• The unit is designed for indoor
installation only.
• Installation work should be done by
authorized dealer or qualified
contractor.
• Install the unit at a suitable minimum
distance or shortest path to the
coupling fan coil unit.
• There should be sufficient space for
piping connection, service and
maintenance. (Refer to Figure 3)
• The area should be isolated from
vibration and noise.
• Ensure the area is free from water
leakage.
WSS 10/15/20/25 AWSS 30/40/50/60 A
THREADED ROD
HEX. NUT
WASHER
WASHER
VIBRATION ISOLATOR
HEX. NUT
WASHER
Figure 4
THREADED ROD
HEX. NUT
WASHER
VIBRATION ISOLATOR
HEX. NUT
• This unit will be mounted on the ceiling by the support of four threaded rods. (Refer to Figure 4)
• Ensure that the supports are strong enough and properly anchored to withstand the weight of the unit.
• Use isolator rubber (natural rubber) with hardness of 35º for better noise and vibration control.
• Do not locate the drainage system at any point above the drain connection.
2
Figure 5
4
5
1: SHUT OFF VALVE
2: WATER OUT
3: WATER IN
4: Y-STRAINER
5: SHUT OFF VALVE
6: FLEXIBLE HOSE
6
BALANCING VALVE
1
2
RUBBER BUSH
ENSURE WATER VALVE ADAPTORS
ARE ALIGNED TO THE CENTER
WITHOUT TOUCHING
(min 2mm) THE RUBBER BUSH
WHEN MAKING
PIPING CONNECTION.
3
Figure 6
Figure 7
! WARNING
• Installation and maintenance should
be performed by qualified persons
who are familiar with local code and
regulation, and experienced with this
type of appliance.
HANDLE
2
3
Lo
HANDLE
Hi
(ALWAYS CLOSED)
1: VACUUM PUMP
2: LIQUID VALVE
1
3: GAS VALVE (3-WAY)
SAFETY PRECAUTIONS
! CAUTION
Please take note of the following important points when installing.
• Do not install the unit where leakage of flammable gas may occur.
If gas leaks and accumulates around the unit, it may cause fire ignition.
• Do not overcharge the unit.
This unit is factory pre-charged. Overcharge will cause over-current or
damage to the compressor.
• Ensure the rated voltage and phase of the unit corresponds to the unit name
plate before carrying out wiring work.
• The unit must be GROUNDED to prevent hazards due to insulation failures.
• Do not ground any electrical equipment to the water piping.
• Ensure all electrical wiring do not touch the refrigerant piping, compressor,
pump or any moving parts.
• Do not operate unit with wet hand(s). It will result in electrical shock.
• Ensure there is water supply into the unit at all times before operating.
• Do not attempt to so any service or maintenance when the unit is operating.
• Unauthorized modification of the unit is not allowed.
3
SCHEMATIC DIAGRAM
WSS 10/15/20/25 A
3
2
1
4
SCHEMATIC DIAGRAM
7
11
6
5
#
8
9
!
11
Figure 8
WSS 30/40/50/60 A
3
2
1
COOLING OPERATION
SCHEMATIC DIAGRAM
67
5
8
9
!
4
Figure 9
NOTE:
1. GAS PIPING8: WATER OUTLET
2: FAN COIL UNIT9: TUBE IN TUBE HEAT EXCHANGER
3: FAN MOTOR10:WATER INLET
4: LIQUID PIPING11:STRAINER
5: COMPRESSOR12:COOLING CAP TUBE
6: HIGH PRESSURE SWITCH
7: LOW PRESSURE SWITCH
* FOR FIGURE 9, ITEM 11 & 12 ARE NOT AVAILABLE.
COOLING OPERATION
4
WSS 10/15 A
ELECTRICAL WIRING CONNECTION
PURPLEWHITE
RED
RED
MAGNETIC
CONTACTOR
BLUEBLUE
REDRED
BLUE
BLACK
BLUE
PURPLE
PURPLE
BLUE
COMPN
HP
BLUE
BLACKBLACK
LP
BLUE
RELAY
(O.R.)
BLUE
GREEN/YELLOW
OLP
CM
S
RC
RED
BLUE
Figure 10
WSS 20/25/30 A
BLUE
REDRED
MAGNETIC
CONTACTOR
( TO INDOOR UNIT)
REDRED
BLACK
PURPLE
PURPLE
PURPLE
BLUE
BLUE
BLUE
BLUE
HP
BLUE
BLACKBLACK
LP
BLUE
RELAY
(O.R.)
GREEN/YELLOW
BLUE
CM
S
RC
RED
BLUE
Figure 11
COMPN
( TO INDOOR UNIT)
5
WSS 40/50/60 A
A1 A2 A3 A4 N
GREEN/YELLOW
BLUE
BLUE
RED
RED
RED
HP
REDRED
WHITEWHITE
LP
BLUE
BLUE
BLUE
RELAY
BLUE
RED
BLUE
RED
WHITE
LNRST
NC
PP
RED
RST
BLUE
RED
CDM
CRANKCASE
WHITE
BLUE
HEATER
COMPRESSOR
DT
ORANGE
ORANGE
• Refer to the wiring diagram provided on
the unit when making electrical wiring
connection. (Refer to Figure 10, 11 & 12).
• Power supply is from fan coil unit
connection.
• All field wiring must comply with your
national or local wiring regulation.
• All terminal wiring must be firmly
connected. Improper connection can cause
electric shock, short circuit or fire
breakout.
• A circuit breaker must be provided for over
current protection.
• All safety precautions need to be strictly
adhere.
NOTE:
1) WITH PHASE PROTECTOR
2) FOR LOCAL SPEC
3) FOR 380~415V/3PH/50Hz
4) WITH CRANKCASE HEATER
--- - FIELD SUPPLY WIRING
PP - PHASE PROTECTOR
HP - AUTO RESET HP SWITCH
LP - AUTO RESET LP SWITCH
Liquid valve connectioninches1/41/41/43/8
Gas valve connectioninches3/81/25/85/8
Service port connection (UNF-20)inches7/167/167/167/16
Refrigerant - Water Heat ExchangerTube in Tube
Water inlet (BSP) MALEinches1/21/21/21/2
Water outlet (BSP) MALEinches1/21/21/21/2
Nominal pressure dropkPa18.524.530.949.7
Nominal flow ratem3/h0.600.901.001.35
Drain Pipe Connection
Steel pipeinches3/43/43/43/4
Figure 12
ELECTRICAL DATA
ModelWSS10AWSS15AWSS20AWSS25A
Power SupplyV/Ph/Hz220 - 240 V / 1 Ph / 50 Hz
Nominal Power Input (Cooling)W717110312701658
Nominal Current (Cooling)A3.35.35.87.6
CapacitoruF25.0 uF40.0 uF45.0 uF40.0 uF
6
RECOMMENDED CABLE SIZE
ModelWSS10AWSS15AWSS20AWSS25A
Rated Voltage Range220 - 240V / 1Ph / 50Hz
Recommended FuseA15152020
Supply Cable Sizemm
Number of Cables3333
Interconnection Cable Sizemm
Number of Cables3333
2
2
1.51.52.52.5
1.51.52.52.5
REFRIGERANT PIPING WORK
1. Piping Length, Elevation and Bends
ModelWSS10AWSS15AWSS20AWSS25A
Max. Length, L12121515
Max. Elevation, H5555
Max. No. of bends10101010
Liquid Valve Size6.35mm6.35mm6.35mm9.52mm
(1/4")(1/4")(1/4")(3/8")
Gas Valve Size9.52mm12.7mm15.88mm15.88mm
(3/8")(1/2")(5/8")(5/8")
• When piping length becomes too long, both
the capacity and compressor reliability drop.
• As the number of bends increases, systempiping resistance to the refrigerant flow
increase thus lowering the capacity of the
unit and as a result the compressor may
become defective.
• Always choose the shortest path and follow
the recommendation as tabulated.
2. Water Piping and Fitting
• Install a 40-60 mesh strainer to ensure water quality is good.
• Water pipe materials recommended are black steel pipe and
copper pipe.
• All piping connections must be properly and firmly connected.
Do not over-tighten the connections.
• Users are recommended to install the pipes as shown in Figure
5 & 6.
• The piping need to be cleaned and flushed prior to operation.
• Air vents must be installed at the highest position while a
drainage system at the lowest position of the water circuit.
4. Flare Work
HEAD PROJECTION DIMENSION
A
FLARE DIE
COPPER TUBE
B
• Head project dimension may
differ according to type of flare
tool.
COPPER TUBE
D
• Flare section should be uniform
or even. Crack on the flare
FLARE NUT
section or burr on the flare edge
is not acceptable. Make new
flare tubing again to prevent
potential gas leak.
3. Refrigerant Piping
• Do not use contaminated, dented or used copper tubing.
• Do not use copper tubes with less than 0.8mm thickness.
• Cut the connection pipe with a pipe cutter.
• Remove burrs from cut edges of the pipes with remover. Hold
the end of the pipe downwards to prevent metal chips from
entering the pipe.
• Use proper torque wrench to tight the flare nuts. If the torque
strength is weak, gas leakage may occur. If it is too tight, the
flare nut may crack and it may be non-removable.
• Insulate the piping to prevent capacity losses and water.
• Use proper torque wrench to tight the flare nuts.
• If the torque strength is weak, gas leakage may occur.
• If it is too tight, the flare nut may crack and it may be non
removable.
VACUUMING AND CHARGING
1. Purging The Piping And The Indoor Unit
Except for the outdoor unit which is pre-charged with
refrigerant, the indoor unit and the refrigerant connection pipes
must be airpurged because the air containing moisture that
remains in the refrigerant cycle may cause malfunction of the
compressor.
• Remove the caps from the valve and the service port.
• Connect the center of the charging gauge to the vacuum
pump. (Refer to Figure 7)
• Connect the charging gauge to the service port of the
3-way valve.
• Start the vacuum pump. Evacuate for approximately 30
minutes. The evacuation time varies with different vacuum
pump capacity. Confirm that the charging gauge needle has
moved towards -760mmHg.
Caution:
• If the gauge needle does not move to -760mmHg, be sure
to check for gas leaks (using the refrigerant detector) at
flare type connection of the indoor and outdoor unit and
repair the leak before proceeding to the next step.
• Close the valve of the charging gauge and stop the vacuum
pump.
• On the outdoor unit, open the suction valve (3 way) and
liquid valve (2 way) (in anti-clockwise direction) with 4mm
key for hexagon sacked screw.
2. Additional Charge
• The pre-charged of R22 in the Water Cooled Split Type
unit is suitable for standard pipe of length up to 7.6m.
• When the piping is more than the above stated standard
pipe length, kindly add additional charge referring to the
table below.
ModelGram/Meter
WSS10A30
WSS15A30
WSS20A30
WSS25A30
3. Charge Operation
This operation must be done by using a gas cylinder and a
precise weighing machine. The additional charge is toppedup into the outdoor unit using the suction valve via the service
port.
• Remove the service port cap.
• Connect the low pressure side of the charging gauge to the
suction service port center of the cylinder tank and close
the high pressure side of the gauge. Purge the air from the
service hose.
• Start the air conditioner unit.
• Open the gas cylinder and low pressure charging valve.
• When the required refrigerant quantity is pumped into the
unit, close the low pressure side and the gas cylinder valve.
• Disconnect the service hose form service port. Put back the
service port cap.
UNIT OPERATION LIMITS
1. Environment
This unit is designed for indoor installation and operation only. This unit also limited to
water loop application only as the heat exchanger can only cater for this application.
2. Power Supply
A voltage variation of +/– 10% of rated voltage stated in the unit label is acceptable.
3. Allowable Operation Conditions
Ensure the operating temperature and conditions are in allowable range. Extreme variations
in temperature, humidity and corrosive water or air will adversely affect unit performance,
reliability and service life.
8
4. Cooling only
45
C)
o
30
Water Entering Temp. (
13
15 19 24
Indoor Temp. (oC WB)
Cooling
STD
6. Water Pressure Drop Graph
70.0
60.0
50.0
40.0
30.0
Pressure drop, kPa
20.0
10.0
0.0
0.000.200.400.600.801.001.201.401.601.80
Graph pressure drop Vs flow rate
WSS15/20/25A
WSS10A
3
Flow rate, m
/hr
SYSTEM CLEANING AND FLUSHING
The water circulating loop system must be cleaned and flushed to remove all construction debris and dirt before operating the
units.
1. If the connection is equipped with water shut-off valve, either electric or pressure operated, the individual supply and return
pipes must be connected together first. This will prevent the introduction of dirt into the unit.
2. Fill the water loop system with your local water supply with all air vents open. After filling, close all air vents. The contractor
should start the main circulator pump with the pressure reducing valve open. Check all vents in sequence to bleed off any
trapped air, ensuring circulation through all components of the system. Power to the heat rejector unit should be off and the
supplementary heat control set at 27ºC (80ºF).
3. While the water is circulating, the contractor should check and repair any leaks in the piping. Drains at the lowest point(s) in the
system should be opened for initial flush and blow down. Make sure the local supply water valves are set to make up for the
required flow rate. Check the pressure gauge at the pump suction and manually adjust the make up to hold the same positive
steady pressure both before and after opening the drain valves. Flush should be continuously for two hours or longer if required
to obtain a clean and clear drain water.
4. Shut off all supplemental heater and circulator pump and open all drains and vents to complete drain down the system. Now, the
short-circuited water connection to the supply and return pipes should be removed and connected to the individual water inlet
and outlet of the unit.
Use proper tape to seal off at the valve connection. Do not use sealant at the valves connection.
5. Trisodium phosphate was formerly recommended as a cleaning agent during flushing. However, some of the local authorities
ban the usage of the phosphate into the sewage systems. The current recommendation is to simply flush longer with warm at
27ºC (80ºF) water.
6. Refill the water loop system with clean water. Test the water for acidity by using a litmus paper. Treat the water if required to
obtain the pH level between 7.5 to 8.5 (slightly alkaline).
7. Once the water system is ready, ensure at all times only clean water is supplied to the system. Dirty water will result in wide
degradation of performance and solids may clog valves, strainers, flow regulator, etc. Pump work will increase and may damage
the pumps. The heat exchanger may become clogged as well which will reduce the compressor service life or causes premature
failure.
8. Finally set the loop water controller heat rejection point to 29ºC (85ºF). Supply power to all motors and start the circulating
pumps. After full flow has been established through all components including heat rejectors (regardless of season) and air
vented and loop temperature stabilized, each of the air conditioner will be ready for check, test and start up, air balancing and
water balancing.
SERVICE AND MAINTENANCE
• Service and maintenance should be performed by authorized dealer or qualified contractor.
• Internal components can be accessed through two service panels (front and back). External control box for easy access of
electrical components.
• Regular checks on the water strainer are recommended. Clean the strainer if dirty or clogged.
• Maintenance a log data on measurement of volts, amps, and water temperature difference is recommended. A comparison of the
data during start-up and periodic data is useful as indicator of general condition of equipment.
9
UNIT START UP AND OPERATION
1. Make sure all wiring connection is correct and power supply is compatible to the rated voltage.
2. Open all valves in full open position and start the circulating pump. Make sure there is water running through the water loop before operating
the unit.
3. Set to mode ‘cool’. Then set the temperature to the coolest. The unit has time delay which protects the compressor for short cycling. Wait for
a few minutes before check on the air discharge for cool air delivery.
4. Measure the temperature difference between entering and leaving water. Leaving water temperature should be higher than entering water
temperature.
Example: If water temperature difference in cooling mode is 5°C (9°F), the heating mode difference should be 3.3°C (6°F).
5. If without automatic flow control valves, target the cooling mode water temperature difference between 5°C (9°F) to 8°C (14.4°F). This can
be achieved by adjusting shut-off/balancing valve in the return piping to a suitable water flow rate to achieve the desire temperature difference.
6. Check for vibration refrigerant piping, fan wheels, etc.
Note:
• Water cooled split type unit is controlled by fan coil unit.
• The controller is located on the fan coil unit.
TROUBLESHOOTING
• Troubleshooting must be performed by authorized dealer or qualified contractor.
FaultCause/Check Point
Unit cannot start1. Power supply plug disconnected.
2. Circuit breaker or fuse tripped / blown.
3. Wiring connection.
4. If fault persist, contact your installer.
Neither fan coil unit1. The fuse may be blown or circuit breaker opened.
and compressor run2. Check electrical circuit or motor winding for shorts or grounds. Investigate for possible over loading.
Replace fuse if necessary.
3. Check wiring connections. Wire may be loosening. Replace or tighten.
4. Control system may be faulty.
Compressor does1. Check capacitor if available. Replace capacitor if faulty.
not operate2. Check wiring connection. Wire may be loosening. Replace or tighten.
3. The high pressure switch may tripped due to:
a) No or insufficient water flows into and leaves heat exchanger. May be clogged.
b) Water entering temperature higher than the maximum operating conditions.
c) Not enough air flow into fan coil unit. May be due to dirty filter or block by object, cardboard and
etc (heating mode).
d) Fan coil motor failure (heating mode).
e) Unit over-charged. Release some of the refrigerant charge.
4. The compressor internal/external overload protection is opened. If the compressor body is extremely
hot, the overload will not reset until it cooled down.
5. The compressor winding may be grounded to the compressor shell. If so, replace the compressor.
Insufficient cooling1. Check controller temperature setting.
2. Filter may be clogged. Check and clean the filter.
3. Check capillary tube for possible restriction of refrigerant flow. Replace capillary tube if proven so.
4. The reversing valve may be defective (valve position is not shifted properly), creating a bypass of
refrigerant. Check the reversing valve coil connection.
5. Check for restriction of air and water flow.
6. Refrigerant leakage. Check all piping bends and connection for leakage. Repair the leakage area
or replace with new piping.
7. Window or door wide open.
8. Unit may be under-sized.
Insufficient water1. Valves are not opened fully.
flow through heat2. Circulating water pump is faulty.
exchanger3. Water pipes or strainers are clogged.
Noisy operation1. Check for loose bolts or screws.
2. Make sure rubber isolators are used for installation.
3. Check for water balance to unit for proper water flow rate.
4. Check for tubing touching compressor or other surface. Readjust tubing by bending it slightly.
5. Fan (fan coil unit) knocking / hitting on its housing.
6. May be due to worn compressor bearing.
10
•In the event that there is any conflict in the interpretation of this manual and any translation of the same in any language,
the English version of this manual shall prevail.
•The manufacturer reserves the right to revise any of the specification and design contain herein at any time without prior
notification.
•En cas de désaccord sur l’interprétation de ce manuel ou une de ses traductions, la version anglaise fera autorité.
•Le fabriquant se réserve le droit de modifier à tout moment et sans préavis la conception et les caractéristiques techniques
des appareils présentés dans ce manuel.
•Im Falle einer widersprüchlichen Auslegung der vorliegenden Anleitung bzw. einer ihrer Übersetzungen gilt die Ausführung
in Englisch.
•Änderungen von Design und technischen Merkmalen der in dieser Anleitung beschriebenen Geräte bleiben dem Hersteller
jederzeit vorbehalten.
•Nel caso ci fossero conflitti nell’interpretazione di questo manuale o delle sue stesse traduzioni in altre lingue, la versione
in lingua inglese prevale.
•Il fabbricante mantiene il diritto di cambiare qualsiasi specificazione e disegno contenuti qui senza precedente notifica.
•En caso de conflicto en la interpretación de este manual, y en su traducción a cualquier idioma, prevalecerá la versión
inglesa.
•El fabricante se reserva el derecho a modificar cualquiera de las especificaciones y diseños contenidos en el presente
manual en cualquier momento y sin notificación previa.
•В случае противоречия перевода данного руководства с другими переводами одного и того же текста,
английский вариант рассматривается как приоритетный.
•Завод-изготовитель оставляет за собой право изменять характеристики и конструкцию в любое время
без предварительного уведомления.
OYL MANUFACTURING COMPANY SDN. BHD.
JALAN PENGAPIT 15/19, P.O. BOX 7072, 40702 SHAH ALAM, SELANGOR DARUL EHSAN, MALAYSIA.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.