H: Horizontal and Not Convertible
N: Horizontal and Convertible
R: Vertical and Convertible
V: Vertical and Not Convertible
Evaporator Fin Type
B: Hydrophilic Blue
Market
M: Malaysia
Electrical Characteristics
A: 1 Phase 50Hz 220-240V
F: 3 Phase 50Hz 380-415V
1
Outdoor
A
5
Brand
A: Acson
Refrigerant
5: R410A
Product Type
MC: Modular Condensing Unit
Capacity
125: 125,000 Btu/hr
Product Series
H: H series
MC 125 H
-
F
M
G R
A
Product Specifi cation
Variation
A: Revision
Air Discharge Orientation
H: Horizontal and Not Convertible
R: Vertical and Convertible
Condenser Fin Type
G: Microchannel
F: E-coating Microchannel
Market
M: Malaysia
Power Supply
Y1: 3 Phase 50Hz 380-415V
2
Product Line-Up
Indoor Unit
A5DB-H
Classifi cation
Control
Nomenclature
W/out Control Module
W/out Contactor
A5DB80HAMBHAXXXXXXX
A5DB100HAMBHAXXXXXXX
A5DB125HFMBNAXXXXXXX
A5DB150HFMBNAXXXXXXX
A5DB200H2FMBNAXXXXXXX
A5DB250H2FMBRAXXXXXXX
A5DB300H2FMBRAXXXXXXX
A5DB300H3FMBRAXXXXXXX
COOLING
A5DB350B3FMBRAXXXXXXX
Fin
Bare Aluminium
Hydrophilic Coated
Handset
Refrigerant Control
Air Filter
W/out Handset
TXV
W/out Air Filter
Air Discharge
Horizontal & Convertible
Horizontal & Not Convertible
Vertical & Convertible
Vertical & Not Convertible
A5DB400H4FMBRAXXXXXXX
A5DB450H3FMBRAXXXXXXX
A5DB500H4FMBRAXXXXXXX
XXXXXXXAVBMF4H006BD5A
XXXXXXXAVBMF5H057BD5A
3
Outdoor Unit
A5MC-H
Classifi cation
Control
Nomenclature
W/out Contactor
With HP/LP Switch/Sensor
With Phase Sequential Protector
A5MC80HFMGHAXXXXX
A5MC80HFMFHAXXXXX
COOLING
A5MC100HFMFRAXXXXX
Fin
Microchannel
E-coating Microchannel
Air Discharge
Horizontal & Convertible
Horizontal & Not Convertible
Vertical & Convertible
Vertical & Not Convertible
XXXXXARGMFH001CM5A
XXXXXARGMFH521CM5A
XXXXXARGMFH051CM5A
A5MC125HFMFRAXXXXX
A5MC150HFMFRAXXXXX
4
APPLICATION INFORMATION
Operating Range
Ensure the operating temperature is in allowance range.
Cooling
Outdoor
DB (°C)
46
43
The use of your air conditioner
outside the range of working
temperature and humidity can
result in serious failure.
19
Cooling Operation Range
DB: Dry Bulb
WB: Wet Bulb
23)C°( BW roodnI41
5
Refrigerant Circuit Diagram
Cooling Only
Outdoor
A5MC100H x 2
Indoor
A5DB200H2
A5MC125H x 2
A5MC150H x 2
A5DB250H2
A5DB300H2
A5MC100H x 3
A5MC100H x 1
A5MC125H x 2
A5DB300H3
A5DB350H3
A5MC150H x 3
A5MC100H x 4
A5DB450H3
A5DB400H4
A5MC125H x 4
A5MC150H x 4
A5DB500H4
A5DB600H4
A5MC150H x 5
A5DB750H5
System
1 IDU
2 ODU
1 IDU
3 ODU
1 IDU
4 ODU
1 IDU
5 ODU
6
Installation Guideline
INDOOR
PRELIMINARY SITE SURVEY
a) Electrical supply and installation is to conform to local authority’s (e.g. National Electricity Board) codes
and regulations.
b) Voltage supply fluctuation must not exceed +/- 10% of rated voltage. Electricity supply line must be
independent of welding transformers which can cause supply fluctuation.
c) Ensure that the location is convenient for wiring and piping.
MOUNTING
a) For ceiling mounted models, locate a position where piping and ducting work can be kept to a minimum.
Ensure that overhead supports are strong enough to hold the unit’s weight. Position hanger rods and
check for alignment with the unit. Check that hangers are secure and that the base of fan-coil unit is level
in two horizontal directions.
DRAINAGE PIPE SIDE
PIPINGS
Do not use contaminated or damaged copper tubings. If pipings, evaporator or condenser are exposed or
had been opened for 15 seconds or more, vacuum and purge with field supplied refrigerant. Generally, do
not remove plastic/rubber plugs/caps from fittings, tubings and coils until ready to connect suction or liquid
line into fittings.
OPERATIONAL CHECK
After all electrical wiring is completed and the system is charged with refrigerant, make sure unit is operating
properly. Check that:
a) Condenser fans are running, with warm air blowing off the condenser coil.
b) Evaporator blowers are running and discharging cool air.
c) Suction line inside condensing unit feels cool.
d) Liquid line inside condensing unit feels warm.
ELECTRICAL CONNECTION
As wiring regulations differ from country to country, please refer to your LOCAL ELECTRICAL CODES for eld wiring regulations and ensure that these are complied with. Besides, observe the following general
precautions:
a) Ensure that the rated voltage of the unit corresponds to that of the name plate before commencing wiring
work.
b) Provide a power outlet to be used exclusively for each unit. A power supply disconnect and a circuit
breaker for over-current protection should be provided in the exclusive line.
c) The unit must be GROUNDED to prevent possible hazard due to insulation failure.
d) All wiring must be firmly connected.
e) Electrical wiring must not touch the refrigerant piping, compressor and any moving parts of the fan
motors.
7
INDOOR CLEARANCE
Mounting
Ensure that the overhead supports are strong enough to hold the unit’s weight. Position hanger rods and
check for alignment with the unit. Check that hangers are secure and that the base of fan-coil unit is level in
the two horizontal directions, taking into account the gradient recommended for drainage flow as shown.
Check the gradient recommended for drainage flow as follow.
Provide clearance for servicing and optimal air flow as shown in the diagram.
The indoor unit must be installed such that there is no short circuit of cool discharge with air discharge.
Respect the installation clearance.
Do not put the indoor unit where there is direct sunlight on unit. The location is suitable for piping and
drainage and it must be have a large distance between a door and unit.
As condensing temperature rises, evaporating temperature rises and cooling capacity drops. In order to
achieve maximum cooling capacity, the location selected should ful fill the following requirements:-
a) Install the condensing (outdoor) unit in a way such that hot air distributed by the outdoor condensing unit
cannot be drawn in again (as in the case of short circuit of hot discharge air). Allow sufficient space for
maintenance around the unit.
b) Ensure that there is no obstruction of air
intake or discharge.
c) The location must be well ventilated, so that the unit can draw and distribute plenty of air thus lowering
the condensing temperature.
d) A place capable of bearing the weight of the outdoor unit and isolating noise and vibration.
e) A place protected from direct sunlight. Otherwise use an awning for protection, if necessary.
f) A place where the hot air discharge and operating sound level will not annoy the neighbours.
g) The location must not be susceptible to dust or oil mist.
flow into or out of the unit. Remove obstacle which block air
If the condensing unit is operated in an atmosphere containing oils (including machine
oils), salt (coastal area), sulphide gas (near hot spring, oil refinery plant), such as
2) ALL DIMENSION MENTIONED ARE
MINIMUM DISTANCE REQUIRED.
UNLESS OTHERWISE SPECIFIED.
Unit Lifting
a) By pallet truck / fork lift
b) By crane
LEFT BY PALLET TRUCK/FOKLIFT
LEFT BY CRANE USING BELT
CONNECT TO 4 CORNER HOIST BRACKET
REMOVE THE TOP CRATE
Step 1Step 2
10
CABLE SIZE
Cooling only
ModelUnit
Voltage range**
Power supply cable size*
a) Indoor Unit
b) Outdoor Unit
c) Total
Number of conductors
a) Indoor Unit
b) Outdoor Unit
Interconnection cable size*
Number of conductors
Recommended fuse/
circuit breaker rating*
a) Indoor Unit
b) Outdoor Unit
c) Total
ModelUnit
Voltage range**
Power supply cable size*
a) Indoor Unit
b) Outdoor Unit
c) Total
Number of conductors
a) Indoor Unit
b) Outdoor Unit
Interconnection cable size*
Number of conductors
Recommended fuse/
circuit breaker rating*
a) Indoor Unit
b) Outdoor Unit
c) Total
Indoor
Outdoor
2
mm
2
mm
2
mm
2
mm
A
A
A
Indoor
Outdoor
2
mm
2
mm
2
mm
2
mm
A
A
A
A5DB80HA5DB100HA5DB125H
A5MC80HA5MC100HA5MC125H
380 - 415V / 3Ph /50Hz + N +
380 - 415V / 3Ph /50Hz + N +
1.0
2.5
2.5
-
5
1
4
6
32
32
1.0
2.5
2.5
-
5
1
4
16
32
40
1.0
2.5
2.5
5
5
-
-
4
40
40
A5DB150HA5DB200H2A5DB250H2
A5MC150H
A5MC100H x 2A5MC125H x 2
380 - 415V / 3Ph /50Hz + N +
380 - 415V / 3Ph /50Hz + N +
1.0
4.0
4.0
5
5
-
-
6
50
50
1.0
2.5
6.0
5
5
-
-
10
32
50
1.0
2.5
10.0
5
5
-
-
16
40
63
11
ModelUnit
Voltage range**
Power supply cable size*
a) Indoor Unit
b) Outdoor Unit
c) Total
Number of conductors
a) Indoor Unit
b) Outdoor Unit
Interconnection cable size*
Number of conductors
Recommended fuse/
circuit breaker rating*
a) Indoor Unit
b) Outdoor Unit
c) Total
Indoor
Outdoor
2
mm
2
mm
2
mm
2
mm
A
A
A
A5DB300H2A5DB300H3A5DB350H3
A5MC150H
x 2
A5MC100H
x 3
A5MC100H
380 - 415V / 3Ph /50Hz + N +
A5MC125H
380 - 415V / 3Ph /50Hz + N +
1.0
4.0
16.0
5
5
-
-
16
50
80
1.0
2.5
16.0
5
5
-
-
16
40
63
1.0
2.5
16.0
5
5
-
-
16
32
80
x 2
-
-
16
40
80
ModelUnit
Voltage range**
Power supply cable size*
a) Indoor Unit
b) Outdoor Unit
c) Total
Number of conductors
a) Indoor Unit
b) Outdoor Unit
Interconnection cable size*
Number of conductors
Recommended fuse/
circuit breaker rating*
a) Indoor Unit
b) Outdoor Unit
c) Total
Indoor
Outdoor
2
mm
2
mm
2
mm
2
mm
A
A
A
A5DB400H4A5DB450H3A5DB500H4
A5MC100H x 4
380 - 415V / 3Ph /50Hz + N +
A5MC150H x 3A5MC125H x 4
380 - 415V / 3Ph /50Hz + N +
1.0
2.5
25.0
5
5
-
-
20
32
80
1.0
4.0
25.0
5
5
-
-
20
50
100
2.5
2.5
25.0
5
5
-
-
32
40
100
12
ModelUnit
Voltage range**
Indoor
Outdoor
A5MC150H x 4A5MC150H x 5
380 - 415V / 3Ph /50Hz + N +
380 - 415V / 3Ph /50Hz + N +
Power supply cable size*
a) Indoor Unit
b) Outdoor Unit
c) Total
mm
mm
mm
2
2
2
2.5
4.0
35.0
2.5
4.0
50.0
Number of conductors
a) Indoor Unit
b) Outdoor Unit
Interconnection cable size*
Number of conductors
mm
5
5
2
-
-
5
5
-
-
Recommended fuse/
circuit breaker rating*
a) Indoor Unit
b) Outdoor Unit
c) Total
A
A
A
32
50
125
50
50
175
IMPORTANT:
* These values are for information only. They should be checked and selected to
comply with local and/or national codes and regulations.
They are also subject to the type of installation and size of conductors.
** The appropriate voltage range should be checked with label data on the unit.
5H057BD5A4H006BD5A
13
REFRIGERANT PIPING
Maximum Piping Length and Maximum Number of Bends
When the pipe length becomes too long, both the capacity and reliability will drop and as the number of
bends increases, system piping resistance to the refrigerant flow increases, thus lowering the cooling
capacity. As a result the compressor may become defective. Always choose the shortest path and follow the
recommendation as tabulated below:
Cooling Only Model
OutdoorA5MC80/100/125/150H
Maximum Allowable Length, m75
Maximum Allowable Elevation, m30
Equivalent length for various fitting (meter)
tnioj LeziS epiPTrap bend
03.181.0)mm25.9 DO( ”8/3
05.102.0 )mm07.21 DO( ”2/1
00.252.0)mm88.51 DO( ”8/5
01.253.0 )mm50.91 DO( ”4/3
00.304.0 )mm32.22 DO( ”8/7
04.354.0 )mm04.52 DO( ”1
07.305.0 )mm85.82 DO( ”8/1 1
04.406.0 )mm29.43 DO( ”8/3 1
Notes:
1. Equivalent piping length is obtained with actual length of gas piping.
2. 90° bend of piping is equivalent to L joint.Bending must be carefully made so as not to crush the pipe.Use a pipe bender to bend a pipe where possible.
CAUTION
Our guarantee on the performance of our air-conditioners is strictly revoked if the height
and/or length of the refrigerant piping system installed is beyond the limit above.
Additional Charge
For Brazed type, if the piping is less than 7.5m, follow the charge level on serial number sticker. When the
piping is more than 7.5m, use the table below.
R410A
Liquid Pipe OD (in)Additional Charge (kg/m)
80.0’’2/1
41.0’’8/5
NOTE:
The additional refrigerant charge amount recommended is a guideline for long piping
application. The actual charge required may be different from the guideline due to different
application and variation in site condition.
Microphone position:
1m away from every side panel of the unit and 1m above the fl oor level.
(Tested with 2m length duct at the air discharge outlet only)
Standard: JIS B 8615
Free return duct
Sound Power Level
ModelSpeed
*A5DB80H
*A5DB100H
High
Med
Low
High
Med
Low
125Hz250Hz500Hz1kHz2kHz4kHz8kHz
6867706964625473
6964686861596070
6662666358564667
7472747366655977
7370737164625575
7068716860594972
1/1 Octave Sound Power Level (dB) ref 1pW
*A5DB125HHigh7576787069625878
*A5DB150HHigh7477787572696380
*A5DB200H2High8384838177736885
A5DB250H2High8586858379757087
A5DB300H2/H3High8788878581777289
A5DB350H3High9091908784807592
A5DB400H4High8889888682787390
A5DB450H3High9192918985817693
A5DB500H4High9495949288847996
A5DB600H4High8788878581777289
A5DB750H5High9192918985817693
Overall
(dBA)
*Remarks: Test with 5ft length discharge duct, terminated flush with the internal wall of reverberation room.
16
NC Curve
80
A5DB80H
70
Pa)
μ
60
H
M
L
50
40
30
Sound pressure level (dB, ref 20
20
10
NC70
NC65
NC60
NC55
NC50
NC45
NC40
NC35
NC30
NC25
NC20
0008000400020001005052521
Octave-band frequency (Hz)
A5DB100H
17
Sound pressure level (dB, ref 20μPa)
80
70
60
NC70
NC65
NC60
50
40
H
M
L
NC55
NC50
NC45
NC40
30
NC35
NC30
20
NC25
NC20
10
0008000400020001005052521
Octave-band frequency (Hz)
A5DB125H
80
Sound pressure level (dB, ref 20μPa)
70
60
NC70
NC65
NC60
50
40
H
NC55
NC50
NC45
NC40
30
NC35
NC30
20
NC25
NC20
10
0008000400020001005052521
Octave-band frequency (Hz)
A5DB150H
80
70
μPa)
60
50
40
30
Sound pressure level (dB, ref 20
20
10
H
Octave-band frequency (Hz)
NC70
NC65
NC60
NC55
NC50
NC45
NC40
NC35
NC30
NC25
NC20
0008000400020001005052521
18
A5DB200H2
80
Sound pressure level (dB, ref 20μPa)
70
70
60
H
50
40
30
20
10
NC70
NC65
NC60
NC55
NC50
NC45
NC40
NC35
NC30
NC25
NC20
0008000400020001005052521
Octave-band frequency (Hz)
A5DB250H2
19
60
H
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Sound pressure level (dB, ref 20μPa)
10
0
1252505001000200040008000
NC-20
Octave-band frequency (Hz)
A5DB300H2
70
60
NC-55
50
40
30
20
Sound pressure level (dB, ref 20μPa)
10
0
1252505001000200040008000
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
Octave-band frequency (Hz)
H
A5DB300H3
70
60
50
40
30
20
10
Sound pressure level (dB, ref 20μPa)
0
1252505001000200040008000
H
NC-45
NC-35
Octave-band frequency (Hz)
NC-55
NC-50
NC-40
NC-30
NC-25
NC-20
20
A5DB350H3
70
H
60
NC-55
50
40
30
20
Sound pressure level (dB, ref 20μPa)
10
0
1252505001000200040008000
Octave-band frequency (Hz)
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
21
A5DB400H4
70
H
60
NC-55
50
40
30
20
Sound pressure level (dB, ref 20μPa)
10
0
1252505001000200040008000
Octave-band frequency (Hz)
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
A5DB450H3
70
H
60
NC-55
50
40
30
20
Sound pressure level (dB, ref 20μPa)
10
0
1252505001000200040008000
Octave-band frequency (Hz)
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
A5DB500H4
70
60
50
40
30
20
Sound pressure level (dB, ref 20μPa)
10
0
1252505001000200040008000
H
Octave-band frequency (Hz)
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
22
A5DB600H4
70
H
60
NC-55
50
40
30
20
Sound pressure level (dB, ref 20μPa)
10
0
1252505001000200040008000
Octave-band frequency (Hz)
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
A5DB750H5
90
80
70
60
50
40
30
20
Sound Pressure Level (dB, ref 20
10
0
1252505001000200040008000
H
NC-50
Octave-band Freque ncy (Hz)
NC-70
NC-65
NC-60
NC-55
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
23
SELECTION PROCESS
Fan Performance Chart
Example 1 :
The following are the design requirements for A5DB250H2 unit:
Model: A5DB250H2
Supply Air Quantity = 9000 CFM
External Static Pressure = 350 Pa
External Static Pressure of 300 Pa did not fulfil the design requirements.
Step 2: Therefore at 9000 CFM and 350 Pa external static pressure,
Total Static Pressure = ISP + ESPPa
= 140 + 350Pa
= 490Pa
Step 3: From the fan curve, the design requirement calls for RPM about 810, whereas the unit can only deliver
RPM about 715 under the same CFM. Therefore, it is necessary to RPM about 810 under the same CFM.
Therefore, it is necessary to resize the pulley sizes.
From the table:
Motor pulley= 90 mmBlower pulley= 200 mmMotor RPM= 1440
In order to obtain 810 RPM, we recalculate the new blower pulley as:
(while maintaining the motor pulley)
)018/0441( x 09 = bD
mm 0.061 =
The nearest pulley size will be a diameter of 160mm
Recheck, with Db = 160mm
Blower pulley= 1440 x (90/160)
= 810
We thus need to change the blower pulley from 200mm to 160mm in order to obtain the higher operating
static pressure.
Step 4:When the pulley is changed, the V-belt length must be rechecked. We have for horizontal air throw