ACUAMP ACT, ACTR ACS150, ACS200, ACSX, ACL1 Service Manual

Page 1
1-800-633-0405
e22-2
Sensors
Volume 14

AC Current Switches, Transducers and Indicator

Overview
The ACUAMP series of AC current sensors is a family of high-performance current sensors offering outstanding features, flexibility, and durability at an incredible price. Choose from a wide selection of current transducers, switches and indicators, all designed in a rugged industry-standard feed-through package, including both fixed core and split core models.
ACT and ACS models have multiple input ranges (set by movable jumpers) for maximum flexibility across many current ratings. The current transducer output choices include 4 to 20mA, 24 VDC loop­powered, and 0 to 10 volt self-powered analog outputs. The Current Switch outputs are isolated solid state switches and are available in Normally Open and Normally Closed configurations.
A unit featuring field adjustable time delay is also offered in the Current Switch series. The ACL1 Current Indicator senses AC current ranging from 0.5 to 100 A and requires no power for the indicating LED.
All models are panel-mountable; conve­nient DIN-rail adapter accessories are available. Use the Selection Guide to find the best sensor for your requirements.
ACUAMP AC Specifications by Model Type
Specifications Transducer Transducer (True RMS) Switch Indicator
Model ACT ACTR ACS150 ACS200 ACSX ACL1
Input Range
Jumper selectable: ACT005: 0 to 2A
0 to 5A
ACT050: 0 to 10A
0 to 20A 0 to 50A
ACT200: 0 to 100A
0 to 150A 0 to 200A
ACT750: 0 to 375A
0 to 500A 0 to 750A
ACT2000: 0 to 1000A
0 to 1333A 0 to 2000A
Jumper selectable: ACTR005: 0 to 2A
0 to 5A
ACTR050: 0 to 10A
0 to 20A 0 to 50A
ACTR200: 0 to 100A
0 to 150A 0 to 200A
ACTR750: 0 to 375A
0 to 500A 0 to 750A
ACTR2000: 0 to 1000A
0 to 1333A 0 to 2000A
Normally Open:
-F core: 1 to 150A
-S core: 1.75 to 150A
Normally Closed:
-F core: 1 to 150A
-S core: 1.75 to 150A
Jumper Selectable: Normally Open:
-F core: 1 to 6A 6 to 40A 40 to 175A
-S core: 1.75 to 6A 6 to 40A 40 to 200A
Normally Closed:
-F core: 1 to 6A 6 to 40A 40 to 175A
-S core: 1.75 to 6A 6 to 40A 40 to 200A
Jumper Selectable: Normally Open:
-F core: 1.5 to 12A 12 to 55A 55 to 175A
-S core: 2 to 12A 12 to 55A 55 to 200A
Normally Closed:
-F core: 1.5 to 12A 12 to 55A 55 to 175A
-S core: 2 to 12A 12 to 55A 55 to 200A
0.5 to
100 A
Output
-10 models: 0–10 VDC
-42L models: 4–20 mA, loop-powered
4–20 mA, loop-powered true RMS
Normally Open:
0.15A @ 240 VAC or VDC
Normally Closed:
0.2A @ 135 VAC or VDC
Normally Open /Normally Closed AC model: 1A @ 240 VAC
Normally Open /Normally Closed DC model:
0.15A @ 30 VDC
Normally Open /Normally Closed AC model: 1A @ 240 VAC
Normally Open /Normally Closed DC model:
0.2A @ 135 VAC/VDC
LED Only
(flashing, red)
Frequency
Range
-10 models: 50 to 60 Hz
sinusoidal waveforms only
-42L models: 20–100 Hz
10 to 400 Hz non-sinusoidal waveforms
6 to 100 Hz 6 to 100 Hz 50 to 100 Hz 50 - 400 Hz
Response
Time
-10 models: 100 ms
-42L models: 300 ms
600 ms 120 ms 40 to 120 ms
Field adjustable time delay:
0.12 to 15 seconds
N/A
Sensing
Aperture
ACT005, ACT050, ACT200:
-F core: 0.75 in [19 mm] dia.
-S core: 0.85 in [21.6 mm] sq.
ACT750, ACT2000:
3.0 in [76.2 mm] dia
ACTR005, ACTR050, ACTR200:
-F core: 0.75 in [19 mm] dia.
-S core: 0.85 in [21.6 mm] sq.
ACTR750, ACTR2000:
3.0 in [76.2 mm] dia
-F core: 0.75 in [19 mm] dia.
-S core: 0.85 in [21.7 mm] sq.
-F core: 0.55 in [13.97 mm] dia.
-S core: 0.85 in [21.7 mm] sq.
-F core: 0.75 in [19 mm] dia.
-S core: 0.85 in [21.7 mm] sq.
0.32 in [8.13 mm]
Page 2
www.automationdirect.com/current-sensors
Sensors
e22-3
Company Information
Systems Overview
Programmable Controllers
Field I/O
Software
C-more & other HMI
Drives
Soft Starters
Motors & Gearbox
Steppers/ Servos
Motor Controls
Proximity Sensors
Photo Sensors
Limit Switches
Encoders
Current Sensors
Pressure Sensors
T
emperature
Sensors
Pushbuttons/ Lights
Process
Relays/ Timers
Comm.
Terminal Blocks & Wiring
Power
Circuit Protection
Enclosures
Tools
Pneumatics
Safety
Appendix
Product Index
Part # Index
Volume 14

AC Current Sensors, Switches and Transducers Application Guide

Pump Jam & Suction Loss Protection
Crusher/Grinder/Shredder Motor Interlocks
Electric Motor Load Status
Pump Load Monitoring
The performance of size reduction equipment like crushers or grinders can be optimized by controlling the in-feed in order to
• Help prevent jamming
• improve the uniformity of the resultant product
• Enhance overall production efficiency
Application Guide
ACUAMP current sensors are a great fit
for many applications including material handling, fan and pump applications, and heating systems. With current transducers, current switches and current indicators, this sensor family gives you valuable data
for processes ranging from monitoring loads to preventive maintenance. Models with the ability to read True RMS non-sinu­soidal waveforms make it easy to monitor applications using variable frequency drives.
Use the application examples to help choose the best sensor model for your application.
Motor Control Signal
Motor Starter
Digital Input
ACS Series Current Operated Switch
0-10v or 4-20mA Input to Controller
True RMS Transducer
Variable Frequency Drive
PLC Inputs
Current Switch or Transducer
Motor Starters
PLC Outputs
Lamp Failure Detection
ACS Series Current Operated Switch
L1
L2 Inactive Relay Contact
When L1 fails, the current drops. The Current Operated Switch detects the drop in current and activates the relay which turns on the back-up lamp L2. The system may be configured fail-safe by using a Normally Open Current switch together with Normally Closed relay contacts
Use: ACTR Series - True RMS Current
Current I
Current Switch or Transducer
Heater Life Prediction
Page 3
1-800-633-0405
e22-4
Sensors
Volume 14
ACT current transducers combine a current transformer and signal conditioner into a single package. The ACT series has jumper-selectable current input ranges and industry standard 4-20 mA or 0-10 VDC outputs. The ACT series is designed for application on ‘linear’ or sinusoidal AC loads and is compatible with most PLCs, data loggers and SCADA systems. Full-scale input ranges are user­selectable from 2A to 2000A. This series is available in split-core or fixed-core models.
Applications
Automation Systems
• Analog current reading for remote monitoring and software alarms
Data Loggers
• Self-powered transducer helps conserve data logger batteries
• Split-core enclosures make using portable data loggers easy
Panel Meters
• Simple connection displays power consumption or other motor status
Features
• Five-year warranty
• 4-20 mA or 0-10 VDC outputs
• Use up to 14 AWG copper wire
• Factory matched and calibrated single piece transducer is more accurate than traditional two-piece field installed products.
• Average responding algorithm gives an RMS output on pure sine waves; perfect for constant speed (linear) loads or ON/OFF loads.
• Selectable input ranges allow end-users to tailor sensing ranges and improves the odds of having the right range for the job.
• Output is magnetically isolated from the input for safety and to eliminate voltage drop.
• Built-in feet with optional 35 mm DIN rail adapter available.
Agency Approvals
UL, cUL, CE approvals accepted worldwide
ACT Series Specifications
10 Models 42L Models up to 200A 42L Models 375 to 2000A
Power Supply
Self-powered 24 VDC loop nominal, 40 VDC max 24 VDC nominal; 40 VDC maximum
Output Signal
0 to 10 VDC 4 - 20 mA, Loop-powered 4 - 20 mA, Loop-powered
Output Limit
15 VDC 32 mA 23 mA
Output Load
1MΩ minimum 100 kΩ (add 1.3%
to accuracy
600 Ω maximum @ 24 VDC 600 Ω maximum @ 24 VDC
Accuracy
1% full scale 1% full scale 1% full scale
Response Time (10-90% step change)
100 ms 300 ms 600 ms
Input Ranges
Field selectable from 0 to 200 A Field selectable from 375 to 2000 A
Sensing Aperture
-F core: 0.74” (19 mm) diameter; -S core: 0.85” (21.6 mm) sq.
3.0” (76.2mm) diameter
Isolation Voltage
UL listed to 1,270VAC. Tested to 5,000 VAC (1 minute max) 600 VAC
Frequency Range (for sinusoidal waveforms)
50 to 60 Hz 20 to 100 Hz 50 to 60 Hz
Case
UL 94V-0 flammability rated
Environmental
Temperature
-4 to 122°F (-20 to 50°C)
Humidity
0 to 95% RH, non-condensing
Agency Listings
UL listed 508, UL file E222847, CE approved

ACT Series AC Current Transducers

Part Number Description Pcs/Pkg Wt (lb) Price ACT050-10-F
AC current transducer, 0-10 VDC output, fixed core 1 0.30 <--->
ACT050-10-S
AC current transducer, 0-10 VDC output, split core 1 0.38 <--->
ACT200-10-F
AC current transducer, 0-10 VDC output, fixed core 1 0.30 <--->
ACT200-10-S
AC current transducer, 0-10 VDC output, split core 1 0.38 <--->
ACT005-42L-F
AC current transducer, 4-20mA output, fixed core 1 0.30 <--->
ACT005-42L-S
AC current transducer, 4-20mA output, split core 1 0.35 <--->
ACT050-42L-F
AC current transducer, 4-20mA output, fixed core 1 0.30 <--->
ACT050-42L-S
AC current transducer, 4-20mA output, split core 1 0.35 <--->
ACT200-42L-F
AC current transducer, 4-20mA output, fixed core 1 0.30 <--->
ACT200-42L-S
AC current transducer, 4-20mA output, split core 1 0.35 <--->
ACT750-42L-F
AC current transducer, 4-20mA output, fixed core 1 2.0 <--->
ACT2000-42L-F
AC current transducer, 4-20mA output, fixed core 1 2.0 <--->
Accessories
DRA-2
DIN rail adapters, 1.69”x0.39”x0.75” (43x10x19 mm) 2 0.40 <--->
ACT Series AC Current Transducers
Maximum Input Ranges
Model Range
Maximum Input Amps
Continuous 6 Sec 1 Sec
ACT005
0 to 2A 80 125 250 0 to 5A 100 125 250
ACT050
0 to 10A 80 125 250 0 to 20A 110 150 300 0 to 50A 175 215 400
ACT200
0 to 100A 200 300 600 0 to 150A 300 450 800 0 to 200A 400 500 1000
ACT750
0 to 375A 750 1500 3750 0 to 500A 750 1500 3750 0 to 750A 750 1500 3750
ACT2000
0 to 1000A 2000 4000 10k 0 to 1333A 2000 4000 10k 0 to 2000A 2000 4000 10k
Page 4
www.automationdirect.com/current-sensors
Sensors
e22-5
Company Information
Systems Overview
Programmable Controllers
Field I/O
Software
C-more & other HMI
Drives
Soft Starters
Motors & Gearbox
Steppers/ Servos
Motor Controls
Proximity Sensors
Photo Sensors
Limit Switches
Encoders
Current Sensors
Pressure Sensors
T
emperature
Sensors
Pushbuttons/ Lights
Process
Relays/ Timers
Comm.
Terminal Blocks & Wiring
Power
Circuit Protection
Enclosures
Tools
Pneumatics
Safety
Appendix
Product Index
Part # Index
Volume 14
0500250
1000750
Total Loop Impedance (Ohms)
25
20
15
10
5
)
C
DV( rewoP pooL
Operating Range
VL = 12VDC + (RL× 0.020A)
where V
L
= Minimum Loop Supply
R
L
= Total Loop Resistance (Ohms)
P
ower Supply
(4–20mA output only)
Connections ACT Series, 0 to 200 Amp
Connections ACT Series, 200 to 2000 Amp
ACT Series AC Current Transducers
Dimensions
Inches [mm]
24 VDC Power
+
+
Load
Output
– +
Captive screw terminals.
Use 12-22 AWG solid or stranded.
Observe polarity.
Notes:
Range Switch
Low Mid High
ACT Series, 2 to 200 Amp Fixed Core
ACT Series, 2 to 200 Amp Split Core
ACT Series, 200 to 2000 Amp Fixed Core
4-20mA Option
Range Jumper
0–10 VDC Option
Load
+
– +
Output
24 VDC Power
– +
Captive screw terminals.
Notes:
Use 12-22 AWG solid or stranded.
Observe polarity.
1MΩ Recommended 100KΩ Acceptable
Range Jumper
Terminals are #6 screws.
– +
Output