
must be carried out by industry professionals according
to the applicable regulations and the indications
provided by the manufacturer.
6. The manufacturer accepts no liability for any personal
injuries, injuries to animals or damage to goods as a
result of any incorrect installation
of the appliance.
7. The packaging (clips, plastic bags, expanded
polystyrene, etc.) must be kept out of the reach of
children.
8. This appliance is not designed for use by persons
(including children) with reduced physical, sensory or
mental capacities, or who do not have sufficient
knowledge or experience, unless they have benefited
from supervision and instruction concerning the use of
the appliance by the person responsible for their safety.
9. Children must be supervised to ensure they do not
play with the appliance
10. Do not touch the appliance with your bare hands or
any wet body parts.
11. For all repairs, call an accredited technician and insist
that genuine spare parts are used. Failure to comply with
these instructions could compromise safety and shall
exempt the manufacturer from all liability. Before
carrying out any repair and/or maintenance operation
on the unit, it is important to isolate all supply sources.
In case of a malfunction in the unit, switch it off and
phone technical assistance.
12. No inflammable objects must be kept near the
appliance.
13. Correct usage also includes following the instructions
for use and installation, and adhering to any additional
documentation, as well as
the inspection and maintenance conditions.
14. Any use outside these conditions is forbidden.
1-2 User recommendation
Before installing the appliance, please read the
instructions in this manual carefully. Failure to comply
with them will invalidate the warranty.
The purchaser is responsible for installing the product.
Installation, start-up, maintenance and repairs must only
be carried
out by a qualified professional in accordance with
industry practice and applicable national standards. It is
essential to comply with all prescriptions relating to
domestic hot water tanks, as well as the instructions
supplied by the manufacturer.
To prevent burns, use suitable mixing devices to avoid
exceeding a temperature of 50°C at the catchment
points.
If the appliance is inactive for a prolonged period (e.g.
during winter holidays) in an unheated area, water may
freeze in the appliance and the pipes. Ensure that the
installation is protected from freezing.
If any accessories are installed on the unit, they must
only be original parts from the manufacturer.
To clean the exterior of the unit, it is recommended to
use a damp cloth and cleaning products intended for this
purpose.
The use of abrasive products or solvents is strongly
discouraged.
No inflammable objects must be kept near the
appliance.
GENERAL SAFETY STANDARDS
Failure to respect the warnings could result in injury and
may even lead to death.
Failure to comply with warnings could result in serious
damage to objects, plants or animals.
The general and specific safety standards relating to the
product must be observed.
Do not carry out any operation which requires the
appliance to be opened.
Burn injuries from hot components or injuries caused by
parts that protrude or by sharp edges.
Do not carry out any operation which requires the
appliance to be moved.
Contact with live components can cause electrocution.
Flooding caused by water escaping from disconnected
pipes.
Do not use the connector plug on the main supply cable
to connect or shut down the appliance.
Electrocution can be caused by a damaged cable, socket
or connector plug.
Do not damage the main supply cable.
Electrocution caused by stripped live wires.
Never place any objects on the appliance.
Injuries can be caused by the item falling due to
vibrations.
Damage to the appliance or items below it caused by
items that fall because of vibrations.
Do not climb on the appliance.
Injury can be caused by the appliance falling over.
Damage to the appliance or items below it due to the
appliance becoming detached from its supports and
falling over.
Do not climb on chairs, step stools, ladders or unstable
supports to clean the appliance.
Injury due to falling or folding of the ladder (double
ladder).
Do not carry out any cleaning operations on the
appliance without having switched it off, disconnected
the connector plug or deactivated the relevant switch.
Contact with live components can cause electrocution.
Install the appliance on a solid wall that will not be
subject to vibrations.
Noise during operation.
When drilling the wall, take care not to damage the
electrical cables or pipes.
EN 7 Document ref.: 42801603
Contact with live conductors can cause electrical arcing.
Explosions, fires or poisoning in the event of gas leaking
from a damaged duct.
Damage to existing installations. Flooding in the event of
water leaking from damaged ducts.
Protect connection cables to prevent them from being
damaged.
Contact with live conductors can cause electrocution
Flooding caused by water escaping from damaged pipes
Check that the part and the installations to which the
appliance will be connected comply with the current
applicable regulations.
Contact with incorrectly installed live conductors can
cause electrocution.
Damage to the appliance due to unsuitable operating
conditions.
Use accessories and manual equipment suitable for the
usage (ensure that the tool is not damaged and the
handle is securely attached and in good condition), use
this equipment correctly, protect it against being
accidentally dropped and store it after use.
Injury may be caused by flying debris or fragments, dust
inhalation, impacts, cuts, pricks and abrasions.
Damage to the appliance or to nearby objects caused by
flying debris or fragments, impacts or incisions
Use suitable electrical equipment (in particular, check
that the supply cable and connector plug are in good
condition and that rotating or alternating parts are
properly secured).
Use the equipment correctly, do not allow a trailing
supply cable to obstruct access, secure it to prevent
falling, and disconnect and store it after use
Injury can be caused by electrocution, projected shards
or fragments, inhaling dust, being hit, or cuts, pricks,
abrasions, noise or vibrations.
Damage to the appliance or to objects nearby caused by
projected debris or fragments, cuts, incisions.
Ensure that portable ladders are stable and sturdy and
will not slip, and that the rungs are in good condition.
Ensure that someone is present to ensure that ladders
cannot move when someone else is using them.
Injury due to falling or folding of the ladder (double
ladder).
Ensure that materials, components or equipment used
during installation cannot fall from height.
Injury or death due to collapsing and/or falling parts.
Ensure that mobile ladders are correctly supported and
sufficiently sturdy, that the rungs are in good condition
and not slippery, and that the rungs and platforms are
fitted with rails.
Injury due to falling.
When working at height (generally during use with
height differences of more than 2 m), ensure that there
is a safety rail surrounding the working area or that
personal equipment is used to prevent falling, that the
route of any potential fall is not obstructed by
dangerous objects and that any possible impact would
be cushioned by semi-rigid or deformable supports.
Injury due to falling.
Ensure that the health and safety conditions are
adequate in terms of lighting, ventilation, structural
soundness and emergency exits.
Injury caused by being hit, tripping, etc.
During work, wear personal protective equipment and
clothing.
Injury can be caused by electrocution, projected shards
or fragments,
inhaling dust, being hit, or cuts, pricks, abrasions, noise
or vibrations.
The utmost care must be taken during operations
inside the appliance, and contact with sharp edges
avoided.
Injury caused by cuts, pricks and abrasions.
Do not use insecticides, solvents or harsh cleaning
products for maintenance of the appliance.
Painted or plastic parts can be damaged.
Do not use the appliance for any use other than
standard household use.
The appliance may be damaged by operation overload.
Damage to incorrectly treated objects.
Do not allow children or inexperienced persons to use
the appliance.
Damage to the appliance may be caused by improper
use.
Electrical connections must be made using conductors
with a suitable cross section.
Fire due to overheating caused by current passing
through cables which are too small.
Protect appliances and nearby areas using suitable
equipment.
Damage to the appliance or to objects nearby caused by
projected debris or fragments, cuts, incisions.
Move the appliance using the necessary protective
equipment and with the utmost care.
Damage to appliances or nearby objects caused by
impacts, incisions or crushing.
Ensure that all equipment is stored in a way that makes
it simple and safe to handle; avoid creating piles which
are in danger of collapsing.
Damage to appliances or nearby objects caused by
impacts, incisions or crushing.
Reset any safety and control functions affected by an
operation on the appliance, and make sure that they
are operating correctly before it is put back in service.
Damage to or stoppage of the appliance due to
uncontrolled operating conditions.
Before working on roofs, structures, surfaces, etc.,
ensure that they are stable and suitable for the work to
be carried out.
Injury or death due to collapsing and/or falling from
height.
SAFETY STANDARDS SPECIFIC TO THE PRODUCT
Drain any components which contain hot water by
activating the drain before using them.
Injury caused by burns
Descale components in accordance with the
instructions in the safety sheet for the product in
question. Carry out the operation in a well-ventilated
area and wear protective clothing.
Avoid mixing different products and protect the
appliance and nearby objects.
Personal injury through skin and eyes coming into
contact with acidic substances, inhalation of ingestion of
harmful chemical agents.
Damage to the appliance or objects nearby due to
corrosion caused by acidic substances.
Do not carry out work on the product in strong
sunlight.
Injury caused by burns
EN 8 Document ref.: 42801603
TRANSPORT, STORAGE AND RECYCLING
INSTRUCTIONS
The appliance must be transported in accordance with
the pictograms hereunder on the packaging.
The appliance must be transported and stored in dry
conditions and freezing conditions must be avoided.
EU directive 2002/96/EC requires selective collection
and recycling of used electrical and electronic devices.
The "crossed-out wheeled bin" symbol on the appliance
indicates that the product must be disposed of
separately from standard household waste at the end of
its useful life, and must be brought to a waste sorting
centre for electrical and electronic devices or returned
to the seller when a replacement appliance is purchased.
DECLARATION OF CONFORMITY
Conformity of design and production
This product conforms to EU directive 97/23EC, article 3,
paragraph 3 concerning pressure equipment and
93/69/CEE relating to standard EN12897-2006 specific to
indirectly heated, unvented water heaters.
If the addition of a resistance is recommended by the
manufacturer (kit specified in the manual), this product
complies with the following European directives and
standards: LVD Directive (electrical safety) 2006/95/EC
EMC Directive 2004/108/EC.
DESCRIPTION OF APPLIANCES
Enameled tanks are designed for both the production
and storage of domestic hot water.
These tanks can be combined with both solar energy
systems and more common energy systems such as gasor oil-fired boilers.
The tanks are protected by an enamel covering applied
at 850°C, in accordance with the requirements of DIN
4753/3.
EN9 Document ref.: 42801603
B
A
D
C
2. INSTALLATION
The appliance must be installed in accordance with professional good practice and in
compliance with the national regulations in force for hydraulic and electrical
connections, under the entire responsibility of the installer.
This appliance must be installed in covered premises, sheltered from frost and
having sufficient upper and lower ventilation.
Installation of the water heater with its raising feet (label A)
Installation of heating components (label B)
Installation of hydraulic accessories (Option)
Installation of safety unit + drain (Option)
Installation of M1 or M0 insulation (label D)
Hydraulic connection (label C)
Principle with 1 water heater
Principle with two water heaters in series
Hydraulic tests
Electrical connection
Assembly test
10 - Funnel to the drain
11 - Example special fitting
(plate exchanger)
12 - Loop pump
13 - Loop reheater
12
11
10
2
10
5
2
4
2
13
6
2
4
3
1
7
4
8
9
Electrical cover
Connecting sleeves
The appliance must be as close as possible to the supply stations.
For operations of maintenance or replacement of heating components, easy
access must be provided. (Fig 1)
Installation of raising feet (using the bolts provided) (Fig 2)
Either use of the lifting rings of the appliance (at the top of the appliance),
Or possibility of tilting the appliance (without lying it down), taking care not to
Position the water heater in its final position.
Check the stability of the water heater.
3. HYDRAULIC CONNECTION
To enable optimal use of the water heater, we recommend that you carry out the
hydraulic connection as follows:
Not all appliances labelled on these installation diagrams are supplied by us.
However, the correct installation of the appliance in accordance with the national
regulations in force is under the entire responsibility of the installer.
SCHEMA DEPRINCIPEAVECUNCHAUFFE-EAU
EN 11 Document ref.: 42801603
put stress on the cylinder of the tank and of course without impact.
For information any external marking may entail internal damage to the
appliance and will therefore invalidate the warranty.
IMPORTANT NOTE
DEPRINCIPEAVECUNCHAUFFE-EAU
DIAGRAM OF PRINCIPLE WITH ONE WATER HEATER
13
10
7
4
2
12
2
8
2
4
8
2
4
10
10
2
4
5
2
2
10
2
2
3
5
4
2
6
2
6
2
1
99
DIAGRAM OF PRINCIPLE WITH TWO WATER HEATERS CONNECTED IN SERIES/PARALLEL
IMPORTANT:
In the event of installation of battery appliances, it is imperative to install a safety valve specific to
each appliance.
Safety units for the whole of the range (as option) to be installed on each appliance.
These valves must be calibrated at 7 bar maximum and comply with NF.
NB:
Generally, with regard to combating the proliferation of Legionnaire’s Disease, it is
necessary to comply with the recommendations of the Conseil Supérieur d’Hygiène Publique de France, and more particularly the conformity of materials and equipment
implemented in respect of the compatibilities defined on pages 59 & 61 of the risk
management guide linked to Legionella of November 2001
The quality of the water distribution pipes is very important.
Beware of connections between different metals; we advise you to comply with the
instructions of DTU 60-1.
Provide a dielectric insulating connection near to the appliance on each pipe connecting to
the water network.
Verify that the pressure of the distribution network does not exceed 5 bars.
Otherwise, install a pressure reducer upstream of the appliance and its safety
systems.
EN12Document ref.: 42801603
To enable the expansion of the water in the water heater, the safety valve must be
fitted with a pipe which will allow this expansion to overflow into a funnel connected
to the drain. Under no circumstances must you reduce its diameter or close this pipe
with a plug or a stop valve. Plugging will invalidate the warranty of the appliance.
Fitting of a filter on the cold water inlet is strongly recommended in order to
eliminate foreign matter such as sand, gravel, sludge, etc.
It is imperative to install a T-square on the low pipe of the appliance enabling a direct
transition valve to be fitted in order to carr out shunts ad eliiate sludge
stagnating at the bottom of the tank.
Provide a degasser with air drain on the hot water outlet (evacuation of dissolved
gas).
Equip the water heater with a domestic circulating system for proper
homogenisation of the water volume
For the purposes of combating Legionella, it is imperative that any thermostatic
mixer is installed as close as possible to the supply points, in order to minimise the
water circuit to 40°, temperature for maximum proliferation of Legionella
There must be no cutout or regulation system between the tank and the safety valve
4. HYDRAULIC TESTS
Upon first filling with water, it is down to the installer to verify the seal of the upper flange
and the manhole, and to tighten the bolts if necessary.
After hydraulic connection of all pipes, and before carrying out the electrical cabling,
completely fill the appliance and pressurise it.
Check and rectify the watertightness of each connection.
After each intervention on the hydraulic installation, it is imperative to carry out a
hydraulic seal test
EN 13 Document ref.: 42801603
5. ELECTRICAL CONNECTION
Before connecting the appliance, check that the power is off, that the appliance is full of
water and that it is watertight.
Recommendations for installation:
The electrical installation must comply with national regulations in force in the
country of installation. For France, see standards NF C 732OO and NFC 15100.
Install a general circuit breaker and calibrated protection upstream on the electrical
supply.
Use correctly sized ires refer to the aufacturers’ alues ad esure all
connections are fully tightened.
The components mentioned on the electrical diagrams are provided with the
electrical kits.
Each component and the tank must be connected to earth (via the sleeves situated
on the flange of the tank).
The resistances must be supplied using an electromagnetic switch (not provided).
Connect its electrical circuit and the loop pump using terminals C1 and C3 of the
terminal block.
Never block it manually.
Do not install manual override switches.
It must be sufficiently sized.
EN 14 Document ref.: 42801603
6. INSTALLATION OF HEATING COMPONENTS
Recommended order of assembly
0 - Assembly of the flange
with tightening to 3dN
1 - Installation of M10Pins
2 - Installation of the seal
3 - Installation of the
resistance (NB loop
downwards for 15 & 30
Kw model)
4 - 1 backflange (model 15 &
30 Kw)
5 - 6 M10 bolts
4 3 2
Duct for
thermostat
centre
Duct for
thermostat
sensor
1
Recommended order of assembly
0 - Assembly of the flange
with tightening to 3dN
1 - Installation of Pins M10
2 - Installation of seal
3 - Installation of resistance
(NB loop downwards for
15 & 30 Kw model)
4 - 1 backflange (Model 15
& 30 Kw)
5 - 6 M10 bolts
0
0
A) Single resistance platinum shielded (9Kw - 15Kw - 30Kw)
Enamelled tank of 300 to 3000 litres with lateral flange DN110.
Enamelled tank of 750 to 3000 litres with lateral flange DN400.
Flange equipped with immersion resistance, straight (9 kW), bent (15 to
30 kW), directed towards the bottom of the tank, thus avoiding cold zones
and the proliferation of bacteria.
Resistance supply voltage 230 TRI, 400 V TRI without neutral.
Dual thermostat, regulation from 30 to 80°C and overheating safety device
at 95°C with manual reset.
Soft jacket cover, M1 fire classification, or steel cover, M0 fire
classification.
These appliances are delivered on a wooden pallet; the tank, insulation (if
M0 jacket, separate parcel) and the electrical kit are fixed to this.
EN17Document ref.: 42801603
15
6h59mn
345
354 3
30
3h29mn
345
354 4
45
2h41mm
348
357 5
60
1h45mm
348
357 5
2000
9
14h56mm
374
383 1 2
15
9h20mm
374
383 3
30
4h39mn
374
383 4
45
3h27mm
377
386 5
60
2h21mm
377
386 5
2500
9
18h42mm
503
513 1 2
15
11h40mm
503
513 3
30
5h49mn
503
513 4
45
4h25mm
506
516 5
60
2h57mm
506
516 5
3000
9
22h25mm
541
552 1 2
15
14h00mm
541
552 3
30
7h00mn
541
552 4
45
5h15mm
544
555 5
60
3h28mm
544
555 5
Supplied with the kit
Supplied by installer
ELECTRIC DIAGRAM
EN 18 Document ref.: 42801603
CABLING DIAGRAMS
Fig N° 1
Star Cabling 9 kW (3x400 V)
ID
TYPE
SECTION
COLOUR
QTY
1
Control
1.5mm²
Red 2 2
Power
10 mm²
Black 3 3
Earth
10 mm²
Green/Yellow
2 4 Power connection
6 mm²
Black
4 Bloc cond.protec. cap
16 mm²
Green/Yellow
1 L Unit block 1 jonc
16 mm²
Grey 3 C
Unit block 1 jonc
5-6 mm²
Grey
3
Fig N° 2
Triangle Cabling 9 kW (3x230 V)
ID
TYPE
SECTION
COLOUR
QTY
1
Control
1.5mm²
Red 2 2
Power
10 mm²
Black 3 3
Earth
10 mm²
Green/Yellow
2 4 Power connection
6 mm²
Black
5 Bloc cond.protec. cap
16 mm²
Green/Yellow
1 L Unit block 1 jonc
16 mm²
Grey 3 C
Unit block 1 jonc
5-6 mm²
Grey
3
Fig N° 3
Triangle Cabling 15 kW (3x400 V)
mise à la terre
mise à la terre
de la cuve
de la bride
4
2
3
A
B
1
2
C1 C2
L1 L2 L3
5
1
ID
TYPE
SECTION
COLOUR
QTY
1
Control
1.5 mm²
Red 2 2
Power
10 mm²
Black 3 3
Earth
10 mm²
Green/Yellow
2 4 Power connection
6 mm²
Black
1
5
Power bar
6 mm²
Brass
2
Bloc cond.protec. cap
16 mm²
Green/Yellow
1 L Unit block 1 jonc
16 mm²
Grey
3
C
Unit block 1 jonc
5-6 mm²
Grey
3
Fig N° 4
Triangle Cabling 30 kW (3x400 V)
ID
TYPE
SECTION
COLOUR
QTY
1
Control
1.5 mm²
Red 2 2
Power
10 mm²
Black 3 3
Earth
10 mm²
Green/Yellow
2 4 Power connection
6 mm²
Black
4
5
Power bar
6 mm²
Brass
5
Bloc cond.protec. cap
16 mm²
Green/Yellow
1
L
Unit block 1 jonc
16 mm²
Grey
3
C
Unit block 1 jonc
5-6 mm²
Grey
3
mise à la terre
mise à la terre
de la cuve
de la bride
4
54
2
3
1
A
B
1
2
C1 C2
L1 L2 L3
EN 19 Document ref.: 42801603
Bulbe de sécurité
Bulbe de régulation
Fig N° 5
Triangle Cabling 45 kW / 60 kW (3x400 V)
Safety bulb
Regulation bulb
EN 20 Document ref.: 42801603
B - Multi steatite resistances
Capacity
in litres
Power in kW
Heating time
Delta T 60K
Weight with jacket
Electrical diagrams
Fig N°
In h,mn
M1
M0
Star
Triangle
In Kg
In Kg
750
(3x3)
9
5h40mn
240
248 6 7
(4x3)
12
4h25mm
250
258 8 9
(5x3)
15
3h30mn
260
268
10
11
1000
(3x3) 9 7h27mm
270
278 6 7
(4X3)
12
5h49mn
280
288 8 9
(5x3)
15
4h39mn
290
298
10
11
1500
(3x3) 9 11h12mm
350
359 6 7
(4x3)
12
8h51mm
360
369 8 9
(5x3)
15
7h00mm
370
379
10
11
(5x6)
30
3h29mn
370
379
10
11
2000
(3x3) 9 14h56mm
377
686 6 7
(4x3)
12
11h50mm
387
396 8 9
(5x3)
15
9h20mm
397
406
10
11
(5x6)
30
4h39mn
397
406
10
11
2500
(3x3) 9 18h42mm
506
516 6 7
(4x3)
12
14h45mm
516
526 8 9
(5x3)
15
11h40mm
526
536
10
11
(5x6)
30
5h49mn
526
536
10
11
3000
(3x3) 9 22h25mm
544
555 6 7
(4x3)
12
17h42mm
554
565 8 9
(5x3)
15
14h00mm
564
575
10
11
(5x6)
30
7h00mn
564
575
10
11
Enamelled tank of 750 to 3000 litres
Flange equipped with immersion steatite resistances (from 2 to 5 steatites
depending on heating power) directed towards the bottom of the tank,
thus avoiding cold zones and the proliferation of bacteria.
Low charge (5 to 6.5W/cm²) so appliance is at low risk of scaling
Resistance power voltage 230 TRI, 400 V TRI without neutral
Dual thermostat, regulation from 30 to 80°C and overheat safety device at
95°C with manual reset
Soft jacket cover, M1 fire classification, or steel cover, M0 fire
classification.
These appliances are delivered on a wooden pallet; the tank, insulation (if
M0 jacket, separate parcel) and the electrical kit are fixed to this.
EN21Document ref.: 42801603
Fig N° 6
Star Cabling 9 – 18 kW (3x400 V)
ID
TYPE
SECTION
COLOUR
QTY
1
Control
1.5 mm²
Red 2 2
Power
10 mm²
Black 3 3
Earth
10 mm²
Green/yellow
2 4 Power connection
6 mm²
Black 6 5
Earth connection
6 mm²
Green/yellow
2 Bloc cond.protec. cap
16 mm²
Green/yellow
1 L Unit block 1 jonc
16 mm²
Grey 3 C
Unit block 1 jonc
5-6 mm²
Grey
3
Fig N° 7
Triangle Cabling 9 – 18 kW (3x230 V)
ID
TYPE
SECTION
COLOUR
QTY
1
Control
1.5 mm²
Red 2 2
Power
10 mm²
Black 3 3
Earth
10 mm²
Green/yellow
2 4 Power connection
6 mm²
Black 6 5
Earth connection
6 mm²
Green/yellow
2 Bloc cond.protec. cap
16 mm²
Green/yellow
1 L Unit block 1 jonc
16 mm²
Grey 3 C
Unit block 1 jonc
5-6 mm²
Grey
3
Fig N° 8
Star Cabling 12 kW (3x400 V)
ID
TYPE
SECTION
COLOUR
QTY
1
Control
1.5 mm²
Red 2 2
Power
10 mm²
Black 3 3
Earth
10 mm²
Green/yellow
2 4 Power connection
6 mm²
Black
9
5
Earth connection
6 mm²
Green/yellow
3
Bloc cond.protec. cap
16 mm²
Green/yellow
1
L
Unit block 1 jonc
16 mm²
Grey
3
C
Unit block 1 jonc
5-6 mm²
Grey
3
Fig N° 9
Triangle Cabling 12 kW (3x400 V)
ID
TYPE
SECTION
COLOUR
QTY
1
Control
1.5 mm²
Red 2 2
Power
10 mm²
Black 3 3
Earth
10 mm²
Green/yellow
2 4 Power connection
6 mm²
Black
9
5
Earth connection
6 mm²
Green/yellow
3
Bloc cond.protec. cap
16 mm²
Green/yellow
1
L
Unit block 1 jonc
16 mm²
Grey
3
C
Unit block 1 jonc
5-6 mm²
Grey
3
CABLING DIAGRAMS
EN 22 Document ref.: 42801603
Fig N° 11
Triangle Cabling 15 – 30 kW (3x230 V)
ID
TYPE
SECTION
COLOUR
QTY
1
Control
1.5 mm²
Red 2 2
Power
10 mm²
Black 3 3
Earth
10 mm²
Green/yellow
2 4 Power connection
6 mm²
Black 6 5
Earth connection
6 mm²
Green/yellow
2 Bloc cond.protec. cap
16 mm²
Green/yellow
1 L Unit block 1 jonc
16 mm²
Grey 3 C
Unit block 1 jonc
5-6 mm²
Grey
2
Fig N° 10
Star Cabling 15 – 30 kW (3x400 V)
ID
TYPE
SECTION
COLOUR
QTY
1
Control
1.5 mm²
Red 2 2
Power
10 mm²
Black 3 3
Earth
10 mm²
Green/yellow
2 4 Power connection
6 mm²
Black
12 5 Earth connection
6 mm²
Green/yellow
4 Bloc cond.protec. cap
16 mm²
Green/yellow
1 L Unit block 1 jonc
16 mm²
Grey 3 C
Unit block 1 jonc
5-6 mm²
Grey
3
EN 23 Document ref.: 42801603
8. PUFFER RANGE
LITRES
Ø A
(mm)
ELEVATION (mm)
WEIGHT WITH
INSULATION
(kg)
B C D E F G H
300
630
1409
1145
920
688
472
150
204
85
500
630
2005
1752
1322
893
472
150
204
112
750
790
1906
1601
1246
861
501
150
196
157
1000
790
2259
1956
1471
936
501
150
196
192
1500
1100
2085
1700
1334
967
600
200
221
314
2000
1100
2274
1888
1458
1029
600
200
221
330
2500
1400
2148
1679
1349
1010
670
200
215
516
3000
1400
2275
1808
1432
1056
670
200
215
536
HOT WATER OUTLET /
DRAIN
COLD WATER INLET /
FULL DRAIN
TEMP. SENSORS
HOT WATER INLET &
OUTLET / DRAIN
HOT WATER INLET &
OUTLET / DRAIN
This is a carbon steel tank designed for the storage of water for primary network (Operating
pressure max : 5bar).
EN 24 Document ref.: 42801603
9. DOMESTIC HOT WATER STORAGE RANGE
LITRES
Ø A
(mm)
ELEVATION (mm)
WEIGHT
WITH
INSULATION
(kg)
B C D E F G H I J K L M N
300
630
1386
1155
807
807
472
150
204
525 - 110
-
330
36
85
500
630
1983
1752
1494
1108
472
150
204
525 - 110
-
330
36
124
750
790
1891
1601
1246
1051
501
150
196
551
704
110 or 400
465
425
34
195/231
1000
790
2244
1956
1471
1246
501
150
196
551
704
110 or 400
465
425
34
247/283
1500
1100
2073
1700
1380
1140
600
200
221
650
803
110 or 400
620
580
32
365/406
2000
1100
2261
1888
1500
1244
600
200
221
650
803
110 or 400
620
580
32
394/430
2500
1400
2136
1680
1350
1180
680
200
216
730
883
110 or 400
730
730
31
517/559
3000
1400
2263
1808
1430
1250
680
200
216
730
883
110 or 400
730
730
31
544/586
ØK
DCW INLET / FULL DRAIN
DHW OUTLET
TEMP. SENSORS
2 or 3 anodes according to models
ØK
This is an enamelled tank designed for the storage of Domestic Hot Water (Operating
pressure max : 7bar).
Important : For the tank of 2500 and 3000L there are 3 side connections extenders in
stainless steel. These pieces are into the box of feet enhancers.
EN 25 Document ref.: 42801603
10. SINGLE COIL RANGE
(L)
Ø A
(mm)
ELEVATION (mm)
EXCHANGE
SURFACE
(m²)
WEIGHT
WITH
INSULATION
(kg)
B C D E F G H I J K L M N O P
300
630
1386
1055
807
807
472
150
204
525 - 110
982
472 - 330
36
1,6
127
500
630
1983
1752
1332
1108
463
150
204
525 - 110
1615
472 - 330
36 3 177
750
790
1891
1601
1246
1051
501
150
196
551
704
110 or
400
1623
502
465
425
34 4 256/295
1000
790
2244
1956
1471
1246
501
150
196
551
704
110 or
400
1929
502
465
425
34
5.2
326/362
1500
1100
2073
1700
1380
1150
600
200
221
650
803
110 or
400
1722
605
620
580
32
5,6
458/500
2000
1100
2261
1885
1500
1244
600
200
221
650
803
110 or
400
1722
605
620
580
32
5,6
489/531
2500
1400
2136
1680
1350
1180
680
200
216
730
883
110 or
400
1587
680
730
730
31 7 636/678
3000
1400
2269
1808
1432
1245
680
200
216
730
883
110 or
400
1587
680
730
730
31 7 658/700
DHW OUTLET
DCW INLET / DRAIN
TEMP. SENSORS
3 FEET ENHANCER
ØK
COIL OUTLET
COIL INTLET
2 or 3 anodes
according to
models
This is an enamelled tank with single exchanger designed for the production of Domestic
Hot Water from a heating application such as boiler or solar panels(Operating pressure max
: 7bar).
Important : For the tank of 2500 and 3000L there are 3 side connections extenders in
stainless steel. These pieces are into the box of feet enhancers.
This range is fitted with both vertical anodes on the upper flange and horizontal anodes.
EN26Document ref.: 42801603
MISECE DE
(L)
Ø A
(mm)
ELEVATION (mm)
EXCHANGE
SURFACE
(m²)
WEIGHT WITH
INSULATION
(kg)
B C D E F G H I J K L
500
630
1983
1752
1108
472
150
204
36
1390
472 - 330
5,5
253
750
790
1891
1601
1051
501
150
196
34
1611
501
465
425 7 334/370
1000
790
2244
1956
1246
501
150
196
34
1713
501
465
425 8 366/402
1500
1100
2073
1700
1150
600
200
221
32
1569
600
620
580 9 470/512
2000
1100
2261
1888
1244
600
200
221
32
1671
600
620
580
10
510/554
DCW INLET / DRAIN
3 FEET ENHANCER
DHW OUTLET
COIL OUTLET
1 or 2 vertical anodes
according to models
ANODES
COIL INLET
11. HEAT PUMP COIL RANGE
This is an enamelled tank with single exchanger designed for the production of Domestic
Hot Water from a heating application such as boiler, Heat Pump or solar panels(Operating
pressure max : 7bar).
This range is fitted with both vertical anodes on the upper flange and horizontal anodes.
EN 27 Document ref.: 42801603
12. DOUBLE COIL RANGE
(L)
Ø A
(mm)
ELEVATION (mm)
EXCHANGE SURFACE (m²)
Weight
(kg)
B C D E F G H I J K L M N O P Q R
Upp.
Coil.
Low.
Coil.TP
Ø 110
Low.
Coil TH
Ø 400
300
630
1386
1155
806
807
472
150
204
525 - 110
1033
880
778
472 - 330
36
0.6
1.2 - 139
500
630
1983
1752
1494
1108
472
150
204
525 - 110
1390
1033
931
472 - 330
36
1.4
1.6 - 176
750
790
1891
1601
1246
1051
501
150
196
551
704
110 or
400
1623
1266
1164
501
465
425
34
1,7 2 2
295
1000
790
2244
1956
1471
1246
501
150
196
551
704
110 or
400
1674
1317
1215
501
465
425
34
1,7
3,2
2,4
317/345
1500
1100
2073
1700
1380
1150
600
200
221
650
803
110 or
400
1695
1722
1467
600
620
580
32
1,8
3,6
3,6
460/502
2000
1100
2261
1888
1500
1244
600
200
221
650
803
110 or
400
1824
1467
1365
600
620
580
32
2,5 5 3,6
491/533
2500
1400
2136
1680
1350
1180
680
200
216
730
883
110 or
400
1689
1434
1332
680
730
730
31
2,4
5,7
4,8
638/680
3000
1400
2263
1808
1430
1250
680
200
216
730
883
110 or
400
1689
1434
1332
680
730
730
31
2,4
5,7
4.8
660/702
DCW INLET / DRAIN
3 FEET ENHANCER
SORTIE E.C.S.
R
UPPER COIL
OUTLET
LOWER COIL
INTLET
UPPER COIL
OUTLET
UPPER COIL
INTLET
ØK
2 OR 3 ANODES
ACCORDING TO
MODELS
TEMP. SENSORS
This is an enamelled tank with double exchanger designed for the production of Domestic Hot Water from
twin applications such as boiler, PAC and solar panels (Operating pressure max : 7bar).
Important : For the tank of 2500 and 3000L there are 3 side connections extenders in
stainless steel. These pieces are into the box of feet enhancers.
This range is fitted with both vertical anodes on the upper flange and horizontal anodes.
EN 28 Document ref.: 42801603
13. INSTALLATION OF HYDRAULIC ACCESSORIES
Capacity in
litres
500
750
1000
1500
2000
2500
3000
Ø of
connections
1"1/2
1"1/2
1"1/2
2"
2"
2"
2"
Discharge
Safety valve
Drain
Cold water inlet
Installation of upper flange using 6 M10 bolts and seal.
The Flange, Seal and Screws assembly is provided in a box inside the electrical kits or
fixed to the pallet.
The drain in the lower part is connected to the cold water
(If sleeves: Need to fit a coil)
(Do not connect anything to these coils before installing the insulation)
(see diagram of hydraulic installation and dimensions).
Connection coils to the left on the lateral part.
ASSEMBLY DIAGRAM OF THE HYDRAULIC KIT
(provided as Option)
IMPORTANT
Every installation MUST comprise a correctly sized hydraulic safety device against:
Overpressure in the distribution network.
Overpressure due to temperature rises (expansion during heating).
Overpressure due to failure of a thermostat or a contact switch.
The sizing of a hydraulic safety device varies according to:
the capacity of the appliance,
the power of the appliance installed.
A hot water expansion vessel and a anti hammer can also be connected to protect the entire
installation. The implementation of these devices will take into account regulatory
recommendations and those of their manufacturers
In the event of installation of battery appliances, it is imperative to install a safety valve specific to
each appliance.
Safety units for the whole range (as option) to be installed on each appliance.
These valves must be calibrated at 7 bar maximum and comply with NF.
EN 29 Document ref.: 42801603
14. INSTALLATION OF THE INSULATION
A – INSTALLATION OF SOFT INSULATION M1 – EUROCLASS B
B -INSTALLATION OF SOFT INSULATION M0 – EUROCLASS A2
Unpack the shells, place them near the water heater.
Install pannels A&B (or +) closed to the tank, rests on the upper bottom.
Close latches C.
EN 30 Document ref.: 42801603
15. COMMISSIONING
15-1 CHECK THAT THE TANK IS FULL OF WATER
To do this:
Fill the water heater (by opening the water inlet valve and a hot water
supply tap to evacuate the air from the tank).
The water heater is full when the water flows normally at this tap.
NB The appliance must never be connected to the mains when it is empty;
the electrical components (if existing) may become damaged.
VERY IMPORTANT
15-2 CHECK:
That the connections are suitable for the specifications of the current
distributed and the heating components.
That all connection terminals are securely tightened.
That the element or the thermostat is not short circuited.
The free flow of the safety valve(s) and their correct sizing.
The good watertightness of the seals, the flange and any electrical
components.
15-3 CONNECTING TO THE MAINS
Connect to the mains and monitor the first rise in temperature in order to
check the thermostat cuts in properly.
15-4 WATERTIGHTNESS
After a few days of operation, check that all seals are watertight.
16. SHUTDOWN OF THE SYSTEM
NORMAL
(less than 3 months, no risk of frost)
Shut off the power to the water heater.
Close the cold water inlet.
PROLONGED
(over 3 months)
Shut off the power to the water heater.
Drain the appliance: Close the cold water shutdown tap
Open a tap on the hot water circuit
Open the drain valve.
EN 31 Document ref.: 42801603
17. USER RECOMMENDATIONS
Thermostat Label
10 9 8 7 6 5 4
Temperature
75
68
60
50
45
40
35
With regard to the water temperature:
The distribution temperature of 65 °C is the ideal temperature for most
needs. However, in the event of hard water the water temperature must be
below 60 °C to limit the scaling of the heating elements.
In the event of boiling in a water heater and emission of steam jets at the
supply taps, immediately switch off the power, open a hot water tap and
notify your installer.
To define an average water temperature via the thermostat, refer to the table
below. (The temperatures on the table are only guidelines and need to be
checked by the user. They cannot be considered as formal and remain
dependent on the thermostat).
With regard to the expansion of the water volume in the tank
Normal dripping of water occurs upon each heating by the safety unit. This
normal phenomenon is inevitable following expansion of the heated water.
:
REMINDER: It is essential to connect the system or the valve to a visible
permanent discharge.
Quality of the water
I order to esure a aiu life epectac of our ater heater and benefit
from the warranty, certain rules must be respected:
:
Hard water: provide an effective anti-scale device
Soft water: Have: - a TH between 12 and 30° F,
NB:Our warranty will not apply if, in the event of incident, these
instructions have been neglected or if the water quality does not allow
correct treatment within the framework of the legislation.
- a pH between 6.8 and 7.3
- resistance between 2200 and 4500 ohm/cm.
EN 32 Document ref.: 42801603
18. MAINTENANCE AND CLEANING
SWITCH OFF THE ELECTRICAL SUPPLY BEFORE ANY WORK ON THE APPLIANCE
The frequency of interventions depends on the quality of the water stored and
the output. However, it is recommended to check the condition of the heating
elements and the inside of the tank twice a year. These water heaters have an
enamelled internal coating. This protection is completed with two or three
magnesium anodes accessible from the front. Check the anodes three months after
filling.
These anodes will wear according to the quality and consumption of water and
its temperature. The anodes must be checked regularly and replaced when their
diameter is below 10 mm.
The internal corrosion protection warranty shall only apply if the anodes have been
checked and changed at the appropriate times.
Nevertheless, for soft water and for regions where the water is very aggressive
or acidic, it is essential to have the water neutralised with an appropriate treatment.
Failure to observe this rule will invalidate the warranty (see Water Quality chapter).
Monthly operation
Check the correct operation of the safety valve (or safety unit) by manoeuvring
the lever that lifts the heating reset flap valve, to check that the water is
expanding normally. A slight drip may manifest during operation of the
appliance.
Carry out shunts via the quick drain valve to eliminate any sludge stagnating at the
bottom of the tank.
Half-yearly operation
Dismantle the heating elements (resistances and sheath) and clean them carefully
of any deposit.
Descaling
In regions where the water is rich in calcium, it is recommended to frequently
check the inside of the tank and remove the scale with a water jet.
If the tank is too scaled, carry out chemical descaling.
As this operation is tricky, you are strongly advised to use a specialised company.
Important note:
Before reassembling each element comprising a seal, change the seals.
EN 33 Document ref.: 42801603
Annual operation (mandatory)
Dissemble the flange and the heating elements (resistances and sheath)
Check the inside of the tank; descale if necessary
Change the seal
Dismantle the heating elements (resistances and sheath) and clean them
carefully of any deposit.
As this operation is tricky, you are strongly advised to use a specialised company.
Our warranty will not apply if, in the event of incident, this operation has been
neglected.
19. TROUBLESHOOTING
This appliance has been designed to give you full satisfaction. However, here are a
few examples of possible malfunctions and the related solutions.
SWITCH OFF THE POWER BEFORE ANY INTERVENTION ON THE
No hot water at all
a) The appliance has not yet worked:
First check that the safety thermostat is not activated. Press the black button
on the outside of the unit to reset it. Incident often caused by transport.
Check, using a voltmeter, that the current is reaching:
1 - the thermostat, otherwise check the circuit breaker, the fuses, the EDF
eter or a other reote cotrol prograed to “TOP.
2 - the switch, otherwise check the thermostat and its adjustment, which
may be too low.
3 - the resistances, otherwise check that the switch is not abnormally stuck
in the open position.
4 - check:
the connection of each resistance
that it corresponds to the type of current
the cabling diagram of the instructions.
5 - Lastly, replace the resistances
b) The appliance has worked before:
If the safety device is not at issue, check the power supply with a voltmeter, in the
order of points 1 to 5 above.
APPLIANCE
EN 34 Document ref.: 42801603
Insufficient hot water
Check successively:
the adjustment of the thermostat, and modify it if it is not in the stop position,
the correct tightening of the connections,
the power of the resistances on the three phases and the type of current used,
use an ohmmeter to check for faulty elements whose values are too far from the
averages read,
change the resistances in question.
Evaporation or water much too hot
Check
:
the condition of the thermostat and its adjustment temperature,
that the switch is not blocked and that its cutout power is adapted to the power
consumed,
that no remote control is shunting the thermostat.
descaling of the thermowell of the thermostat
Losses of earth perceived on the taps and pipes
:
Check
that the appliance and its components are properly connected to earth and that
this is effective,
the tightening of the connections,
the condition of the components (resistances, thermostat) to detect any
accidental earthing.
Water leaks
A dripping flow in the discharge of the safety valve is normal; it is caused by the
expansion of the water in the heating periods.
On an ongoing basis
Check the pressure of the cold water; if this is greater than 4 bars, install a
pressure reducer upstream of the safety valve.
Check the hot water and cold water connections and the flange seals. Tighten
them or change them.
Lastly, implicate the tank and contact the supplier.
,
20. WARRANTY
Tank guarantee: 5 years (Please refer to our General Conditions of Sale).
Parts guarantee: 2 years (Please refer to our General Conditions of Sale).
In case of trouble or damage, please note the Serial Number of the boiler in all your
enquiries. You can find it at the lowest part of the tank (see the picture below).
Then contact your authorized dealer.
EN35Document ref.: 428016 03
ACV International
Oude Vijverweg 6
1653 DWORP
BELGIUM
EN 36 Document ref.: 42801603
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.