Acson MSV-0903 user guide manual

INSTALLATION MANUAL
Model: IM-MSV-0903-ACSON
INVERTER
AC INVERTER MULTI SPLIT
TYPE AIR CONDITIONER
Indoor Unit (WMX-F)
OUTLINE AND DIMENSIONS
A
C
TOP VIEW
B
Dimension
10 / 15 F / FR
20 F / FR
A
815
(32,1)
1060
(41,7)
(11,4)
(12,2)
Indoor Unit (WMX-G)
FRONT VIEW
A
GF
H
E
B
I
B
291
310
J
C
181
(7,1)
200
(7,9)
D
719
(28,3)
912
(35,9)
K L
E
278
(10,9)
294
(11,6)
F
47
(1,9)
99
(3,9)
A
D
CENTER
LINE
INSTALLATION
PLATE
G
47
(0,5)
(1,9)
51
(0,3)
(2,0)
H
12
8
SIDE VIEW
FOR PIPE HOLE POSITION IN THE WALL HOLE O 65.0mm
M
I
32
(1,3)
48
(1,9)
I
J
35
(1,4)
43
(1,7)
ON
All dimensions are in mm/ (in)
N
M
L
K
118
302
(11,9)
354
(13,9)
342
(13,5)
403
(15,9)
100
(3,9)
160
(6,3)
(4,6)
138
(5,4)
O
172
(6,8)
160
(6,3)
Dimension
10 / 15 G / GR
A
899
(35,4)
B
260
(10,2)
B
H
E
I
C
198
(7,8)
G
J
D
590
(23,2)
TOP VIEW
FRONT VIEW
D
K
L
E
246
(9,7)
F
185
(7,3)
G
124
(4,9)
i
C
SIDE VIEW
F
O
N
I
M
All dimensions are in mm/ (in)
H
(0,3)
I
56
8
(2,2)
(2,0)
50
K
J
495
419
(19,5)
(16,5)
M
L
128
50
(5,1)
(2,0)
O
N
132
(5,2)
Indoor Unit (WMX-G)
A
B
B
MH
I
J
TOP VIEW
FRONT VIEW
A DFG
ON
I
K L
INSTALLATION
PLATE
M
C
SIDE VIEW
All dimensions are in mm/ (in)
Dimension
20 G / GR
A
1060 (41,7)
B
310
(12,2)
C
220
(8,6)
D
912
(35,9)
E
294
(11,6)
F
99
(3,9)
G
51
(2,0)
H
8
(0,3)
I
48
(1,9)
J
43
(1,7)
K
354
(13,9)
L
403
(15,9)
M
160
(6,3)
N
138
(5,4)
O
160
(6,3)
ii
Outdoor Unit (MSV25A)
J
Dimension
A
F
ED
C
E
G
K
L
A
925
(36,4)
B
839
(33,0)
B
HII
N
M
C
408
(16,0)
D
378
(14,8)
E
15
(0,6)
F
38
(1,5)
O QPR
WWWWWWW
STU
G
39
(1,5)
H
590
(23,2)
All dimensions are in mm/ (in)
V
I
125
(4,9)
J
356
(14,0)
K
296
(11,6)
L
318
(12,5)
MSV25A
M
647
(25,4)
(24,8)
Outdoor Unit (MSV35A)
EDE
J
N
630
O
330
(13,0)
IL
P
83
(3,2)
A BCC
Q
160
(6,3)
R
87
(3,4)
K
S
428
(16,8)
G
F
G
T
141
(5,5)
U
47
(1,8)
All dimensions are in mm/ (in)
M
OOOOOOO
V
216
(8,5)
W
42
(1,6)
Dimension
MSV35A
A
1028
(40,4)
H
B
746
(29,4)
C
141
(5,5)
D
448
(17,6)
E
20
(0,8)
F
488
(19,2)
G
44
(1,7)
iii
H
26
(1,0)
I
390
(15,3)
N
J
408
(16,0)
K
852
(33,5)
L
399
(15,7)
M
311
(12,2)
N
107
(4,2)
O
55
(2,2)
Sharp edges and coil surfaces are potential locations which may cause injury
E
.
P
.
à
la r
ééé
é
t
ййкйй
ééé
é
tre ces centres. Ceci
p
é
.
.
à
à
locali. Questa disposizione
è
i
dell
U.E.
é
ó
n
e
fico
i
ó
i
ó
n
.
n
G
tes
ü
öüö
ndiges Abfall-Amt. Dieser
Hinweis gilt nur f
.
с
у
о
у
и
в
и
а
о
! Caution
hazards. Avoid from being in contact with these places.
NOTICE
This product is subjected to Waste of Electrical and Electronic Equipment Regulations (WEE Regulations). The waste product shall be separately collected by specific collection and treatment centre
lease refer to local authorithy for these centres. This is only applicable to European Union countries
Ce produit est soumis
est uniquement applicable aux pays de l'Union Euro
Dieses Produkt unterliegt den Bestimmungen zur Entsorgung von elektrischen und elektronische
er
ll bei Ihrer
ischen Union
Questo prodottoè soggetto alle disposizioni RAEE (Rifiuti di apparecchiature elettriche ed elettroniche)
de colecc solamente aplicable a los pases de la Un
Процес отходо
правил
тилизациианногопродуктарегулируетсяправиламип
Europea
enne
ctrico y Electr
(WEEE Regulations).
Европейског
lectriques e
valida solamente i paes
ico en materia d
тилизаци
т
iv
INSTALLATION MANUAL
This manual provides the procedures of installation to ensure a safe and good standard of operation for the air conditioner unit. Special adjustment may be necessary to suit local requirements.
Before using your air conditioner, please read this instruction manual carefully and keep it for future reference.
INVERTER MULTI SPLIT TYPE AIR CONDITIONER
MODEL
OUTDOOR UNIT
MSV25A / AMSV025A
MSV35A / AMSV035A
English
INDOOR UNIT
WMX10F / AWMX010F
WMX15F / AWMX015F
WMX20F / AWMX020F
WMX10G / AWMX010G
WMX15G / AWMX015G
WMX20G / AWMX020G
Part No.: A08019020770
IM-MSV-0903 (1)-Acson
CONTENTS
- Outline and Dimensions page i-iv
- Safety Precautions page 1
- Installation Diagram page 2
- Installation of Outdoor Unit page 3
- Installation of the Indoor Unit page 4
- Refrigerant Piping page 5
- Electrical Wiring Connection page 7
- Ampere Limit Change Method page 8
- Vacuuming and Charging page 10
- Indicator Lights page 11
- Air Conditioner Unit Operation page 13
- Operating Range page 13
- Electrostatic filter page 14
- Auto Random Re-start Function page 14
- Service and Maintenance page 15
- Troubleshooting page 16
SAFETY PRECAUTIONS
Before installing the air conditioner unit, please read the following safety precautions carefully.
! WARNING
Installation and maintenance should be performed by qualified persons who are familiar with local code and regulation, and experienced with this type of appliance.
All field wiring must be installed in accordance with the national wiring regulation.
Ensure that the rated voltage of the unit corresponds to that of the name plate before commencing wiring work according to the wiring diagram.
The unit must be GROUNDED to prevent possible hazards due to insulation failure.
All electrical wiring must not touch the refrigerant piping, compressor or any moving parts of the fan motors.
Confirm that the unit has been switched OFF before installing or servicing the unit.
Before servicing inverter air conditioning unit, switch off the power and wait for 2 - 3 minutes for controller to discharge.
IMPORTANT
DO NOT INSTALL OR USE THE AIR CONDITIONER UNIT IN A LAUNDRY ROOM.
! CAUTION
Please take note of the following important points when installing.
Do not install the unit where leakage of flammable gas may occur.
If gas leaks and accumulates at the surrounding of the unit, it may cause fire ignition.
Ensure that the drainage piping is connected properly.
If the drainage piping is not connected properly, it may cause water leakage which will dampen the furniture.
Do not overcharge the unit.
This unit is factory pre-charged. Overcharge will cause over-current or damage to the compressor.
Ensure that the units panel is closed after service or installation.
Unsecured panels will cause the unit to operate noisily.
1-1
INSTALLATION DIAGRAM
Indoor Unit
Air Intake
Grille
INDOOR UNIT
Air Filter
Indicator Light
Drain
House
Signal Receiver
Front Frame
Back Housing ON/OFF Switch
English
Return Air
Air Discharge Nozzle
Outdoor Unit
OUTDOOR UNIT
Indoor Unit Combination
Indoor Units with model name WMX10F, WMX15F, WMX20F, WMX10G, WMX15G and WMX20G could be coupled with this outdoor unit. The following table shows the possible coupling combinations available.
No. Coupling Combinations (WMX) 1 10 + 10 + 10 + 10
2 10 + 10 + 10 + 15 3 10 + 10 + 10 + 20 4 10 + 10 + 15 + 15 5 10 + 10 + 15 + 20 6 10 + 15 + 15 + 15 7 15 + 15 + 15 + 15
However, there are a total of 21 operation combinations available with this outdoor unit, from one unit to four units. For further details on operation combinations, total capacity and other technical specifications, please refer to the technical manual.
1-2
INSTALLATION OF OUTDOOR UNIT
The outdoor unit must be installed in such a way, so as to prevent short circuit of the hot discharged air or obstruction to the smooth air flow. Please follow the installation clearance shown in the figures on the right. Select the coolest possible place where intake air temperature is not greater than the outside air temperature (maximum 45°C/113°F). Ensure that the unit is installed 1 or 2 meter away from other electronic devices like television or radio to prevent interference.
Note: If there is any obstacle higher than 2m (6.56ft), or if there is any obstruction at the upper part of the unit, please allow more space than the figure indicated in the table shown below.
Installation Clearance
Dimension A Minimum 300 1000 Distance (mm) (11.8) (39.4)
CD
RETURN AIR
OBSTACLE
OBSTACLE
SERVICE SPACE
B C
300
(11.8)
D
500
(19.7)
AB
OBSTACLE
RETURN AIR
AIR DISCHARGE
OBSTACLE
Before installing the piping and connecting rod, please remove the access panel and plastic valve plate cover or service panel for easy access and safety. Refer to figures shown below.
PLEASE REMOVE ACCESS PANEL & PLASTIC VALVE COVER PLATE WHEN CONNECTING THE PIPING AND CONNECTING CORD.
PLEASE REMOVE SERVICE PANEL
PUSH & PULL UP
1-3
INSTALLATION OF THE INDOOR UNIT
The indoor unit must be installed in such a way so as to prevent short circuit of the cool discharged air with the hot return air. Please follow the installation clearance shown in the figure. Do not place the indoor unit where there could be direct sunlight shining on it. Also, this location must be suitable for piping and drainage, and be away from doors or windows.
Air Flow Direction
Maintenance & Servicing Space
50.0 mm
50.0 mm
Higher Than
Eye Level
Routing Of Piping
Remove the screw holding the front panel.
Piping Routing
Mounting Installation Plate
Ensure that the wall is strong enough to withstand the weight of the unit. Otherwise, it is necessary to reinforce the wall with plates, beams or pillars. Use the level gauge for horizontal mounting, and fix it with 4 suitable screws. In case the rear piping draws out, drill a hole 65mm in diam­eter with a cone drill, slightly lower on the outside wall (see figure).
Screw position in the wall
Centre Line
72.0
Ø 65.0 mm Hole in the wall
Screw position in the wall
Ø 65.0 mm Hole in the wall
English
1
2
3
4
5
The refrigerant piping can be routed to the unit in a number of ways (left or right from the back of the unit), by using the cut-out holes on the casing of the unit (see figure). Bend the pipes carefully to the required position in order to aligned it with the holes. For the right hand and rear side out, hold the bottom of the piping and then position it to the required direction (see figure). The condensation drain hose can be taped to the pipes.
Right & Rear Side Routing
Unit piping
Drain hose
Fix with vinyl tape
Hole With Cone Drill
Indoor Side
Outdoor Side
Mount The Unit Onto The Installation Plate
Hook the indoor unit onto the upper portion of the installation plate (Engage the two hooks at the rear top of the indoor unit with the upper edge of the installation plate). Ensure that the hooks are properly seated on the installation plate by moving it to the left and right.
1. Hook the unit onto the installation plate.
Water Drainage Piping
The indoor drain pipe must be in a downward gradient for smooth drainage. Avoid situations that are likely to cause water to leak.
Water Drainage
1-4
Correct
Water Leaking
Wrong
Water Leaking
Wrong
Water Leaking
Wrong
End Dipped Into Water
Drain
REFRIGERANT PIPING
Piping Length & Elevation
If the pipe is too long, both capacity and reliability of the unit will drop. As the number of bends increases, resistance to the flow of refrigerant system increases, thus lowering cooling capacity. As a result, the compressor may become defective. Always choose the shortest path and follow the recommendations as tabulated below.
Coupling Model WMX10 WMX15 WMX20
Max. Length, L (m / ft) 12 / 39.4 12 / 39.4 15 / 49.2 L1 + L2 + L3 + L
4
Max. Elevation, H (m / ft) 5 / 16.4 5 / 16.4 8 / 26.2 Max. Number of Bends 10 10 10 Liquid Pipe Size 1/4" 1/4" 1/4" Gas Pipe Size 3/8" 1/2" 5/8"
Individual indoor unit can have a maximum length of 12m (39.4ft) to 15m (49.2ft), maximum elevation of 5m (16.4ft) to 8m (26.3ft) and maximum number of bends of 10, however, total pipe length must not exceed 60 m (196.8ft).
Remark: The refrigerant pre-charged in the outdoor unit is for piping length up to 60 m (196.8ft).
(Total 60 m / 196.8 ft maximum)
INDOOR UNIT
VERTICAL HEIGHT DIFFERENCE MAX. H
L4
L3
L2
L1
OUTDOOR UNIT
1-5
Piping Works
Do not use contaminated or damaged copper tubing. Do
not remove plastic, rubber plugs and brass nuts from the valves, fittings, tubings and coils until you are ready to connect suction or liquid line into valves or fittings.
If any brazing work is required, ensure that the nitrogen gas is passed through coil and joints while the brazing work is being done. This will eliminate soot formation on the inside walls of the copper tubings.
Cut the connection pipe with a pipe cutter.
Remove burrs from cut edges of the pipes with remover.
Hold the end of the pipe downwards to prevent metal chips from entering the pipe.
Insert the flare nuts, mounted on the connection parts of both the indoor unit and outdoor unit onto the copper pipes.
Flare the pipe with extra length above the flaring tool as shown in the table below.
The flared edge must be even and not cracked or scratched.
Copper tube
Swaging block
Ø Tube, D A (mm)
Inch mm Imperial Rigid
1/4" 6.35 1.3 0.7 3/8" 9.52 1.6 1.0
1/2" 12.70 1.9 1.3 5/8" 15.88 2.2 1.7
3/4" 19.05 2.5 2.0
PIPE CONNECTION
Cutting copper tube
1/4t
Remove burr Indoor
Piping Connection To The Units
The outdoor unit is equipped with four sets of flare joints. Refer to table below for flare joint size and location.
In the case where the gas pipe from the indoor unit does not match the outdoor flare joints, four different flare joint connectors are provided. The connector should be connected as shown in figure.
No. Flare Joint Connectors 1 5/8" to 1/2" Connectors 2 3/8" to 1/2" Connectors 3 1/2" to 3/8" Connectors
4 1/2" to 5/8" Connectors
English
INDOOR UNIT D
INDOOR UNIT C
INDOOR UNIT B
INDOOR UNIT A
Position Liquid Pipe Size Gas Pipe Size
MSV25A MSV35A
A 1/4" 3/8" 3/8" B 1/4" 3/8" 3/8" C 1/4" 1/2" 1/2" D 1/4" 1/2" 5/8"
Align the center of the piping and tighten the flare nut
sufficiently with fingers.
Finally, tighten the flare nut with the torque wrench until
the wrench clicks.
Pipe Size mm / (in) Torque Nm /(ft - Ib)
6.35 (1/4) 18 (13.3)
9.53 (3/8) 42 (31.0)
12.70 (1/2) 55 (40.6)
15.88 (5/8) 65 (48.0)
19.05 (3/4) 78 (57.6)
FLARE JOINT CONNECTOR
INDOOR PIPING
SPANNER
TORQUE WRENCH
FLARE TUBE
FLARE NUT
1-6
ELECTRICAL WIRING CONNECTION
Cooling Unit
IMPORTANT : The figures shown in the table are for information purpose only. They should be checked and selected to
comply with the local/national codes of regulations. This is also to the type of installation and conductors used.
1
2
INDOOR UNIT D TERMINAL BLOCK
INDOOR UNIT C TERMINAL BLOCK
INDOOR UNIT B TERMINAL BLOCK
INDOOR UNIT A TERMINAL BLOCK
3
N
L
POWER
SUPPLY
1
2
3
N
L
1
2
3
N
L
1
2
3
N
L
There must be a double pole switch with a minimum 3 mm contact gap and fuse/ circuit breaker as recommended in the fixed installation circuit.
N
L
3
D
N
L
3
C
N
L
3
B
N
L
3
A
N
L
All wires must be firmly connected.
All wires must not touch the refrigerant piping, compres-
sor or any moving parts of the fan motor.
The connecting wires between the indoor unit and the outdoor unit must be clamped on the wire clamps and the cable tie (push releasable) at the indoor unit and out­door unit respectively as shown in the figures.
The power supply cord must be equivalent to H05RN-F (245IEC57) which is the minimum requirement.
1-7
MAIN CONTROL BOARD EARTH WIRE
FAN EARTH WIRE
INTERCONNECTION
CABLE
POWER SUPPLY
CABLE CABLE TIE (PUSH RELEASABLE)
Wire Clamp
Interconnection
Cable
Power Supply
Cable
English
Voltage range 220-240V/1Ph/50Hz + Power supply cable size*mm
Model WMX10/15 WMX20
2
3.0 4.0
!
Number of wires 33 Recommended time delay fuse for O/D unit 30
Indoor coupling models WMX10/15/20G Interconnection cable size mm
2
1.5
Number of wires 4
The table above shows the electrical wire sizing for different connection cables. If the length of the cable is more than 2m (6.65ft), use cable with bigger size.
The figures shown in the table are for information purpose only. They should be checked and selected to comply with the local/national codes of regulations. This is also to the type of installation and conductors used.
AMPERE LIMIT CHANGE METHOD
WARNING !
Do not attemp to adjust the “Current Limit Switch” yourself. If there is a need to meet HDB requirement or local authorities, kindly contact our local authorized dealers.
1-8
Current Limit Switch Setting
The current limit requirement set by certain countries can be activated by the “Current Limit Switch”, placed at the
outdoor unit p.c.board, as shown on the illustration.
Before adjusting the “Current Limit Switch”, be sure to turn off the main power supply. Wait until the LED light on the p.c.board is turned off then only is safe to adjust the switch.
The current limit settings on the switch are shown on the table below.
Current limit Switch Position
ON
123
ON
123
ON
123
No change
ON
123
ON
123
Current Limit
MSV25A MSV35A
11 A
(Default Setting)
(Default Setting)
8.5 A
17 A
23 A
11 A
17 A
1-9
VACUUMING AND CHARGING
Purging the piping and the indoor unit
Except for the outdoor unit which is pre-charged with refrigerant R22, the indoor unit and the refrigerant connection pipes must be air-purged because the air containing moisture that remains in the refrigerant cycle may cause malfunction of the compressor.
Make sure all pipes are connected securely to the outdoor and indoor valves.
Remove the caps from the flare valves and the service ports (or ball valves). Take note that there are a total of four service ports for MSV25A and two service ports for MSV35A.
Connect the centre of the charging gauge to the vacuum pump.
(MSV25A) (MSV35A)
Starting from the bottom 3­way valve (labeled A), connect the charging gauge to the 3-way valve’s service port. (There are a total of four 3-way valves).
Start the vacuum pump. Evacuate for approximately 30 minutes. The evacuation time varies with different vacuum pump capacity. Confirm that the charging gauge needle has moved towards -760mmHg.
Proceed to the next 3-way valve and repeat the step above for the rest of the 3-way valves.
Caution If the gauge needle does not move towards -760mmHg, be sure to check for gas leaks (using the refrigerant detector) at flare type connection of the indoor and outdoor unit and repair the leak before proceeding to the next step.
Connect the charging gauge to the suction (gas side) ball valve’s service port.
Allen Key
Service Port
Indoor Unit
Open
Vacuum pump
Low
Flare Unit
Outdoor Unit 3 Ways Valve
Liquid side
Gas side
Hi
Close
Refrigerant Piping
Valve
Suction
Valve
Outdoor Unit
Close
Close
Discharge
Charge operation
This operation must be done by using a cylinder and a pre­cise weighing machine. The additional charge is topped­up into the outdoor unit using the suction valve via the ser­vice port.
Remove the service port cap.
Connect the low pressure side of the charging gauge to the suction service port center of the cylinder tank and close the high pressure side of the gauge. Purge the air from the service hose.
Start the air conditioner unit.
Open the cylinder and low pressure charging valve.
When the required refrigerant quantity is pumped into the unit, close the low pressure side and the cylinder valve.
Disconnect the service hose from service port. Put back the service port cap.
Indoor Unit
Liquid side
Discharge
Valve
Outdoor Unit
Open
English
Close the valve of the charging gauge and stop the vacuum pump.
Open the suction valve (3­way) and liquid valve (2­way) in anti-clockwise
Open the suction and liquid ball valves in anti-clockwise direction with pliers.
Check Valve
Low
Gas side
Hi
Close
Suction
Valve
Open
direction with 4mm key for hexagon sacked screw.
Additional charge
The refrigerant is pre-charged in the outdoor unit for maximum piping length. Therefore, no additional charge is required for additional piping length.
1-10
INDICATOR LIGHTS
IR signal receiver
When an infrared remote control operating signal has been transmitted, the signal receiver on the indoor unit will make a <beep> sound to confirm acceptance of the signal transmission. The table shows the LED indicator lights for the indoor air conditioner unit under normal operation and fault conditions. The LED indicator lights are located at the bottom right side of the air conditioner unit for WMX-F series and at the middle of the air conditioner unit for WMX­G series.
Inverter Cooling Unit (WMX-F)
LED Indicator Lights
LED Indicator Lights : Normal Operation And Fault Conditions For Cooling Unit
Timer on.
Sleep mode on.
LED Indicator Lights for Cooling Unit
Timer
Sleep mode
Operation / Fault Indication
Power ON
Dry mode
Action
ON
Dry mode.
Compressor overload protection.
Indoor temperature sensors contact loose / short.
Outdoor temperature & current sensors contact loose / short.
Gas leak / compressor overheat.
Communication error between indoor and outdoor.
Inverter error / PFC error.
Outdoor total current trip / DC peak.
Indoor fan feedback error.
ON or OFF
Call your dealer
Call your dealer
Call your dealer
Call your dealer
Call your dealer
Call your dealer
Call your dealer
Call your dealer
Blinking
1-11
Inverter Cooling Unit (WMX-G) LED Indicator Lights for Cooling / Heat Pump Unit
English
Sleep
Mode
Red
Sleep Mode
IR Receiver
LED indicator lights
Cool Timer Ionizer
LED Indicator Lights : Normal Operationg and Fault Conditions for Cooling / Heat Pump Unit
Normal Operation / Fault Indication Action
Cool Timer Ionizer
Green
Green/ Red
Green/ Red
Green/ Red
Red
Yellow
Green
Cool mode
Sleep mode on
Timer on
Ionizer on
Defrost operation
Green
Green
Green
Green
ON
Indoor temperature sensor loose / short Call your dealer
Coil temperature sensor loose / short Call your dealer
Outdoor temperature sensor loose / short Call your dealer
Compressor overload protection Call your dealer
IPM / PFC error Call your dealer
Outdoor total current trip / DC peak Call your dealer
Compressor overheat / Gas leak Call your dealer
Indoor fan feedback error Call your dealer
Communication error between indoor
Call your dealer
and outdoor
ON or OFF Blinking
1-12
AIR CONDITIONER UNIT OPERATION
Dry mode
• When the air humidity is high, the unit can operate in dry mode. Press <MODE> button and choose <DRY>.
• If the room temperature is 2°C/35.6°F higher than the set temperature, the air conditioner will operate under cooling mode until it reaches within the 2°C/35.6°F range of difference compared to the set temperature before it converts to dry mode.
• If the room temperature is within the 2°C/35.6°F range of difference compared to the set temperature, it will directly operate under dry mode.
• The indoor fan will operate at super low speed under dry mode.
Horizontal Air Flow Control
• For more effective air circulation, you can manually ad­just the air discharge grille to the left or right.
• During cool mode operation and dry mode operation, do not direct the air discharge louver downwards for too long. If operating continues in this way, condensation may oc­cur on the louver, thus resulting in drippings.
Frost prevention
Fan speed and rated cooling capacity
• The rated cooling capacity is provided at the maximum fan speed.
• The cooling capacity is lower when the unit is operating at MEDIUM and LOW fan speed.
Turbo function
• If higher cooling or heating is required during operation, press "Turbo" button on the remote control to increase the cooling or heating capacity to maximum.
• This function will operate for 15 minutes before it resume to the actual setting.
• The fan noise may be higher if the unit operates in "Turbo" mode.
Horizontal
Dry
Cooling
25˚C / 77˚F
• When the air filter is dirty, the evaporating temperature will decrease and eventually cause frosting.
• When this happens, the compressor will reduce its running speed to prevent freezing. If the coil temperature is still very low, the compressor will stop.
OPERATING RANGE
Cooling Unit
Temperature Ts °C / °F Th °C / °F
Minimum indoor temperature 19.0 / 66.2 14.0 / 57.2 Maximum indoor temperature 32.0 / 89.6 23.0 / 73.4 Minimum outdoor temperature 19.4 / 66.92 - Maximum outdoor temperature 46.0 / 114.8 -
Ts: Dry bulb temperature. Th: Wet bulb temperature.
1-13
ELECTROSTATIC FILTER
DUAL ACTION ELECTROSTATIC AIR PURIFYING
AND DEODORIZING FILTER MEDIA AND FILTER FRAME
ACTION 1­ELECTROSTATIC AIR PURIFYING FILTER
Removes microscopic dust, smoke and small invisible particles to keep the room air clean with pre-charged electrostatic polypropylene filter.
HOW TO INSTALL
Open the front frame grille.
Slide out the original filters.
ACTION 2­DEODORIZING FILTER
English
Removes unwanted smells and odors in the air and keeps the room air fresh with activated carbon filter.
Insert the dual action electrostatic and deodorizing filters into the slot.
Slide back the original filter.
! CAUTION
1. The electrostatic air purifying and deodorizing filter should be replaced once every 6 months or when the filter changes color to brownish, whichever is sooner.
2. Used dusty filters should be disposed and shouldn't be reused, even if it has been cleaned and washed.
3. The filter is a consumable part which you can purchase from your air conditioner dealer.
4. Use the new filter immediately once it has been taken out from its sealed packing. Do not unpack the new filter too early before it is actually used as this may decrease its deodorizing effect.
! WARNING
Disconnect from the main power supply before servicing the air conditioner unit.
DO NOT pull out the power cord when the power is ON. This may cause serious electrical shocks which may result
in fire hazards.
AUTO RANDOM RE-START FUNCTION
If there is a power cut when the unit is operating, it will automatically resume the same operating mode when the power is restored.
! CAUTION
Before turning off the power supply, set the remote controller's ON/OFF switch to the "OFF" position to prevent the nuisance tripping of the unit. If this is not done, the unit's fans will start turning automatically when power resumes, posing a hazard to service personnel or the user.
1-14
SERVICE AND MAINTENANCE
Service Parts
Indoor air filter
Indoor unit
Maintenance Procedures
1. Remove any dust adhering to the filter by using a vacuum cleaner or wash in lukewarm water (below 40°C) with a neutral cleaning detergent.
2. Rinse the filter well and dry before placing it back onto the unit.
3. Do not use gasoline, volatile substances or chemicals to clean the filter.
1. Clean any dirt or dust on the grille or panel by wiping it off with a soft cloth soaked in lukewarm water (below 40°C) and a neutral detergent solution.
2. Do not use gasoline, volatile substances or chemicals to clean the indoor unit.
Period
At least once every 2 weeks.
More frequently if necessary.
At least once every 2 weeks.
More frequently if necessary.
1 Off the unit. 2 Unscrew the air discharge housing. 3 Flip open the air discharge housing. 4 Clean the blower. 5 Close the air discharge housing and tighten it with screw.
! CAUTION
Do not operate any heating apparatus too close to the air conditioner unit. This may cause the plastic panel to melt
or deform as a result of the excessive heat.
WHEN THE UNIT IS NOT USED FOR AN EXTENDED PERIOD OF TIME
Operate the unit for 2 hours with the following setting.
Operating mode : cool Temperature : 30°C
Remove the power plug. If you are using an independent electric circuit for your unit, cut off the circuit. Remove the batteries in the remote control.
1-15
TROUBLESHOOTING
If there is any malfunction of the air conditioner unit detected, please switch off the main power supply immediately before proceeding with the following troubleshooting procedures as safety precautions.
The followings are some common fault conditions and simple troubleshooting tips. If encounter any faulty conditions which are not listed, please contact your nearest local dealer or service maintenance. Do not attemp to troubleshoot the unit yourself.
English
No.
1.
The air conditioner unit will not start straight away after a power failure or restart of unit.
The compressor does not operate 3 minutes after
2. the air conditioner unit is started.
The air flow is too slow or room cannot be
3. cooled sufficiently.
4.
Discharge air flow has bad odour.
Condensation on the front air grille of the indoor
5. unit.
Water flowing out from the air conditioner unit.
6.
Hissing air flow sound from the air conditioner
7. unit during operation.
Fault Conditions
Possible Causes / Corrective Actions
The air conditioner unit has a 3 minutes restart protection.
Please wait for the unit to restart by leaving the main power on.
Protection against frequent starting.
Wait for 3 or 4 minutes for the compressor to start operating
by itself.
The air filter is dirty.
The doors or windows are opened.
The air suction and discharge of both indoor and outdoor units
are clogged or blocked.
The regulated temperature or temperature setting is not high enough.
Odour may be caused by cigarrettes, smoke particles, perfume and others, which might have adhered onto the coil.
Contact the nearest dealer for coil cleaning.
This is caused by air humidity after an extended period of
operation.
The set temperature is too low, increase the temperature setting and operate the unit at high fan speed.
Switch off unit and call dealer. This might be due to tilted installation.
Refrigerant fluid flowing into the evaporator coil.
8.
The indoor unit’s LED indication keeps blinking.
9.
The outdoor unit will not operate and the indoor unit’s LED indication does not blink.
Check the fault indication listed under section INDICATOR LIGHTS.
If LED display indicates defrost operation, ignore it. This shows that the outdoor unit is defrosting the ice at the outdoor unit.
For other LED display, follow the COMPRESSOR STOPPED TROUBLESHOOTING INSTRUCTIONS at next section.
Power failure or fuse needs to be replaced. Check power supply.
The main power plug is disconnected or the circuit breaking is turned off.
It is possible that the delay timer has been set incorrectly.
If the problem persist after all these verifications, follow the
COMPRESSOR STOPPED TROUBLESHOOTING INSTRUCTIONS at next section.
1-16
10
Compressor Stopped Troubleshooting Instructions
Keep the Main Power Supply ON
Open up the Outdoor Unit’s Top Panel or Service Panel
Notice the Yellow LED on the P.C. Board
➝➝➝
DO NOT TOUCH ANY OF THE
WIRES INSIDE THE UNIT!
Count the number of blinks
indicated by the LED
Blink Fault Indication Corrective Action
1 Outdoor Ambient Sensor Error Check ambient sensor wire and connection 2 Outdoor Coil Sensor Error Check coil sensor wire and connection 3 Outdoor Discharge Sensor Error / Check discharge sensor wire and connection /
Compressor Overheat Indication Not enough refrigerant / Indoor overload / Outdoor fan
not functioning 4 DC Compressor Feedback Call local dealer 5 Communication Error Check Interconnection communication wire 6 Over Current Call local dealer 7 No Load Check compressor wire and connection 8 Over / Under Voltage Check power supply 9 DC Compressor Start Failure Call local dealer 10 Cooling Overload Check whether outdoor unit is blocked or not 11 Defrost Wait till defrost is over then restart 12 IPM Protection Check IPM 13 EEPROM Read Error Change EEPROM 14 EEPROM Write Error Change EEPROM 15 DC Fan Motor Feedback Error Check fan motor wire connection 16 AC Peak Current Error Call local dealer 17 Outdoor Suction Sensor Error Check suction sensor wire and connection 19 DC Compressor Speed Control Error Call local dealer 21 Outdoor Suction A Sensor Error Check A suction sensor wire and connection 22 Outdoor Suction B Sensor Error Check B suction sensor wire and connection 23 Outdoor Suction C Sensor Error Check C suction sensor wire and connection 24 Outdoor Suction D Sensor Error Check D suction sensor wire and connection 31 Indoor A Communication Error Check Interconnection communication wire to Indoor A 32 Indoor B Communication Error Check Interconnection communication wire to Indoor B 33 Indoor C Communication Error Check Interconnection communication wire to Indoor C 34 Indoor D Communication Error Check Interconnection communication wire to Indoor D
* If the problem still persist, contact your local dealer straight away.
1-17
11
If the air conditioner unit has no faulty indications and the compressor is running at normal mode, the outdoor P.C. Board’s LED indication will blink at a slower paste. The table below shows the significant meaning of different running mode and limitation for this air conditioner unit.
One must not attemp to see the LED indication blinking unless instructed to do so.
Normal Running Mode Condition
Blinks Blinking Indication
1 Normal Running, with no limitation 2 Voltage Limit
3 Cooling unit : Outdoor Coil Temperature Limit 4 Total Current Limit 5 Discharge Temperature Limit 6 Cooling unit : Indoor Coil Temperature Limit 7 Indoor Fan Control 8 Outdoor Frequency Adjustment
English
1-18
MEMO
1-19
In the event that there is any conflict in the interpretation of this manual and any translation of the same in any language, the English version of this manual shall prevail.
The manufacturer reserves the right to revise any of the specification and design contain herein at any time without prior notification.
En cas de désaccord sur l’interprétation de ce manuel ou une de ses traductions, la version anglaise fera autorité.
Le fabriquant se réserve le droit de modifier à tout moment et sans préavis la conception et les caractéristiques techniques des appareils présentés dans ce manuel.
Im Falle einer widersprüchlichen Auslegung der vorliegenden Anleitung bzw. einer ihrer Übersetzungen gilt die Ausführung in Englisch.
Änderungen von Design und technischen Merkmalen der in dieser Anleitung beschriebenen Geräte bleiben dem Hersteller jederzeit vorbehalten.
Nel caso ci fossero conflitti nell’interpretazione di questo manuale o delle sue stesse traduzioni in altre lingue, la versione in lingua inglese prevale.
Il fabbricante mantiene il diritto di cambiare qualsiasi specificazione e disegno contenuti qui senza precedente notifica.
En caso de conflicto en la interpretación de este manual, y en su traducción a cualquier idioma, prevalecerá la versión inglesa.
El fabricante se reserva el derecho a modificar cualquiera de las especificaciones y diseños contenidos en el presente manual en cualquier momento y sin notificación previa.
В случае противоречия перевода данного руководства с другими переводами одного и того же текста,
английский вариант рассматривается как приоритетный.
Завод-изготовитель оставляет за собой право изменять характеристики и конструкцию в любое время без предварительного уведомления.
OYL MANUFACTURING COMPANY SDN. BHD.
JALAN PENGAPIT 15/19, P.O. BOX 7072, 40702 SHAH ALAM, SELANGOR DARUL EHSAN, MALAYSIA.
Loading...