This unit is contemporary in design and match even the most up to date interior decor. The slim, round
profile and compact design of this unit adds a touch of elegance to every decor. No indoor connection pipe
and hanger bracket are visible.
CEILING AND FLOOR CONVERTIBLE WITH SPACE SAVING INSTALLATION
This unit is designed for ceiling exposed type and floor exposed type with a very economical and space
saving installation. No need renovation to wall or ceiling for ceiling exposed and no foundation work is
required for floor exposed installation. This easy to install and ready to operate unit ensure rapid and low
installation cost.
STRONG AND ROBUST
The unit is built from strong casing material and robust parts to ensure long lasting reliable service. The
drain pan is made from the POLYSTYRENE with a plastic coating on the surface to ensure no leaking and
no condensation occur.
FRIENDLY SERVICEABILITY
The air filter, electrical parts, fan and fan motor assembly can all be inspected and replace from bottom of
the unit by simply removing the newly designed press in, pull out air intake grille. The POLYSTYRENE drain
pan and the heat exchanger coils can remove from the unit easily by remove the bottom panel.
MICROCOMPUTER REMOTE CONTROLLER
The incorporated microprocessor give more accurate control and with the following extra features:
•Fan motor speed can be set at high/medium/low and automatic.
•Timer on/off - the unit can be pre-set to on and off automatically.
•Electronic thermostat - room temperature is precisely controlled resulting in energy saving and increase
comfort.
•Sleep mode automatically increase set temperature since room temperature is lower at night thus
achieving healthy sleep.
WIRELESS REMOTE CONTROLLER
The compact wireless remote controller makes it possible to operate the air conditioner anywhere within the
room.
AUTO OR MANUAL CONTROL ON VERTICAL AIRFLOW DIRECTION
With auto control, the louver will automatically swing up and down to create an excellent air distribution. You
can select your desired horizontal air flow direction by adjusting the vertical grille.
7
3. APPLICATION INFORMATION
OPERATING RANGE
Ensure the operating temperature is in allowable range.
Cooling only
52
46
35
19
Outdoor temp. (°CDB)
-5
Heat pump
18
6
High ambient
unit
Standard
point
The use of your air conditioner
outside the range of working
!
Caution :
temperature and humidity can
result in serious failure
Low ambient kit
15
24
Indoor temp. (°CWB)
HeatingCooling
52
46
35
Standard
point
19
High ambient
unit
.
Standard
point
Outdoor temp. (°CWB)
-9
1521
27
Indoor temp. (°CDB)
Note :
Standard operating range.
With High ambient unit. (Optional item)
Please refer to local dealer for unit of this specification.
With Low ambient kit. (Optional item)
Please refer to local dealer for unit of this specification.
• The source where the signal will be transmitted.• Set the desired off time by pressing the SET button
2. SIGNAL TRANSMISSION INDICATIONcontinuosly.
• Blink to confirm the last setting has been send to• Press the CLR button to cancel the off timer
the unit. setting.
3. ON/OFF BUTTON9. AUTOMATIC AIR SWING (OPTIONAL)
• Press once to start the air conditioner.• Press the SWING button to activate the automatic
• Press again to stop the unit. air swing function.
4. TEMPERATURE SETTING• To distribute the air to a specific direction, press
• To set the desired room temperature, press the the SWING button and wait until the louver move to
button to increase or decrease the set temperature. the desired direction and press the button once
• The temperature setting range is from 16°C to again.
30°C (Optional setting 18°C to 30°C).10. SLEEP MODE SETTING
• Press both buttons simultaneously to toggle the• Press the button to activate sleep mode. This
temperature setting between °C and °F. function is available under COOL, HEAT & AUTO
5. OPERATION MODE mode.
• Press the MODE button to select the type of • When it is activated in COOL mode, the set
operating mode. temperature will be increased 0.5°C after 0 mins,
• For cooling only unit, the available modes are : 1°C after 1 hour and 2°C after 2 hours.
COOL, DRY & FAN. • When it is activated in HEAT mode, the set
• For heat pump unit, the available modes are : temperature will be descreased 1 °C after 30 mins,
AUTO, COOL, DRY, FAN & HEAT. 2°C after 1 hour and 3°C after 2 hours.
6. FAN SPEED SELECTION11. CLOCK TIME SETTING
• Press the button until the desired fan speed is • Press button + or - to increase or decrease the
achieved. clock time.
7. ON TIMER SETTING
• Press the SET button will activate the on timer
function.
• Set the desired on time by pressing the SET button
continuously. If the timer is set to 7.30am, the air
conditioner will turn on at 7.30am sharp.
• Press the CLR button to cancel the on timer
setting.
8. OFF TIMER SETTING
• Press the SET button will activate the off timer
function.
14
8
3
6
T
10
9
2
5
TIMER
TEMP
AUTO
HIGH
SENSOR
ON/OFF
COOL
DRY
FAN
LOW
SWING
MODE
HEATMED
FAN
SLEEP
1
7
4
7
5
FANON/OFF
EMP
SWING
TIMERMODE
SLEEP
1
2
6
3
SLMAC-5300 (OPTIONAL)
1. “ON/OFF” SWITCH6. “SLEEP” MODE
• Press to start the air conditioner unit. • Press button to activate the sleep
• Press again to stop the unit. function can only be activated under
“cool” or heating mode operation.
2. TEMPERATURE SETTING activated under “cool” mode operation, the
• Set the desired room temperature. set temperature will increase 0.5°C after 30
• Press button to increase or decrease the minutes, 1°C after 1 hour and 2°C after 2
set temperature. Setting range are between hours. If it is actiaved under “HEAT” mode
16°C to 30°C (60°F to 80°F). operation, the set temperature will be
descreased 0.5°C after 30 minutes, 1°C
3. OPERATION MODES after 1 hour and 2°C after 2 hours.
• Press the “mode” button for select the type
of operating mode.7. AIR SWING
- Cooling Only :• Press button to activate the automatic air
COOL, DRY, FAN swing function.
- Heat Pump :
AUTO, COOL, DRY, HEAT, FAN8. SENSOR
(AUTO mode is represented by both• Infra red sensor to receive signals from
COOL and HEAT LED light on) wireless controller.
4. FAN SPEED SELECTION.9. LED DISPLAY
• Press the button until the desired fan speed • To display the set temperature (in °C) and
is achieved. timer delay setting (in hours).
5. TIMER.10. TRANSMISSION SOURCE
• Press the set button to select the switch • To transmit signals to the air conditioner.
timer of the air conditioner unit (the setting
range is between 1 to 10 hours).
15
OPERATING STATE AND FAULT TABLE
WIRELESS REMOTE CONTROLLER - HANDSET
COOLING: LED INDICATOR LIGHT DISPLAYHEATPUMP : LED INDICATOR LIGHT DISPLAY
COOL DRY FANCOOL DRY FAN HEAT
Self Diagnosis Table
COOL DRY FAN HEAT
{
{
Cool M od e
{
Dry Mode
{
Fan Mode
{
◑
Operation / Faulty Indication
Heat Mode
Auto Mode - Cool
◑
◑
◑
{ ON { / z ON or OFF
WIRED REMOTE CONTROL - SLM
COOLING / HEATPUMP MODEL
Error Code at 7 Segment Display Operation / Faulty Indication
{ Auto Mode - Heat
Compressor Overl oad
◑
◑
◑
Gas Leak
Outdoor Coil Sensor Open / Short
◑
◑
◑
Blink E1 Room sensor open / short
Blink E2 Indoor coil sensor open
Blink E3 Outdoor coil sensor open
Blink E4 Compressor overload /
Blink E5 Gas leak
Blink Heat LED Outdoor defrost ( for He atpump only)
Indoor Coil Sensor Open / Short
Room Sensor Open / Short
BLINKING
Indoor Coil Sensor S hort /
Outdoor Coil Sensor Short
16
PHSAE SEQUENCER
The unit with Scroll Compressor can only rotate in one direction. For this reason, a protective device (phase
sequencer) is fitted to prevent incorrect wiring of the electrical phases. When the three phases are not
connected correctly, the phase sequencer operates, and the unit will not start. This devise is located in the
control box of the outdoor unit.
The following table shows the LED indicator light for phase sequencer under normal operation and fault conditions.
LED_P
(Red)
Normal Operation On - - Reverse Phase Blink Blink Blink Blink
S & T Phase Missing Blink - Blink Blink
T Phase Missing Blink - - Blink
S Phase Missing Blink - Blink R Phase Missing - - - Overload Blink - - Sensor Missing Blink On On On
Notes: 1. “-” means LED off.
2. When R phase missing, no LED or buzzer will indicate the error, but relay 71 (Common) and 81 (NO)
will cut off.
3. The unit will check the discharge sensor availability only during power up.
4. All errors can only recover through manually reset.
LED_R
(Yellow)
LED_S
(Yellow)
LED_T
(Yellow)
17
INSTALLATION
!Caution
Sharp edges and coil surfaces are potential injury hazard. Avoid from contact with them.
(1) INSTALLATION OF OUTDOOR UNIT
PRELIMINARY SITE SURVEY
•Electrical supply and installation is to conform to local authority’s (e.g. National Electrical Board) codes and
regulations.
•Voltage supply fluctuation must not exceed ± 10% of rated voltage. Electricity supply lines must be independent of
welding transformer which can cause high supply fluctuations.
•Ensure that the location is convenient for wiring, piping and drainage
STANDARD MOUNTING
Ensure that the overhead supports are strong enough to hold the weight of the unit. Position the hanger rods (wall
mounting bracket for floor standing), and check for its alignment with the unit as shown in Figure A. Also, check that
the hangers are secured and the base of the fan coil unit is leveled in both horizontal directions, taking into account
the gradient for drainage flow as recommended in Figure B.
Please ensure that the following steps are taken :
•Check the gradient for drainage flow as recommended in Figure B.
•Provide clearance for easy servicing and optimal air flow as shown in Figure C.
•The indoor unit must be installed such that there is no short circuit of the cool discharge air with the
warm return air.
•Do not install the indoor unit where there is direct sunlight shining on the unit. The location should be
suitable for piping and drainage installation. The unit must be a large distance away from the door.
SEMI-ENCLOSED MOUNTING
• In case the unit is to be half recessed into false ceiling, please check the unit is well align.
RCM-D
19
RCM 62C
Figure C
• Provide the installation space as shown in Figure D.
RCM-DRCM 62C
Figure D
20
INSTALLATION - CEILING EXPOSED TYPE
STEP 1
Remove air intake grille, side panel, side close-up and hanger bracket from the unit; see Fig E
Figure E
STEP 2
Position the hanger rods as per Fig B and install the hanger bracket; see Fig F.
.
Figure F
STEP 3
Hanger up the unit and tighten the bolt, after completed the piping and drain pipe; install back the grille and panel Fig.
G.
Figure G
21
INSTALLATION - FLOOR STANDING TYPE
* Floor standing type installation not applicable for MCM 020D/DR, MCM 025D/DR, M5/CM 062C/CR.
STEP 1
Remove air intake grille, side panel, side close-up and side panel from the unit; see Fig E.
STEP 2
Position the floor support (field supply) as per Fig B. install the unit; see Fig I.
STEP 3
Two types of piping and drain pipe connection as Fig J.
PIPING AND DRAIN PIPE INSTALLATION
Figure I
Figure J
22
(2) INSTALLATION OF OUTDOOR UNIT
As condensing temperature rises, evaporating temperature rises and cooling capacity drops. In order to achieve maximum
cooling capacity, the location selected for outdoor unit should fulfill the following requirements :
•Install the condensing (outdoor) unit in a way such that hot air distributed by the outdoor condensing unit cannot be
drawn in again (as in the case of short circuit of hot discharge air). Allow sufficient space for maintenance around the
.
unit
•Ensure that there is no obstruction of air flow into or out of the unit. Remove obstacles which block air intake or
discharge.
•The location must be well ventilated, so that the unit can draw in and distribute plenty of air thus lowering the condensing
temperature.
•A place capable of bearing the weight of the outdoor unit and isolating noise and vibration.
•A place protected from direct sunlight. Otherwise use an awning for protection, if necessary.
•The location must not be susceptible to dust or oil mist.
INSTALLATION CLEARANCE
•Outdoor units must be installed such that there is no short circuit of the hot discharge air or obstruction to smooth air
flow. Select the coolest possible place where intake air should not be hotter than the outside temperature (max. 45°C)
ALL MODELSABCD
Minimum Distance300 mm1000 mm300 mm500 mm
CAUTION : If the condensing unit is operated in an atmosphere containing oils(including machine oils),
salt(coastal area), sulphide gas(near hot spring, oil refinery plant), such substances may lead to failure of the
unit.
23
(3) REFRIGERANT PIPING
D/DR
D/DR
D/DR
D/DR
D/DR
D/DR
D/DR
D/DR
D/DR
D/DR
D/DR
15
D/DR
D/DR
MAXIMUM PIPE LENGTH AND MAXIMUM NUMBER OF BENDS
•When the pipe length becomes too long, both the capacity and reliability drop. As the number of bends increases,
system piping resistance to the refrigerant flow increases, thus lowering the cooling capacity, and as the result the
font compressor may become defective. Always choose the shortest path and follow the recommendation
as tabulated below:
Model
Maximum Length, m 15 15 15 45
Maximum Elevation, m 8 8 8 25
Maximum No. of Bends 10 10 10 10
Model
Maximum Length, m 45 45 35
Maximum Elevation, m 25 25 20
Maximum No. of Bends 10 10 10
•Align the center of the piping and tighten the flare nut sufficiently with fingers.
•Finally tighten the flare nut with torque wrench unit the wrench clicks.
•When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on
the wrench.
Pipe Size (mm/in) Torque (Nm)
6.35 (1/4) 18
9.52 (3/8) 42
12.70 (1/2) 55
15.88 (5/8) 65
19.05 (3/4) 78
24
4) WIRING
ELECTRICAL CONNECTIONS
•Wiring regulations on wire diameters differ from country to country. Please refer to your LOCAL ELECTRICAL
CODES for field wiring rules. Be sure that installations comply with the rules and regulations.
GENERAL PRECAUTIONS
•Ensure that the rated voltage of the unit corresponds to the name plate before carrying out proper wiring
according to the wiring diagram.
•Provide a power outlet to be used exclusively for each unit. A power supply disconnects and a circuit
breaker for over-current protection should be provided in the exclusive line.
•The unit must be GROUNDED to prevent possible hazards due to insulation failures.
•All wiring must be firmly connected.
•All wiring must not touch the hot refrigerant piping, compressor or any moving parts of fan motors.
(5) VACUUMING AND CHARGING
The pre-charged outdoor unit does not need any vacuuming or charging. However once it is connected, the
connecting pipe line and the indoor unit need to be vacuumed before releasing the R22/R407C/R410A from the
outdoor unit.
1.Open the service port core cap.
2.Connect pressure gauge to the service port.
3.Connect the line to vacuum pump. Open the charging manifold valve and turn the pump on. Vacuum to -0.1
MPa (-760mmHg) or lower. (Evacuation time varies by the pump but averagely in 1 hour).
The additional refrigerant charge amount recommended is a guideline for longer piping application. The actual
charge required may be different from the guideline due to different application and variation in site conditions.
SPECIAL PRECAUTIONS WHEN DEALING WITH REFRIGERANT R410A UNIT
1) WHAT IS NEW REFRIGERANT R410A?
R410A is a new HFC refrigerant which does not damage the ozone layer. The working pressure of this new
refrigerant is 1.6 times higher than conventional refrigerant (R22), thus proper installation / servicing is
essential.
2) COMPONENTS
Mixture of composition by weight : R32(50%) and R125(50%)
3) CHARACTERISTIC
•R410A liquid and vapor components have different compositions when the fluid evaporates or
condenses. Hence, when leak occurs and only vapor leaks out, the composition of the refrigerant
mixture left in the system will change and subsequently affect the system performance. DO NOT add
new refrigerant to leaked system. It is recommended that the system be evacuated thoroughly before
recharging with R410A.
•When refrigerant R410A is used, the composition will differ depending on whether it is in gaseous or
liquid phase.
Hence when charging R410A, ensure that only liquid is being withdrawn from the cylinder or can. This
is to make certain that only original composition of R410A is being charged into the system.
•POE oil is used as lubricant for R410A compressor, which is different from the mineral oil used for R22
compressor.
Extra precaution must be taken to avoid exposing the R410A system to moist air.
4) CHECK LIST BEFORE INSTALLATION / SERVICING
•Tubing
Refrigerant R410A is more easily affected by dust or moisture compared with R22, make sure to
temporarily cover the ends of the tubing prior to installation
•Compressor oil
No additional charge of compressor oil is permitted.
•Refrigerant
No other refrigerant other that R410A
•Tools (size of service port is different from R22 system)
Tools specifically for R410A only (must not be used for R22 or other refrigerant)
i)Gauge manifold and charging hose
ii)Gas leak detector
iii)Refrigerant cylinder/charging cylinder
iv)Vacuum pump c/w adapter
v)Flare tools
vi)Refrigerant recovery machine
5)HANDLING AND INSTALLATION GUIDELINES
Like R22 systems, the handling and installation of R410A system are closely similar. All precautionary
measures; such as ensuring no moisture, no dirt or chips in the system, clean brazing using nitrogen, and
thorough leak check and vacuuming are equally important requirements. However, due to its hydroscopic
POE oil, additional precautions must be taken to ensure optimum and trouble-free system operation.
a) During installation or servicing, avoid prolong exposure of the internal part of the refrigerant system to
moist air. Residual POE oil in the piping and components can absorb moisture from the air.
b) Ensure that the compressor is not expose to open air for more than the recommended time specified by
its manufacturer (typically less than 10 minutes). Removed the seal-plugs only when the compressor is
about to be brazed.
c) The system should be thoroughly vacuumed to 1.0 Pa ( 700mmHg) or lower. This vacuuming level is
more stringent than R22 system so as to ensure no incompressible gas and moisture in the system.
27
d) When charging R410A, ensure that only liquid is being withdrawn from the cylinder or can. This is to
ensure that only the original composition of R410A is being delivered into the system. The liquid
composition can be different from the vapor composition.
Dip-pipeInvert cylinder
without dip-pipe
Liquid
withdrawal
e) Normally, the R410A cylinder or can is being equipped with a dip-pipe for liquid withdrawal. However, if
the dip-pipe is not available, invert the cylinder or can so as to withdraw liquid from the valve at the
bottom.
28
(6) OVERALL CHECKING
•Ensure the following, in particular:
1.The unit is mounted solidly and rigid in position.
2.Piping and connections are leak proof after charging.
3.Proper wiring has been done.
•Drainage check – pour some water into drain pan.
•Test run
1.Conduct a test run after water drainage test and gas leakage test.
2.Watch out for the following:
(a) Is the electric plug firmly inserted into the socket?
(b) Is there any abnormal sound from the unit?
(c) Is there any abnormal vibration with regard to the unit itself or piping?
(d) Is there smooth drainage of water?
•Check that:
1.Outdoor fan is running, with warm air blowing off the outdoor unit (cooling cycle).
2.Indoor blower is running and discharge cool air (cooling cycle).
3.Suction (low side) pressure is as per recommendations.
4.The remote controller has incorporated a 3 minutes delay in the circuit. Thus, it requires about 3
minutes before the outdoor unit can start up.
(7) STANDARD OPERATING CONDITION
COOLING ONLY UNIT
Temperature Ts ˚C / ˚F Th ˚C / ˚F
Minimum Indoor Temperature 19.4 / 66.9 13.9 / 57.0
Maximum Indoor Temperature 26.7 / 80.1 19.4 / 66.9
Minimum Outdoor Temperature 19.4 / 66.9 13.9 / 57.0
Maximum Outdoor Temperature 46 / 114.8 24 / 75.2
HEAT PUMP UNIT
Temperature Ts ˚C / ˚F Th ˚C / ˚F
Minimum Indoor Temperature 10 / 50 Maximum Indoor Temperature 26.7 / 80.1 Minimum Outdoor Temperature -8 / 17.6 -9 / 15.8
Maximum Outdoor Temperature 24 / 75.2 18 / 64.4
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 0.8m BELOW THE UNIT.
39
GENERAL DATA - HEAT PUMP (R22)
JIS C 9612
MODEL
NOMINAL COOLING CAPACITY
NOMINAL HEATING CAPACITY
NOMINAL TOTAL INPUT POWER (COOLING)
NOMINAL TOTAL INPUT POWER (HEATING)
NOMINAL RUNNING CURRENT (COOLING)
NOMINAL RUNNING CURRENT (HEATING)
POWER SOURCE
EER
COP
REFRIGERANT TYPE
REFRIGERANT CONTROL (EXPANSION DEVICE)
CONTROL
AIR FLOW
EXTERNAL STATIC PRESSURE (H/M/L)mmAq
SOUND PRESSURE LEVEL (H/M/L)
UNIT DIMENSION
INDOOR UNIT
PACKING
DIMENSION
UNIT WEIGHT
CONDENSATE DRAIN SIZE
AIR FLOW
SOUND PRESSURE LEVEL
UNIT DIMENSION
PACKING
DIMENSION
OUTDOOR UNIT
UNIT WEIGHT
PIPE CONNECTION
REFRIGERANT C HAR GE
AIR DISCHARGE
OPERATIONW IRELESSS OR WIRED MICROCOMPUTER REMOTE CONTROL
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 0.8m BELOW THE UNIT.
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
41
GENERAL DATA - HEAT PUMP (R22)
35DR
40DR
852 / 33.6
1010 / 39.8
1180 / 46.5
514 / 20.2
JIS B 8616
SIZE
INDOOR UNIT
OUTDOOR UNIT
HIGH
MEDIUM
LOW
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
TYPE
LIQUIDmm/in
GASmm/in
MODEL
NOMINAL COOLING CAPACITY - 1Ø / <3Ø>
NOMINAL HEATING CAPACITY - 1Ø / <3Ø>
NOMINAL TOTAL INPUT POWER (COOLING) - 1Ø / <3Ø>
NOMINAL TOTAL INPUT POWER (HEATING) - 1Ø / <3Ø>
NOMINAL RUNNING CURRENT (COOLING) - 1Ø / <3Ø>
NOMINAL RUNNING CURRENT (HEATING) - 1Ø / <3Ø>
POWER SOURCE - 1Ø / <3Ø>
EER - 1Ø / <3Ø>
COP - 1Ø / <3Ø>
REFRIGERANT TYPE
REFRIGERANT CONTROL (EXPANSION DEVICE)
CONTROL
AIR FLOW
EXTERNAL STATIC PRESSURE (H/M/L)mmAq
SOUND PRESSURE LEVEL (H/M/L)
UNIT DIMENSION
INDOOR UNIT
PACKING DIMENSION
UNIT WEIGHT
CONDENSATE DRAIN SIZE
AIR FLOW
SOUND PRESSURE LEVEL
UNIT DIMENSION
PACKING DIMENSION
OUTDOOR UNIT
UNIT WEIGHT
PIPE CONNECTION
REFRIGERANT C HAR GE
AIR DISCHARGE
OPERATIONWIRELESSS OR WIRED MICROCOMPUTER REMOTE CONTROL
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
45
GENERAL DATA - HEAT PUMP (R410A)
35DR
40DR
86 / 189
852 / 33.6
1010 / 39.8
1180 / 46.5
514 / 20.2
95 / 209
JIS B 8616
MODEL
NOMINAL COOLING CAPACITY - 1Ø / <3Ø>
NOMINAL HEATING CAPACITY - 1Ø / <3Ø>
NOMINAL TOTAL INPUT POWER (COOLING) - 1Ø / <3Ø>
NOMINAL TOTAL INPUT POWER (HEATING) - 1Ø / <3Ø>
NOMINAL RUNNING CURRENT (COOLING) - 1Ø / <3Ø>
NOMINAL RUNNING CURRENT (HEATING) - 1Ø / <3Ø>
POWER SOURCE - 1Ø / <3Ø>
EER - 1Ø / <3Ø>
COP - 1Ø / <3Ø>
REFRIGERANT TYPE
REFRIGERANT CONTROL (EXPANSION DEVICE)OUTDOOR CAP. TUBE
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
47
COMPONENTS DATA (R22)
IP X4
MODEL
INDOOR UNIT
OUTDOOR UNIT
TYPE
QUANTITY
INDOOR FAN
MATERIAL
DRIVE
DIAMETER
LENGTH
INDOOR FAN
MOTOR
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
QUANTITY
OUTDOOR FAN MATERIAL
DRIVE
DIAMETER
OUTDOOR FAN
MOTOR
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
COMPRESSOR
OIL TYPE
OIL AMOUNT
TUBE
INDOOR COIL
FIN
TUBE
OUTDOOR COIL
FIN
AIR QUALITYFI LTER
INDOOR UNIT
CASING
OUTDOOR UNIT
MATERIAL
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FACE AREA
ROW
FIN PER INCH
MATERIAL
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FACE AREA
ROW
FIN PER INCH
TYPE
QUANTITY
LENGTHmm/in
SIZE
WIDTHmm/in
THICKNESSmm/in
mm/in
mm/in
mm/in
3
cm
/ fl.oz.
mm/in
mm/in
mm/in
2
2
/ft
m
mm/in
mm/in
mm/in
2
2
m
/ft
pc
MATERIAL
FINISHING
COLOUR
MATERIAL
FINISHING
COLOUR
RCM 20D
ALC 18CALC 2 0C
CROSS FLOW
2
ABS
DIRECT
146 / 5.75
200 / 7.87
INDUCTION
1
N/A
PROPELLER
1
GLASS REINFORCED ACRYL STYRENE RESIN
DIRECT
457 / 18
INDUCTION
1
IP54
ROTARY
ATMOS NM56M or SUNISO 4GDID
670 / 23.6
SEAMLESS COPPER
9.52 / 3/8
0.30 / 0.012
ALUMINIUM (CORR. FIN)
0.11 / 0.0043
0.19 / 2.06
3
12
SEAMLESS INNER GROOVE COPPER
7.00 / 0.276
0.28 / 0.011
ALUMINIUM (RAISE LANCE)
0.10 / 0.004
0.52 / 5.59
12
2024
WASHABLE SARANET FILTER
2
544 / 21.4
270 / 10.6
3 / 0.11
GALVANIZED MILD STEEL
POLYESTER POWDER
LIGHT GREY
GALVANIZED MILD STEEL
POLYESTER POWDER
LIGHT GREY
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
48
COMPONENTS DATA (R22)
IP X4
MODEL
INDOOR UNIT
OUTDOOR UNIT
TYPE
QUANTITY
INDOOR FAN
INDOOR FAN
MOTOR
MATERIAL
DRIVE
DIAMETER
LENGTH
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
mm/in
mm/in
TYPE
QUANTITY
OUTDOOR FAN MATERIAL
GLASS REINFORCED ACRYL STYRENE RESIN
DRIVE
OUTDOOR FAN
MOTOR
DIAMETER
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
mm/in
TYPE
COMPRESSOR
INDOOR COIL
OIL TYPE
OIL AMOUNT
MATERIAL
TUBE
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FACE AREA
FIN
cm
mm/in
mm/in
mm/in
3
m
/ fl.oz.
2
2
/ft
ATMOS NM56M or SUNISO 4GDID
SEAMLESS COPPER
ALUMINIUM (CORR. FIN)
ROW
FIN PER INCH
OUTDOOR COIL
TUBE
FIN
MATERIAL
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FACE AREA
mm/in
mm/in
mm/in
2
m
/ft
2
SEAMLESS INNER GROOVE COPPER
ALUMINIUM (RAISE LANCE)
ROW
FIN PER INCH
AIR QUALITYFI LTER
TYPE
QUANTITY
LENGTHmm/in
SIZE
WIDTHmm/in
pc
WASHABLE SARANET FILTER
THICKNESSmm/in
GALVANIZED MILD STEEL
POLYESTER POWDER
GALVANIZED MILD STEEL
POLYESTER POWDER
CASING
INDOOR UNIT
OUTDOOR UNIT
MATERIAL
FINISHING
COLOUR
MATERIAL
FINISHING
COLOUR
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
RCM 25D
ALC 25C
CROSS FLOW
2
ABS
DIRECT
146 / 5.75
200 / 7.87
INDUCTION
1
N/A
PROPELLER
1
DIRECT
457 / 18
INDUCTION
1
IP54
ROTARY
700 / 24.6
9.52 / 3/8
0.30 / 0.012
0.11 / 0.0043
0.19 / 2.06
3
12
7.00 / 0.276
0.28 / 0.011
0.10 / 0.004
0.62 / 6.67
2
18
2
544 / 21.4
270 / 10.6
3 / 0.11
LIGHT GREY
LIGHT GREY
49
Components Data (R22)
30D
IP 24
IP 44
MODEL
INDOOR UNIT
OUTDOOR UNIT
TYPE
QUANTITY
INDOOR FAN
MATERIAL
DRIVE
DIAMETER
LENGTH
INDOOR FAN
MOTOR
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
QUANTITY
OUTDOOR FAN MATERIAL
DRIVE
DIAMETER
OUTDOOR FAN
MOTOR
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
COMPRESSOR
OIL TYPE
OIL AMOUNT
TUBE
INDOOR COIL
FIN
TUBE
OUTDOOR COIL
FIN
AIR QUALITYFI LTER
INDOOR UNIT
CASING
OUTDOOR UNIT
MATERIAL
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FACE AREA
ROW
FIN PER INCH
MATERIAL
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FACE AREA
ROW
FIN PER INCH
TYPE
QUANTITY
LENGTHmm/in
SIZE
WIDTHmm/in
THICKNESSmm/in
RCM 30D
ALC 28CALC 3 0C
CROSS FLOW
3
ABS
DIRECT
mm/in
mm/in
146 / 5.75
200 / 7.87
INDUCTION
1
N/A
PROPELLER
1
GLASS REINFORCED ACRYL STYRENE RESIN
DIRECT
mm/in
457 / 18609.6 / 24
INDUCTION
1
IP54-
ROTARYSCROLL
ATMOS M60 or SUNISO 4GDIDMINERAL (Sontex 200 LT)
cm
3
/ fl.oz.
1130 / 39.81240 / 43.6
SEAMLESS INNER GROOVE COPPER
mm/in
mm/in
9.52 / 3/8
0.30 / 0.012
ALUMINIUM (HYDROPHILIC)
mm/in
2
m
/ft
2
0.11 / 0.0043
0.24 / 2.58
3
12
mm/in
mm/in
SEAMLESS INNER GROOVE COPPER
9.52 / 3/89.52 / 3/8
0.33 / 0.0130.35 / 0.014
SEAMLESS COPPER
ALUMINIUM (SLIT FIN)ALUMINIUM (SLIT FIN)
mm/in0.12 / 0.0050.12 / 0.005
2
2
/ft
m
0.61 / 6.520.87 / 9.33
21
1816
WASHABLE SARANET FILTER
pc
2
544 / 21.4
270 / 10.6
3 / 0.11
MATERIAL
FINISHING
COLOUR
MATERIAL
FINISHING
COLOUR
GALVANIZED MILD STEEL
POLYESTER POWDER
LIGHT GREY
GALVANIZED MILD STEEL
POLYESTER POWDER
LIGHT GREY
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
50
COMPONENTS DATA (R22)
35D
40D
IP 44
MODEL
INDOOR UNIT
OUTDOOR UNIT
TYPE
QUANTITY
INDOOR FAN
MATERIAL
DRIVE
DIAMETER
LENGTH
INDOOR FAN
MOTOR
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
QUANTITY
OUTDOOR FAN MATERIAL
DRIVE
DIAMETER
OUTDOOR FAN
MOTOR
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
COMPRESSOR
OIL TYPE
OIL AMOUNT
TUBE
INDOOR COIL
FIN
TUBE
OUTDOOR COIL
FIN
AIR QUALITYFI LTER
INDOOR UNIT
CASING
OUTDOOR UNIT
RCM 40D
ALC 35CALC 4 0C
CROSS FLOW
4
ABS
DIRECT
mm/in
mm/in
146 / 5.75
200 / 7.87
INDUCTION
1
N/A
PROPELLER
1
GLASS REINFORCED ACRYL STYRENE RESIN
DIRECT
mm/in
609.6 / 24
INDUCTION
1
-
SCROLL
MINERAL (Sontex 200LT)MINERAL (Sontex 200LT)
MATERIAL
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FACE AREA
ROW
FIN PER INCH
MATERIAL
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FACE AREA
ROW
FIN PER INCH
3
/ fl.oz.
cm
mm/in
mm/in
mm/in
2
2
m
/ft
mm/in
mm/in
mm/in0.127 / 0.0050.127 / 0.005
2
2
m
/ft
1240 / 43.61240 / 43.6
SEAMLESS COPPER
9.52 / 3/8
0.30 / 0.012
ALUMINIUM (HYDROPHILIC)
0.11 / 0.0043
0.36 / 3.95
4
12
SEAMLESS COPPER
9.52 / 3/8
0.35 / 0.014
ALUMINIUM (SLIT FIN)ALUMINIUM (CORR. FIN)
0.87 / 9.330.87 / 9.33
12
1614
TYPEWASHABLE SARANET FILTER
QUANTITY2 + 1
LENGTHmm/in
SIZE
WIDTHmm/in
THICKNESSmm/in
pc
MATERIAL
FINISHING
COLOUR
MATERIAL
FINISHING
COLOUR
544 + 494 / 21.4 + 19.4
270 / 10.6
3 / 0.11
GALVANIZED MILD STEEL
POLYESTER POWDER
LIGHT GREY
GALVANIZED MILD STEEL
POLYESTER POWDER
LIGHT GREY
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
51
COMPONENTS DATA (R22)
50D
61D
IP 44
IP 20
MODEL
INDOOR UNIT
OUTDOOR UNIT
TYPE
QUANTITY
INDOOR FAN
MATERIAL
DRIVE
DIAMETER
LENGTH
INDOOR FAN
MOTOR
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
QUANTITY
OUTDOOR FAN MATERIAL
DRIVE
DIAMETER
OUTDOOR FAN
MOTOR
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
COMPRESSOR
OIL TYPE
OIL AMOUNT
TUBE
INDOOR COIL
FIN
TUBE
OUTDOOR COIL
FIN
AIR QUALITYFI LTER
INDOOR UNIT
CASING
OUTDOOR UNIT
RCM 50DRCM 62C
ALC 50CALC 6 1C
CROSS FLOW
4
ABSALU
DIRECT
mm/in
mm/in
146 / 5.75 160 / 6.30
200 / 7.87202 / 7.95
INDUCTION
12
N/AN/A
PROPELLER
1
GLASS REINFORCED ACRYL STYRENE RESIN
DIRECT
mm/in
609.6 / 24
INDUCTION
1
-
SCROLL
MINERAL (Sontex 200LT)MINERAL (Sontex 200LT)
MATERIAL
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FACE AREA
ROW
FIN PER INCH
MATERIAL
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FACE AREA
ROW
FIN PER INCH
3
/ fl.oz.
cm
mm/in
mm/in
mm/in
2
2
/ft
m
mm/in
mm/in
mm/in0.127 / 0.0050.127 / 0.005
2
2
/ft
m
1950 / 68.61950 / 68.6
SEAMLESS INNER GROOVE COPPER
9.52 / 3/8
0.30 / 0.012
ALUMINIUM (HYDROPHILIC)ALUMINIUM (SLIT FIN)
0.11 / 0.00430.11 / 0.0043
0.36 / 3.950.42 / 4.51
44
1214
SEAMLESS COPPER
SEAMLESS INNER GROOVE COPPER
9.52 / 3/89.52 / 3/8
0.35 / 0.0140.33 / 0.013
ALUMINIUM (CORR. FIN)ALUMINIUM (SLIT FIN)
0.87 / 9.330.84 / 9.04
23
1614
TYPEWASHABLE SARANET FILTER
QUANTITY2 + 3
LENGTHmm/in
SIZE
WIDTHmm/in
THICKNESSmm/in
pc
MATERIAL
FINISHING
COLOUR
MATERIAL
FINISHING
COLOUR
500 + 400 / 19.6 + 15.7
285 / 11.2
3 / 0.11
GALVANIZED MILD STEEL
POLYESTER POWDER
LIGHT GREY
GALVANIZED MILD STEEL
POLYESTER POWDER
LIGHT GREY
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
52
COMPONENTS DATA (R22)
IP X4
MODEL
INDOOR UNIT
OUTDOOR UNIT
TYPE
QUANTITY
INDOOR FAN
MATERIAL
DRIVE
DIAMETER
LENGTH
INDOOR FAN
MOTOR
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
QUANTITY
OUTDOOR FAN MATERIAL
DRIVE
DIAMETER
OUTDOOR FAN
MOTOR
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
COMPRESSOR
OIL TYPE
OIL AMOUNT
TUBE
INDOOR COIL
FIN
TUBE
OUTDOOR COIL
FIN
AIR QUALITYFI LTER
INDOOR UNIT
CASING
OUTDOOR UNIT
RCM 20DR
ALC 18CRALC 20CR
CROSS FLOW
2
ABS
DIRECT
mm/in
mm/in
146 / 5.75
200 / 7.87
INDUCTION
1
N/A
PROPELLER
1
GLASS REINFORCED ACRYL STYRENE RESIN
DIRECT
mm/in
457 / 18
INDUCTION
1
IP54
ROTARY
ATMOS NM56M or SUNISO 4GDID
MATERIAL
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FACE AREA
ROW
FIN PER INCH
MATERIAL
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FACE AREA
ROW
FIN PER INCH
cm
mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
3
m
m
/ fl.oz.
2
2
/ft
2
2
/ft
SEAMLESS INNER GROOVE COPPER
12
2024
670 / 23.6
SEAMLESS COPPER
9.52 / 3/8
0.30 / 0.012
ALUMINIUM (CORR. FIN)
0.11 / 0.0043
0.19 / 2.06
3
12
7.00 / 0.276
0.28 / 0.011
ALUMINIUM (RAISE LANCE)
0.10 / 0.004
0.52 / 5.59
TYPEWASHABLE SARANET FILTER
QUANTITY2
LENGTHmm/in
SIZE
WIDTHmm/in
THICKNESSmm/in
pc
MATERIAL
FINISHING
COLOUR
MATERIAL
FINISHING
COLOUR
544 / 21.4
270 / 10.6
3 / 0.11
GALVANIZED MILD STEEL
POLYESTER POWDER
LIGHT GREY
GALVANIZED MILD STEEL
POLYESTER POWDER
LIGHT GREY
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
53
COMPONENTS DATA (R22)
IP X4
MODEL
INDOOR UNIT
OUTDOOR UNIT
TYPE
QUANTITY
INDOOR FAN
MATERIAL
DRIVE
DIAMETER
LENGTH
INDOOR FAN
MOTOR
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
QUANTITY
OUTDOOR FAN MATERIAL
DRIVE
DIAMETER
OUTDOOR FAN
MOTOR
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
COMPRESSOR
OIL TYPE
OIL AMOUNT
TUBE
INDOOR COIL
FIN
TUBE
OUTDOOR COIL
FIN
AIR QUALITY
FILTER
INDOOR UNIT
CASING
OUTDOOR UNIT
RCM 25DR
ALC 25CR
CROSS FLOW
2
ABS
DIRECT
mm/in
mm/in
146 / 5.75
200 / 7.87
INDUCTION
1
N/A
PROPELLER
1
GLASS REINFORCED ACRYL SYRENE RESIN
DIRECT
mm/in
457 / 18
INDUCTION
1
IP54
ROTARY
ATMOS NM56M or SUNISO 4GDID
MATERIAL
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FACE AREA
ROW
FIN PER INCH
MATERIAL
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FACE AREA
ROW
FIN PER INCH
cm
3
/ fl.oz.
mm/in
mm/in
mm/in
2
m
/ft
mm/in
mm/in
mm/in
2
m
/ft
2
SEAMLESS INNER GROOVE COPPER
2
700 / 24.6
SEAMLESS COPPER
9.52 / 3/8
0.30 / 0.012
ALUMINIUM (CORR. FIN)
0.11 / 0.0043
0.19 / 2.06
3
12
7.00 / 0.276
0.28 / 0.011
ALUMINIUM (RAISE LANCE)
0.10 / 0.004
0.62 / 6.67
2
18
TYPEWASHABLE SARANET FILTER
QUANTITY2
LENGTHmm/in
SIZE
WIDTHmm/in
THICKNESSmm/in
pc
MATERIAL
FINISHING
COLOUR
MATERIAL
FINISHING
COLOUR
544 / 21.4
270 / 10.6
3 / 0.11
GALVANIZED MILD STEEL
POLYESTER POWDER
LIGHT GREY
GALVANIZED MILD STEEL
POLYESTER POWDER
LIGHT GREY
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
54
COMPONENTS DATA (R22)
30DR
IP 24
IP 44
MODEL
INDOOR UNIT
OUTDOOR UNIT
TYPE
QUANTITY
INDOOR FAN
MATERIAL
DRIVE
DIAMETER
LENGTH
INDOOR FAN
MOTOR
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
QUANTITY
OUTDOOR FAN MATERIAL
DRIVE
DIAMETER
OUTDOOR FAN
MOTOR
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
COMPRESSOR
OIL TYPE
OIL AMOUNT
TUBE
INDOOR COIL
FIN
TUBE
OUTDOOR COIL
FIN
AIR QUALITYFI LTER
INDOOR UNIT
CASING
OUTDOOR UNIT
RCM 30DR
ALC 28CRALC 30CR
CROSS FLOW
3
ABS
DIRECT
mm/in
mm/in
146 / 5.75
200 / 7.87
INDUCTION
1
N/A
PROPELLER
1
GLASS REINFORCED ACRYL STYRENE RESIN
DIRECT
mm/in
457 / 18609.6 / 24
INDUCTION
1
IP54-
ROTARYSCROLL
ATMOS M60 or SUNISO 4GDIDMINERAL (Sontex 200 LT)
MATERIAL
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FACE AREA
ROW
FIN PER INCH
MATERIAL
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FACE AREA
ROW
FIN PER INCH
3
/ fl.oz.
cm
mm/in
mm/in
mm/in
2
2
m
/ft
SEAMLESS INNER GROOVE COPPER
mm/in
mm/in
mm/in0.12 / 0.0050.12 / 0.005
2
2
/ft
m
1130 / 39.81240 / 43.6
SEAMLESS INNER GROOVE COPPER
9.52 / 3/8
0.30 / 0.012
ALUMINIUM (HYDROPHILIC)
0.11 / 0.0043
0.24 / 2.58
3
12
SEAMLESS COPPER
9.52 / 3/89.52 / 3/8
0.33 / 0.0130.35 / 0.014
ALUMINIUM (SLIT FIN)ALUMINIUM (CORR. FIN)
0.61 / 6.520.87 / 9.33
22
1816
TYPEWASHABLE SARANET FILTER
QUANTITY2
LENGTHmm/in
SIZE
WIDTHmm/in
THICKNESSmm/in
pc
MATERIAL
FINISHING
COLOUR
MATERIAL
FINISHING
COLOUR
544 / 21.4
270 / 10.6
3 / 0.11
GALVANIZED MILD STEEL
POLYESTER POWDER
LIGHT GREY
GALVANIZED MILD STEEL
POLYESTER POWDER
LIGHT GREY
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
55
COMPONENTS DATA (R22)
35DR
40DR
IP 44
MODEL
INDOOR UNIT
OUTDOOR UNIT
TYPE
QUANTITY
INDOOR FAN
MATERIAL
DRIVE
DIAMETER
LENGTH
INDOOR FAN
MOTOR
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
QUANTITY
OUTDOOR FAN MATERIAL
DRIVE
DIAMETER
OUTDOOR FAN
MOTOR
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
COMPRESSOR
OIL TYPE
OIL AMOUNT
TUBE
INDOOR COIL
FIN
TUBE
OUTDOOR COIL
FIN
AIR QUALITYFI LTER
INDOOR UNIT
CASING
OUTDOOR UNIT
MATERIAL
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FACE AREA
ROW
FIN PER INCH
MATERIAL
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FACE AREA
ROW
FIN PER INCH
TYPE
QUANTITY
LENGTHmm/in
SIZE
WIDTHmm/in
THICKNESSmm/in
mm/in
mm/in
mm/in
3
/ fl.oz.
cm
mm/in
mm/in
mm/in
2
2
m
/ft
mm/in
mm/in
mm/in
2
2
m
/ft
pc
MATERIAL
FINISHING
COLOUR
MATERIAL
FINISHING
COLOUR
RCM 40DR
ALC 35CRALC 40CR
CROSS FLOW
4
ABS
DIRECT
146 / 5.75
200 / 7.87
INDUCTION
1
N/A
PROPELLER
1
GLASS REINFORCED ACRYL STYRENE RESIN
DIRECT
609.6 / 24
INDUCTION
1
-
SCROLL
MINERAL (Sontex 200LT)MINERAL (Sontex 200LT)
1240 / 43.61240 / 43.6
SEAMLESS COPPER
9.52 / 3/8
0.30 / 0.012
ALUMINIUM (HYDROPHILIC)
0.11 / 0.0043
0.36 / 3.95
4
12
SEAMLESS INNER GROOVE COPPER
9.52 / 3/8
0.33 / 0.013
ALUMINIUM (CORR. FIN)
0.127 / 0.005
0.87 / 9.33
2
16
WASHABLE SARANET FILTER
2 + 1
544 + 494 / 21.4 + 19.4
270 / 10.6
3 / 0.11
GALVANIZED MILD STEEL
POLYESTER POWDER
LIGHT GREY
GALVANIZED MILD STEEL
POLYESTER POWDER
LIGHT GREY
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
56
COMPONENTS DATA (R22)
50DR
61DR
IP 20
IP 20
MODEL
INDOOR FAN
INDOOR FAN
MOTOR
OUTDOOR FAN MATERIAL
OUTDOOR FAN
MOTOR
COMPRESSOR
INDOOR COIL
OUTDOOR COIL
AIR QUALITYFI LTER
CASING
INDOOR UNIT
OUTDOOR UNIT
TYPE
QUANTITY
MATERIAL
DRIVE
DIAMETER
LENGTH
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
QUANTITY
DRIVE
DIAMETER
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
OIL TYPE
OIL AMOUNT
TUBE
FIN
TUBE
FIN
INDOOR UNIT
OUTDOOR UNIT
MATERIAL
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FACE AREA
ROW
FIN PER INCH
MATERIAL
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FACE AREA
ROW
FIN PER INCH
TYPE
QUANTITY
LENGTHmm/in
SIZE
WIDTHmm/in
THICKNESSmm/in
RCM 50DRRCM 62CR
ALC 50CRALC 61CR
CROSS FLOW
4
ABSALU
DIRECT
mm/in
mm/in
mm/in
3
/ fl.oz.
cm
mm/in
mm/in
mm/in
2
2
/ft
m
mm/in
mm/in
mm/in0.127 / 0.0050.127 / 0.005
2
2
m
/ft
pc
MATERIAL
FINISHING
COLOUR
MATERIAL
FINISHING
COLOUR
146 / 5.75 160 / 6.30
200 / 7.87202 / 7.95
INDUCTION
12
N/AN/A
PROPELLER
1
GLASS REINFORCED ACRYL STYRENE RESIN
DIRECT
609.6 / 24
INDUCTION
1
-
SCROLL
MINERAL (Sontex 200LT)MINERAL (Sontex 200LT)
1950 / 68.61950 / 68.6
SEAMLESS INNER GROOVE COPPER
9.52 / 3/8
0.30 / 0.012
ALUMINIUM (HYDROPHILIC)ALUMINIUM (SLIT FIN)
0.11 / 0.00430.11 / 0.0043
0.36 / 3.950.42 / 4.51
44
1214
SEAMLESS INNER GROOVE COPPER
9.52 / 3/8
0.33 / 0.013
ALUMINIUM (CORR. FIN)ALUMINIUM (SLIT FIN)
0.87 / 9.330.84 / 9.04
23
1614
WASHABLE SARANET FILTER
2 + 3
500 + 400 / 19.6 + 15.7
285 / 11.2
3 / 0.11
GALVANIZED MILD STEEL
POLYESTER POWDER
LIGHT GREY
GALVANIZED MILD STEEL
POLYESTER POWDER
LIGHT GREY
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
57
COMPONENT DATA (R410A)
035D
040D
IP 44
MODEL
INDOOR UNIT
OUTDOOR UNIT
TYPE
QUANTITY
INDOOR FAN
MATERIAL
DRIVE
DIAMETER
LENGTH
INDOOR FAN
MOTOR
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
QUANTITY
OUTDOOR FAN MATERIAL
DRIVE
DIAMETER
OUTDOOR FAN
MOTOR
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
COMPRESSOR
OIL TYPE
OIL AMOUNT
TUBE
INDOOR COIL
FIN
TUBE
OUTDOOR COIL
FIN
AIR QUALITYFI LTER
INDOOR UNIT
CASING
OUTDOOR UNIT
R5CM 40D
A5LC 35CA5LC 40C
CROSS FLOW
4
ABS
DIRECT
mm/in
mm/in
146 / 5.75
200 / 7.87
INDUCTION
1
N/A
PROPELLER
1
GLASS REINFORCED ACRYL STYRENE RESIN
DIRECT
mm/in
609.6 / 24
INDUCTION
1
-
SCROLLSCROLL
MOBIL EAL ARCTIC 22CCMOBIL EAL ARCTIC 22CC
MATERIAL
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FACE AREA
ROW
FIN PER INCH
MATERIAL
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FACE AREA
ROW
FIN PER INCH
3
/ fl.oz.
cm
mm/in
mm/in
mm/in
2
2
m
/ft
mm/in
mm/in
mm/in0.10 / 0.00390.10 / 0.0039
2
2
m
/ft
1242 / 43.71951 / 68.7
SEAMLESS COPPER
9.52 / 3/8
0.30 / 0.012
ALUMINIUM (HYDROPHILIC)
0.11 / 0.0043
0.36 / 3.95
4
12
SEAMLESS INNER GROOVE COPPER
7.00 / 0.276
0.28 / 0.011
ALUMINIUM (CORR. FIN)ALUMINIUM (CORR. FIN)
0.87 / 9.330.87 / 9.33
22
1818
TYPEWASHABLE SARANET FILTER
QUANTITY2 + 1
LENGTHmm/in
SIZE
WIDTHmm/in
THICKNESSmm/in
pc
MATERIAL
FINISHING
COLOUR
MATERIAL
FINISHING
COLOUR
544 + 494 / 21.4 + 19.4
270 / 10.6
3 / 0.11
GALVANIZED MILD STEEL
POLYESTER POWDER
LIGHT GREY
GALVANIZED MILD STEEL
POLYESTER POWDER
LIGHT GREY
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
58
COMPONENT DATA (R410A)
50D
61D
IP 20
IP 54
MODEL
INDOOR UNIT
OUTDOOR UNIT
TYPE
QUANTITY
INDOOR FAN
MATERIAL
DRIVE
DIAMETER
LENGTH
INDOOR FAN
MOTOR
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
QUANTITY
OUTDOOR FAN MATERIAL
DRIVE
DIAMETER
OUTDOOR FAN
MOTOR
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
COMPRESSOR
OIL TYPE
OIL AMOUNT
TUBE
INDOOR COIL
FIN
TUBE
OUTDOOR COIL
FIN
AIR QUALITYFI LTER
INDOOR UNIT
CASING
OUTDOOR UNIT
R5CM 50DR5CM 62C
A5LC 50CA5LC 61C
CROSS FLOW
44
ABSALU
DIRECT
mm/in
mm/in
146 / 5.75 160 / 6.30
200 / 7.87202 / 7.95
INDUCTION
12
N/AN/A
PROPELLER
1
GLASS REINFORCED ACRYL STYRENE RESIN
DIRECT
mm/in
609.6 / 24
INDUCTION
1
--
SCROLL
MOBIL EAL ARCTIC 22CCMOBIL EAL ARCTIC 22CC
3
/ fl.oz.
cm
MATERIAL
DIAMETER
THICKNESS
mm/in9.52 / 3/89.52 / 3/8
mm/in0.30 / 0.0120.30 / 0.012
SEAMLESS INNER GROOVED COPPER
MATERIAL
THICKNESS
FACE AREA
mm/in
2
/ft
m
2
ROW
FIN PER INCH
MATERIAL
DIAMETER
THICKNESS
mm/in
mm/in
MATERIAL
THICKNESS
FACE AREA
mm/in0.10 / 0.0039
2
2
m
/ft
ROW
FIN PER INCH
TYPE
QUANTITY2 + 3
pc
LENGTHmm/in
SIZE
WIDTHmm/in
THICKNESSmm/in
MATERIAL
FINISHING
COLOUR
MATERIAL
FINISHING
COLOUR
1656 / 58.31591 / 56
ALUMINIUM (HYDROPHILIC)ALUMINIUM (SLIT FIN)
0.11 / 0.00430.11 / 0.0043
0.36 / 3.950.42 / 4.51
44
1814
SEAMLESS COPPER
7.00 / 0.276
0.28 / 0.011
ALUMINIUM (CORR. FIN)
0.87 / 9.330.84 / 9.04
2
18
WASHABLE SARANET FILTER
500 + 400 / 19.6 + 15.7
285 / 11.2
3 / 0.11
GALVANIZED MILD STEEL
POLYESTER POWDER
LIGHT GREY
GALVANIZED MILD STEEL
POLYESTER POWDER
LIGHT GREY
SEAMLESS COPPER
ALUMINIUM (CORR. FIN)
0.10 / 0.0039
3
18
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
59
COMPONENT DATA (R22)
(R410A)
A5LC 35DR
R5CM 40DR
A5LC 40DR
IP 44
MODEL
INDOOR FAN
INDOOR FAN
MOTOR
OUTDOOR FAN MATERIAL
OUTDOOR FAN
MOTOR
COMPRESSOR
INDOOR COIL
OUTDOOR COIL
AIR QUALITYFI LTER
CASING
INDOOR UNIT
OUTDOOR UNIT
TYPE
QUANTITY
MATERIAL
DRIVE
DIAMETER
LENGTH
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
QUANTITY
DRIVE
DIAMETER
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
OIL TYPE
OIL AMOUNT
TUBE
FIN
TUBE
FIN
INDOOR UNIT
OUTDOOR UNIT
MATERIAL
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FACE AREA
ROW
FIN PER INCH
MATERIAL
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FACE AREA
ROW
FIN PER INCH
TYPE
QUANTITY
LENGTHmm/in
SIZE
WIDTHmm/in
THICKNESSmm/in
RCM 40DR
ALC 35CRALC 40CR
CROSS FLOW
4
ABS
DIRECT
mm/in
mm/in
GLASS REINFORCED ACRYL STYRENE RESIN
mm/in
SCROLLSCROLL
3
/ fl.oz.
cm
mm/in
mm/in
mm/in
2
2
m
/ft
mm/in
mm/in
mm/in0.10 / 0.00390.10 / 0.0039
2
2
m
/ft
pc
MATERIAL
FINISHING
COLOUR
MATERIAL
FINISHING
COLOUR
MOBIL EAL ARCTIC 22CCMOBIL EAL ARCTIC 22CC
1242 / 43.71951 / 68.7
ALUMINIUM (HYDROPHILIC)
SEAMLESS INNER GROOVE COPPER
ALUMINIUM (CORR. FIN)ALUMINIUM (CORR. FIN)
0.87 / 9.330.87 / 9.33
22
1818
WASHABLE SARANET FILTER
146 / 5.75
200 / 7.87
INDUCTION
1
N/A
PROPELLER
1
DIRECT
609.6 / 24
INDUCTION
1
-
SEAMLESS COPPER
9.52 / 3/8
0.30 / 0.012
0.11 / 0.0043
0.36 / 3.95
4
12
7.00 / 0.276
0.28 / 0.011
2 + 1
544 + 494 / 21.4 + 19.4
270 / 10.6
3 / 0.11
GALVANIZED MILD STEEL
POLYESTER POWDER
LIGHT GREY
GALVANIZED MILD STEEL
POLYESTER POWDER
LIGHT GREY
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
60
COMPONENT DATA (R410A)
050DR
061DR
IP 20
IP 54
MODEL
INDOOR UNIT
OUTDOOR UNIT
TYPE
QUANTITY
INDOOR FAN
MATERIAL
DRIVE
DIAMETER
LENGTH
INDOOR FAN
MOTOR
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
QUANTITY
OUTDOOR FAN MATERIAL
DRIVE
DIAMETER
OUTDOOR FAN
MOTOR
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
COMPRESSOR
OIL TYPE
OIL AMOUNT
TUBE
INDOOR COIL
FIN
TUBE
OUTDOOR COIL
FIN
AIR QUALITYFI LTER
INDOOR UNIT
CASING
OUTDOOR UNIT
MATERIAL
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FACE AREA
ROW
FIN PER INCH
MATERIAL
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FACE AREA
ROW
FIN PER INCH
TYPE
QUANTITY
LENGTHmm/in
SIZE
WIDTHmm/in
THICKNESSmm/in
R5CM 50DRR5CM 62CR
A5LC 50CRA5LC 61CR
CROSS FLOW
4
ABSALU
DIRECT
mm/in
mm/in
146 / 5.75 160 / 6.30
200 / 7.87202 / 7.95
INDUCTION
12
N/AN/A
PROPELLER
1
GLASS REINFORCED ACRYL STYRENE RESIN
DIRECT
mm/in
609.6 / 24
INDUCTION
1
-
SCROLL
MOBIL EAL ARCTIC 22CCMOBIL EAL ARCTIC 22CC
cm
3
/ fl.oz.
SEAMLESS INNER GROOVED COPPER
1656 / 58.31591 / 56
SEAMLESS COPPER
mm/in9.52 / 3/89.52 / 3/8
mm/in0.30 / 0.0120.30 / 0.012
ALUMINIUM (HYDROPHILIC)ALUMINIUM (SLIT FIN)
mm/in
2
/ft
m
2
0.11 / 0.00430.11 / 0.0043
0.36 / 3.950.42 / 4.51
44
1814
SEAMLESS COPPER
mm/in
mm/in
ALUMINIUM (CORR. FIN)
mm/in0.10 / 0.0039
2
2
m
/ft
0.87 / 9.330.84 / 9.04
7.00 / 0.276
0.28 / 0.011
ALUMINIUM (CORR. FIN)
0.10 / 0.0039
2
18
WASHABLE SARANET FILTER
pc
2 + 3
500 + 400 / 19.6 + 15.7
285 / 11.2
3 / 0.11
MATERIAL
FINISHING
COLOUR
MATERIAL
FINISHING
COLOUR
GALVANIZED MILD STEEL
POLYESTER POWDER
LIGHT GREY
GALVANIZED MILD STEEL
POLYESTER POWDER
LIGHT GREY
3
18
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
61
SAFETY DEVICES
35D
30D
40D
MODEL
SAFETY DEVICE
MODEL
SAFETY DEVICE
INDOOR UNIT
OUTDOOR UNIT
TYPE
HIGH PRESSURE SWITCH
LOW PRESSURE SWITCH
PHASE SEQUENCER
DISCHARGE THERMOSTAT SETTING°C / °F
INDOOR UNIT
OUTDOOR UNIT
HIGH PRESSURE SWITCH
LOW PRESSURE SWITCH
PHASE SEQUENCER
DISCHARGE THERMOSTAT SETTING°C / °F
OPENkPa / psi
CLOSEkPa / psi
TYPE
OPEN kPa / psi
CLOSEkPa / psi
TYPE
OPENkPa / psi
CLOSEkPa / psi
TYPE
OPEN kPa / psi
CLOSEkPa / psi
RCM 20D
ALC 18CALC 20C
N/AN/A
N/AN/A
N/AN/A
N/AN/A
N/AN/A
N/AN/A
N/AN/A
N/AN/A
RCM 25D
ALC 2 5C
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
MODEL
SAFETY DEVICE
MODEL
SAFETY DEVICE
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
INDOOR UNIT
OUTDOOR UNIT
TYPE
HIGH PRESSURE SWITCH
LOW PRESSURE SWITCH
PHASE SEQUENCER - 1Ø / <3Ø>
DISCHARGE THERMOSTAT SETTING - 1Ø / <3Ø>
INDOOR UNITRCM 40D
OUTDOOR UNIT
HIGH PRESSURE SWITCH
LOW PRESSURE SWITCH
PHASE SEQUENCER - 1Ø / <3Ø>
DISCHARGE THERMOSTAT SETTING - 1Ø / <3Ø>
OPENkPa / psi
CLOSEkPa / psi
TYPE
OPEN kPa / psi
CLOSEkPa / psiN/A193 / 28
°C / °FN/AN/A / <130 / 266>
TYPE
OPENkPa / psi
CLOSEkPa / psi
TYPE
OPEN kPa / psi124 / 18124 / 18
CLOSEkPa / psi193 / 28193 / 28
°C / °FN/AN/A / <130 / 266>
ALC 28CALC 30C
N/ANC
N/A2937 / 426
N/A2413 / 350
N/ANC
N/A124 / 18
N/AN/A / <YES>
ALC 35CALC 40C
NCNC
2937 / 4262937 / 426
2413 / 3502413 / 350
NCNC
N/AN/A / <YES>
RCM 30D
62
SAFETY DEVICES
050D
061D
30DR
MODEL
SAFETY DEVICE
MODEL
SAFETY DEVICE
INDOOR UNIT
OUTDOOR UNIT
TYPE
HIGH PRESSURE SWITCH
LOW PRESSURE SWITCH
PHASE SEQUENCER
DISCHARGE THERMOSTAT SETTING°C / °F
INDOOR UNITRCM 20DR
OUTDOOR UNIT
HIGH PRESSURE SWITCH
LOW PRESSURE SWITCH
PHASE SEQUENCER
DISCHARGE THERMOSTAT SETTING°C / °F
OPENkPa / psi
CLOSEkPa / psi
TYPE
OPEN kPa / psi
CLOSEkPa / psi
TYPE
OPENkPa / psi
CLOSEkPa / psi
TYPE
OPEN kPa / psi
CLOSEkPa / psi
RCM 50DRCM 62C
ALC 5 0CALC 61C
NCNC
2937 / 4262937 / 426
2413 / 3502413 / 350
NCNC
124 / 18124 / 18
193 / 28193 / 28
YESYES
130 / 266130 / 266
ALC 18CRALC 20CR
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
MODEL
SAFETY DEVICE
MODEL
SAFETY DEVICE
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
Interpolation and Extrapolation method can be used to get the total capacity, TC and sensible capacity, SC at
those temperatures which are not stated out in the table.
-23°C is located between 20°C and 24°C (Thus, Interpolation need to be applied)
2.Refer to the Indoor WB column,
-15°C only available in the case of Indoor DB = 20°C. (Thus, Extrapolation between 16°C WB
and 17°C WB during 24°C indoor DB is required)
3.Refer to the Outdoor DB column,
-37°C is located between 35°C and 40°C. (Thus, Interpolation need to be applied)
Please follow the steps below in order to get the required capacity.
s
1
Step
Extrapolation of Indoor WB
Find TC, SC for
(a) Indoor: 24°C DB,
Outdoor: 35°C DB
(b) Indoor: 24°C DB,
Outdoor: 40°C DB
15°C WB
15°C WB
n
2
Step
Interpolation of Indoor DB
Find TC, SC for
(a) Indoor:
Outdoor: 35°C DB
(b) Indoor:
Outdoor: 40°C DB
23°C DB
23°C DB
, 15°C WB
, 15°C WB
r
3
Step
Interpolation of Outdoor DB
Find TC, SC for
(a) Indoor: 23°C DB, 15°C WB
Outdoor:
37°C DB
66
Details:
st
1
Step:
To obtain the Total capacity and Sensible capacity for
(a) Indoor Condition: 24°C DB, 15°C WB
Outdoor Condition: 35°C DB
Outdoor DB ° C
Indoor DBIndoor WB35
° C° CTC (kW)SC (kW)
15x
1
y
1
24164.9993.465
175.1133.243
Total capacity, TC
x1 = 4.885kW (Same as Total capacity at 20 °C Indoor DB / 15 °C Indoor WB & 35 °C Outdoor WB)*
⇒
Sensible capacity, SC
Extrapolation Method:
17°C - 15°C = 3.243kW - y
⇒
1
17°C - 16°C 3.243kW - 3.465kW
= 3.687kW
⇒ y
1
(b) Indoor Condition: 24°C DB, 15°C WB
Outdoor Condition: 40°C DB
Outdoor DB ° C
Indoor DBIndoor WB40
° C° CTC (kW)SC (kW)
15x
2
y
2
24164.6213.058
174.7582.845
Total capacity, TC
x2 = 4.485kW (Same as Total capacity at 20°C Indoor DB / 15 °C Indoor WB & 40 °C Outdoor WB)*
⇒
Sensible capacity, SC
Extrapolation Method:
⇒
17°C - 15°C = 2.845kW - y
2
17°C - 16°C 2.845kW - 3.058kW
= 3.271kW
⇒ y
2
* This is due to 2 different conditions with same WB temperature, will have the same level of enthalpy. For
more details, please refer to psychrometrics chart
67
2nd Step:
To obtain the Total capacity and Sensible capacity for
(a) Indoor Condition:23°C DB, 15°C WB
Outdoor Condition: 35°C DB
Outdoor DB ° C
Indoor DBIndoor WB35
° C° CTC (kW)SC (kW)
20154.8852.460
2315x
3
y
3
24154.8853.687
Total capacity, TC
= 4.885kW (Same as Total capacity at 20°C Indoor DB / 15 °C Indoor WB & 35 °C Outdoor WB)*
x
3
Sensible capacity, SC
Interpolation Method:
24°C - 20°C = 3.687kW - 2.460kW
⇒
24°C - 23°C 3.687kW - y
3
= 3.380kW
⇒ y
3
(b) Indoor Condition:23°C DB, 15°C WB
Outdoor Condition: 40°C DB
Outdoor DB ° C
Indoor DBIndoor WB40
° C° CTC (kW)SC (kW)
20154.4852.045
2315x
4
y
4
24154.4853.271
Total capacity, TC
⇒
= 4.485kW (Same as Total capacity at 20°C Indoor DB / 15°C Indoor WB & 40°C Outdoor WB)*
x
4
Sensible capacity, SC
Interpolation Method:
24°C - 20°C = 3.271kW - 2.045kW
⇒
24°C - 23°C 3.271kW - y
4
= 2.965kW
⇒ y
4
* This is due to 2 different conditions with same WB temperature will have the same level of enthalpy. For
more details, please refer to psychrometrics chart
6868
3rd Step:
To obtain the Total capacity and Sensible capacity for