Model PV belt drive fans are centrifugal power roof ventilators
designed for exhausting clean air. Capacities up to 40,608 CFM
and up to 2 inch static pressure. The aerodynamic design of the
PV impeller and orifice results in high air performance and low
sound. Typical applications for the PV includes a wide range of
commercial, institutional, and industrial facilities such as
schools, office buildings, hospitals, prisons, assembly areas,
and restaurants.
Centrifugal Exhausters
Construction Features
Housing
Hoods and housing
•
constructed of heavy
gauge aluminum
Wheel and drive assembly
•
supported by rugged steel
frame
Steel fasteners are zinc
•
dichromate plated
Heavy gauge galvanized wire birdscreen
•
Vibration Isolation
•
Centrifugal Wheel
Aluminum construction backward curved blades
•
Non-overloading design for safe operation
•
Precision balanced for smooth vibration free operation
•
Bearings
Permanently lubricated in an Acme D.S. pillow block
•
housing
Bearings are resiliently mounted in neoprene rings
•
Rated at L50life of 200,000 hours
•
5 year limited warranty on Acme D.S. pillow block
•
bearings
PV75 through PV240
DIMENSIONS
Fan
Model
PV07521.0023.6223.673.4416.5 x 16.5AR16C19.5
PV08521.0023.6223.673.4416.5 x 16.5AR16C19.5
PV10021.0023.6223.673.4416.5 x 16.5AR16C19.5
PV12021.0026.7529.384.0616.5 x 16.5AR16C19.5
PV13521.0026.7529.384.0616.5 x 16.5AR16/ARQ16C19.5
PV15024.0030.9635.145.1919.5 x 19.5AR18/ARQ18C22.5
PV16524.0030.9635.145.1919.5 x 19.5AR18/ARQ18C22.5
PV18028.0035.4039.606.1923.5 x 23.5AR22/ARQ22C26.5
PV20028.0035.4039.606.1923.5 x 23.5AR22/ARQ22C26.5
PV22034.0038.3946.497.7529.5 x 29.5AR28/ARQ28C32.5
PV24034.0038.3946.497.7529.5 x 29.5AR28/ARQ28C32.5
PV26040.0037.0053.008.7535.5 x 35.5AR34/ARQ34C38.5
PV30040.0037.0053.008.7535.5 x 35.5AR34/ARQ34C38.5
PV36546.0046.0064.009.5041.5 x 41.5ARQ40C44.5
PV42560.0050.0082.0011.5055.5 x 55.5ARQ54C58.5
PV49060.0054.0082.0015.5055.5 x 55.5ARQ54C58.5
PV54360.0057.0082.0016.5055.5 x 55.5ARQ54C58.5
Dimensions are shown in inches.
*Recommended maximum
‡ Please contact your local representative for correct rated sizing for hurricane construction
ABCE
PV260 through PV543
Roof
Opening* ‡
Damper
Model
Curb
Model ‡
Drive Assembly
• Cast iron drives sized for 150% of drive horsepower
•
Static free, oil and heat resistant belts
Motors
•
Continuous duty motors located outside the airstream
•
Motor compartment cooled by fins located on top of
impeller
•
Factory wired to junction box
Options/Accessories
•
Roof Curbs
•
Dampers
•
Coatings
•
Aluminum Birdscreen
Acme Engineering & Manufacturing Corporation certifies
that the models shown herein are licensed to bear the
AMCA seal. The ratings shown are based on tests and
procedures performed in accordance with AMCA
Publication 211 and AMCA Publication 311 and comply
with the requirements of the AMCA Certified Ratings
Program.
Page 8
U.L. 705 ListedCSA Certified
Consult your Acme representative for availability.
Performance certified is for Installation Type A: Free Inlet, Free Outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating
(BHP) does not include transmission losses. The sound ratings shown are loudness values in hemispherical sones at 1.5 m (5ft) in a hemispherical free field calculated
per AMCA Standard 301. Values shown are for Installation Type A: Free Inlet hemispherical sone levels. The brake horsepower capability of an exhauster motor is
dependent on the degree of cooling the motor receives from the air moving through the motor. The motor loading beyond the motor nameplate rating does not overheat
the motor and is in accordance with the motor manufacturer’s recommendations. It is therefore not detrimental to the motor and is economically desirable.
Performance certified is for Installation Type A: Free Inlet, Free Outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating
(BHP) does not include transmission losses. The sound ratings shown are loudness values in hemispherical sones at 1.5 m (5ft) in a hemispherical free field calculated
per AMCA Standard 301. Values shown are for Installation Type A: Free Inlet hemispherical sone levels. The brake horsepower capability of an exhauster motor is
dependent on the degree of cooling the motor receives from the air moving through the motor. The motor loading beyond the motor nameplate rating does not overheat
the motor and is in accordance with the motor manufacturer’s recommendations. It is therefore not detrimental to the motor and is economically desirable.