12. EXPLODED VIEW & PARTS LIST ........................................................................ 115
Page 3
Indoor
Others
A : First issue
Other Specifications
I : Ionizer Generator
N : Non Thermal Plasma
Controller
Specifications
G : Wireless handset
S : SLM3
N : Netware III
Market Region
C : Export with CE mark
1. NOMENCLATURE
Electrical
A : 220 - 240V/1Ph/50Hz
ACM20
5
E
R
GIACA-
Model Type
R : heatpump
Omitted if Cooling Only
Series
E : E series
Capacity
20 : 20,000 Btu/h
Model Name
CM : Ceiling Convertible
Refrigerant
5 : R410A
Omitted if R22 model
Brand
A : ACSON
1
Page 4
Outdoor
Others
A : First issue
Specifications Variation
O : Standard unitI : Gold Fin
B : With ContactorL : Long Piping Unit
G : Low Ambient UnitS : With H/L Pressure Switch
H : High ambient unitX :Oxygen Unit
Compressor
P : Matsushita Rotary T : Toshiba Rotary
M :Mitsubishi Rotary
Market Region
C : Export with CE marking
E : Export without marking
U : ETL Spec.
Electrical
A : 220 - 240V/1Ph/50Hz
ALC20CR
5POACA-
Model Type
R : heatpump
Omitted if Cooling
Series
C : C series
Capacity
20 : 20,000 Btu/h
Model Name
LC : Single Split Condensing unit
Refrigerant
5 : R410A
Omitted if R22 model
Brand
A : ACSON
2
Page 5
2. PRODUCT LINE UP
INDOOR UNIT
ACM-E SERIES PRODUCT LINE UP
Classification
ACM
15EACGIAXXXXXX
ACGIAXXXXXX
20E
ACGNAXXXXXX
ACGIAXXXXXX
25E
ACGNAXXXXXX
Cooling ModelHeat Pump Model
15ERACGIAXXXXXX
20ER
25ER
28ER
ACGIAXXXXXX
28E
ACGNAXXXXXX
ACGIAXXXXXX
ACGNAXXXXXX
ACGIAXXXXXX
ACGNAXXXXXX
ACGIAXXXXXX
ACGNAXXXXXX
A5CM-E SERIES PRODUCT LINE UP
Handset
Control Module
Nomenclature
L2
SLM3
Netware III
G12 Handset
Classification
Fin
Marking
NTP
Ionizer
CE Mark
W/out Marking
Hydrophilic (SLIT)
Control
Refrigerant
Cap. Tube
W/out Cap. Tube
Handset
A5CM
15EACGIAXXXXXX
ACGI AXXXXXX
20E
ACGNAXXXXXX
ACGI AXXXXXX
25E
ACGNAXXXXXX
Cooling ModelHeat Pump Model
15ERACGIAXXXXXX
20ER
25ER
28ER
ACGI AXXXXXX
28E
ACGNAXXXXXX
ACGI AXXXXXX
ACGNAXXXXXX
ACGI AXXXXXX
ACGNAXXXXXX
ACGI AXXXXXX
ACGNAXXXXXX
Control Module
L2
NONMENCLATURE
SLM3
Netware III
G12 Handset
Fin
Marking
NTP
Negative Ionizer
CE Mark
W/out Marking
Hydrophilic (SLIT)
Cap. Tube
Control
Refrigerant
W/out Cap.Tube
3
Page 6
OUTDOOR UNIT
ALC-C SERIES PRODUCT LINE UP
Classification
Cooling Model
Heat Pump Model
ALC
15CR
18CR
20CR
25CR
28CR
30CR
Safety Devices
Gold Fin
High Ambient Kit
Special
Low Ambient Kit
Contactor
Phase Sequencer
Nantong Press. SW
Low Pressure Switch
High Pressure Switch
Ctrl + Fin
Refrigerant
Nomenclature
ACPO DXXX
15C
18C
20C
25C
28C
30C
ACPIDXXXX
ACPBDXXXX
ACPYDXXXXX
ACPO D
ACPID
ACPO D
ACPID
ACPO D
ACPID
ACPOA
ACPIA
AFGEXXXXXX
AFGFXXXXXXX
AFGGXXXXXXX
FFGEXXXXXXX
FFGGXXXXXXXX
ACPO BXXX
ACPIBXXXX
ACPO DXXX
ACPIDXXXX
ACPO D
ACPID
ACPO D
ACPID
ACPOA
ACPIA
AFFB XXXXXXXX
AFFCXXXXXXXXX
AFFD XXXXXXXXX
FFFB XXXXXXXXX
FFFD XXXXXXXXXX
TXV
Cap. Tube
XXX
XXXX
XXX
XXXX
XXX
XXXX
XXX
XXX
XXXX
XXX
XXXX
XXX
XXXX
Grille
Compressor
Drain Elbow
Copeland Scroll Comp.
XX
Rotary
Marking
ETL
CE Marking
4
Page 7
OUTDOOR UNIT
A5LC-C SERIES PRODUCT LINE UP
Classification
Safety Devices
Ctrl + Fin
Refrigerant
A5LC
Nomenclature
15CACPOCXXX
ACPI AXXXX
ACPOAXXX
20C
FCPOCXXXX
FCPICXXXXX
ACPI AXXXX
ACPOAXXX
25C
FCPOCXXXX
PCPICXXXXX
Cooling Model
15CRACPOCXXX
20CR
25CR
28CR
Heat Pump Model
35CR
ACPOAXXX
ACPI AXXXX
28C
FCPOAXXXX
FCPIAXXXXX
ACCOAXXXXXXX
35C
ACCIA XXXXXXXX
FCCOAXXXXXXXXX
ACPI AXXXX
ACPOCXXX
FCPOCXXXXX
FCPICXXXXXX
ACPI AXXXX
ACPOCXXX
FCPOCXXXXX
FCPICXXXXXX
ACPOAXXX
ACPI AXXXX
FCPOAXXXXX
FCPIAXXXXXX
ACCOAXXXXXXX
ACCGAXXXXXXXX
FCCOAXXXXXXXXXX
FCCGAXXXXXXXXXX
TXV
Cap. Tube
Special
Gold Fin
High Ambient Kit
Contactor
Low Ambient Kit
High Pressure Switch
Low Pressure Switch
Nantong Press. SW
Grille
Drain Elbow
Phase Sequencer
Copeland Scroll Comp.
Compressor
Marking
Rotary
ETL
CE Marking
5
Page 8
3. FEATURES
Ceiling And Floor Installation Option
The unit is uniquely designed with the option to install either below the ceiling or mounted at low wall position
without any modification needed. Furthermore, the unit is design adds a touch of elegance to suit any interior
design requirement
Excellent Air Distribution
The louver with automatic air swing function fully optimize the room comfort by enables the air flow to be
evenly distributed into the room from the front discharge area.
Negative Ion Generator
ACSON emphasis on provide indoor air quality solution. Therefore, the negative ionizer technology is being
brought in as an essential part of the unit. The negative ion generator increases the amount of negative ion in
the air-conditioning area, creating a refreshing and healthy living environment.
Easy Installation
The ceiling convertible fan coil unit is easily installed with a very economical and space saving installation. No
need renovation on wall or ceiling for installation. This easy to install and ready to operate unit ensure rapid
and low installation cost.
Magnificent Serviceability
The blower, fan motor assembly and electrical parts can be inspected and air filter can be accessed by pulling
down the air intake grille. During servicing or repairing, only the bottom panel needs to be removed in order to
access the fan motor, blower, control box piping connection and drain pan.
Wireless Remote Controller
The standard unit comes with a simple, user friendly and stylish wireless controller. The G12 controller offers
many features:
•The compact LCD transmitter is able to operate the indoor unit within 9 meters of distance.
•Fan speed can be set at low/medium/high or automatic.
•Sleep mode auto control will gradually increase or decrease the set temperature to provide a comfort-
able surrounding for sleeping.
•The real time timer allows the unit to be switched ON and OFF automatically based on user settings.
•Ionizer or non-thermal plasma is available to create better air quality.
•Turbo mode function is available to enables the required set temperature to be achieved in a short time.
•Personalized Setting allows user to preset and store 2 groups of personal settings (including timer
setting) in the handset.
Auto Random Restart
Auto random restart function allows the unit to automatic restart as the last setting condition when the power
supply is resumed after power failure. However, the compressor will restart randomly if more than one unit is
installed and sharing the same phase of power.
Self Diagnosis
The microprocessor provides the possibility to detect and diagnose any fault or malfunction that occurs in the
system. The error will be reflected by the blinking of the LED lights.
6
Page 9
4. APPLICATION INFORMATION
Operating Range
Ensure the operating temperature is in allowable range.
Cooling only
Heatpump
54
46
35
19
Outdoor temp. (°CDB)
-5
18
6
High ambient
unit
Standard
point
Low ambient kit
15
24
Indoor temp. (°CWB)
Heating
Standard
point
Caution :
The use of your air conditioner
outside the range of working
temperature and humidity can
result in serious failure.
Cooling
54
46
35
19
High ambient
unit
Standard
point
Note :
Outdoor temp. (°CWB)
-9
1521
27
Indoor temp. (°CDB)
Standard operating range.
With High ambient unit. (Optional item)
Please refer to local dealer for unit of this specification.
With Low ambient kit. (Optional item)
Please refer to local dealer for unit of this specification.
7
Outdoor temp. (°CDB)
-5
Low ambient kit
15
24
Indoor temp. (°CWB)
Page 10
Refrigerant Circuit Diagrams
MODEL : ACM / A5CM 15E - ALC / A5LC 15CACM 20E - ALC 18C
•To set the desired room
temperature, press the button to
increase or decrease the set
temperature.
•The temperature setting range is
from 16°C to 30°C
•Press both buttons simultaneously
to toggle the temperature setting
between °C and °F
On/Off Button
•Press Once to start the air
conditioner
•Press again to stop the unit
ON Timer Setting
•Press the SET button will activate
the on timer function.
•Set the desired on time by pressing
the SET button continuously.
•Press the CLR button to cancel the
off timer setting
Personalised Setting
•Press and hold the button for 3s to
initiate personalized setting.
•Set the individual setting e.g.
MODE, SET TEMP or FAN SPEED
and leave for 4s to save
•2 groups of settings are allowed to
stored in the handset
OFF Timer Setting
•Press the SET button will activate
the off timer function.
•Set the desired off time by
pressing the SET button
continuously.
•Press the CLR button to cancel the
off timer setting
Clock Time Setting
•Press button + or - to increase or
decrease the clock time.
Fan Speed Selection
•Press the button until the desired
fan speed is achieved.
Turbo Mode
•Press the TURBO button to
achieve the required set
temperature in a short time.
Automatic Air Awing
•Press the SWING button to activate
the automatic air swing function.
•To distribute the air to a specific
direction, press the SWING button
and wait until the louver move to
the desired direction and press the
button once again.
Ionizer
•Press the button to activate the
negative Ion function, which will
refresh the indoor air effectively.
Sleep Mode
•Press the button to activate sleep
mode. This function is available
under COOL, HEAT & AUTO
mode.
•When it is activated in COOL
mode, the set temperature will be
increased 0.5°C after 30mins, 1°C
after 1 hour and 2°C after 2 hours.
•When it is activated in HEAT
mode, the set temperature will be
decreased 1°C after 30mins, 2°C
after 1 hour and 3°C after 2 hours.
Operating Mode
•Press the MODE button to select
the type of operating mode.
•For Cooling only unit, the available
modes are: COOL, DRY & FAN.
•For Heatpump unit, the available
modes are: AUTO, COOL, DRY,
FAN & HEAT.
14
Page 17
SLMAC-5300 (OPTIONAL)
1. “ON/OFF” switch
• Press to start the air conditioner unit.
• Press again to stop the unit.
2. Temperature setting
• Set the desired room temperature.
• Press button to increase or decrease the set
temperature. Setting range are between 16°C
to 30°C (60°F to 80°F).
3. Operation Modes
• Press the “mode” button for select the type of
operating mode.
- Cooling Only :
COOL, DRY, FAN
- Heat Pump :
AUTO, COOL, DRY, HEAT, FAN
(AUTO mode is represented by bothCOOL and
HEAT LED light on)
4. Fan Speed selection
• Press the button until the desired fan speed is
achieved.
6. “Sleep” mode
• Press button to activate the sleep function can
only be activated under “cool” or heating mode
operation. When it is activated under “cool”
mode operation, the set temperature will
increase 0.5°C after 30 minutes, 1°C after 1 hour
and 2°C after 2
“HEAT” mode operation, the set temperature
will be descreased 0.5°C after 30 minutes, 1°C
after 1 hour and 2°C after 2 hours.
7. Air Swing
• Press button to activate the automatic air swing
function.
8. Sensor
• Infra red sensor to receive signals from wireless
controller.
9. LED Display
• To display the set temperature (in °C) and timer
delay setting (in hours).
10. Transmission source
• To transmit signals to the air conditioner.
hours. If it is actiaved under
5. Timer
• Press the set button to select the switch timer
of the air conditioner unit (the setting range is
between 1 to 10 hours).
15
Page 18
Operating State and Fault Table
Wireless Remote Control – Handset
LED Indicator Light Display
Cooling OnlyHeatpump
COOL
COOLDRYFANHEAT
DRY
|
|
|
|
|
|
FAN
Normal Operation / Fault Indication
Cool mode
Heat mode
Dry mode
Fan mode
Auto mode in cooling operation
Auto mode in heating operation
Room air sensor open or short
Indoor coil sensor open or short
Outdoor coil sensor open or short
COOL
DRY
FAN
HEAT
| - ON
Compressor overload / indoor coil sensor short / outdoor coil sensor short
Gas leak
- Blinking
16
Page 19
Wired Remote Control – SLM
Cooling / Heatpump Model
Error Code at 7 Segment DisplayOperation / Faulty Indication
Blink E1Room sensor open or short
Blink E2Indoor coil sensor open
Blink E3Outdoor coil sensor open
Compressor overload /
Phase Sequencer
Normal Operation
Reverse Phase
S & T Phase Missing
T Phase Missing
S Phase Missing
R Phase Missing
Overload
Sensor Missing
Blink E4
Indoor coil sensor short /
Outdoor coil sensor short
Blink E5Gas leak
Blink E6Water pump faulty
LED_PLED_RLED_SLED_T
(Red)(Yellow)(Yellow)(Yellow)
On---
BlinkBlinkBlinkBlink
Blink-BlinkBlink
Blink--Blink
Blink-Blink-
----
Blink---
BlinkOnOnOn
Notes: 1. “-” means LED off.
2. When R phase missing, no LED or buzzer will indicate the error, but relay 71 (Common) and 81
(NO) will cut off.
3. The unit will check the discharge sensor availability only during power up.
4. All errors can only recover through manually reset.
17
Page 20
Installation
Caution
Sharp edges and coil surfaces are potential injury hazard. Avoid from contact with them.
(1) Installation of Indoor Unit
Preliminary Site Survey
• Electrical supply and installation is to confirm to local authority's (e.g. National Electrical Board) codes and
regulations.
• Voltage supply fluctuation must not exceed ± 10% of rated voltage. Electricity supply lines must be indepen-
dent of welding transformers which can cause high supply fluctuation.
• Ensure that the location is convenient for wiring, piping and drainage.
Standard Mounting
Ensure that the overhead supports are strong enough to hold the weight of the unit. Position the hanger rods
(wall mounting bracket for floor standing), and check for its alignment with the unit as shown in Figure A. Also,
check that the hangers are secured and the base of the fan coil unit is leveled in both horizontal directions,
taking into account the gradient for drainage flow as recommended in Figure B.
Figure A
18
Page 21
Please ensure that the following steps are taken:
• Check the gradient for drainage flow as recommended in Figure B.
• Provide clearance for easy servicing and optimal air flow as shown in Figure C.
• The indoor unit must be installed such that there is no short circuit of the cool discharge air with the warm
return air.
• Don not install the indoor unit where there is direct sunlight shining on the unit. The location should be
suitable for piping and drainage installation. The unit must be a large distance away from the door.
Figue B
Under ceiling type
Floor standing type
Figue C
19
Page 22
Under Ceiling Installation
Install the Suspension Bolts
1.Install the suspension bolts so that it can support the indoor unit.
2.Adjust the distance to ceiling before installation.
3.Refer to the dimension given (Figure A) to install the unit.
Install the Indoor Unit
1.Insert the suspension bolts into the fittings of the hanger bracket.
2.Set the nuts and washer on the both side of the metal fittings.
3.Secure it with nuts.
4.Attach the hanger cover (4 pcs) to the units.
20
Page 23
Floor standing installation
1. Refer to the dimension as illustrated when installing the mounting bracket.
2. Determine the pipe hose position using the rear piping hole. Drill the pipe hole at the slight downward slant
to the outdoor side.
21
Page 24
Piping and Drain Hose Installation
Under Ceiling Type
1. The piping direction can be 2 ways as illustrated.
2. The drain hose is only 1 way.
OR
Floor standing type
OR
How to Install the Drain Hose
1. Remove the 2 screws and the drain pipe holder.
2. Cut a slit for the drain hose hole.
3. Place the drain hose on the v-shape area and secure it with drain pipe holder and 2 screws.
22
Page 25
How to Remove the Air Inlet Grille
1. Remove the air inlet grille by both hands as the direction shown.
2. Loosen the screws for fixing the panel arm (3 screws - Left, Right and Center). Do not remove the
screws at this time.
3. Move the air inlet grille upward, and then turn it backwards. (Do not use too much force).
4. Remove the grille holder (both left and right side). After that, remove the air intake grille.
5. Remove the grille holder (center) from the panel.
23
Page 26
How to install the air filter
To Adjust the Vane Direction
Adjust the vane linkage as the direction shown to get the required vane direction.
Dimension of the Fresh Air Intake Hole
24
Page 27
(2) Installation Of Outdoor Unit
As condensing temperature rises, evaporating temperature rises and cooling capacity drops. In order to achieve maximum
cooling capacity, the location selected for outdoor unit should fulfill the following requirements :
•Install the condensing (outdoor) unit in a way such that hot air distributed by the outdoor condensing unit cannot be
drawn in again (as in the case of short circuit of hot discharge air). Allow sufficient space for maintenance around the
.
unit
•Ensure that there is no obstruction of air flow into or out of the unit. Remove obstacles which block air intake or
discharge.
•The location must be well ventilated, so that the unit can draw in and distribute plenty of air thus lowering the condensing
temperature.
•A place capable of bearing the weight of the outdoor unit and isolating noise and vibration.
•A place protected from direct sunlight. Otherwise use an awning for protection, if necessary.
•The location must not be susceptible to dust or oil mist.
Installation Clearance
•Outdoor units must be installed such that there is no short circuit of the hot discharge air or obstruction to smooth air
flow. Select the coolest possible place where intake air should not be hotter than the outside temperature (max. 45°C)
ALL MODELSABCD
Minimum Distance300 mm1000 mm300 mm500 mm
CAUTION : If the condensing unit is operated in an atmosphere containing oils(including machine oils),
salt(coastal area), sulphide gas(near hot spring, oil refinery plant), such substances may lead to failure of the
unit.
25
Page 28
(3) Refrigerant Piping
Maximum Piping Length And Maximum Number Of Bends
When the pipe length becomes too long, both the capacity and reliability drop. As the number of bends increases, system piping resistance to the refrigerant flow increases, thus lowering the cooling capacity, and as
the result the compressor may become defective. Always choose the shortest path and follow the recommendation as tabulated below:
•Align the center of the piping and tighten the flare nut sufficiently with fingers.
•Finally tighten the flare nut with torque wrench unit the wrench clicks.
•When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on
the wrench.
Pipe Size (mm/in)Torque (Nm)
6.35 (1/4)18
9.52 (3/8)42
12.70 (1/2)55
15.88 (5/8)65
19.05 (3/4)78
26
Page 29
(4) Wiring
Electrical Connections
•Wiring regulations on wire diameters differ from country to country. Please refer to your LOCAL ELECTRI-
CAL CODES for field wiring rules. Be sure that installations comply with the rules and regulations.
General Precautions
•Ensure that the rated voltage of the unit corresponds to the name plate before carrying out proper wiring
according to the wiring diagram.
•Provide a power outlet to be used exclusively for each unit. A power supply disconnects and a circuit
breaker for over-current protection should be provided in the exclusive line.
•The unit must be GROUNDED to prevent possible hazards due to insulation failures.
•All wiring must be firmly connected.
•All wiring must not touch the hot refrigerant piping, compressor or any moving parts of fan motors.
(5) Vacuuming And Charging
The pre-charged outdoor unit does not need any vacuuming or charging. However once it is connected, the
connecting pipe line and the indoor unit need to be vacuumed before releasing the R22/R407C/R410A from
the outdoor unit.
1. Open the service port core cap.
2. Connect pressure gauge to the service port.
3. Connect the line to vacuum pump. Open the charging manifold valve and turn the pump on. Vacuum to -
0.1 MPa (-760mmHg) or lower. (Evacuation time varies by the pump but averagely in 1 hour).
Note : R407C – Fix filter dryer
R22 - Nil
R410A - Nil
(6) Additional Charge
•The refrigerant charge has already charged into the outdoor unit. For the piping length of 7.6m, additional
refrigerant charge after vacuuming is not necessary.
•When the piping length is more than 7.6m, please use the table below (unit in gram).
The additional refrigerant charge amount recommended is a guideline for longer piping application. The actual
charge required may be different from the guideline due to different application and variation in site conditions.
27
Page 30
Diagram shows typical charging method:
Note : R407C – Fix filter dryer
R22 - Nil
R410A - Nil
(7) Overall Checking
•Ensure the following, in particular:
1.The unit is mounted solidly and rigid in position.
2.Piping and connections are leak proof after charging.
3.Proper wiring has been done.
•Drainage check – pour some water into drain pan.
•Test run
1.Conduct a test run after water drainage test and gas leakage test.
2.Watch out for the following:
(a) Is the electric plug firmly inserted into the socket?
(b) Is there any abnormal sound from the unit?
(c) Is there any abnormal vibration with regard to the unit itself or piping?
(d) Is there smooth drainage of water?
•Check that:
1. Outdoor fan is running, with warm air blowing off the outdoor unit (cooling cycle).
2. Indoor blower is running and discharge cool air (cooling cycle).
3. Suction (low side) pressure is as per recommendations.
4. The remote controller has incorporated a 3 minutes delay in the circuit. Thus, it requires about 3
minutes before the outdoor unit can start up.
(8) Standard Operating Condition
Cooling Only Unit
T
Temperature
˚C / ˚FT
s
Minimum Indoor Temperature19.4 / 66.913.9 / 57.0
Maximum Indoor Temperature26.7 / 80.119.4 / 66.9
Minimum Outdoor Temperature19.4 / 66.913.9 / 57.0
Maximum Outdoor Temperature46 / 114.824 / 75.2
Heat Pump Unit
˚C / ˚FT
Temperature
T
s
Minimum Indoor Temperature10 / 50-
Maximum Indoor Temperature26.7 / 80.1-
Minimum Outdoor Temperature-8 / 17.6-9 / 15.8
Maximum Outdoor Temperature24 / 75.218 / 64.4
28
˚C / ˚F
h
˚C / ˚F
h
Page 31
(9) Special Precautions When Dealing With Refrigerant R410a Unit
i)What Is New Refrigerant R410A?
R410A is a new HFC refrigerant which does not damage the ozone layer. The working pressure of this
new refrigerant is 1.6 times higher than conventional refrigerant (R22), thus proper installation / servicing
is essential.
ii) Components
Mixture weight composition R32(50%) and R125(50%)
iii) Characteristic
•R410A liquid and vapor components have different compositions when the fluid evaporates or condenses.
Hence, when leak occurs and only vapor leaks out, the composition of the refrigerant mixture left in the
system will change and subsequently affect the system performance. DO NOT add new refrigerant to
leaked system. It is recommended that the system should be evacuated thoroughly before recharging
with R410A.
•When refrigerant R410A is used, the composition will differ depending on whether it is in gaseous or
liquid phase. Hence when charging R410A, ensure that only liquid is being withdrawn from the cylinder or
can. This is to make certain that only original composition of R410A is being charged into the system.
•POE oil is used as lubricant for R410A compressor, which is different from the mineral oil used for R22
compressor. Extra precaution must be taken not to expose the R410A system too long to moist air.
iv) Check List Before Installation/Servicing
•Tubing
Refrigerant R410A is more easily affected by dust of moisture compared with R22, make sure to temporarily
cover the ends of the tubing prior to installation
•Compressor oil
No additional charge of compressor oil is permitted.
•Refrigerant
No other refrigerant other that R410A
•Tools (size of service port is different from R22 system)
Tools specifically for R410A only (must not be used for R22 or other refrigerant)
Like R22 system, the handling and installation of R410A system are closely similar. All precautionary measures;
such as ensuring no moisture, no dirt or chips in the system, clean brazing using nitrogen, and thorough leak
check and vacuuming are equally important requirements. However, due to its hydroscopic POE oil, additional
precautions must be taken to ensure optimum and trouble free system operation.
a) During installation or servicing, avoid prolong exposure of the internal part of the refrigerant system to
moist air. Residual POE oil in the piping and components can absorb moisture from the air.
b) Ensure that the compressor is not expose to open air for more than the recommended time specified by
its manufacturer (typically less than 10 minutes). Removed the seal plugs only when the compressor is
about to be brazed.
c) The system should be thoroughly vacuumed to 1.0 Pa ( 700mmHg) or lower. This vacuuming level is
more stringent than R22 system so as to ensure no incompressible gas and moisture in the system.
29
Page 32
d) When charging R410A, ensure that only liquid is being withdrawn from the cylinder or can. This is to
ensure that only the original composition of R410A is being delivered into the system. The liquid
composition can be different from the vapor composition.
Invert cylinder
Dip-pipe
without dip-pipe
Liquid
withdrawal
f)Normally, the R410A cylinder or can is being equipped with a dip pipe for liquid withdrawal. However, if
the dip pipe is not available, invert the cylinder or can so as to withdraw liquid from the valve at the
bottom.
30
Page 33
5. ENGINEERING AND PHYSICAL DATA
GENERAL DATA - COOLING ONLY (R22)
MODEL
NOMINAL CAPACITY
NOMINAL TOTAL INPUT POWER
NOMINAL RUNNING CURRENT
POWER SOURCE
EER2.82
REFRIGERANT TYPER22
REFRIGERANT CONTROL (EXPANSION DEVICE)
CONTROL
AIR FLO W
EXTERNAL STATIC PRESSURE (H/M/L)Pa / in.wg.
SOUND PRESSURE LEVEL (H/M/L)
UNIT DIMENSION
INDOOR UNIT
PACKING
DIMENSION
UNIT WEIGHT
CONDENSATE DRAIN SIZE
AIR FLO W
SOUND PRESSURE LEVEL
UNIT DIMENSION
PACKING
DIMENSION
OUTDOOR UNIT
UNIT WEIGHT
PIPE CONNECTION
REFRIGERANT CHARGE
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND
1m BELOW THE UNIT.
AIR DISCHARGE
OPERATION
SIZE
INDOOR UNIT
OUTDOOR UNIT
HIGH
MEDIUM
LOW
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
TYPE
LIQUIDmm/in
GASmm/in
Btu/h
W
W
A
V/Ph/Hz
W/W
AUTOMATIC LOUVER (UP & DOWN)
WIRELESS OR WIRED MICROCOMPUTER REMOTE CONTROL
l/s / CFM
l/s / CFM
l/s / CFM
dBA
mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/lb
mm/in
l/s / CFM
dBA
mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/lb
kg/lb
ACM 15E
ALC 15C
12000
3520
1250
5.6
220 - 240 / 1 / 50
OUTDOOR CAP. TUBE
240 / 508
182 / 386
165 / 350
0
48 / 43 / 41
218 / 8.6
1080 / 42.5
630 / 24.8
297 / 11.7
1197 / 47.1
740 / 29.1
26
19.1 / 3/4
453 / 960
49
540 / 21.3
700 / 27.6
250 / 9.8
620 / 24.4
810 / 31.9
330 / 13.0
32 / 71
FLARE VALVE
6.4 / 1/4
12.7 / 1/2
0.60 / 1.32
31
Page 34
GENERAL DATA - COOLING ONLY (R22)
MODEL
NOMINAL CAPACITY
NOMINAL TOTAL INPUT POWER
NOMINAL RUNNING CURRENT
POWER SOURCE
EER
REFRIGERANT TYPE
REFRIGERANT CONTROL (EXPANSION DEVICE)
CONTROL
AIR FLO W
EXTERNAL STATIC PRESSURE (H/M/L)Pa / in.wg.
UNIT DIMENSION
INDOOR UNIT
PACKING
DIMENSION
UNIT WEIGHT
CONDENSATE DRAIN SIZE
AIR FLO W
SOUND PRESSURE LEVEL
UNIT DIMENSION
PACKING
DIMENSION
OUTDOOR UNIT
UNIT WEIGHT
PIPE CONNECTION
REFRIGERANT CHARGE
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND
1m BELOW THE UNIT.
AIR DISCHARGE
OPERATION
SIZE
INDOOR UNIT
OUTDOOR UNIT
HIGH
MEDIUM
LOW
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
TYPE
LIQUIDmm/in
GASmm/in
ALC 18CALC 20C
Btu/h1800019000
W52805570
W
A8.48.0
V/Ph/Hz220 - 240 / 1 / 50220 - 240 / 1 / 50
W/W
WIRELESS OR WIRED MICROCOMPUTER REMOTE CONTROL
l/s / CFM
l/s / CFM
l/s / CFM
dBA
mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/lb
mm/in
l/s / CFM
dBA
mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/lb
kg/lb0.85 / 1.871.35 / 2.98
18701861
2.822.99
AUTOMATIC LOUVER (UP & DOWN)
58 / 12859 / 130
ACM 20E
R22
OUTDOOR CAP. TUBE
245 / 520
217 / 460
192 / 406
0
48 / 46 / 43SOUND PRESSURE LEVEL (H/M/L)
218 / 8.6
1080 / 42.5
630 / 24.8
297 / 11.7
1197 / 47.1
740 / 29.1
27 / 60
19.1 / 3/4
614 / 1300
51
648 / 25.5
855 / 33.7
328 / 12.9
710 / 28.0
990 / 39.0
415 / 16.3
FLARE VALVE
6.4 / 1/4
15.9 / 5/8
32
Page 35
GENERAL DATA - COOLING ONLY (R22)
MODEL
NOMINAL CAPACITY
NOMINAL TOTAL INPUT POWER
NOMINAL RUNNING CURRENT
POWER SOURCE
EER
REFRIGERANT TYPE
REFRIGERANT CONTROL (EXPANSION DEVICE)
CONTROL
AIR FLO W
EXTERNAL STATIC PRESSURE (H/M/L)Pa / in.wg.
SOUND PRESSURE LEVEL (H/M/L)
UNIT DIMENSION
INDOOR UNIT
PACKING
DIMENSION
UNIT WEIGHT
CONDENSATE DRAIN SIZE
AIR FLO W
SOUND PRESSURE LEVEL
UNIT DIMENSION
PACKING
DIMENSION
OUTDOOR UNIT
UNIT WEIGHT
PIPE CONNECTION
REFRIGERANT CHARGE
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND
1m BELOW THE UNIT.
AIR DISCHARGE
OPERATION
SIZE
INDOOR UNIT
OUTDOOR UNIT
HIGH
MEDIUM
LOW
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
TYPE
LIQUIDmm/in
GASmm/in
Btu/h
W
W
A
V/Ph/Hz
W/W
AUTOMATIC LOUVER (UP & DOWN)
WIRELESS OR WIRED MICROCOMPUTER REMOTE CONTROL
l/s / CFM
l/s / CFM
l/s / CFM
dBA
mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/lb
mm/in
l/s / CFM
dBA
mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/lb
kg/lb
ACM 25E
ALC 25C
24000
7030
2573
11.5
220 - 240 / 1 / 50
2.73
R22
OUTDOOR CAP. TUBE
274 / 580
250 / 530
231 / 490
0
50 / 47 / 46
218 / 8.6
1080 / 42.5
630 / 24.8
297 / 11.7
1197 / 47.1
740 / 29.1
27 / 60
19.1 / 3/4
755 / 1600
52
750 / 29.5
855 / 33.7
328 / 12.9
810 / 31.9
990 / 39.0
415 / 16.3
62 / 137
FLARE VALVE
9.5 / 3/8
15.9 / 5/8
1.50 / 3.31
33
Page 36
GENERAL DATA - COOLING ONLY (R22)
MODEL
NOMINAL CAPACITY
NOMINAL TOTAL INPUT POWER
NOMINAL RUNNING CURRENT
POWER SOURCE
EER
REFRIGERANT CONTROL (EXPANSION DEVICE)
CONTROL
AIR FLO W
EXTERNAL STATIC PRESSURE (H/M/L)Pa / in.wg.
SOUND PRESSURE LEVEL (H/M/L)
UNIT DIMENSION
INDOOR UNIT
PACKING
DIMENSION
UNIT WEIGHT
CONDENSATE DRAIN SIZE
AIR FLO W
SOUND PRESSURE LEVEL
UNIT DIMENSION
PACKING
DIMENSION
OUTDOOR UNIT
UNIT WEIGHT
PIPE CONNECTION
REFRIGERANT CHARGE
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND
1m BELOW THE UNIT.
AIR DISCHARGE
OPERATION
SIZE
INDOOR UNIT
OUTDOOR UNIT
Btu/h2800028000
W82108210
W
A13.613.3
V/Ph/Hz220 - 240 / 1 / 50220 - 240 / 1 / 50
W/W2.922.99
WIRELESS OR WIRED MICROCOMPUTER REMOTE CONTROL
HIGH
MEDIUM
LOW
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
TYPE
LIQUIDmm/in9.5 / 3/89.5 / 3/8
GASmm/in15.9 / 5/815.9 / 5/8
l/s / CFM
l/s / CFM
l/s / CFM
dBA
mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/lb
mm/in
l/s / CFM741 / 15701605 / 3400
dBA5458
mm/in
mm/in855 / 33.71030 / 40.55
mm/in328 / 12.9400 / 15.75
mm/in
mm/in
mm/in415 / 16.3560 / 22.05
kg/lb68 / 15095 / 209
kg/lb2.40 / 5.31.40 / 3.09
ALC 28CALC 30C
28112747
AUTOMATIC LOUVER (UP & DOWN)
750 / 29.5850 / 33.46
810 / 31.91000 / 39.37
990 / 39.01200 / 47.24
ACM 28E
R22 REFRIGERANT TYPE
INDOOR CAP. TUBE
302 / 640
264 / 560
217 / 460
0
56 / 51 / 44
218 / 8.6
1080 / 42.5
630 / 24.8
297 / 11.7
1197 / 47.1
740 / 29.1
28 / 62
19.1 / 3/4
FLARE VALVE
34
Page 37
GENERAL DATA - HEATPUMP (R22)
MODEL
NOMINAL COOLING CAPACITY
NOMINAL HEATING CAPACITY
NOMINAL TOTAL INPUT POWER (COOLING)
NOMINAL TOTAL INPUT POWER (HEATING)
NOMINAL RUNNING CURRENT (COOLING)
NOMINAL RUNNING CURRENT (HEATING)
POWER SOURCE
EER
COP
REFRIGERANT TYPE
REFRIGERANT CONTROL (EXPANSION DEVICE)
CONTROL
AIR FLO W
EXTERNAL STATIC PRESSURE (H/M/L)Pa / in.wg.
SOUND PRESSURE LEVEL (H/M/L)
UNIT DIMENSION
INDOOR UNIT
PACKING
DIMENSION
UNIT WEIGHT
CONDENSATE DRAIN SIZE
AIR FLO W
SOUND PRESSURE LEVEL
UNIT DIMENSION
PACKING
DIMENSION
OUTDOOR UNIT
UNIT WEIGHT
PIPE CONNECTION
REFRIGERANT CHARGE
AIR DISCHARGE
OPERATIONWIRELESS OR WIRED MICROCOMPUTER REMOTE CONTROL
SIZE
INDOOR UNIT
OUTDOOR UNIT
HIGH
MEDIUM
LOW
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
TYPE
LIQUIDmm/in
GASmm/in
V/Ph/Hz
l/s / CFM
l/s / CFM
l/s / CFM
l/s / CFM
Btu/h
W
Btu/h
W
W
W
A
A
W/W
W/W
dBA
mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/lb
mm/in
dBA
mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/lb
kg/lb
ACM 15E R
ALC 15CR
12000
3520
12000
3520
1250
998
5.6
4.5
220 - 240 / 1 / 50
2.82
3.53
R22
OUTDOOR CAP. TUBE
AUTOMATIC LOUVER (UP & DOWN)
240 / 508
182 / 386
165 / 350
0
48 / 43 / 41
218 / 8.6
1080 / 42.5
630 / 24.8
297 / 11.7
1197 / 47.1
740 / 29.1
26
19.1 / 3/4
453 / 960
49
540 / 21.3
700 / 27.6
250 / 9.8
620 / 24.4
810 / 31.9
330 / 13.0
32 / 71
FLARE VALVE
6.4 / 1/4
12.7 / 1/2
1.20 / 2.65
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m
BELOW THE UNIT.
35
Page 38
GENERAL DATA - HEATPUMP (R22)
MODEL
NOMINAL COOLING CAPACITY
NOMINAL HEATING CAPACITY
NOMINAL TOTAL INPUT POWER (COOLING)
NOMINAL TOTAL INPUT POWER (HEATING)
NOMINAL RUNNING CURRENT (COOLING)
NOMINAL RUNNING CURRENT (HEATING)
POWER SOURCE
EER
COP
REFRIGERANT TYPE
CONTROL
AIR FLO W
EXTERNAL STATIC PRESSURE (H/M/L)Pa / in.wg.
SOUND PRESSURE LEVEL (H/M/L)
UNIT DIMENSION
INDOOR UNIT
PACKING
DIMENSION
UNIT WEIGHT
CONDENSATE DRAIN SIZE
AIR FLO W
SOUND PRESSURE LEVEL
UNIT DIMENSIONWIDTH
PACKING
DIMENSION
OUTDOOR UNIT
UNIT WEIGHT
PIPE CONNECTION
REFRIGERANT CHARGE
AIR DISCHARGE
OPERATION
SIZE
INDOOR UNIT
OUTDOOR UNIT
HIGH
MEDIUM
LOW
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
HEIGHT
DEPTH
HEIGHT
WIDTH
DEPTH
TYPE
LIQUIDmm/in
GASmm/in
V/Ph/Hz220 - 240 / 1 / 50220 - 240 / 1 / 50
l/s / CFM
l/s / CFM
l/s / CFM
l/s / CFM
ACM 20E R
ALC 18CRALC 20CR
Btu/h1800019000
W52805570
Btu/h
W54205720
W18701861
W
A
A7.78.0
W/W
W/W3.173.16
WIRELESS OR WIRED MICROCOMPUTER REMOTE CONTROL
dBA
mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/lb
mm/in
dBA
mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/lb58 / 12859 / 130
kg/lb0.85 / 1.871.35 / 2.98
1850019500
17101811
8.48.2
2.822.99
R22
OUTDOOR CAP. TUBEREFRIGERANT CONTROL (EXPANSION DEVICE)
AUTOMATIC LOUVER (UP & DOWN)
245 / 520
217 / 460
192 / 406
0
48 / 46 / 43
218 / 8.6
1080 / 42.5
630 / 24.8
297 / 11.7
1197 / 47.1
740 / 29.1
27 / 60
19.1 / 3/4
614 / 1300
51
648 / 25.5
855 / 33.7
328 / 12.9
710 / 28.0
990 / 39.0
415 / 16.3
FLARE VALVE
6.4 / 1/4
15.9 / 5/8
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m
BELOW THE UNIT.
36
Page 39
GENERAL DATA - HEATPUMP (R22)
MODEL
NOMINAL COOLING CAPACITY
NOMINAL HEATING CAPACITY
NOMINAL TOTAL INPUT POWER (COOLING)
NOMINAL TOTAL INPUT POWER (HEATING)
NOMINAL RUNNING CURRENT (COOLING)
NOMINAL RUNNING CURRENT (HEATING)
POWER SOURCE
EER
COP
REFRIGERANT TYPE
REFRIGERANT CONTROL (EXPANSION DEVICE)
CONTROL
AIR FLO W
EXTERNAL STATIC PRESSURE (H/M/L)Pa / in.wg.
SOUND PRESSURE LEVEL (H/M/L)
UNIT DIMENSION
INDOOR UNIT
PACKING
DIMENSION
UNIT WEIGHT
CONDENSATE DRAIN SIZE
AIR FLO W
SOUND PRESSURE LEVEL
UNIT DIMENSION
PACKING
DIMENSION
OUTDOOR UNIT
UNIT WEIGHT
PIPE CONNECTION
REFRIGERANT CHARGE
AIR DISCHARGE
OPERATIONWIRELESS OR WIRED MICROCOMPUTER REMOTE CONTROL
SIZE
INDOOR UNIT
OUTDOOR UNIT
HIGH
MEDIUM
LOW
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
TYPE
LIQUIDmm/in
GASmm/in
V/Ph/Hz
l/s / CFM
l/s / CFM
l/s / CFM
l/s / CFM
Btu/h
W
Btu/h
W
W
W
A
A
W/W
W/W
dBA
mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/lb
mm/in
dBA
mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/lb
kg/lb
ACM 25E R
ALC 25CR
24000
7030
25000
7330
2573
2493
11.5
11.2
220 - 240 / 1 / 50
2.73
2.94
R22
OUTDOOR CAP. TUBE
AUTOMATIC LOUVER (UP & DOWN)
274 / 580
250 / 530
231 / 490
0
50 / 47 / 46
218 / 8.6
1080 / 42.5
630 / 24.8
297 / 11.7
1197 / 47.1
740 / 29.1
27 / 60
19.1 / 3/4
755 / 1600
52
750 / 29.5
855 / 33.7
328 / 12.9
810 / 31.9
990 / 39.0
415 / 16.3
62 / 137
FLARE VALVE
9.5 / 3/8
15.9 / 5/8
1.50 / 3.31
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m
BELOW THE UNIT.
37
Page 40
GENERAL DATA - HEATPUMP (R22)
MODEL
NOMINAL COOLING CAPACITY
NOMINAL HEATING CAPACITY
NOMINAL TOTAL INPUT POWER (COOLING)
NOMINAL TOTAL INPUT POWER (HEATING)
NOMINAL RUNNING CURRENT (COOLING)
NOMINAL RUNNING CURRENT (HEATING)
POWER SOURCE
EER
COP
REFRIGERANT TYPE
REFRIGERANT CONTROL (EXPANSION DEVICE)
CONTROL
AIR FLO W
EXTERNAL STATIC PRESSURE (H/M/L)Pa / in.wg.
SOUND PRESSURE LEVEL (H/M/L)
UNIT DIMENSION
INDOOR UNIT
PACKING
DIMENSION
UNIT WEIGHT
CONDENSATE DRAIN SIZE
AIR FLO W
SOUND PRESSURE LEVEL
UNIT DIMENSION
PACKING
DIMENSION
OUTDOOR UNIT
UNIT WEIGHT
PIPE CONNECTION
REFRIGERANT CHARGE
AIR DISCHARGE
OPERATIONWIRELESS OR WIRED MICROCOMPUTER REMOTE CONTROL
SIZE
INDOOR UNIT
OUTDOOR UNIT
V/Ph/Hz220 - 240 / 1 / 50220 - 240 / 1 / 50
HIGH
MEDIUM
LOW
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
TYPE
LIQUIDmm/in9.5 / 3/89.5 / 3/8
GASmm/in15.9 / 5/815.9 / 5/8
l/s / CFM
l/s / CFM
l/s / CFM
l/s / CFM
ACM 28E R
ALC 28CRALC 30CR
Btu/h2800028000
W82108210
Btu/h
W83508350
W28622747
W
A
A13.814.1
W/W
W/W2.882.83
dBA
mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/lb
mm/in
dBA5458
mm/in750 / 29.5850 / 33.5
mm/in855 / 33.71030 / 40.6
mm/in328 / 12.9400 / 15.8
mm/in
mm/in990 / 39.01200 / 47.2
mm/in415 / 16.3560 / 22.1
kg/lb68 / 15095 / 209
kg/lb2.40 / 5.302.15 / 4.12
2850028500
29022954
13.713.3
2.872.99
R22R22
OUTDOOR CAP. TUBEOUTDOOR CAP TUBE + TXV
AUTOMATIC LOUVER (UP & DOWN)
302 / 640
264 / 560
217 / 460
0
56 / 51 / 44
218 / 8.6
1080 / 42.5
630 / 24.8
297 / 11.7
1197 / 47.1
740 / 29.1
28 / 62
19.1 / 3/4
741 / 15701605 / 3400
810 / 31.91000 / 39.4
FLARE VALVE
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m
BELOW THE UNIT.
38
Page 41
GENERAL DATA - COOLING ONLY (R410A)
MODEL
NOMINAL CAPACITY
NOMINAL TOTAL INPUT POWER
NOMINAL RUNNING CURRENT
POWER SOURCE
EER
REFRIGERANT TYPE
REFRIGERANT CONTROL (EXPANSION DEVICE)
CONTROL
AIR FLO W
EXTERNAL STATIC PRESSURE (H/M/L)Pa / in.wg.
UNIT DIMENSION
INDOOR UNIT
PACKING
DIMENSION
UNIT WEIGHT
CONDENSATE DRAIN SIZE
AIR FLO W
SOUND PRESSURE LEVEL
UNIT DIMENSION
PACKING
DIMENSION
OUTDOOR UNIT
UNIT WEIGHT
PIPE CONNECTION
REFRIGERANT CHARGE
AIR DISCHARGE
OPERATION
SIZE
INDOOR UNIT
OUTDOOR UNIT
HIGH
MEDIUM
LOW
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
TYPE
LIQUIDmm/in
GASmm/in
Btu/h
W
W
A
V/Ph/Hz
W/W
l/s / CFM
l/s / CFM
l/s / CFM
dBA
mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/lb
mm/in
l/s / CFM
dBA
mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/lb
kg/lb
A5CM 15E
A5LC 15C
12900
3780
1280
5.8
220 - 240 / 1 / 50
2.95
R410A
OUTDOOR CAP. TUBE
AUTOMATIC LOUVER (UP & DOWN)
WIRELESS OR WIRED MICROCOMPUTER REMOTE CONTROL
240 / 508
182 / 386
165 / 350
0
48 / 43 / 41SOUND PRESSURE LEVEL (H/M/L)
218 / 8.6
1080 / 42.5
630 / 24.8
297 / 11.7
1197 / 47.1
740 / 29.1
26
19.1 / 3/4
453 / 960
49
540 / 21.3
700 / 27.6
250 / 9.8
620 / 24.4
810 / 31.9
330 / 13.0
32 / 71
FLARE VALVE
6.4 / 1/4
12.7 / 1/2
0.83 / 1.83
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND
1m BELOW THE UNIT.
39
Page 42
GENERAL DATA - COOLING ONLY (R410A)
MODEL
NOMINAL CAPACITY - 1Ø / <3Ø>
NOMINAL TOTAL INPUT POWER - 1Ø / <3Ø>
NOMINAL RUNNING CURRENT - 1Ø / <3Ø>
POWER SOURCE
EER - 1Ø / <3Ø>
REFRIGERANT TYPE
REFRIGERANT CONTROL (EXPANSION DEVICE)
CONTROL
AIR FLO W
EXTERNAL STATIC PRESSURE (H/M/L)Pa / in.wg.00
SOUND PRESSURE LEVEL (H/M/L)
UNIT DIMENSIONWIDTH
INDOOR UNIT
PACKING
DIMENSION
UNIT WEIGHT
CONDENSATE DRAIN SIZE
AIR FLO W
SOUND PRESSURE LEVEL
UNIT DIMENSION
PACKING
DIMENSION
OUTDOOR UNIT
UNIT WEIGHT
PIPE CONNECTION
REFRIGERANT CHARGE
AIR DISCHARGE
OPERATION
SIZE
INDOOR UNIT
OUTDOOR UNIT
Btu/h17500 / <18100>20000 / <22860>
W5130 / <5300>5860 / <6700>
W
A7.6 / <3.3>8.8 / <4.2>
V/Ph/Hz
W/W2.98 / <3.02>2.97 / <3.00>
HIGH
MEDIUM
LOW
HEIGHT218 / 8.6
DEPTH
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
TYPE
LIQUIDmm/in6.4 / 1/46.4 / 1/4
GASmm/in12.7 / 1/215.9 / 5/8
l/s / CFM
l/s / CFM217 / 460250 / 530
l/s / CFM192 / 406231 / 490
dBA
mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/lb
mm/in
l/s / CFM614 / 1300689 / 1460
dBA5252
mm/in
mm/in855 / 33.7855 / 33.7
mm/in328 / 12.9328 / 12.9
mm/in710 / 28.0810 / 31.9
mm/in
mm/in415 / 16.3415 / 16.3
kg/lb59 / 13062 / 137
kg/lb1.40 / 3.091.65 / 3.64
A5CM 20EA5CM 25E
A5LC 20CA5LC 25C
1723 / <1757>1973 / <2231>
220 - 240 / 1 / 50 / <380 - 415 / 3 / 50>
R410A
OUTDOOR CAP. TUBE
AUTOMATIC LOUVER (UP & DOWN)
WIRELESS OR WIRED MICROCOMPUTER REMOTE CONTROL
245 / 520274 / 580
48 / 46 / 4350 / 47 / 46
1080 / 42.5
630 / 24.8
297 / 11.7
1197 / 47.1
740 / 29.1
27 / 60
19.1 / 3/4
648 / 25.5750 / 29.5
990 / 39.0990 / 39.0
FLARE VALVE
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND
1m BELOW THE UNIT.
40
Page 43
GENERAL DATA - COOLING ONLY (R410A)
MODEL
NOMINAL CAPACITY - 1Ø / <3Ø>
NOMINAL TOTAL INPUT POWER - 1Ø / <3Ø>
NOMINAL RUNNING CURRENT - 1Ø / <3Ø>
POWER SOURCE
EER - 1Ø / <3Ø>
REFRIGERANT TYPE
REFRIGERANT CONTROL (EXPANSION DEVICE)
CONTROL
AIR FLO W
EXTERNAL STATIC PRESSURE (H/M/L)Pa / in.wg.
SOUND PRESSURE LEVEL (H/M/L)
UNIT DIMENSION
INDOOR UNIT
PACKING
DIMENSION
UNIT WEIGHT
CONDENSATE DRAIN SIZE
AIR FLO W
SOUND PRESSURE LEVEL
UNIT DIMENSION
PACKING
DIMENSION
OUTDOOR UNIT
UNIT WEIGHT
PIPE CONNECTION
REFRIGERANT CHARGE
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND
1m BELOW THE UNIT.
AIR DISCHARGE
OPERATION
SIZE
INDOOR UNIT
OUTDOOR UNIT
Btu/h26000 / <26000>30000 / <30000>
W7620/ <7620>8790 / <8790>
W
A12.6 / <4.7>14.5 / <3.6>
V/Ph/Hz
W/W2.85 / <2.81>3.01 / <3.12>
HIGH
MEDIUM
LOW
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
TYPE
LIQUIDmm/in9.5 / 3/89.5 / 3/8
GASmm/in15.9 / 5/815.9 / 5/8
l/s / CFM
l/s / CFM
l/s / CFM
dBA
mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/lb
mm/in
l/s / CFM684 / 14501605 / 3400
dBA5458
mm/in
mm/in855 / 33.71030 / 40.6
mm/in328 / 12.9400 / 15.8
mm/in810 / 31.91000 / 39.4
mm/in
mm/in415 / 16.3560 / 22.1
kg/lb68 / 15095 / 209
kg/lb1.70 / 3.751.90 / 4.19
A5LC 28CA5LC 35C
2670 / <2715>2917 / <2817>
220 - 240 / 1 / 50 / <380 - 415 / 3 / 50>
R410A R410A
OUTDOOR CAP. TUBEOUTDOOR CAP. TUBE & TXV
AUTOMATIC LOUVER (UP & DOWN)
WIRELESS OR WIRED MICROCOMPUTER REMOTE CONTROL
750 / 29.5850 / 33.5
990 / 39.01200 / 47.2
A5CM 28E
302 / 640
264 / 560
217 / 460
0
56 / 51 / 44
218 / 8.6
1080 / 42.5
630 / 24.8
297 / 11.7
1197 / 47.1
740 / 29.1
28 / 62
19.1 / 3/4
FLARE VALVE
41
Page 44
GENERAL DATA - HEATPUMP (R410A)
MODEL
NOMINAL COOLING CAPACITY
NOMINAL HEATING CAPACITY
NOMINAL TOTAL INPUT POWER (COOLING)
NOMINAL TOTAL INPUT POWER (HEATING)
NOMINAL RUNNING CURRENT (COOLING)
NOMINAL RUNNING CURRENT (HEATING)
POWER SOURCE
EER
COP
REFRIGERANT TYPE
REFRIGERANT CONTROL (EXPANSION DEVICE)
CONTROL
AIR FLO W
EXTERNAL STATIC PRESSURE (H/M/L)Pa / in.wg.
SOUND PRESSURE LEVEL (H/M/L)
UNIT DIMENSION
INDOOR UNIT
PACKING
DIMENSION
UNIT WEIGHT
CONDENSATE DRAIN SIZE
AIR FLO W
SOUND PRESSURE LEVEL
UNIT DIMENSION
PACKING
DIMENSION
OUTDOOR UNIT
UNIT WEIGHT
PIPE CONNECTION
REFRIGERANT CHARGE
AIR DISCHARGE
OPERATIONWIRELESS OR WIRED MICROCOMPUTER REMOTE CONTROL
SIZE
INDOOR UNIT
OUTDOOR UNIT
HIGH
MEDIUM
LOW
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
TYPE
LIQUIDmm/in
GASmm/in
Btu/h
W
Btu/h
W
W
W
A
A
V/Ph/Hz
W/W
W/W
l/s / CFM
l/s / CFM
l/s / CFM
dBA
mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/lb
mm/in
l/s / CFM
dBA
mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/lb
kg/lb
A5CM 15ER
A5LC 15CR
12900
3780
11800
3460
1268
1138
6.0
5.1
220 - 240 / 1 / 50
2.98
3.04
R410A
OUTDOOR CAP. TUBE
AUTOMATIC LOUVER (UP & DOWN)
240 / 508
182 / 386
165 / 350
0
48 / 43 / 41
218 / 8.6
1080 / 42.5
630 / 24.8
297 / 11.7
1197 / 47.1
740 / 29.1
26
19.1 / 3/4
453 / 960
49
540 / 21.3
700 / 27.6
250 / 9.8
620 / 24.4
810 / 31.9
330 / 13.0
32 / 71
FLARE VALVE
6.4 / 1/4
12.7 / 1/2
0.83 / 1.83
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m
BELOW THE UNIT.
42
Page 45
GENERAL DATA - HEATPUMP (R410A)
MODEL
NOMINAL COOLING CAPACITY - 1Ø / <3Ø>
NOMINAL HEATING CAPACITY - 1Ø / <3Ø>
NOMINAL TOTAL INPUT POWER (COOLING) - 1Ø / <3Ø>
NOMINAL TOTAL INPUT POWER (HEATING) - 1Ø / <3Ø>
NOMINAL RUNNING CURRENT (COOLING) - 1Ø / <3Ø>
NOMINAL RUNNING CURRENT (HEATING) - 1Ø / <3Ø>
POWER SOURCE
EER - 1Ø / <3Ø>
COP - 1Ø / <3Ø>
REFRIGERANT TYPE
REFRIGERANT CONTROL (EXPANSION DEVICE)
CONTROL
AIR FLO W
EXTERNAL STATIC PRESSURE (H/M/L)Pa / in.wg.00
SOUND PRESSURE LEVEL (H/M/L)
UNIT DIMENSION
INDOOR UNIT
PACKING
DIMENSION
UNIT WEIGHT
CONDENSATE DRAIN SIZE
AIR FLO W
SOUND PRESSURE LEVEL
UNIT DIMENSION
PACKING
DIMENSION
OUTDOOR UNIT
UNIT WEIGHT
PIPE CONNECTION
REFRIGERANT CHARGE
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m
BELOW THE UNIT.
AIR DISCHARGE
OPERATION
SIZE
INDOOR UNIT
OUTDOOR UNIT
Btu/h17500 / <18100>20000 / <26000>
W5130 / <5300>5860 / <6700>
Btu/h
W5420 / <5500>6450 / <6800>
W1723 / <1757>1973 / <2231>
W
A
A6.6 / <2.8>9.1 / <4.0>
V/Ph/Hz
W/W
W/W3.63 / <3.60>3.22 / <3.20>
HIGH
MEDIUM
LOW
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
TYPE
LIQUIDmm/in6.4 / 1/46.4 / 1/4
GASmm/in12.7 / 1/215.9 / 5/8
l/s / CFM245 / 520274 / 580
l/s / CFM
l/s / CFM
dBA48 / 46 / 4350 / 47 / 46
mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/lb
mm/in
l/s / CFM
dBA5252
mm/in
mm/in855 / 33.7855 / 33.7
mm/in328 / 12.9328 / 12.9
mm/in
mm/in
mm/in415 / 16.3415 / 16.3
kg/lb59 / 13062 / 137
kg/lb
A5CM 20 ERA5CM 25 ER
A5LC 20CRA5LC 25CR
18500 / <18770>22000 / <23200>
1493 / <1527>2003 / <2124>
7.6 / <3.3>8.9 / <4.2>
220 - 240 / 1 / 50 / <380 - 415 / 3 / 50>
2.98 / <3.02>2.97 / <3.00>
R410A
OUTDOOR CAP. TUBE
AUTOMATIC LOUVER (UP & DOWN)
WIRELESS OR WIRED MICROCOMPUTER REMOTE CONTROL
217 / 460250 / 530
192 / 406231 / 490
218 / 8.6
1080 / 42.5
630 / 24.8
297 / 11.7
1197 / 47.1
740 / 29.1
27 / 60
19.1 / 3/4
614 / 1300689 / 1460
648 / 25.5750 / 29.5
810 / 31.9810 / 31.9
990 / 39.0990 / 39.0
FLARE VALVE
1.40 / 3.091.65 / 3.64
43
Page 46
GENERAL DATA - HEATPUMP (R410A)
MODEL
NOMINAL COOLING CAPACITY - 1Ø / <3Ø>
NOMINAL HEATING CAPACITY - 1Ø / <3Ø>
NOMINAL TOTAL INPUT POWER (COOLING) - 1Ø / <3Ø>
NOMINAL TOTAL INPUT POWER (HEATING) - 1Ø / <3Ø>
NOMINAL RUNNING CURRENT (COOLING) - 1Ø / <3Ø>
NOMINAL RUNNING CURRENT (HEATING) - 1Ø / <3Ø>
POWER SOURCE
EER - 1Ø / <3Ø>
COP - 1Ø / <3Ø>
REFRIGERANT TYPE
REFRIGERANT CONTROL (EXPANSION DEVICE)
CONTROL
AIR FLO W
EXTERNAL STATIC PRESSURE (H/M/L)Pa / in.wg.
SOUND PRESSURE LEVEL (H/M/L)
UNIT DIMENSION
INDOOR UNIT
PACKING
DIMENSION
UNIT WEIGHT
CONDENSATE DRAIN SIZE
AIR FLO W
SOUND PRESSURE LEVEL
UNIT DIMENSION
PACKING
DIMENSION
OUTDOOR UNIT
UNIT WEIGHT
PIPE CONNECTION
REFRIGERANT CHARGE
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m
BELOW THE UNIT.
AIR DISCHARGE
OPERATION
SIZE
INDOOR UNIT
OUTDOOR UNIT
Btu/h26000 / <26000>30000 / <30000>
W7620 / <7620>8790 / <8790>
Btu/h
W7770 / <7770>9090 / <9090>
W2670 / <2715>2917 / <2817>
W
A
A11.7 / <4.3>13.6 / <3.4>
V/Ph/Hz
W/W
W/W3.21 / <3.27>3.27 / <3.41>
HIGH
MEDIUM
LOW
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
DEPTH
TYPE
LIQUIDmm/in9.5 / 3/89.5 / 3/8
GASmm/in15.9 / 5/815.9 / 5/8
l/s / CFM
l/s / CFM
l/s / CFM
dBA
mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/lb
mm/in
l/s / CFM
dBA5458
mm/in
mm/in855 / 33.71030 / 40.6
mm/in328 / 12.9400 / 15.8
mm/in
mm/in
mm/in415 / 16.3560 / 22.1
kg/lb68 / 15095 / 209
kg/lb
A5LC 28CRA5LC 35CR
26500 / <26500>31000 / <31000>
2420 / <2378>2777 / <2667>
12.6 / <4.7>14.5 / <3.6>
220 - 240 / 1 / 50 / <380 - 415 / 3 / 50>
2.85 / <2.81>3.01 / <3.12>
R410A R410A
OUTDOOR CAP. TUBEOUTDOOR CAP. TUBE & TXV
AUTOMATIC LOUVER (UP & DOWN)
WIRELESS OR WIRED MICROCOMPUTER REMOTE CONTROL
684 / 14501605 / 3400
750 / 29.5850 / 33.5
810 / 31.91000 / 39.4
990 / 39.01200 / 47.2
1.70 / 3.751.90 / 4.19
A5CM 28ER
302 / 640
264 / 560
217 / 460
0
56 / 51 / 44
218 / 8.6
1080 / 42.5
630 / 24.8
297 / 11.7
1197 / 47.1
740 / 29.1
28 / 62
19.1 / 3/4
FLARE VALVE
44
Page 47
COMPONENTS DATA (R22)
MODEL
INDOOR FAN
INDOOR FAN
MOTOR
OUTDOOR FAN MATERIAL
OUTDOOR FAN
MOTOR
COMPRESSOR
INDOOR COIL
OUTDOOR COIL
AIR QUALITYFILTER
CASING
INDOOR UNIT
OUTDOOR UNIT
TYPE
QUANTITY
MATERIAL
DRIVE
DIAMETER
LENGTH
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
QUANTITY
DRIVE
DIAMETER
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
OIL TYPE
OIL AMOUNT
MATERIAL
TUBE
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FIN
FACE AREA
ROW
FIN PER INCH
MATERIAL
TUBE
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FIN
FACE AREA
ROW
FIN PER INCH
TYPE
QUANTITY
LENGTHmm/in
SIZE
WIDTHmm/in
THICKNESSmm/in
INDOOR UNIT
OUTDOOR UNIT
mm/in
mm/in
mm/in
3
/ fl.oz.
cm
mm/in
mm/in
mm/in
2
2
/ft
m
mm/in
mm/in
mm/in
2
2
/ft
m
pc
MATERIAL
FINISHING
COLOUR
MATERIAL
FINISHING
COLOUR
ACM 15E
ALC 15C
CROSS FLOW
2
ABS
DIRECT
146 / 5.75
200 / 7.87
INDUCTION
1
N/A
PROPELLER
1
GLASS REINFORCED ACRYL STYRENE RESIN
DIRECT
404 / 16
INDUCTION
1
IP54
ROTARY
ATMOS M60 or SUNISO 4GDID
350 / 11.8
SEAMLESS INNER GROOVE COPPER
7.00 / 0.276
0.28 / 0.011
ALUMINIUM (SLIT FIN)
0.11 / 0.0043
0.27 / 2.90
2
16
SEAMLESS INNER GROOVE COPPER
7.00 / 0.276
0.28 / 0.011
ALUMINIUM (RAISE LANCE)
0.10 / 0.004
0.36 / 3.88
1
20
WASHABLE SARANET FILTER
2
309.20 / 12.17
383.00 / 15.08
2.25 / 0.09
PS
ETCHING SURFACE
LIGHT GREY
GALVANISED MILD STEEL
POLYESTER POWDER
LIGHT GREY
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
45
Page 48
COMPONENTS DATA (R22)
MODEL
INDOOR UNIT
OUTDOOR UNIT
ALC 18CALC 20C
TYPE
QUANTITY
INDOOR FAN
INDOOR FAN
MOTOR
MATERIAL
DRIVE
DIAMETER
LENGTH
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
mm/in
mm/in
TYPE
QUANTITY
OUTDOOR FAN MATERIAL
GLASS REINFORCED ACRYL STYRENE RESIN
DRIVE
OUTDOOR FAN
MOTOR
DIAMETER
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
mm/in
TYPE
COMPRESSOR
INDOOR COIL
OIL TYPE
OIL AMOUNT
MATERIAL
TUBE
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FIN
FACE AREA
cm
3
/ fl.oz.
mm/in
mm/in
mm/in
2
/ft
m
ATMOS NM56M or SUNISO 4GDID
SEAMLESS INNER GROOVE COPPER
2
ROW
FIN PER INCH
SEAMLESS INNER GROOVE COPPER
ALUMINIUM (RAISE LANCE)
12
2024
WASHABLE SARANET FILTER
TUBE
OUTDOOR COIL
FIN
AIR QUALITYFILTER
MATERIAL
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FACE AREA
ROW
FIN PER INCH
TYPE
QUANTITY
LENGTHmm/in
SIZE
WIDTHmm/in
mm/in
mm/in
mm/in
2
/ft
m
pc
2
THICKNESSmm/in
MATERIAL
INDOOR UNIT
CASING
OUTDOOR UNIT
FINISHING
COLOUR
MATERIAL
FINISHING
GALVANISED MILD STEEL
COLOUR
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
ACM 20E
CROSS FLOW
2
ABS
DIRECT
146 / 5.75
200 / 7.87
INDUCTION
1
N/A
PROPELLER
1
DIRECT
457 / 18
INDUCTION
1
IP54
ROTARY
670 / 23.6
7.00 / 0.276
0.28 / 0.011
ALUMINIUM (SLIT FIN)
0.11 / 0.0043
0.27 / 2.90
2
18
7.00 / 0.276
0.28 / 0.011
0.10 / 0.004
0.52 / 5.59
2
309.20 / 12.17
383.00 / 15.08
2.25 / 0.09
PS
ETCHING SURFACE
LIGHT GREY
POLYESTER POWDER
LIGHT GREY
46
Page 49
COMPONENTS DATA (R22)
MODEL
INDOOR FAN
INDOOR FAN
MOTOR
OUTDOOR FAN MATERIAL
OUTDOOR FAN
MOTOR
COMPRESSOR
INDOOR COIL
OUTDOOR COIL
AIR Q UALI TY
CASING
INDOOR UNIT
OUTDOOR UNIT
TYPE
QUANTITY
MATERIAL
DRIVE
DIAMETER
LENGTH
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
QUANTITY
DRIVE
DIAMETER
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
OIL TYPE
OIL AMOUNT
MATERIAL
TUBE
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FIN
FACE AREA
ROW
FIN PER INCH
MATERIAL
TUBE
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FIN
FACE AREA
ROW
FIN PER INCH
TYPE
QUANTITY
FILTER
LENGTHmm/in
SIZE
WIDTHmm/in
THICKNESSmm/in
INDOOR UNIT
OUTDOOR UNIT
mm/in
mm/in
mm/in
3
cm
/ fl.oz.
mm/in
mm/in
mm/in
2
2
/ft
m
mm/in
mm/in
mm/in
2
2
/ft
m
pc
MATERIAL
FINISHING
COLOUR
MATERIAL
FINISHING
COLOUR
ACM 25E
ALC 25C
CROSS FLOW
2
ABS
DIRECT
146 / 5.75
200 / 7.87
INDUCTION
1
N/A
PROPELLER
1
GLASS REINFORCED ACRYL STYRENE RESIN
DIRECT
457 / 18
INDUCTION
1
IP54
ROTARY
ATMOS NM56M or SUNISO 4GDID
700 / 24.6
SEAMLESS INNER GROOVE COPPER
7.00 / 0.276
0.28 / 0.011
ALUMINIUM (SLIT FIN)
0.11 / 0.0043
0.27 / 2.90
3
18
SEAMLESS INNER GROOVE COPPER
7.00 / 0.276
0.28 / 0.011
ALUMINIUM (RAISE LANCE)
0.10 / 0.004
0.62 / 6.67
2
18
WASHABLE SARANET FILTER
2
309.20 / 12.17
383.00 / 15.08
2.25 / 0.09
PS
ETCHING SURFACE
LIGHT GREY
GALVANISED MILD STEEL
POLYESTER POWDER
LIGHT GREY
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
47
Page 50
COMPONENTS DATA (R22)
MODEL
INDOOR UNIT
OUTDOOR UNIT
ALC 28CALC 30C
TYPE
QUANTITY
INDOOR FAN
INDOOR FAN
MOTOR
MATERIAL
DRIVE
DIAMETER
LENGTH
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
mm/in
mm/in
TYPE
QUANTITY
OUTDOOR FAN MATERIAL
GLASS REINFORCED ACRYL STYRENE RESIN
DRIVE
OUTDOOR FAN
MOTOR
COMPRESSOR
INDOOR COIL
DIAMETER
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
OIL TYPE
OIL AMOUNT
MATERIAL
TUBE
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FIN
FACE AREA
mm/in457 / 18609.6 / 24
IP54-
ROTARYSCROLL
ATMOS M60 or SUNISO 4GDIDMINERAL (Sontex 200 LT)
cm
3
/ fl.oz.
1130 / 39.81240 / 43.6
SEAMLESS INNER GROOVE COPPER
mm/in
mm/in
mm/in
2
2
/ft
m
ROW
FIN PER INCH
SEAMLESS INNER GROOVE COPPER
ALUMINIUM (SLIT FIN)ALUMINIUM (SLIT FIN)
0.12 / 0.0050.12 / 0.005
2
0.61 / 6.520.87 / 9.33
21
1816
WASHABLE SARANET FILTER
OUTDOOR COIL
AIR Q UALI TY
TUBE
FIN
FILTER
MATERIAL
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FACE AREA
ROW
FIN PER INCH
TYPE
QUANTITY
LENGTHmm/in
SIZE
WIDTHmm/in
mm/in9.52 / 3/89.52 / 3/8
mm/in0.33 / 0.0130.35 / 0.014
mm/in
2
/ft
m
pc
THICKNESSmm/in
MATERIAL
INDOOR UNIT
CASING
OUTDOOR UNIT
FINISHING
COLOUR
MATERIAL
FINISHING
GALVANISED MILD STEEL
COLOUR
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
ACM 28E
CROSS FLOW
2
ABS
DIRECT
146 / 5.75
200 / 7.87
INDUCTION
1
N/A
PROPELLER
1
DIRECT
INDUCTION
1
7.00 / 0.276
0.28 / 0.011
ALUMINIUM (SLIT FIN)
0.11 / 0.0043
0.27 / 2.90
3
18
2
309.20 / 12.17
383.00 / 15.08
2.25 / 0.09
PS
ETCHING SURFACE
LIGHT GREY
POLYESTER POWDER
LIGHT GREY
SEAMLESS COPPER
48
Page 51
COMPONENTS DATA (R22)
MODEL
INDOOR FAN
INDOOR FAN
MOTOR
OUTDOOR FAN MATERIAL
OUTDOOR FAN
MOTOR
COMPRESSOR
INDOOR COIL
OUTDOOR COIL
AIR Q UALI TY
CASING
INDOOR UNIT
OUTDOOR UNIT
TYPE
QUANTITY
MATERIAL
DRIVE
DIAMETER
LENGTH
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
QUANTITY
DRIVE
DIAMETER
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
OIL TYPE
OIL AMOUNT
MATERIAL
TUBE
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FIN
FACE AREA
ROW
FIN PER INCH
MATERIAL
TUBE
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FIN
FACE AREA
ROW
FIN PER INCH
TYPE
QUANTITY
FILTER
LENGTHmm/in
SIZE
WIDTHmm/in
THICKNESSmm/in
INDOOR UNIT
OUTDOOR UNIT
mm/in
mm/in
mm/in
3
cm
/ fl.oz.
mm/in
mm/in
mm/in
2
2
/ft
m
mm/in
mm/in
mm/in
2
2
/ft
m
pc
MATERIAL
FINISHING
COLOUR
MATERIAL
FINISHING
COLOUR
ACM 15E R
ALC 15CR
CROSS FLOW
2
ABS
DIRECT
146 / 5.75
200 / 7.87
INDUCTION
1
N/A
PROPELLER
1
GLASS REINFORCED ACRYL STYRENE RESIN
DIRECT
404 / 16
INDUCTION
1
IP54
ROTARY
ATMOS M60 or SUNISO 4GDID
350 / 11.8
SEAMLESS INNER GROOVE COPPER
7.00 / 0.276
0.28 / 0.011
ALUMINIUM (SLIT FIN)
0.11 / 0.0043
0.27 / 2.90
2
16
SEAMLESS INNER GROOVE COPPER
7.00 / 0.276
0.28 / 0.011
ALUMINIUM (RAISE LANCE)
0.10 / 0.004
0.36 / 3.88
1
20
WASHABLE SARANET FILTER
2
309.20 / 12.17
383.00 / 15.08
2.25 / 0.09
PS
ETCHING SURFACE
LIGHT GREY
GALVANISED MILD STEEL
POLYESTER POWDER
LIGHT GREY
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
49
Page 52
COMPONENTS DATA (R22)
MODEL
INDOOR FAN
INDOOR FAN
MOTOR
OUTDOOR FAN MATERIAL
OUTDOOR FAN
MOTOR
COMPRESSOR
INDOOR COIL
OUTDOOR COIL
AIR Q UALI TY
CASING
INDOOR UNIT
OUTDOOR UNIT
TYPE
QUANTITY
MATERIAL
DRIVE
DIAMETER
LENGTH
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
QUANTITY
DRIVE
DIAMETER
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
OIL TYPE
OIL AMOUNT
MATERIAL
TUBE
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FIN
FACE AREA
ROW
FIN PER INCH
MATERIAL
TUBE
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FIN
FACE AREA
ROW
FIN PER INCH
TYPE
QUANTITY
FILTER
LENGTHmm/in
SIZE
WIDTHmm/in
THICKNESSmm/in
INDOOR UNIT
OUTDOOR UNIT
mm/in
mm/in
mm/in
3
cm
/ fl.oz.
mm/in
mm/in
mm/in
2
2
/ft
m
mm/in
mm/in
mm/in
2
2
/ft
m
pc
MATERIAL
FINISHING
COLOUR
MATERIAL
FINISHING
COLOUR
ACM 20E R
ALC 18CRALC 20CR
CROSS FLOW
2
ABS
DIRECT
146 / 5.75
200 / 7.87
INDUCTION
1
N/A
PROPELLER
1
GLASS REINFORCED ACRYL STYRENE RESIN
DIRECT
457 / 18.0
INDUCTION
1
IP54
ROTARY
ATMOS NM56M or SUNISO 4GDID
670 / 23.6
SEAMLESS INNER GROOVE COPPER
7.00 / 0.276
0.28 / 0.011
ALUMINIUM (SLIT FIN)
0.11 / 0.0043
0.27 / 2.90
2
18
SEAMLESS INNER GROOVE COPPER
7.00 / 0.276
0.28 / 0.011
ALUMINIUM (RAISE LANCE)
0.10 / 0.004
0.52 / 5.59
12
2024
WASHABLE SARANET FILTER
2
309.20 / 12.17
383.00 / 15.08
2.25 / 0.09
PS
ETCHING SURFACE
LIGHT GREY
GALVANISED MILD STEEL
POLYESTER POWDER
LIGHT GREY
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
50
Page 53
COMPONENTS DATA (R22)
MODEL
INDOOR UNIT
OUTDOOR UNIT
TYPE
QUANTITY
INDOOR FAN
INDOOR FAN
MOTOR
MATERIAL
DRIVE
DIAMETER
LENGTH
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
mm/in
mm/in
TYPE
QUANTITY
OUTDOOR FAN MATERIAL
GLASS REINFORCED ACRYL SYRENE RESIN
DRIVE
OUTDOOR FAN
MOTOR
DIAMETER
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
mm/in
TYPE
COMPRESSOR
INDOOR COIL
OIL TYPE
OIL AMOUNT
MATERIAL
TUBE
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FIN
FACE AREA
cm
3
/ fl.oz.
mm/in
mm/in
mm/in
2
/ft
m
ATMOS NM56M or SUNISO 4GDID
SEAMLESS INNER GROOVE COPPER
2
ROW
FIN PER INCH
SEAMLESS INNER GROOVE COPPER
ALUMINIUM (RAISE LANCE)
OUTDOOR COIL
TUBE
FIN
MATERIAL
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FACE AREA
mm/in
mm/in
mm/in
2
m
/ft
2
ROW
FIN PER INCH
WASHABLE SARANET FILTER
AIR Q UALI TY
FILTER
TYPE
QUANTITY
LENGTHmm/in
SIZE
WIDTHmm/in
pc
THICKNESSmm/in
MATERIAL
INDOOR UNIT
CASING
OUTDOOR UNIT
FINISHING
COLOUR
MATERIAL
FINISHING
COLOUR
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
ACM 25E R
ALC 25CR
CROSS FLOW
2
ABS
DIRECT
146 / 5.75
200 / 7.87
INDUCTION
1
N/A
PROPELLER
1
DIRECT
457 / 18
INDUCTION
1
IP54
ROTARY
700 / 24.6
7.00 / 0.276
0.28 / 0.011
ALUMINIUM (SLIT FIN)
0.11 / 0.0043
0.27 / 2.90
3
18
7.00 / 0.276
0.28 / 0.011
0.10 / 0.004
0.62 / 6.67
2
18
2
309.20 / 12.17
383.00 / 15.08
2.25 / 0.09
PS
ETCHING SURFACE
LIGHT GREY
GALVANISED MILD STEEL
POLYESTER POWDER
LIGHT GREY
51
Page 54
COMPONENTS DATA (R22)
MODEL
INDOOR FAN
INDOOR FAN
MOTOR
OUTDOOR FAN MATERIAL
OUTDOOR FAN
MOTOR
COMPRESSOR
INDOOR COIL
OUTDOOR COIL
AIR Q UALI TY
CASING
INDOOR UNIT
OUTDOOR UNIT
TYPE
QUANTITY
MATERIAL
DRIVE
DIAMETER
LENGTH
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
QUANTITY
DRIVE
DIAMETER
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
OIL TYPE
OIL AMOUNT
MATERIAL
TUBE
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FIN
FACE AREA
ROW
FIN PER INCH
MATERIAL
TUBE
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FIN
FACE AREA
ROW
FIN PER INCH
TYPE
QUANTITY
FILTER
LENGTHmm/in
SIZE
WIDTHmm/in
THICKNESSmm/in
INDOOR UNIT
OUTDOOR UNIT
ACM 28E R
ALC 28CRALC 30CR
CROSS FLOW
2
ABS
DIRECT
mm/in
mm/in
146 / 5.75
200 / 7.87
INDUCTION
1
N/A
PROPELLER
1
GLASS REINFORCED ACRYL STYRENE RESIN
DIRECT
mm/in457 / 18609.6 / 24
INDUCTION
1
IP54-
ROTARYSCROLL
ATMOS M60 or SUNISO 4GDIDMINERAL (Sontex 200 LT)
cm
3
/ fl.oz.
1130 / 39.81240 / 43.6
SEAMLESS INNER GROOVE COPPER
mm/in
mm/in
7.00 / 0.276
0.28 / 0.011
ALUMINIUM (SLIT FIN)
mm/in
2
/ft
m
2
0.11 / 0.0043
0.27 / 2.90
3
18
SEAMLESS INNER GROOVE COPPER
SEAMLESS COPPER
mm/in9.52 / 3/89.52 / 3/8
mm/in0.33 / 0.0130.35 / 0.014
ALUMINIUM (SLIT FIN)ALUMINIUM (CORR. FIN)
mm/in0.12 / 0.0050.12 / 0.005
2
2
m
/ft
0.61 / 6.520.87 / 9.33
22
1816
WASHABLE SARANET
pc
2
309.20 / 12.17
383.00 / 15.08
2.25 / 0.09
MATERIAL
FINISHING
COLOUR
MATERIAL
FINISHING
COLOUR
ETCHING SURFACE
GALVANISED MILD STEEL
POLYESTER POWDER
PS
LIGHT GREY
LIGHT GREY
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
52
Page 55
COMPONENTS DATA (R410A)
MODEL
INDOOR FAN
INDOOR FAN
MOTOR
OUTDOOR FAN MATERIAL
OUTDOOR FAN
MOTOR
COMPRESSOR
INDOOR COIL
OUTDOOR COIL
AIR QUALITYFILTER
CASING
INDOOR UNIT
OUTDOOR UNIT
TYPE
QUANTITY
MATERIAL
DRIVE
DIAMETER
LENGTH
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
QUANTITY
DRIVE
DIAMETER
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
OIL TYPE
OIL AMOUNT
MATERIAL
TUBE
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FIN
FACE AREA
ROW
FIN PER INCH
MATERIAL
TUBE
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FIN
FACE AREA
ROW
FIN PER INCH
TYPE
QUANTITY
LENGTHmm/in
SIZE
WIDTHmm/in
THICKNESSmm/in
INDOOR UNIT
OUTDOOR UNIT
mm/in
mm/in
mm/in
3
cm
/ fl.oz.
mm/in
mm/in
mm/in
2
2
/ft
m
mm/in
mm/in
mm/in
2
2
/ft
m
pc
MATERIAL
FINISHING
COLOUR
MATERIAL
FINISHING
COLOUR
A5CM 15E
A5LC 15C
CROSS FLOW
2
ABS
DIRECT
146 / 5.75
200 / 7.87
INDUCTION
1
N/A
PROPELLER
1
GLASS REINFORCED ACRYL STYRENE RESIN
DIRECT
404 / 16
INDUCTION
1
IP54
ROTARY
RB68A or Freol Alpha68M
430 / 15.1
SEAMLESS INNER GROOVE COPPER
7.00 / 0.276
0.28 / 0.011
ALUMINIUM (SLIT FIN)
0.11 / 0.0043
0.26 / 2.90
2
16
SEAMLESS INNER GROOVE COPPER
7.00 / 0.276
0.28 / 0.011
ALUMINIUM (RAISE LANCE)
0.10 / 0.004
0.360 / 3.940
1
20
WASHABLE SARANET FILTER
2
309.20 / 12.17
383.00 / 15.08
2.25 / 0.09
PS
ETCHING SURFACE
LIGHT GREY
GALVANISED MILD STEEL
POLYESTER POWDER
LIGHT GREY
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
53
Page 56
COMPONENTS DATA (R410A)
MODEL
INDOOR UNIT
OUTDOOR UNIT
TYPE
QUANTITY
INDOOR FAN
INDOOR FAN
MOTOR
MATERIAL
DRIVE
DIAMETER
LENGTH
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
mm/in
mm/in
TYPE
QUANTITY
OUTDOOR FAN MATERIAL
DRIVE
OUTDOOR FAN
MOTOR
DIAMETER
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
mm/in
TYPE
COMPRESSOR
OIL TYPE
OIL AMOUNT
cm
3
/ fl.oz.
MATERIAL
TUBE
INDOOR COIL
FIN
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FACE AREA
mm/in
mm/in
mm/in
2
/ft
m
2
ROW
FIN PER INCH
MATERIAL
TUBE
OUTDOOR COIL
FIN
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FACE AREA
mm/in
mm/in
ALUMINIUM (RAISE LANCE)ALUMINIUM (RAISE LANCE)
mm/in0.10 / 0.0040.10 / 0.004
2
2
m
/ft
ROW
FIN PER INCH
TYPE
AIR Q UALI TY
FILTER
QUANTITY
LENGTHmm/in
SIZE
WIDTHmm/in
pc
THICKNESSmm/in
MATERIAL
INDOOR UNIT
CASING
OUTDOOR UNIT
FINISHING
COLOUR
MATERIAL
FINISHING
COLOUR
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
A5CM 20EA5CM 25E
A5LC 20CA5LC 25C
CROSS FLOW
2
ABS
DIRECT
146 / 5.75
200 / 7.87
INDUCTION
1
N/A
PROPELLER
1
GLASS REINFORCED ACRYL STYRENE RESIN
DIRECT
457 / 18
INDUCTION
1
IP54
ROTARY
RB68A or Freol Alpha68M
670 / 23.61130 / 39.8
SEAMLESS INNER GROOVE COPPER
7.00 / 0.276
0.28 / 0.011
ALUMINIUM (SLIT FIN)
0.11 / 0.0043
0.27 / 2.90
3
18
SEAMLESS INNER GROOVE COPPER
7.00 / 0.276
0.28 / 0.011
0.510 / 5.4600.620 / 6.630
22
1818
WASHABLE SARANET FILTER
2
309.20 / 12.17
383.00 / 15.08
2.25 / 0.09
PS
ETCHING SURFACE
LIGHT GREY
GALVANISED MILD STEEL
POLYESTER POWDER
LIGHT GREY
54
Page 57
COMPONENTS DATA (R410A)
MODEL
INDOOR FAN
INDOOR FAN
MOTOR
OUTDOOR FAN MATERIAL
OUTDOOR FAN
MOTOR
COMPRESSOR
INDOOR COIL
OUTDOOR COIL
AIR QUALITYFILTER
CASING
INDOOR UNIT
OUTDOOR UNIT
TYPE
QUANTITY
MATERIAL
DRIVE
DIAMETER
LENGTH
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
QUANTITY
DRIVE
DIAMETER
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
OIL TYPE
OIL AMOUNT
MATERIAL
TUBE
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FIN
FACE AREA
ROW
FIN PER INCH
MATERIAL
TUBE
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FIN
FACE AREA
ROW
FIN PER INCH
TYPEWASHABLE SARANET FILTER
QUANTITY
LENGTHmm/in
SIZE
WIDTHmm/in
THICKNESSmm/in
INDOOR UNIT
OUTDOOR UNIT
A5CM 28E
A5LC 28CA5LC 35C
CROSS FLOW
2
ABS
DIRECT
mm/in
mm/in
146 / 5.75
200 / 7.87
INDUCTION
1
N/A
PROPELLER
1
GLASS REINFORCED ACRYL STYRENE RESIN
DIRECT
mm/in457 / 18609.6 / 24
INDUCTION
1
IP54N/A
ROTARYSCROLL
RB68A or Freol Alpha68MMOBIL EAL ARCTIC 22CC
cm
3
/ fl.oz.
1130 / 39.81242 / 43.7
SEAMLESS INNER GROOVE COPPER
mm/in
mm/in
7.00 / 0.276
0.28 / 0.011
ALUMINIUM (SLIT FIN)
mm/in
2
/ft
m
2
0.11 / 0.0043
0.27 / 2.90
3
18
SEAMLESS INNER GROOVE COPPER
SEAMLESS COPPER
mm/in7.00 / 0.2767.00 / 0.276
mm/in0.28 / 0.0110.28 / 0.011
ALUMINIUM (CORR. FIN)ALUMINIUM (CORR. FIN)
mm/in
2
/ft
m
2
0.11 / 0.00430.11 / 0.0043
0.620 / 6.6300.87 / 9.33
22
1818
pc
2
309.20 / 12.17
383.00 / 15.08
2.25 / 0.09
MATERIAL
FINISHING
COLOUR
MATERIAL
FINISHING
COLOUR
ETCHING SURFACE
GALVANISED MILD STEEL
POLYESTER POWDER
PS
LIGHT GREY
LIGHT GREY
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
55
Page 58
COMPONENTS DATA (R410A)
MODEL
INDOOR UNIT
OUTDOOR UNIT
TYPE
QUANTITY
INDOOR FAN
INDOOR FAN
MOTOR
MATERIAL
DRIVE
DIAMETER
LENGTH
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
mm/in
mm/in
TYPE
QUANTITY
OUTDOOR FAN MATERIAL
GLASS REINFORCED ACRYL STYRENE RESIN
DRIVE
OUTDOOR FAN
MOTOR
DIAMETER
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
mm/in
TYPE
COMPRESSOR
INDOOR COIL
OIL TYPE
OIL AMOUNT
MATERIAL
TUBE
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FIN
FACE AREA
cm
3
/ fl.oz.
mm/in
mm/in
mm/in
2
/ft
m
SEAMLESS INNER GROOVE COPPER
2
ROW
FIN PER INCH
SEAMLESS INNER GROOVE COPPER
OUTDOOR COIL
TUBE
FIN
MATERIAL
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FACE AREA
mm/in
mm/in
mm/in
2
/ft
m
2
ROW
FIN PER INCH
AIR Q UALI TY
FILTER
TYPE
QUANTITY
LENGTHmm/in
SIZE
WIDTHmm/in
pc
WASHABLE SARANET FILTER
THICKNESSmm/in
MATERIAL
INDOOR UNIT
CASING
OUTDOOR UNIT
FINISHING
COLOUR
MATERIAL
FINISHING
COLOUR
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
A5CM 15ER
A5LC 15CR
CROSS FLOW
2
ABS
DIRECT
146 / 5.75
200 / 7.87
INDUCTION
1
N/A
PROPELLER
1
DIRECT
404 / 16
INDUCTION
1
IP54
ROTARY
RB68A or Freol Alpha68M
430 / 15.1
7.00 / 0.276
0.28 / 0.011
ALUMINIUM (SLIT FIN)
0.11 / 0.0043
0.26 / 2.90
2
16
7.00 / 0.276
0.28 / 0.011
ALUMINIUM (RAISE LANCE)
0.10 / 0.004
0.360 / 3.940
1
20
2
309.20 / 12.17
383.00 / 15.08
2.25 / 0.09
PS
ETCHING SURFACE
LIGHT GREY
GALVANISED MILD STEEL
POLYESTER POWDER
LIGHT GREY
56
Page 59
COMPONENTS DATA (R410A)
MODEL
INDOOR FAN
INDOOR FAN
MOTOR
OUTDOOR FAN MATERIAL
OUTDOOR FAN
MOTOR
COMPRESSOR
INDOOR COIL
OUTDOOR COIL
AIR QUAL ITYFILTE R
CASING
INDOOR UNIT
OUTDOOR UNIT
TYPE
QUANTITY
MATERIAL
DRIVE
DIAMETER
LENGTH
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
QUANTITY
DRIVE
DIAMETER
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
TYPE
OIL TYPE
OIL AMOUNT
MATERIAL
TUBE
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FIN
FACE AREA
ROW
FIN PER INCH
MATERIAL
TUBE
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FIN
FACE AREA
ROW
FIN PER INCH
TYPE
QUANTITY
LENGTHmm/in
SIZE
WIDTHmm/in
THICKNESSmm/in
INDOOR UNIT
OUTDOOR UNIT
mm/in
mm/in
mm/in
3
cm
/ fl.oz.
mm/in
mm/in
mm/in
2
2
m
/ft
mm/in
mm/in
mm/in
2
2
/ft
m
pc
MATERIAL
FINISHING
COLOUR
MATERIAL
FINISHING
COLOUR
A5CM 20ERA5CM 25ER
A5LC 20CRA5LC 25CR
CROSS FLOW
2
ABS
DIRECT
146 / 5.75
200 / 7.87
INDUCTION
1
N/A
PROPELLER
1
GLASS REINFORCED ACRYL SYRENE RESIN
DIRECT
457 / 18
INDUCTION
1
IP54
ROTARY
RB68A or Freol Alpha68M
670 / 23.61130 / 39.8
SEAMLESS INNER GROOVE COPPER
7.00 / 0.276
0.28 / 0.011
ALUMINIUM (SLIT FIN)
0.11 / 0.0043
0.27 / 2.90
3
18
SEAMLESS INNER GROOVE COPPER
7.00 / 0.276
0.28 / 0.011
ALUMINIUM (RAISE LANCE)ALUMINIUM (RAISE LANCE)
0.10 / 0.0040.10 / 0.004
0.510 / 5.4600.620 / 6.630
22
1818
WASHABLE SARANET FILTER
2
309.20 / 12.17
383.00 / 15.08
2.25 / 0.09
PS
ETCHING SURFACE
LIGHT GREY
GALVANISED MILD STEEL
POLYESTER POWDER
LIGHT GREY
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
57
Page 60
COMPONENTS DATA (R410A)
MODEL
INDOOR UNIT
OUTDOOR UNIT
A5LC 28CRA5LC 35CR
TYPE
Q'TY
INDOOR FAN
INDOOR FAN
MOTOR
MATERIAL
DRIVE
DIAMETER
LENGTH
TYPE
Q'TY
INDEX OF PROTECTION (IP)
mm/in
mm/in
TYPE
Q'TY
OUTDOOR FAN MATERIAL
GLASS REINFORCED ACRYL STYRENE RESIN
DRIVE
OUTDOOR FAN
MOTOR
COMPRESSOR
INDOOR COIL
DIAMETER
TYPE
Q'TY
INDEX OF PROTECTION (IP)
TYPE
OIL TYPE
OIL AMOUNT
MATERIAL
TUBE
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FIN
FACE AREA0.27 / 2.90
mm/in457 / 18609.6 / 24
IP54-
ROTARYSCROLL
RB68A or Freol Alpha68MMOBIL EAL ARCTIC 22CC
cm
3
/ fl.oz.
1130 / 39.81242 / 43.7
SEAMLESS INNER GROOVE COPPER
mm/in
mm/in
mm/in
2
2
/ft
m
ROW
FIN PER INCH
SEAMLESS INNER GROOVE COPPER
ALUMINIUM (CORR. FIN)ALUMINIUM (CORR. FIN)
0.11 / 0.00430.11 / 0.0043
2
0.620 / 6.6300.87 / 9.33
22
1818
WASHABLE SARANET FILTER
OUTDOOR COIL
AIR Q UALI TY
MATERIAL
TUBEDIAMETER
THICKNESS
MATERIAL
THICKNESS
FIN
FACE AREA
ROW
FIN PER INCH
TYPE
QUANTITY
FILTER
LENGTHmm/in
SIZE
WIDTHmm/in
mm/in7.00 / 0.2767.00 / 0.276
mm/in0.28 / 0.0110.28 / 0.011
mm/in
2
/ft
m
pc
THICKNESSmm/in
MATERIAL
INDOOR UNIT
CASING
OUTDOOR UNIT
FINISHING
COLOUR
MATERIAL
FINISHING
COLOUR
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
62
Page 65
6. PERFORMANCE DATA
Interpolation and Extrapolation method can be used to get the total capacity, Q and sensible capacity, SC at
those temperatures which are not stated out in the table.
Example:
Model: ACM 15E / ALC 15C
Indoor Condition: 23°C DB, 15°C WB
Outdoor Condition: 37°C DB
Solution:
Overall
Based on the Performance table in page 67,
1. Refer to the Indoor DB column,
-23°C is located between 20°C and 24°C (Thus, Interpolation need to be applied)
2. Refer to the Indoor WB column,
-15°C only available in the case of Indoor DB = 20°C. (Thus, Extrapolation between 16°C WB
and 17°C WB during 24°C indoor DB is required)
3. Refer to the Outdoor DB column,
-37°C is located between 35°C and 40°C. (Thus, Interpolation need to be applied)
Please follow the steps below in order to get the required capacity.
1st Step
Extrapolation of Indoor WB
Find TC, SC for
(a) Indoor : 24°C DB, 15°C WB
Outdoor : 35°C DB
(b) Indoor : 24°C DB, 15°C WB
Outdoor : 40°C DB
2nd Step
Interpolation of Indoor DB
Find TC, SC for
(a) Indoor : 23°C DB, 15°C WB
Outdoor : 35°C DB
(b) Indoor : 23°C DB, 15°C WB
Outdoor : 40°C DB
3rd Step
Interpolation of Outdoor DB
Find TC, SC for
(a) Indoor : 23°C DB, 15°C WB
Outdoor : 37°C DB
63
Page 66
Details:
1st Step:
To obtain the Total capacity and Sensible capacity for
(a) Indoor Condition: 24°C DB, 15°C WB
Outdoor Condition: 35°C DB
Outdoor DB ° C
Indoor DBIndoor WB35
° C° CTC (kW)SC (kW)
15x
1
y
1
24163.3632.381
173.4312.288
Total capacity, TC
x1 = 3.295kW (Same as Total capacity at 20°C Indoor DB / 15°C Indoor WB & 35°C Outdoor WB)*
⇒
Sensible capacity, SC
Extrapolation Method:
17°C - 15°C
⇒
2.288kW - y
=
1
17°C - 16°C 2.288kW - 2.381kW
⇒ y1 = 2.474kW
(b) Indoor Condition: 24°C DB, 15°C WB
Outdoor Condition: 40°C DB
Outdoor DB ° C
Indoor DBIndoor WB40
° C° CTC (kW)SC (kW)
15x
2
y
2
24163.0662.056
173.1371.954
Total capacity, TC
x2 = 2.995kW (Same as Total capacity at 20°C Indoor DB / 15°C Indoor WB & 40°C Outdoor WB)*
⇒
Sensible capacity, SC
Extrapolation Method:
⇒
17°C - 15°C
1.954kW - y
=
2
17°C - 16°C 1.954kW - 2.056kW
⇒ y2 = 2.158kW
* This is due to 2 different conditions with same WB temperature, will have the same level of enthalpy. For
more details, please refer to psychrometrics chart
64
Page 67
2nd Step:
To obtain the Total capacity and Sensible capacity for
x3 = 3.295kW (Same as Total capacity at 20°C Indoor DB / 15°C Indoor WB & 35°C Outdoor WB)*
⇒
Sensible capacity, SC
Interpolation Method:
⇒
24°C - 20°C = 2.474kW - 1.510kW
24°C - 23°C 2.474kW - y
3
⇒ y3 = 2.233kW
(b) Indoor Condition: 23°C DB, 15°C WB
Outdoor Condition: 40°C DB
Outdoor DB ° C
Indoor DBIndoor WB40
° C° CTC (kW)SC (kW)
20152.9951.195
2315x
4
y
4
24152.9952.158
Total capacity, TC
x4 = 2.995kW (Same as Total capacity at 20°C Indoor DB / 15°C Indoor WB & 40°C Outdoor WB)*
⇒
Sensible capacity, SC
Interpolation Method:
24°C - 20°C = 2.158kW - 1.195kW
⇒
24°C - 23°C 2.158kW - y
4
⇒ y4 = 1.917kW
* This is due to 2 different conditions with same WB temperature will have the same level of enthalpy. For
more details, please refer to psychrometrics chart
65
Page 68
3rd Step:
To obtain the Total capacity and Sensible capacity for