Acme Engineering RMD12E Installation Manual

ACME ENGINEERING &
MANUFACTURING CORP.
P.O. Box 978 Muskogee, OK 74402 Phone: 918/682-7791
Hazardous Location
Ring Fan
Model RMD
Provides heavy duty ventilation of atmospheres containing flammable or explosive vapors, gases, or dusts (per NEC
500). These fans have a heavy steel circular frame with ample mounting holes and a fixed-position motor base attached to rigid tubular supports and spark resistant aluminum fan blades.
Motors are 115 VAC, 60 Hz or 115/230 VAC), single phase Class I, group D and Class II, groups E, F, and G applications.
Performance
Model
RMD12E 12
RMD16E 16
RMD18F 18
RMD20G 20
RMD24G 24
RMD24H 24
RMD30H 30
Performance certified is for installation Type A, Free Inlet, Free Outlet. Speed (RPM) shown is nominal. Performance is based on actual speed of test. Performance ratings do not include the effects of appurtenances in the airstream. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5mm) in a hemispherical-free calculated per AMCA Standard 301. Values certified are for installation Type A, Free Inlet and Fan sone levels.
Propeller
Dia. (In.)
0.0” 0.125” 0.250” 0.375” 0.500”
800 650 360 150 1725 1/4
1890 1510 1270 1100 760 1725 1/4
2150 1750 1500 1200 900 1725 1/4
2380 1970 1700 1500 1200 1725 1/4
3600 2900 2150 1730 1100 1725 1/3
4500 3900 3350 2700 2250 1725 1/2
8270 7400 6400 5200 3900 1140 3/4
CFM Air Delivery
Motor
RPM
HP
Max
BHP
.115
.301
.288
.299
.396
.674
.750
Watts
173 13.8
352 24
337 27
349 28
483 28
776 34
844 30
Sones
5 Ft.
.000”
SP
Acme Engineering & Manufacturing Corporation certifies that the ventilators shown herein are licensed to bear the AMCAseal. The ratings shown are based on tests and procedures performed in accordance with AMCAPublication 211 and AMCA Publication 311 and comply with the requirements of the AMCA Certified Ratings Program.
EXHAUSTERS
CEILING AND CABINET
EXHAUSTERS
IN-LINE CENTRIFUGAL
FANS
IN-LINE AXIAL FANSCENTRIFUGAL
PROPELLER
ROOF FANS
ROOF VENTS
WALL FANS
PLENUM FANS
UTILITY BLOWERS
BACKWARD
INCLINED/AIRFOIL
CENTRIFUGAL FANS
SUPPLY AIR FANSPROPELLER
CENTRIFUGAL
INDUSTRIAL
EXHAUSTERS
LIMITED WARRANTY Acme Engineeringand Man ufacturing Corporation extends this limited warranty to the original purchaser and warrants that products described herein shall be free from original defects in workmanship and materials for two years from date of shipment (except forAcme’s exclusive duplexsplit pillow block bearings and shaft 5 years from ship ment, belts one year from shipment, and polyethyl ene tubingat 90 daysfrom shipping), provided same have been properly handled, stored, installed, ser viced, maintained and operated. Refer to Form MS149 for complete limited warrantyterms and con ditions. This form is available to anyone at www.acmefan.com. The Company's warranty is in lieu of all otherwarranties, express or implied, arising by law or otherwise, including without limitation the implied warrantiesof merchantability and fitnessfor a particular purpose, which are hereby expressly dis claimed claimed and waived.
ACME ENGINEERING &
MANUFACTURING CORP.
P.O. Box 978, Muskogee, Oklahoma 74402
Telephone: 918-682-7791 Fax: 918-682-0134
www.acmefan.com e-mail: acmefan@acmefan.com
-
Acme products are designed and manufactured to provide reliable performance but they are not guar anteed to be 100% free of defects. Even reliable products will experience occasional failures and this possibility should be recognized by the Purchaser and EndUser. If these products areused in alife sup port ventilation system where failure could result in
­loss or injury, the Purchaser and End User should
­provide adequate back-up ventilation, supplemen
tary natural ventilation or failure alarm system, or ac
­knowledge willingness to accept the risk of such loss
or injury.
­WARNING DO NOT use in HAZARDOUS ENVI
RONMENTS where fan’s electrical system could provide ignition to combustible or flammable materi als unless unitis specifically built for hazardous envi ronments. Comply with all local and national safety
-
codes including the National Electrical Code (NEC) and National Fire Protection Act (NFPA). Guards
Member Air Movement and Control Association International, Inc.
must be installed when fan is within reach of person
-
nel or withinseven (7) feet (2.134 m) of working level or when deemed advisable for safety.
DISCLAIMER The Company has made a diligent ef fort to illustrate and describe the products in this liter
­ature accurately; however, such illustrations and
descriptions are for the sole purpose of identification, and do not express or imply a warranty that the prod
­ucts are merchantable, or fit for aparticular purpose.
-
INDEMNITY Purchaser acknowledges various warnings by the Company regarding the products
-
and its installation and use. If the Company incurs any claims, lawsuits, settlements, or expenses (in
-
cluding attorney fees) for any loss, injury, death or
-
property damage including, but not limited to, claims arising out of the Purchaser’s or any end user ’s in stallation or use of the products, the Purchaser shall indemnify and hold the Company harmless.
July 2005 Form B223A
-
-
-
-
-
-
Loading...