Acson ART 60 A, ART 55 AR, ART 80 AR, ART 100 AR, ART 100 A, ART 120 A, ART 120 AR, ART 150 A, ART 150 AR, ART 200 A, ART 250 A, ART 200 AR, ART 250 AR, ART 300 A, ART 300 AR, ART 360 A, ART 360 AR, ART 420 A, ART 420 AR, A4RT 60 A, A4RT 60 AR, ART 80 A, ART 60 AR Technical Manual
150AFXAAXXXXXXXX
150AFXADXXXXXXXX
200AFXAAXXXXXXXX
200AFXADXXXXX
250AFXAAXXXXXX
250AFXACXXXXXX
300AFXAAXXXXXX
300AFXACXXXXXX
360AFXACXXX
420AFXACXXXXXXX
55AFXAIXXXXXX
60AFXAHXXXXXXX
60AFXAIXXXXXXX
80AFXBC X X X X X X
80AFXBH X X X X X X
80AFXBI X X X X X X X X
80AFXBN X X X X X X X
100AFXBC X X X X X X
100AFXBH X X X X X X
100AFXBI X X X X X X X X
100A FXBN X X X X X X X
120AFXBH X X X X X X X X
120AFXBI X X X X X X X X
150AFXBC X X X X X X X
150AFXBH XX X X X X
150AFXBI X X X X X X X X
150AFXBN X X X X X X X
200AFXBC X X X X X X
200AFXBH X X X X X X
200AFXBI X X X X X X X X
200A FXBN
250AFXAAXXXXXXX
250AFXADXXXXXXX
250AFXAHXXXXXXX
300AFXAAXXXXXXX
300AFXADXXXXXXX
300AFXAHXXXXXXX
360AFXAAXXXXXXX
360AFXAHXXXXXXX
420AFXAAXXXXXXX
420AFXAHXXXXXXX
The Acson rooftop unit is supplied with high efciency and reliable scroll compressor (except ART 80/100/150/
200 AR).
Package Unit
Dubbed the “Plug and Play” equivalent in the air-conditioning industry, the single unit conguration allows hassle
free installation. No additional piping work is required as both the indoor and outdoor sides are pre-connected.
Refrigerant is factory pre-charged to ensure clean and efcient operation.
Flexibility Of Air Supply
Acson rooftop unit uses a belt driven fan such that the air volume and static required can be adjusted according
to the requirement. This exibility allows for wider application.
Flat Top Design
Acson rooftop unit’s at top design allows for maximum utilization of warehouse and container space.
Electrical Control Capability
All series are equipped with our Electronic Remote Controller (SLM and Sequential LCD). The Sequential LCD
features 7 days programmable timer, compressor run/error status, cool/heat/fan/dry/auto modes, etc, while the
SLM features a 15 hour delay timer, cool/heat/fan/dry/auto modes, etc.
Part loading of system capacity is now possible with the use of our Sequential PAC (Package Air-Condition)
control for multiple compressor Acson rooftop units (A(4)RT150/200/250/300/360/420 A/AR).
4
Page 7
The use of your air conditioner
outside the range of working
temperature and humidity can
result in serious failure.
Caution :
Ensure the operating temperature is in allowable range.
Cooling (R22)
Cooling Only Unit
Heat pump
Heat Pump Unit Only
Outdoor temp. (°C WB)
Indoor temp. (°C WB)
-9
1527
18
Outdoor temp. (°C DB)
Indoor temp. (°C WB)
1524
19
40
50
20301025
30
10
0
52
5
15
20
10
0
-5
20301025
••••••••••
Cooling (R22)
Cooling Mode For Heat Pump Model
Indoor temp. (°C WB)
Outdoor temp. (°C DB)
1524
46
19
40
50
30
10
0
1520301025
Cooling (R407C)
Cooling Only Unit & Cooling Mode For Heat Pump Model
Outdoor abnormal compressor
overload trip or gas leak
E5 blinking
Controllers
1. “ON/OFF” Switch
• Press to start the air conditioner unit.
• Press again to stop the unit.
2. Temperature Setting
• Set the desired room temperature.
• Press button to increase or decrease the
set temperature. Setting range are
between16ºC to 30ºC (60ºF to 80ºF).
6. “SLEEP” Mode
• Press button to activate the sleep function.
This function can only be activated under
“cool” or heating mode operation. When it is
activated under ìcoolî mode operation, the
set temperature will increase 0.5oC after
30 minutes, 1ºC after 1 hour and 2ºC after 2
hours. If it is activated under “HEAT”
mode operation, the set temperature will
be decreased 0.5ºC after 30 minutes, 1ºC
3. Operation Modes
after 1 hour and 2ºC after 2 hours.
• Press the “mode” button for select the type
of operating mode.
- Cooling Only :
COOL, DRY, FAN
7. Air Swing
• Press button to activate the automatic air
swing function.
- Heat Pump :
AUTO, COOL, DRY, HEAT, FAN
(AUTO mode is represented by both
COOL and HEAT LED light on)
4. Fan Speed Selection
• Press the button until the desired fan speed
is achieved.
8. Sensor
• Infra red sensor to receive signals from
wireless controller.
9. LED Display
• To display the set temperature (inºC) and
timer delay setting (in hours).
5. Timer
• Press the set button to select the switch
10. Transmission Source
• To transmit signals to the air conditioner.
timer of the air conditioner unit (the
setting range is between 1 to 15 hours).
A : Time display
B : Error indication
C : Compressor running display (up to 4 compressors)
D : Key lock display
E : Heater display (up to 2 heaters)
F : Energy saving mode display
G : Compressor defrost cycle display (up to 4 compressors)
H : Operation mode display
I : Temperature set display
2) Operating Guide
a) ON/OFF Key
Press once to start the air conditioning unit.
Press again to stop the unit.
The operation lamp next to the key lights up and goes off respectively when the unit is running or not
running.
Caution : In the case when the ON/OFF key is pressed immediately after the operation is
stopped, the unit will not restart until 3 minutes later to protect the compressor.
b) Selecting Operation Mode
Press the MODE key to select the type of operating mode. Consecutive press of the key switches the
operation over “COOL”, “HEAT”, “AUTO” and “FAN”
c) Save Mode
Press the SAVE key to select the energy saving function. This option is only available for “COOL”,
“HEAT” and “AUTO” modes.
d) Auxiliary Electric Heater
If the “HEAT” mode provides insufcient heating to a room even at the highest temperature setting
(30ºC), press the HEATER key to activate the auxiliary electric heater. For models with two heaters,
consecutive press of the key allows the selection of one or both heaters active.
e) Temperature Setting
To set the desired room temperature, press or to increase or decrease the set temperature in the range of 16ºC to 30ºC. Press both and simultaneously to toggle between ºC and ºF setting.
f) Time Setting
Real time Clock
Press the CLOCK key once to activate set clock mode.
Press again to disable set clock mode.
Under set clock mode, the time of the present day can be set by pressing the respective MINUTE,
HOUR and DAY key.
22
Page 25
7-days timer
Error
code
Possible fault
Error
code
Possible fault
E01Require manual reset (possible causes)
E02Compressor 1 high temperature (overload)E20Indoor coil sensor 1 open
E03Compressor 2 high temperature(overload)E21Indoor coil sensor 2 open
E06Compressor 1 high pressure trip / contact openE24Outdoor coil sensor 1 short
E07Compressor 2 high pressure trip / contact openE25Outdoor coil sensor 2 short
E10Compressor 1 trip / low R-22 / outdoor abnormalE28Outdoor coil sensor 1 open
E11Compressor 2 trip / low R-22 / outdoor abnormalE29Outdoor coil sensor 2 open
E14Room sensor shortE32Compressor 1 de-ice
E15Room sensor openE33Compressor 2 de-ice
E16Indoor coil sensor 1 short
E17Indoor coil sensor 2 short
Press the ON TIMER key to activate auto-ON timer mode. Under this mode, press the respective
MINUTE, HOUR and DAY key to select the time of the week when the air-conditioning unit is to automatically start running. Press the ON TIMER key again to save the setting.
Press the OFF TIMER key to activate auto-OFF timer mode. Under this mode, press the respective
MINUTE, HOUR and D AY key to select the time of the week when the air-conditioning unit is to
automatically stop running. Press the ON TIMER key again to save the setting.
Then to activate the 7-days timer, press and hold the TIMER ACTIVE key until the word “TIMER
ACTIVE” appears on the LCD screen. Repeat the same step to disable the 7-days timer.
g) Other Function
Key Lock
Press the MINUTE key 3 times consecutively and fast to activate the key lock. A “KEY LOCK” symbol
will appear on the LCD screen. At this point, only the ON/OFF key is valid.
To disable the key lock, again press the MINUTE key 3 times consecutively and fast.
Test run
Press the TEST key 2 times consecutively to test run the unit.
3) Error Code
When the system is on and an error occurs, the ON/OFF LED on the LCD panel will blink and an error
code is shown. When the system is off and there is a thermistor error, the ON/OFF LED is off but the
error code is still displayed. Each error code represents different message as below
4) Installation Of LCD Remote Controller
a) Accessories
The following accessories are included. If any part is missing, contact your dealer immediately.
1 Remote controller
2 Wooden screw 4.1 x 16 (2 pieces)
3 Instruction manual
23
Page 26
Lower slot
for opening LCD
casing
Connection behind
top case
LCD Remote
(Bottom case)
Connection
wires
LCD Remote
(Top case)
2 x Wooden
screw
Connection at
main board
GND
+5V
B
A
GND
+5V
B
A
b) Step-by-step guide
i) First, open up the casing of the LCD remote controller into its top and bottom
case using a screwdriver. To do this, insert the screwdriver into the lower slot and slide it in the
outward direction.
ii) Fix the bottom case onto the wall with the 2 wooden screws provided. Then, insert the 4 connecting
wires (from the main board) through the slot on the lower right.
iii) Connect one end in each of the 4 wires to the terminal block behind the top case as shown below.
The wire that goes into the “GND” terminal at the top case must be connected at the other end to
the “GND” terminal at the main board. The same goes for the “+5V”, “B” and “A” connection.
iv) Fasten back the top and bottom case into place. Hook the two upper claws into their respective
slots and snap the lower part shut.
5) Auto Random Restart
When power is resumed, the unit will automatically restart and operate at the previous setting as before
power failure occurred. (Remove jumper at JH/JP1 to cancel the auto random restart function. Please
refer to wiring diagram for the location of JH/JP1 Jumper).
24
Page 27
Precaution & Installation
Safety Precautions
Before installing the air conditioner unit, please read the following safety precautions carefully.
WARNING
• Installation and maintenance should be performed by qualied persons who are familiar with local
code and regulation, and experienced with this type of appliance.
• All eld wiring must be installed in accordance with the national wiring regulation.
• Ensure that the rated voltage of the unit corresponds to that of the name plate before commencing
wiring work
• According to the wiring diagram.
• The unit must be GROUNDED to prevent possible hazard due to insulation failure.
• All electrical wiring must not touch the refrigerant piping, compressor and any moving parts of the
fan motors.
• Conrm that the unit has been switched OFF before installing or servicing the unit.
Before installing the air conditioner unit, please read the following safety precautions carefully.
CAUTION
Please take note of the following important points when installing
• Do not install the unit where leakage of ammable gas may occur
If gas leaks and accumulates around the unit, it may cause re ignition.
• Conrm drainage piping is connected properly
If the drainage piping is not connected perfectly, it may cause water leakage which will
dampen the furniture.
• Do not overcharge the unit
This unit is factory pre-charged. Over charge will cause over current or damage to the
compressor.
• Ensure that the unit panel is closed after service or installation.
Unsecured panel will cause unit to operate noisily.
25
Page 28
Installation
ART55A/AR
Air
Outlet
Air
Inlet
Air
Inlet
1000
Comp and
Controller
services space
800800400
(Min Clearance)
(Min Clearance)
Indoor
Motor
service space
(unit ; mm)
All space value ; minimum clearance
All series of air conditioners are designed for outdoor installations and are to be placed on a slab or rooftop.
However, if the air conditioner is to be installed in a plant room, please contact your equipment supplier prior
to installation for further advise.
Access to the compressors, control wiring, and fans for service and installation purpose must be provided.
Please see item 1: Space Required Around Units for recommendations.
1. Space Required Around Units.
(1) Care must be taken to prevent recirculation of air. To stabilize compressor and condensing pressure, it is
recommended that wherever possible the condenser air inlet side should be faced away from prevailing
winds. Please see diagrams below.
(2) For rooftop installation, the type of mounting base depends on the construction of the roof. A built-up
roof may not support the weight of the unit. Hence, it may be necessary to support the unit by adding
structural members below it.
(3) The units are equipped with hoisting hangers for rigging and hoisting of the unit. Please see item 3:
Lifting method for further information.
The hoisting plates are located on the top of the unit. When hoisting the unit with a crane, spreader bars
must be used to prevent damage to side panels by the supporting cables.
26
Page 29
A(4)RT60/80/100/120 A/AR
Condenser
inlet
Electrical
control circuit
& compressor
service
Evaporator coil,
air filter service
300
300
700
1000
1500
Condenser
outlet
Electrical
control circuit
& compressor
service
Condenser
inlet
Condenser
inlet
1000
300
700
1000
500
(min clearance)
(min clearance)
condenser outlet
(unit : mm)(unit : mm)
1500
300
Evaporator
coil, air filter
service
Evaporator
coil, air filter
service
A(4)RT150/200 A/AR
A(4)RT250/300 A/ARA(4)RT360/420 A/AR
Electrical
control circuit
& compressor
service
Electrical
control circuit
& compressor
service
Condenser
inlet
Condenser
inlet
Evaporator coil,
motor service
1000
500
1000
500
500
500
(min clearance)
(min clearance)
(min clearance)
condenser outlet
2000
Condenser
inlet
Condenser
inlet
Evaporator coil,
motor service
2000
1000
1500
1000
1000
1000
(min clearance)
condenser outlet
(unit : mm)
(unit : mm)
3000
27
Page 30
2. Duct Construction.
Duct connection with
a vertical air plenum
Duct connection atARTdown flow unit
at ART side flow unit
ART side flow unit
ART down flow unit
Duct connection witha vertical air plenum
Duct connection at
ART down flow unit
at ART side flow unit
ART side flow unit
ART down flow unit
(1) Series ART side ow units are equipped with horizontal supply
and return air openings. Duct connection to the unit should be made
with duct anges and secured directly to the air openings with exible
duct connectors to avoid normal noise transmission.
(2) For vertical air supply, a eld supply plenum should be used. The
gure shows the recommended method for duct connection.
(3) To prevent air leakage, all duct seams should be taped. Duct
runs in air spaces that are not air-conditioned must be insulated and
provided with a vapor barrier.
Ducts exposed outdoors must be weather proofed. For quiet
operation, we recommend that the insulation on the supply duct be
placed inside, lining the duct.
(4) Where ducts from outdoors enter a building, the duct openings in
the building should be sealed with weather stripping to prevent rain,
dirt, sand, etc. from entering the building.
(5) Correctly sized lters must be tted. There is no provision within
the unit for the placement of lter. However, the lters may be installed
in the return air chamber.
(6) Duct earth wiring must be connected. Please refer to the section
“Outlines and dimensions” for the correct position.
Optional Feature (Down Flow)*
Series ART down ow units are equipped with vertical supply and
return air openings. Duct connection to the unit should be made with
duct anges to avoid normal noise transmission.
When connecting duct earth wiring for down ow conguration, we
must use accessory screw attached on the control box cover.
* Site modication required. Please refer to item 6:
OPTIONAL FEATURES for details.
28
Page 31
Hook (as directly aligned
over the center of gravity
as possible)
The drain piping should have a drain trap.
3. Lifting Method.
ART55AART60AART80AART100AART120AART150A
Refrigerant charge
per circuit (kg)
3.65.24.05.96.22 x 4.5
ART200AART250AART300AART360AART420A
Refrigerant charge
per circuit (kg)
2 x 5.92 x 10.52 x 10.416.5 , 19.52 x 19.5
ART55ARART60ARART80ARART100ARART120ARART150AR
Refrigerant charge
per circuit (kg)
3.94.54.75.66.02 x 4.7
ART200AR
ART250ARART300ARART360ARART420AR
Refrigerant charge
per circuit (kg)
2 x 5.62 x 10.02 x 9.413.5 , 162 x 16.4
A4RT60A
A4RT80AA4RT100AA4RT120AA4RT150A
Refrigerant charge
per circuit (kg)
4.64.65.95.62 x 3.9
A4RT200A
A4RT250AA4RT300AA4RT360A
Refrigerant charge
per circuit (kg)
2 x 4.22 x 9.62 x 10.414.5 , 18.02 x 18.0
A4RT60AR
A4RT80AR
A4RT100ARA4RT120ARA4RT150AR
Refrigerant charge
per circuit (kg)
4.35.26.06.02 x 5.0
A4RT200AR
A4RT250AR
A4RT300ARA4RT360AR
Refrigerant charge
per circuit (kg)
2 x 5.82 x 9.42 x 9.613.5 , 162 x 16
A4RT420A
A4RT420AR
When the unit is to be lifted and moved, attach ropes to the hoisting
hangers (4 pieces) provided on the top corners of the unit.
When the unit is lifted, its center of gravity tends to shift the unit to
one side. Imbalance such as that in the gure should be attained.
The angles at which the ropes suspend the unit should be at
least 60º at the compressor end and at least 45º at the condenser
end. Care should be taken to avoid contact with the unit while it is
being lifted.
4. Drain Piping.
(1) The condensate drain tting (R1) is provided. The drain pipe can
be led out at the right or left side. Please see Chapter 10:
Outlines & Dimensions for further details.
(2) The drain pipe must be provided with a trap on the outside of
the unit and also installed at an incline for proper drainage, as
shown below.
(3) To prevent condensate formation and leakage, provide the drain
pipe with insulation to safeguard against sweating.
(4) Upon completion of the piping work, check that there is no
leakage and that the water drains off properly.
5. Refrigerant Charge
An additional charge is unnecessary.
The table below shows the amount of the charge when the unit is shipped from the factory.
29
Page 32
STEP 1STEP 3
STEP 2STEP 4
Remove
top panel
Remove
service panel
Remove
duct flange
Remove
duct flange
Remove
Remove
low cover
Remove
supply air cover
2.Additional
casing leg
(Accessory parts)
1.Additional
side inlet cover
(Accessory parts)
Re-install
supply air cover
Re-install
fan assy
Re-install
top panel
Re-install
service panel
6. Optional Features (Down Flow) - Site Modication Required.
Reconstruction Method. (From Side Flow To Down Flow)
(For A(4)RT80/100/120/150/200A/AR Only)
Series ART side ow units are able to be modied to down ow in the eld with the help of additional
accessory items.
The following diagrams show the necessary steps to reconstruct the unit from side ow to down ow.
30
Page 33
7. Special Precautions When Dealing With Refrigerant R407C Unit
(1) What Is New Refrigerant R407C?
R407C is a zeotropic refrigerant mixture which has Zero Ozone Depletion Potential (ODP = 0) and thus,
conforms to the Montreal Protocol regulation. It requires Polyol-ester (POE) oil for its compressor’s
lubricant. Its refrigerant capacity and performance are about the same as the refrigerant R22.
(2) Components
Mixture of composition by weight: R32(23%), R125(25%), R134a(52%)
(3) Characteristic
• R407C liquid and vapor components have different compositions when the uid evaporates or
condenses. Hence, when a leak occurs and only vapor leaks out, the composition of the
refrigerant mixture left in the system will change and subsequently affect the system performance.
DO NOT add new refrigerant to a leaked system. It is recommended that the system should be
evacuated thoroughly before recharging with R407C.
• When refrigerant R407C is used, the composition will differ depending on whether it is in gaseous
or liquid phase. Hence when charging R407C, ensure that only liquid is being withdrawn from the
cylinder or can. This is to make certain that only original composition of R407C is being charged
into the system.
• POE oil is used as a lubricant for R407C compressor, which is different from the mineral oil
used for R22 compressor. Extra precaution must be taken to avoid exposing the R407C system
to moist air.
(4) Check List Before Installation/servicing
• Tubing
Refrigerant R407C is more easily affected by dust of moisture compared with R22, make sure to
temporarily cover the ends of the tubing prior to installation
• Compressor oil
No additional charge of compressor oil is permitted.
• Refrigerant
No other refrigerant other that R407C
• Tools
Tools specically for R407C only (must not be used for R22 or other refrigerant)
Like R22 systems, the handling and installation of R407C systems are closely similar. All precautionary
measures; such as ensuring no moisture, no dirt or chips in the system, clean brazing using nitrogen,
and thorough leak check and vacuuming are equally important requirements. However, due to the
zeotropic nature of R407C and its hydroscopic POE oil, additional precautions must be taken to ensure
optimum and trouble-free system operation.
(a) Filter-dryer must be installed along the liquid line for all R407C air conditioners. This is to
minimise the contamination of moisture and dirt in the refrigerant system. Filter-dryer must be
of molecular sieve type. For a heat-pump system, install a two-way ow lter dryer along the
liquid line.
(b) During installation or servicing, avoid prolong exposure of the internal part of the refrigerant
system to moist air. Residual POE oil in the piping and components can absorb moisture from
the air.
31
Page 34
c) Ensure that the compressor is not exposed to open air for more than the recommended time
Composition of R407C in vapour phase
is different from liquid phase.
R32/R125/R134
33% / 33% / 34%
23% / 25% / 52%
Dip-pipe
Invert cylinder
without dip-pipe
Liquid
withdrawal
specied by its manufacturer (typically less than 10 minutes). Remove the seal-plugs only when the
compressor is about to be brazed.
d) The system should be thoroughly vacuumed to 1.0 Pa (-700mmHg) or lower. This vacuuming level is
more stringent than R22 system so as to ensure no incompressible gas and moisture in the system.
e) When charging R407C, ensure that only liquid is being withdrawn from the cylinder or can. This is to
ensure that only the original composition of R407C is being delivered into the system. The liquid
composition can be different from the vapor composition.
f) Normally, the R407C cylinder or can is being equipped with a dip-pipe for liquid withdrawal. However, if the dip -pipe is not available, invert the cylinder or can so as to withdraw liquid from the
valve at the bottom.
g) When servicing leaks, the top-up method, commonly practiced for R22 system, is not recommended
for R407C systems. Unlike R22 where the refrigerant is of a single component, the composition of
R407C (which is made-up of three different components) may have changed during the leak.
Consequently, atop-up may not ensure that the R407C in the system is of the original composition.
This composition shift may adversely affect the system performance. It is recommended that the
system be evacuated thoroughly before recharging with R407C.
32
Page 35
ModelPower cable
Breaker
capacity
Over current
protection switch
Earth cable
ART55A/AR
4 mm
2
25A25A
4 mm
2
over
A(4)RT60A/AR
8 mm
2
40A40A
8 mm
2
over
A(4)RT80A/AR
14 mm
2
50A50A
14 mm
2
over
A(4)RT100A/AR
14 mm
2
50A50A
14 mm
2
over
A(4)RT120A/AR
14 mm
2
50A50A
14 mm
2
over
A(4)RT150A/AR
22 mm
2
100A100A
22 mm
2
over
A(4)RT200A/AR
22 mm
2
100A100A
22 mm
2
over
A(4)RT250A/AR
38 mm
2
125A125A
38 mm
2
over
A(4)RT300A/AR
38 mm
2
125A125A
38 mm
2
over
A(4)RT360A/AR
38 mm
2
125A125A
22 mm
2
over
A(4)RT420A/AR
38 mm
2
125A125A
22 mm
2
over
a. Power supply
b. Main switch/fuse (field supply)
c. Power supply wiring for unit
d. Unit
e. Remote controller
f.
Connection wiring for unit / remote
controller (no polarity)
g. Earth
8. Electric Wiring
Construct The Earth Connection.
All electrical work must be carried out by a suitable qualied electrical trades-person and in accordance with
local supply authority requirements and associated regulators.
The unit is to be wired directly from an electrical distribution board either by a circuit breaker (preferred) or
HRC fuse.
Fix power source wiring to control box by using buffer bushing for sensible force (PG connection or the like).
Connect control wiring to control terminal block through the knockout hole of control box using ordinary
bushing.
NOTE : Earth wiring must be connected.
Arrangement such as terminal block in control box.
Method For Connecting Electric Wire
Please carry out the wiring after consulting with local electric power company on local regulations.
(I) The entire wiring diagram of unit.
(II) Electrical wiring
Remove the panel on the right side A(4)RT60~120A/AR or the rear side A(4)RT150~420A/AR of the unit
and connect the units power supply wiring to the proper terminals in the control box.
Connect the wires by following the wiring diagram. Mis-connection will damage the controller.
(III) Wiring example and selection of earth leakage breaker
380~415V, 50Hz, 3Ø
The grounding wire must be of the same diameter as the power cable wires. The table above is an
example. The selection of other capacities should be determined in accordance with the relevantlocal standards, in the country of installation.
Note:
All electrical wiring must comply with
local electrical authority regulations.
33
Page 36
Connector For
Remote Control Wires
Terminal Block For
Power Supply Wires
Connector For
Remote Control Wires
Terminal Block For
Power Supply Wires
connector for
remote control
Terminal Block for
power supply wire
Control Module Of Unit ART55A/AR
Control Module Of Unit A(4)RT60A
Control Module Of Unit A(4)RT80/100A
34
Page 37
Control Module Of Unit A(4)RT120A
Connector For
Remote Control Wires
Te rminal Block For
Power Supply Wires
Connector For
Remote Control Wires
Terminal Block For
Power Supply Wires
Control Module Of Unit A(4)RT150/200A
35
Page 38
Control Module Of Unit A(4)RT250/300A
Connector For
Remote Control Wires
Terminal Block For
Power Supply Wires
Connector For
Remote Control Wires
Te rminal Block For
Power Supply Wires
Control Module Of Unit A(4)RT60AR
36
Page 39
Control Module Of Unit ART80/100AR
Connector For
Remote Control Wires
Te rminal Block For
Power Supply Wires
Connector For
Remote Control Wires
Terminal Block For
Power Supply Wires
Control Module Of Unit A4RT80/100AR
37
Page 40
Control Module Of Unit A(4)RT120AR
Connector For
Remote Control Wires
Terminal Block For
Power Supply Wires
Connector For
Remote Control Wires
Te rminal Block For
Power Supply Wires
Control Module Of Unit ART150/200AR
38
Page 41
Control Module Of Unit A4RT150/200AR
Connector For
Remote Control Wires
Te rminal Block For
Power Supply Wires
Connector For
Remote Control Wires
Terminal Block For
Power Supply Wires
Control Module Of Unit A(4)RT250/300AR
39
Page 42
Control Module Of Unit A(4)RT360/420A/AR
Terminal Block for
power supply wires
51F1
52F
51C2
TB2 & 3
52C2
52C1
51C1
X1X2
PCB
52F2
52F3
TB1
47
F1
connector for
remote control
wires
(4)RT-AR only
40
Page 43
9. The Putting Condition Of The Belt
Ta ble 1
Parallel angle
pulley
10 or less
Gap of 3mm every 1m
Ta ble 2
mminch
60-802.5-3.0
81-903.5
91-1054
106-above 4.5-above
1.6-2.0
1.9-2.9
Size of Pulley Motor
K(i)note
pulley
Flexion load
W(kgf)
1.1-1.4
1.3-1.7
1. Set the parallel angle of the fan and the motor pulley as shown in table 1 and gure 1.
2. Set the tension of one belt when the exion load is within the range as shown in gure 2 and table 2
at the proper exion. (A=0.016xC mm)
3. Adjust the suitable tension after the belt sit properly across the pulley (after working for 24-28 hours).
When a new belt is used, adjust the suitable tension about 1.3 times the maximum value of the
exion load.
4. Readjust the belt every 2,000 hours after the rst adjustment.
Exchange the belt when the belt’s surroundings length has expanded by 2% including the rst
expansion (about 1%) of the belt (after approximately 8,000 hours converted working time).
10. Before Starting The Trial Run
After having installed the unit, check that :
(1) The unit is xed securely.
(2) The unit is installed properly.
(3) The drain pipe is provided with a drain trap.
(4) The electrical wiring has been connected correctly and the terminal screws have been properly
tightened.
(5) The duct work has been performed correctly.
Before turning the unit on:
(1) Measure the resistance between the terminals of the electrical parts and ground to ensure that
the value is at least 1.0M ohm.
If the measured value is below 1.0M ohm, do not operate the unit.
(2) The unit is using a phase protector.
If wiring phase of power supply is mistaken, the unit does not run.
Please reconrm and modify wiring phase.
After the unit is turned on:
(1) Check that the fans are rotating in the proper direction.
(2) Check to see whether there are refrigerant leakage, and slack in power or transmission cable.
(3) Check the operation of high-pressure switch.
If the two lead wires of the outdoor unit fan motor are disconnected from the contactor and cooling is
performed, the high-pressure switch should function and stop the unit after 5 to 10 minutes.
Perform trial operation after completion of above items.
41
Page 44
11. Before Operating The Unit
Ground
Obstacle blocking air inlet
Ceiling
Inlet grille
Ceiling
Outlet grille
Obstacle blocking air outlet
1. Check points for operation
Check the following points before you operate your air conditioner.
(1) Check that there is nothing blocking the ow of air from the air outlet into the air inlet.
Indoor Side
Outdoor Side
(2) Make sure the air conditioner is properly grounded by checking the ground terminal.
2. Caution for use
Keep the following points in mind to safeguard against failures and breakdowns.
• For safety, conrm that the earth terminal has been connected to the earth wire correctly.
• Never block or cover the unit’s intakes or outlets.
It will reduce the unit’s efciency.
• To start the unit again after it is stopped, ensure 3 minutes has elapsed before turning the
unit ON. Repeated stopping and starting within 3 minutes gives improper force to the machine. This
can cause the fuse or power source to trip.
42
Page 45
OverallNoise
125Hz250Hz500Hz1kHz2kHz4kHz8kHz(dBA)Criteria
ART55A/AR737265625852446866
A(4)RT60A/AR676159605549426359
A(4)RT80A/AR686564625449396561
A(4)RT100A/AR696764605651426658
A(4)RT120A/AR686462656053456864
A(4)RT150A/AR746868676053447066
A(4)RT200A/AR746967666052437065
A(4)RT250A/AR767270716555467470*
A(4)RT300A/AR777271726555467471*
A(4)RT360A/AR6774747576696080> 70*
A(4)RT420A/AR7276767575695880> 70*
Model
1/1 Octave Sound Pressure Level (dB, ref 20 µPa)
* THE DATA DOES NOT APPLY TO INDOOR NOISE CRITERION.
Note:
1. ART55A/AR, A(4)RT80A/AR, A(4)RT100A/AR, A(4)RT150A/AR and A(4)RT200A/AR
- Microphone position: 1 m in front of the unit and 1 m above the floor.
2. A(4)RT60A/AR, A(4)RT120A/AR, A(4)RT250A/AR, A(4)RT300A/AR, A(4)RT360A/AR, and A(4)RT420A/AR
- Microphone position: 1 m from the service panel and 1 m height from the floor level.
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 13253.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
5) EFFECTIVE POWER INPUT IS USED IN THE RATED EER/COP CALCULATION, ACCORDING TO ISO STANDARD: ISO 13253
6. ENGINEERING & PHYSICAL DATA
Specications
63
Page 65
General Data - Cooling Only (R22)
General Data - Cooling Only (R22)
Btu/h100000116000
W2930034000
W10500 11560
A18.2 22.1
V/Ph/Hz
R22 / CAPILLARY TUBER22 / TXV
W/W2.942.94
AIR DISCHARGE
OPERATION
AIR FLOWl/s / cfm1667 / 35321699 / 3600
EXTERNAL STATIC PRESSUREPa/in.wg.
mm/in
l/s / cfm2667 / 56503776 / 8000
dBA66 68
mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/lb400 / 882425 / 937
kg/lb5.9 / 136.2 / 13.7
NOMINAL CAPACITY
98 / 0.39
SLM CONTROLLER
EVAPORATOR
DUCTED
CONDENSATE DRAIN SIZE
REFRIGERANT TYPE / CONTROL
EER
1680 / 66.1
ART120A
380 ~ 415 / 3 / 50
1000 / 39.4
1300 / 51.2
1450 / 57.1
25.4 / 1
ART100A
1530 / 60.2
1090 / 42.9
CONDENSER
PACKING DIMENSION
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
REFRIGERANT CHARGE
DEPTH
UNIT WEIGHT
MODEL
UNIT DIMENSION
SOUND PRESSURE LEVEL
NOMINAL TOTAL INPUT POWER
NOMINAL RUNNING CURRENT
CONTROL
AIR FLOW
POWER SOURCE
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 13253.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
5) EFFECTIVE POWER INPUT IS USED IN THE RATED EER/COP CALCULATION, ACCORDING TO ISO STANDARD: ISO 13253
Btu/h150000200000
W4400058600
W15600 20700
A29.0 35.7
V/Ph/Hz
W/W2.512.58
AIR DISCHARGE
OPERATION
AIR FLOWl/s / cfm2667 / 56513167 / 6710
EXTERNAL STATIC PRESSUREPa/in.wg.
mm/in
l/s / cfm
dBA
mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/lb665 / 1466765 / 1687
kg/lb2 x 4.5 / 2 x 9.92 x 5.9 / 2 x 13
AIR FLOW5333 / 11300
70
25.4 / 1
ART200A
380 ~ 415 / 3 / 50
CONTROL
MODEL
POWER SOURCE
NOMINAL CAPACITY
NOMINAL TOTAL INPUT POWER
REFRIGERANT TYPE / CONTROL
UNIT WEIGHT
UNIT DIMENSION
SOUND PRESSURE LEVEL
1200 / 47.2
PACKING DIMENSION
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
CONDENSER
ART150A
1670 / 65.7
1320 / 52.0
1810 / 71.3
1990 / 78.4
2100 / 82.7
REFRIGERANT CHARGE
DEPTH
NOMINAL RUNNING CURRENT
EER
R22 / CAPILLARY TUBE
196 / 0.79
SEQUENTIAL CONTROLLER
EVAPORATOR
DUCTED
CONDENSATE DRAIN SIZE
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 13253.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
5) EFFECTIVE POWER INPUT IS USED IN THE RATED EER/COP CALCULATION, ACCORDING TO ISO STANDARD: ISO 13253
64
Page 66
General Data - Cooling Only (R22)
General Data - Cooling Only (R22)
Btu/h250000300000
W7327087930
W27560 35960
A49.6 62.7
V/Ph/Hz
W/W2.56
2.39
AIR DISCHARGE
OPERATION
AIR FLOWl/s / cfm3776 / 80004531 / 9600
EXTERNAL STATIC PRESSUREPa/in.wg.
mm/in
l/s / cfm
dBA
mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/lb1200 / 26461350 / 2976
kg/lb2 x 10.5 / 2 x 23.12 x 10.4 / 2 x 22.9
2250 / 88.5
2250 / 88.5
NOMINAL CAPACITY
294 / 1.18
SEQUENTIAL CONTROLLER
EVAPORATOR
DUCTED
CONDENSATE DRAIN SIZE
CONDENSER
PACKING DIMENSION
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
REFRIGERANT CHARGE
DEPTH
UNIT WEIGHT
ART250A
2800 / 110.0
1900 / 75
2900 / 114
UNIT DIMENSION
SOUND PRESSURE LEVEL
NOMINAL TOTAL INPUT POWER
NOMINAL RUNNING CURRENT
ART300A
380 ~ 415 / 3 / 50
CONTROL
MODEL
REFRIGERANT TYPE / CONTROL
EER
R22 / TXV
74
1735 / 68.0
AIR FLOW
POWER SOURCE
9439 / 20000
25.4 / 1
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 13253.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
5) EFFECTIVE POWER INPUT IS USED IN THE RATED EER/COP CALCULATION, ACCORDING TO ISO STANDARD: ISO 13253
Btu/h
329000404000
W
96420118410
W39870 46800
A67.2 72.8
V/Ph/Hz
W/W2.422.53
AIR DISCHARGE
OPERATION
AIR FLOWl/s / cfm5191 / 110005899 / 12500
EXTERNAL STATIC PRESSUREPa/in.wg.
mm/in
l/s / cfm
dBA
mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/lb1510 / 33291600 / 3527
kg/lb16.5 / 36.4 & 19.5 / 43.02 x 19.5 / 2 x 43.0
MODEL
70
AIR FLOW
POWER SOURCE
9439 / 20000
25.4 / 1
NOMINAL TOTAL INPUT POWER
NOMINAL RUNNING CURRENT
WIDTH
REFRIGERANT CHARGE
DEPTH
UNIT WEIGHT
REFRIGERANT TYPE / CONTROL
EER
ART360A
3180 / 125.0
CONTROL
CONDENSER
PACKING DIMENSION
HEIGHT
WIDTH
DEPTH
2150 / 84.5
3250 / 128.0
ART420A
380 ~ 415 / 3 / 50
1974 / 78.0
2252 / 89.0
2300 / 90.5
R22 / TXV
HEIGHT
NOMINAL CAPACITY
294 / 1.18
SEQUENTIAL CONTROLLER
EVAPORATOR
DUCTED
CONDENSATE DRAIN SIZE
UNIT DIMENSION
SOUND PRESSURE LEVEL
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 13253.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
5) EFFECTIVE POWER INPUT IS USED IN THE RATED EER/COP CALCULATION, ACCORDING TO ISO STANDARD: ISO 13253
65
Page 67
General Data - Heat pump (R22)
General Data - Heat pump (R22)
Btu/h
W
Btu/h
W
W
W
A
A
V/Ph/Hz
W/W
W/W
AIR DISCHARGE
OPERATION
AIR FLOWl/s / cfm
EXTERNAL STATIC PRESSURE
Pa/in.wg.
mm/in
l/s / cfm
dBA
mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/lb
kg/lb
REFRIGERANT TYPE / CONTROL
R22 / TXV (HEATING), CAP TUBE (COOLING)
EER
COP
2.93
19./ 0.75
916 / 36
1386 /55
1045/ 41.1
1090 / 43
1650/3500
5128
10.2
9.4
850 / 1800
380 ~ 415 / 3 / 50
98 / 0.39
DUCTED
3.41
ART55AR
55000
16119
NOMINAL RUNNING CURRENT (HEATING)
NOMINAL TOTAL INPUT POWER (COOLING)
NOMINAL TOTAL INPUT POWER (HEATING)
NOMINAL RUNNING CURRENT (COOLING)
56500
16559
5778
POWER SOURCE
MODEL
CONTROL
EVAPORATOR*
NOMINAL COOLING CAPACITY
NOMINAL HEATING CAPACITY
CONDENSATE DRAIN SIZE
SOUND PRESSURE LEVEL
CONDENSER*
PACKING DIMENSION
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
230 / 506
REFRIGERANT CHARGE
AIR FLOW
DEPTH
UNIT WEIGHT
1430 / 56.3
1110 /43.7
68
3.9 / 8.6
UNIT DIMENSION
SLM CONTROLLER
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 13253.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
5) * DESIGNATION BASED ON COOLING CYCLE.
6) EFFECTIVE POWER INPUT IS USED IN THE RATED EER/COP CALCULATION, ACCORDING TO ISO STA NDARD: ISO 13253
Btu/h
5600080000
W
1641023450
Btu/h
6800078600
W
1993023000
W
6220 9400
W
5970 7800
A
12.7 16.8
A
12.4 14.8
V/Ph/Hz
R22 / TXVR22 / CAPILLARY TUBE
W/W
2.641.73
W/W
3.342.98
AIR DISCHARGE
OPERATION
AIR FLOWl/s / cfm
850 / 18001334 / 2826
EXTERNAL STATIC PRESSUREPa/in.wg.
mm/in
l/s / cfm
2124 / 45002667 / 5650
dBA
63 65
mm/in
mm/in
1100 / 43.31300 / 51.2
mm/in
mm/in
mm/in
1250 / 49.2
1450 / 57.1
mm/in
kg/lb
320 / 705385 / 849
kg/lb
4.5 / 9.94.7 / 10.4
1680 / 66.1
25.4 / 1
1000 / 39.4
1530 / 60.2
1090 / 42.9
ART60ARART80AR
380 ~ 415 / 3 / 50
98 / 0.39
DUCTED
SLM CONTROLLER
NOMINAL RUNNING CURRENT (HEATING)
POWER SOURCE
REFRIGERANT TYPE / CONTROL
EER
COP
MODEL
CONTROL
EVAPORATOR*
NOMINAL COOLING CAPACITY
NOMINAL HEATING CAPACITY
NOMINAL TOTAL INPUT POWER (COOLING)
NOMINAL TOTAL INPUT POWER (HEATING)
NOMINAL RUNNING CURRENT (COOLING)
CONDENSATE DRAIN SIZE
UNIT DIMENSION
SOUND PRESSURE LEVEL
CONDENSER*
PACKING DIMENSION
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
REFRIGERANT CHARGE
AIR FLOW
DEPTH
UNIT WEIGHT
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 13253.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
5) * DESIGNATION BASED ON COOLING CYCLE.
6) EFFECTIVE POWER INPUT IS USED IN THE RATED EER/COP CALCULATION, ACCORDING TO ISO STANDARD: ISO 13253
NOMINAL TOTAL INPUT POWER (COOLING)
NOMINAL TOTAL INPUT POWER (HEATING)
NOMINAL RUNNING CURRENT (COOLING)
NOMINAL RUNNING CURRENT (HEATING)
POWER SOURCE
REFRIGERANT TYPE / CONTROL
EER
COP
ART100ARART120AR
380 ~ 415 / 3 / 50
98 / 0.39
DUCTED
SLM CONTROLLER
1680 / 66.1
25.4 / 1
1000 / 39.4
1530 / 60.2
1090 / 42.9
1300 / 51.2
1450 / 57.1
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 13253.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
5) * DESIGNATION BASED ON COOLING CYCLE.
6) EFFECTIVE POWER INPUT IS USED IN THE RATED EER/COP CALCULATION, ACCORDING TO ISO STANDARD: ISO 13253
Btu/h
150000200000
W
4400058600
Btu/h155000
208000
W45400
61000
W18600 23500
W15400 20400
A33.0 39.2
A29.0 35.0
V/Ph/Hz
W/W2.26
2.19
W/W3.022.80
AIR DISCHARGE
OPERATION
AIR FLOWl/s / cfm2667 / 5651
3167 / 6710
EXTERNAL STATIC PRESSUREPa/in.wg.
mm/in
l/s / cfm
dBA
mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/lb700 / 1543
800 / 1764
kg/lb2 x 4.7 / 2 x 10.4
2 x 5.6 / 2 x 12.3
1938 / 76.3
25.4 / 1
1200 / 47.2
1800 / 70.9
1320 / 52.0
1990 / 78.4
2100 / 82.7
5333 / 11300
70
ART150ARART200AR
380 ~ 415 / 3 / 50
196 / 0.79
DUCTED
SEQUENTIAL CONTROLLER
R22 / CAPILLARY TUBE
NOMINAL RUNNING CURRENT (HEATING)
POWER SOURCE
REFRIGERANT TYPE / CONTROL
EER
COP
MODEL
CONTROL
EVAPORATOR*
NOMINAL COOLING CAPACITY
NOMINAL HEATING CAPACITY
NOMINAL TOTAL INPUT POWER (COOLING)
NOMINAL TOTAL INPUT POWER (HEATING)
NOMINAL RUNNING CURRENT (COOLING)
CONDENSATE DRAIN SIZE
UNIT DIMENSION
SOUND PRESSURE LEVEL
CONDENSER*
PACKING DIMENSION
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
REFRIGERANT CHARGE
AIR FLOW
DEPTH
UNIT WEIGHT
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 13253.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
5) * DESIGNATION BASED ON COOLING CYCLE.
6) EFFECTIVE POWER INPUT IS USED IN THE RATED EER/COP CALCULATION, ACCORDING TO ISO STANDARD: ISO 13253
NOMINAL TOTAL INPUT POWER (COOLING)
NOMINAL TOTAL INPUT POWER (HEATING)
NOMINAL RUNNING CURRENT (COOLING)
NOMINAL RUNNING CURRENT (HEATING)
POWER SOURCE
REFRIGERANT TYPE / CONTROL
EER
COP
ART250ARART300AR
380 ~ 415 / 3 / 50
294 / 1.18
DUCTED
SEQUENTIAL CONTROLLER
R22 / TXV
2900 / 114
25.4 / 1
1735 / 68.0
2800 / 110.0
1900 / 75
2250 / 88.5
2250 / 88.5
9439 / 20000
74
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 13253.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
5) * DESIGNATION BASED ON COOLING CYCLE.
6) EFFECTIVE POWER INPUT IS USED IN THE RATED EER/COP CALCULATION, ACCORDING TO ISO STANDARD: ISO 13253
Btu/h335000384000
W98180112540
Btu/h348000412000
W101990120750
W39210 46400
W35830 40800
A70.6 72.5
A66.6 65.3
V/Ph/Hz
W/W2.502.43
W/W2.852.96
AIR DISCHARGE
OPERATION
AIR FLOWl/s / cfm
5191 / 110005899 / 12500
EXTERNAL STATIC PRESSUREPa/in.wg.
mm/in
l/s / cfm
dBA
mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/lb
1510 / 33291600 / 3527
kg/lb
13.5/ 29.7 & 16 / 36.22 x 16.4 / 2 x 36.2
9439 / 20000
70
EER
COP
ART360ARART420AR
380 ~ 415 / 3 / 50
294 / 1.18
DUCTED
SEQUENTIAL CONTROLLER
R22 / TXV
NOMINAL RUNNING CURRENT (COOLING)
NOMINAL RUNNING CURRENT (HEATING)
POWER SOURCE
REFRIGERANT TYPE / CONTROL
DEPTH
MODEL
CONTROL
EVAPORATOR*
NOMINAL COOLING CAPACITY
NOMINAL HEATING CAPACITY
NOMINAL TOTAL INPUT POWER (COOLING)
NOMINAL TOTAL INPUT POWER (HEATING)
2252 / 89.0
CONDENSER*
PACKING DIMENSION
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
REFRIGERANT CHARGE
AIR FLOW
UNIT WEIGHT
3250 / 128.0
2300 / 90.5
CONDENSATE DRAIN SIZE
UNIT DIMENSION
SOUND PRESSURE LEVEL
25.4 / 1
1974 / 78.0
3180 / 125.0
2150 / 84.5
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 13253.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
5) * DESIGNATION BASED ON COOLING CYCLE.
6) EFFECTIVE POWER INPUT IS USED IN THE RATED EER/COP CALCULATION, ACCORDING TO ISO STA NDARD: ISO 13253
NOMINAL RUNNING CURRENT (HEATING)
POWER SOURCE
REFRIGERANT TYPE / CONTROL
EER
COP
MODEL
CONTROL
EVAPORATOR*
NOMINAL COOLING CAPACITY
NOMINAL HEATING CAPACITY
NOMINAL TOTAL INPUT POWER (COOLING)
NOMINAL TOTAL INPUT POWER (HEATING)
NOMINAL RUNNING CURRENT (COOLING)
CONDENSATE DRAIN SIZE
UNIT DIMENSION
SOUND PRESSURE LEVEL
CONDENSER*
PACKING DIMENSION
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
REFRIGERANT CHARGE
AIR FLOW
DEPTH
UNIT WEIGHT
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 13253.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
5) * DESIGNATION BASED ON COOLING CYCLE.
6) EFFECTIVE POWER INPUT IS USED IN THE RATED EER/COP CALCULATION, ACCORDING TO ISO STANDARD: ISO 13253
NOMINAL TOTAL INPUT POWER (COOLING)
NOMINAL TOTAL INPUT POWER (HEATING)
NOMINAL RUNNING CURRENT (COOLING)
NOMINAL RUNNING CURRENT (HEATING)
POWER SOURCE
REFRIGERANT TYPE / CONTROL
EER
COP
1300 / 51.2
A4RT100ARA4RT120AR
380 ~ 415 / 3 / 50
98 / 0.39
DUCTED
SLM CONTROLLER
R407C / TXV
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 13253.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
5) * DESIGNATION BASED ON COOLING CYCLE.
6) EFFECTIVE POWER INPUT IS USED IN THE RATED EER/COP CALCULATION, ACCORDING TO ISO STANDARD: ISO 13253
kg/lb700 / 1543800 / 1764
kg/lb2 x 5.0 / 2 x 11.02 x 5.8 / 2 x 12.8
1938 / 76.3
25.4 / 1
1200 / 47.2
1800 / 70.9
1320 / 52.0
1990 / 78.4
2100 / 82.7
5333 / 11300
70
A4RT150ARA4RT200AR
380 ~ 415 / 3 / 50
196 / 0.79
DUCTED
SEQUENTIAL CONTROLLER
R407C / TXV
NOMINAL RUNNING CURRENT (HEATING)
POWER SOURCE
REFRIGERANT TYPE / CONTROL
EER
COP
MODEL
CONTROL
EVAPORATOR*
NOMINAL COOLING CAPACITY
NOMINAL HEATING CAPACITY
NOMINAL TOTAL INPUT POWER (COOLING)
NOMINAL TOTAL INPUT POWER (HEATING)
NOMINAL RUNNING CURRENT (COOLING)
CONDENSATE DRAIN SIZE
UNIT DIMENSION
SOUND PRESSURE LEVEL
CONDENSER*
PACKING DIMENSION
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
REFRIGERANT CHARGE
AIR FLOW
DEPTH
UNIT WEIGHT
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 13253.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STA NDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
5) * DESIGNATION BASED ON COOLING CYCLE.
6) EFFECTIVE POWER INPUT IS USED IN THE RATED EER/COP CALCULATION, ACCORDING TO ISO STANDARD: ISO 13253
kg/lb1200 / 26461350 / 2976
kg/lb2 x 9.4 / 2 x 20.72 x 9.6 / 2 x 21.2
REFRIGERANT CHARGE
AIR FLOW
DEPTH
UNIT WEIGHT
CONDENSATE DRAIN SIZE
UNIT DIMENSION
SOUND PRESSURE LEVEL
CONDENSER*
PACKING DIMENSION
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
MODEL
CONTROL
EVAPORATOR*
NOMINAL COOLING CAPACITY
NOMINAL HEATING CAPACITY
NOMINAL TOTAL INPUT POWER (COOLING)
NOMINAL TOTAL INPUT POWER (HEATING)
NOMINAL RUNNING CURRENT (COOLING)
NOMINAL RUNNING CURRENT (HEATING)
POWER SOURCE
REFRIGERANT TYPE / CONTROL
EER
COP
A4RT250ARA4RT300AR
380 ~ 415 / 3 / 50
294 / 1.18
DUCTED
SEQUENTIAL CONTROLLER
R407C / TXV
2900 / 114
25.4 / 1
1735 / 68.0
2800 / 110.0
1900 / 75
2250 / 88.5
2250 / 88.5
9439 / 20000
74
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 13253.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
5) * DESIGNATION BASED ON COOLING CYCLE.
6) EFFECTIVE POWER INPUT IS USED IN THE RATED EER/COP CALCULATION, ACCORDING TO ISO STANDARD: ISO 13253
NOMINAL RUNNING CURRENT (COOLING)
NOMINAL RUNNING CURRENT (HEATING)
POWER SOURCE
REFRIGERANT TYPE / CONTROL
DEPTH
MODEL
CONTROL
EVAPORATOR*
NOMINAL COOLING CAPACITY
NOMINAL HEATING CAPACITY
NOMINAL TOTAL INPUT POWER (COOLING)
NOMINAL TOTAL INPUT POWER (HEATING)
2252 / 89.0
CONDENSER*
PACKING DIMENSION
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
REFRIGERANT CHARGE
AIR FLOW
UNIT WEIGHT
3250 / 128.0
2300 / 90.5
CONDENSATE DRAIN SIZE
UNIT DIMENSION
SOUND PRESSURE LEVEL
25.4 / 1
1974 / 78.0
3180 / 125.0
2150 / 84.5
109610
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 13253.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEAT ING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
5) * DESIGNATION BASED ON COOLING CYCLE.
6) EFFECTIVE POWER INPUT IS USED IN THE RATED EER/COP CALCULATION, ACCORDING TO ISO STANDARD: ISO 13253
74
Page 76
Components Data (R22)
mm/in
mm/in
mm/in
cm
3
/fl.oz.
mm/in
mm/in
mm/in
m
2
/ft
2
mm/in
mm/in
mm/in
m2/ft
2
pc
LENGTHmm/in
WIDTHmm/in
THICKNESSmm/in
THICKNESS
ROW
FIN PER INCH
MATERIAL
MATERIAL
0.28 / 0.011
SONTEX 200LT
1
FACE AREA
MATERIAL
THICKNESS
DIAMETER
THICKNESS
MATERIAL
COMPRESSOR
TYPE
OIL TYPE
QUANTITY
OIL AMOUNT
CONDENSER FAN
MOTOR
CONDENSER FAN MATERIAL
DRIVE
TYPE
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
QUANTITY
DIAMETER
EVAPORATOR
FAN MOTOR
QUANTITY
MATERIAL
DRIVE
INDEX OF PROTECTION (IP)
TYPE
QUANTITY
DIAMETER
MODEL
TYPE
EVAPORATOR
FAN
LENGTH
CONDENSER
COIL
FIN
FIN
TUBE
TUBE
EVAPORATOR
COIL
CASING
AIR QUALITYFILTER
TYPE
QUANTITY
INSULATION / THICKNESS
EXTERNAL FINISHING
COLOUR
SIZE
MATERIAL
ROW
FIN PER INCH
FACE AREA
0.11 / 0.004
9.52 / 3/8
0.28 / 0.011
ALUMINIUM
3
DIAMETER
THICKNESS
CENTRIFUGAL
1
1
PLASTIC
1
IP22
254 / 10
THREE PHASE SQUIRREL CAGE INDUCTION MOTOR
PROPELLER
N/A
N/A
N/A
BELT DRIVE
1
ALUMINIUM
INDUCTION MOTOR
DIRECT DRIVE
SCROLL
9.52 / 3/8
609.6 / 24.0
IP54
LIGHT GREY
PE / 10mm
0.11 / 0.004
N/A
ELECTRO GALVANISED MILD STEEL
EPOXY POLYESTER POWDER
2
0.44 / 4.75
S.I.G.C.
18
N/A
ART55A
1770 / 62.3
S.I.G.C.
0.44 / 4.75
14
METAL
203 / 8
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER.
75
Page 77
Components Data (R22)
PLASTICGALVANISED STEEL
mm/in
mm/in254 / 10254 / 10 & 203.2 / 8.0
mm/in609.6 / 24.0660.4 / 26.0
IP54
IP44
cm3/fl.oz.
1770 / 62.32510 / 88.3
S.I.G.C.
SEAMLESS COPPER
mm/in
mm/in
mm/in
m2/ft
2
0.53 / 5.700.65 / 6.96
1615
S.I.G.C.
SEAMLESS COPPER
mm/in
mm/in
mm/in
m2/ft
2
16
pc
LENGTHmm/in820 / 32.31020 / 40.2
WIDTHmm/in
THICKNESSmm/in
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER.
16
FACE AREA
DIAMETER
THICKNESS
THICKNESS
ROW
FIN PER INCH
MATERIAL
MATERIAL
THREE PHASE SQUIRREL CAGE INDUCTION MOTOR
PROPELLER
ALUMINIUM
INDUCTION MOTOR
DIRECT DRIVE
SCROLL
9.52 / 3/8
0.33 / 0.013
SONTEX 200LT
1
MATERIAL
THICKNESS
COMPRESSOR
TYPE
OIL TYPE
QUANTITY
OIL AMOUNT
DIAMETER
THICKNESS
MATERIAL
CONDENSER FAN
MOTOR
CONDENSER FAN
MATERIAL
DRIVE
TYPE
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
QUANTITY
DIAMETER
EVAPORATOR
FAN MOTOR
QUANTITY
MATERIAL
DRIVE
INDEX OF PROTECTION (IP)
TYPE
QUANTITY
DIAMETER
MODEL
TYPE
EVAPORATOR
FAN
LENGTH
CONDENSER
COIL
FIN
FIN
TUBE
TUBE
EVAPORATOR
COIL
CASING
AIR QUALITYFILTER
TYPE
QUANTITY
INSULATION / THICKNESS
EXTERNAL FINISHING
COLOUR
SIZE
MATERIAL
ROW
FIN PER INCH
FACE AREA
ART60A
0.11 / 0.004
9.52 / 3/8
0.33 / 0.013
ALUMINIUM
3
254 / 10
1 / 0.04
ART80A
BELT DRIVE
CENTRIFUGAL
2
1
GALVANISED STEEL
1
IP22
1
LIGHT GREY
PE / 10mm
0.11 / 0.004
WASHABLE SARANET
ELECTRO GALVANISED MILD STEEL
EPOXY POLYESTER POWDER
2
1.41 / 15.17
1
615 / 24.2
76
Page 78
Components Data (R22)
mm/in
mm/in
mm/in660.4 / 26.0762 / 30
IP44N/A
cm3/fl.oz.
SEAMLESS COPPERS.I.G.C.
mm/in
mm/in
mm/in
m2/ft
2
0.65 / 6.960.65 / 6.99
1514
SEAMLESS COPPERS.I.G.C.
mm/in
mm/in
mm/in
m2/ft
2
1614
pc
LENGTHmm/in
WIDTHmm/in
THICKNESSmm/in
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER.
PE / 10mm
SONTEX 200LT
3250 / 114.4
QUANTITY1
OIL AMOUNT
0.11 / 0.004
WASHABLE SARANET
ELECTRO GALVANISED MILD STEEL
EPOXY POLYESTER POWDER
254 / 10
254 / 10 & 203.2 / 8.0
3
ALUMINIUM
ALUMINIUM
0.11 / 0.004
9.52 / 3/8
0.33 / 0.013
THREE PHASE SQUIRREL CAGE INDUCTION MOTOR
PROPELLER
1020 / 40.2
1
1.42 / 15.28
615 / 24.2
1 / 0.04
THREE PHASE INDUCTION MOTOR
DIRECT DRIVE
1
1
IP22
GALVANISED STEEL
1
4
SCROLL
ART100AART120A
BELT DRIVE
CENTRIFUGAL
GALVANISED STEEL
2
FIN PER INCH
DIAMETER
THICKNESS
THICKNESS
FACE AREA
CASING
AIR QUALITYFILTER
TYPE
QUANTITY
INSULATION / THICKNESS
SIZE
MATERIAL
EXTERNAL FINISHING
COLOUR
CONDENSER
COIL
FIN
FIN
TUBE
TUBE
MODEL
TYPE
EVAPORATOR
FAN
DIAMETER
LENGTH
EVAPORATOR
FAN MOTOR
QUANTITY
MATERIAL
DRIVE
INDEX OF PROTECTION (IP)
TYPE
QUANTITY
CONDENSER FAN
MOTOR
CONDENSER FAN
MATERIAL
DRIVE
TYPE
TYPE
QUANTITY
DIAMETER
INDEX OF PROTECTION (IP)
QUANTITY
COMPRESSOR
TYPE
OIL TYPE
EVAPORATOR
COIL
DIAMETER
THICKNESS
THICKNESS
MATERIAL
LIGHT GREY
9.52 / 3/8
0.33 / 0.013
MATERIAL
ROW
FACE AREA
FIN PER INCH
MATERIAL
MATERIAL
ROW
77
Page 79
Components Data (R22)
mm/in
mm/in
mm/in
cm3/fl.oz.
2510 / 88.33250 / 114.4
mm/in
mm/in
mm/in
m2/ft
2
34
mm/in
mm/in
mm/in
m2/ft
2
23
pc
LENGTHmm/in
WIDTHmm/in
THICKNESSmm/in
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER.
PE / 10mm
1 / 0.04
SIZE
MATERIAL
EXTERNAL FINISHING
THICKNESS
THICKNESS
FACE AREA
DIAMETER
MATERIAL
ROW
FIN PER INCH
MATERIAL
9.52 / 3/8
0.33 / 0.013
ALUMINIUM
ALUMINIUM
2 x 0.57 / 2 x 6.12
0.11 / 0.004
9.52 / 3/8
0.33 / 0.013
15
S.I.G.C.
384.5 / 15.1
374.0 / 14.7
660.4 / 26.0
THREE PHASE SQUIRREL CAGE INDUCTION MOTOR
PROPELLER
1
2
IP22
GALVANISED STEEL
SONTEX 200LT
S.I.G.C.
THREE PHASE INDUCTION MOTOR
DIRECT DRIVE
IP44
2
SCROLL
2
MATERIAL
DIAMETER
CONDENSER FAN
MOTOR
INDEX OF PROTECTION (IP)
QUANTITY
COMPRESSOR
TYPE
OIL TYPE
QUANTITY
OIL AMOUNT
CONDENSER FAN
MATERIAL
DRIVE
TYPE
TYPE
QUANTITY
DIAMETER
TYPE
QUANTITY
EVAPORATOR
FAN MOTOR
QUANTITY
MATERIAL
DRIVE
INDEX OF PROTECTION (IP)
DIAMETER
LENGTH
MODEL
TYPE
EVAPORATOR
FAN
CONDENSER
COIL
FIN
FIN
TUBE
TUBE
EVAPORATOR
COIL
CASING
AIR QUALITYFILTER
TYPE
QUANTITY
INSULATION / THICKNESS
COLOUR
MATERIAL
ROW
FIN PER INCH
THICKNESS
THICKNESS
FACE AREA
ART150AART200A
BELT DRIVE
CENTRIFUGAL
PLASTIC
2
0.11 / 0.004
WASHABLE SARANET
ELECTRO GALVANISED MILD STEEL
LIGHT GREY
EPOXY POLYESTER POWDER
2 X 1.25 / 2 x 13.44
2
840 / 33.1
16
667 / 26.3
78
Page 80
Components Data (R22)
mm/in
mm/in480 / 18.9481 / 18.9
mm/in
cm3/fl.oz.
3250 / 114.44140 / 145.7
mm/in
mm/in
mm/in
m2/ft
2
SEAMLESS COPPERS.I.G.C.
mm/in
mm/in
mm/in
m2/ft
2
pc
LENGTHmm/in
WIDTHmm/in
THICKNESSmm/in
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER.
735 / 28.9
1 / 0.04
MATERIAL
EXTERNAL FINISHING
TYPE
QUANTITY
SIZE
ROW
FIN PER INCH
FACE AREA
DIAMETER
THICKNESS
THICKNESS
MATERIAL
MATERIAL
OIL AMOUNT
DIAMETER
THICKNESS
THICKNESS
TUBE
457.2 / 18
2 x 3.01 / 2 x 32.44
ALUMINIUM
2 x 0.91 / 2 x 9.84
14
GALVANISED STEEL
IP22
9.52 / 3/8
0.33 / 0.013
2
0.33 / 0.013
PE / 10mm
0.11 / 0.004
WASHABLE SARANET
ELECTRO GALVANISED MILD STEEL
LIGHT GREY
EPOXY POLYESTER POWDER
2
2
1370 / 53.9
14
THREE PHASE SQUIRREL CAGE INDUCTION MOTOR
PROPELLER
THREE PHASE INDUCTION MOTOR
DIRECT DRIVE
1
2
812.8 / 32.0
4
0.11 / 0.004
ART250AART300A
BELT DRIVE
CENTRIFUGAL
GALVANISED STEEL
1
CASING
CONDENSER
COIL
FIN
FIN
TUBE
COLOUR
INSULATION / THICKNESS
FACE AREA
AIR QUALITYFILTER
TYPE
QUANTITY
MATERIAL
DRIVE
INDEX OF PROTECTION (IP)
QUANTITY
QUANTITY
MODEL
TYPE
EVAPORATOR
FAN
DIAMETER
LENGTH
EVAPORATOR
FAN MOTOR
QUANTITY
INDEX OF PROTECTION (IP)
CONDENSER FAN
MATERIAL
DRIVE
TYPE
QUANTITY
DIAMETER
CONDENSER FAN
MOTOR
TYPE
ROW
FIN PER INCH
COMPRESSOR
TYPE
OIL TYPE
EVAPORATOR
COIL
MATERIAL
MATERIAL
IP55
SCROLL
9.52 / 3/8
ALUMINIUM
SEAMLESS COPPER
2
SONTEX 200LT
79
Page 81
Components Data (R22)
mm/in
mm/in
mm/in
320 SZ
cm 3 /fl.oz.
8000 / 281.6
S.I.G.C.
160P & 320SZ
6600 / 232.3 & 8000 / 281.6
S.I.G.C.
mm/in
mm/in
mm/in
m 2 /ft
2
S.I.G.C. S.I.G.C.
mm/in
mm/in
mm/in
m 2 /ft
2
pc
LENGTH mm/in
WIDTH mm/in
THICKNESS mm/in
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER.
SCROLL
9.52 / 3/8
ALUMINIUM
2
CONDENSER FAN
MOTOR
TYPE
ROW
FIN PER INCH
COMPRESSOR
TYPE
OIL TYPE
EVAPORATOR
COIL
MATERIAL
MATERIAL
INDEX OF PROTECTION (IP)
CONDENSER FAN
MATERIAL
DRIVE
TYPE
QUANTITY
DIAMETER
INDEX OF PROTECTION (IP)
QUANTITY
QUANTITY
MODEL
TYPE
EVAPORATOR
FAN
DIAMETER
LENGTH
EVAPORATOR
FAN MOTOR
QUANTITY
TYPE
QUANTITY
MATERIAL
DRIVE
CASING
CONDENSER
COIL
FIN
FIN
TUBE
COLOUR
INSULATION / THICKNESS
FACE AREA
AIR QUALITYFILTER
ART360AART420A
BELT DRIVE
560 / 22
457 / 18
CENTRIFUGAL
GALVANISED STEEL
1
13
THREE PHASE SQUIRREL CAGE INDUCTION MOTOR
PROPELLER
GALVANISED STEEL
THREE PHASE INDUCTION MOTOR
DIRECT DRIVE
1
IP22
IP55
2
812.8 / 32.0
3 & 4
0.11 / 0.004
3.02 / 32.5
0.33 / 0.013
PE / 10mm
0.11 / 0.004
3.50 / 37.7
WASHABLE SARANET
ELECTRO GALVANISED MILD STEEL
LIGHT GREY
EPOXY POLYESTER POWDER
860 / 33.86
4 / 0.16
505 / 19.88 & 600 / 23.62
3
14 & 13
2 & 3
2 & 4
ALUMINIUM
14 & 13
4
13
9.52 / 3/8
0.33 / 0.013
2
OIL AMOUNT
DIAMETER
THICKNESS
THICKNESS
TUBE
FACE AREA
DIAMETER
THICKNESS
THICKNESS
MATERIAL
MATERIAL
TYPE
QUANTITY
SIZE
ROW
FIN PER INCH
MATERIAL
EXTERNAL FINISHING
80
Page 82
Components Data (R22)
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER.
3) * DESIGNATION BASED ON COOLING CYCLE.
mm/in
mm/in
mm/in
cm
3
/fl.oz.
mm/in
mm/in
mm/in
m
2
/ft
2
mm/in
mm/in
mm/in
m
2
/ft
2
pc
LENGTHmm/in
WIDTHmm/in
THICKNESSmm/in
THICKNESS
ROW
FIN PER INCH
MATERIAL
MATERIAL
0.28 / 0.011
SONTEX 200LT
1
FACE AREA
MATERIAL
THICKNESS
DIAMETER
THICKNESS
MATERIAL
COMPRESSOR
TYPE
OIL TYPE
QUANTITY
OIL AMOUNT
CONDENSER
*
FAN
MOTOR
CONDENSER
*
FAN
MATERIAL
DRIVE
TYPE
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
QUANTITY
DIAMETER
EVAPORATOR*
FAN MOTOR
QUANTITY
MATERIAL
DRIVE
INDEX OF PROTECTION (IP)
TYPE
QUANTITY
DIAMETER
MODEL
TYPE
EVAPORATOR
*
FAN
LENGTH
CONDENSER*
COIL
FIN
FIN
TUBE
TUBE
EVAPORATOR*
COIL
CASING
AIR QUALITYFILTER
TYPE
QUANTITY
INSULATION / THICKNESS
EXTERNAL FINISHING
COLOUR
SIZE
MATERIAL
ROW
FIN PER INCH
FACE AREA
0.11 / 0.004
9.52 / 3/8
0.28 / 0.011
ALUMINIUM
3
DIAMETER
THICKNESS
CENTRIFUGAL
1
1
PLASTIC
1
IP22
254 / 10
THREE PHASE SQUIRREL CAGE INDUCTION MOTOR
PROPELLER
N/A
N/A
N/A
BELT DRIVE
1
ALUMINIUM
INDUCTION MOTOR
DIRECT DRIVE
SCROLL
9.52 / 3/8
609.6 / 24.0
IP54
LIGHT GREY
PE / 10mm
0.11 / 0.004
N/A
ELECTRO GALVANISED MILD STEEL
EPOXY POLYESTER POWDER
3
0.44 / 4.75
S.I.G.C.
14
N/A
ART55AR
1770 / 62.3
S.I.G.C.
0.44 / 4.75
14
METAL
203 / 8
81
Page 83
Components Data (R22)
PLASTICGALVANISED STEEL
mm/in254 / 10286.0 / 11.3
mm/in254 / 10274.0 / 10.8 & 184.0 / 7.2
mm/in609.6 / 24.0660.4 / 26.0
IP54IP44
SCROLLRECIPROCATING
SONTEX 200LTDIAMOND MS 32(N-1)
cm3/fl.oz.
1770 / 62.33000 / 106.0
mm/in
mm/in
mm/in
m2/ft
2
0.53 / 5.700.65 / 6.96
1615
mm/in
mm/in
mm/in
m2/ft
2
1613
pc
LENGTHmm/in820 / 32.31020 / 40.2
WIDTHmm/in
THICKNESSmm/in
LIGHT GREY
LIGHT GREY
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.