Page 1
Belt Drive Filtered Supply Fans
Models AFSI, AFSN and AFSL
Models AFSI, AFSN and AFSL provide a complete roof top 
package that includes the blower, washable aluminum filters 
and removable hood. These fans are designed to supply fresh, 
filtered make-up air to replace air being removed by ventilation 
systems exhausting fumes, gases and odors from building.
AFSI
AFSN
Construction Features
Housing
Constructed of heavy gauge galvanized steel
•
Designed for efficient airflow and maximum weather
•
resistance 
Pre-punched mounting holes reduce installation time
•
Platform constructed of heavy gauge galvanized steel
•
Hood
AFSN/AFSI - Constructed of heavy gauge steel
•
AFSL - Constructed of extruded aluminum louvers with
•
mitered and welded corners 
Insulated with 1” fiberglass to prevent condensation
•
Hood held in place with quick release clips allowing easy
•
access to filters and blower 
1" washable aluminum filters
•
Blower
Double width, double inlet blowers for maximum air delivery
•
at higher pressures 
Forward curved galvanized steel wheels dynamically
•
balanced for vibration free operation 
Bearing rated at L50life of 200,000 hours
•
Open dripproof motor with sealed ball bearings designed for
•
continuous operation 
Static free, oil and heat resistant belts
•
Adjustable motor pulleys for system balancing
•
Disconnect Switch
•
Standard NEMA 1 toggle switch mounted on blower housing 
sized for voltage and horsepower requirement (except 
explosion proof motors)
Utility  B lowers 
Supply Air Fans
AFSL
Acme Engineering & Manufacturing Corporation 
certifies that Models AFSN and AFSL shown 
herein are licensed to bear the AMCA seal for air 
performance. The ratings shown are based on 
tests and procedures performed in accordance 
with AMCA Publication 211 comply with the re 
quirements of the AMCA Certified Ratings Pro
AFSL
for sound performance. The ratings shown are based on tests and proce 
dures performed in accordance with AMCA Publication 311 and comply with 
the requirements of the AMCA Certified Ratings Program.
The A-weighted sound ratings shown have been calculated per AMCA Stan 
dard 301. Values shown are for [inlet Lw(A)] sound power levels for Installa
AFSN
gram.
Model AFSN also licensed to bear the AMCA seal
Options/Accessories
•
Roof Curbs
•
Dampers
•
2” Aluminum Filters
•
Side Discharge (AFSN & AFSL)
U.L. 705 Listed  CSA Certified
Consult your Acme representative for availability.
tion Type B: Free Inlet, Ducted Outlet. Ratings do not include the effects of 
duct end correction.
The application of sound ratings to various fan installations produces differ 
ent sound rating requirements. Also, some engineers have preferences for
-
-
-
-
-
the type of sound rating they want to use. For these reasons, Acme has pro 
vided two different sound rating values for the noise produced by each fan. 
They are shown in the following values:
DECIBELS this is the sound power level in decibels (db) for each of the 8 
octave bands to the reference power of 10-12 watt.
Lw(A) - is a single number sound power level in decibels adjusted to repre 
sent the affect of the “A” weighted network on each octave band.
Complete licensed sound rating data is available in Bulletin S20.
-
-
-
Page 84
Page 2
DIMENSIONS
Fan
Model
AFSI106
AFSI126
AFSI150
AFSI181
ABCRTQ
27.88 28.75 28.25 25.27 23.04  3.0
31.86 33.88 32.25 31.45 28.54  3.0
39.85 41.50 40.25 38.00 35.79  3.0
45.97 45.75 46.44 38.00 35.79  3.0
AFSI200  55.96 53.55 56.44 45.11 42.76  3.0
Dimensions are shown in inches.
DIMENSIONS
Fan
Model
AFSN106
AFSN126
AFSN150
AFSN181
AFSN200
Dimensions are shown in inches.
ABC E
27.87  26.70  39.00  11.68
31.86  35.15  44.00  16.43
39.85  39.45  52.00  18.46
45.97  50.16  61.36  20.20
55.96  58.22  77.49  28.97
AFSI
AFSN
DIMENSIONS
Fan
Model
AFSL106
AFSL126
AFSL150
AFSL181
AFSL200
Dimensions are shown in inches.
ABC E
27.87  27.04  35.63  11.69
31.86  36.09  39.63  16.57
39.85  40.25  47.63  18.68
45.97  53.10  53.79  20.80
55.96  61.16  63.91  31.57
AFSL
Supply Air Fans
Utility  B low ers
Page 85
Page 3
Fan Size
Hp
106E
.25
106F
.33
106G
50
.
106H
.75
106J
1.00
106K
1.50
AFSI106
PERFORMANCE DATA
.000"  .125"  .250"  .375"  .500"  .625"  .750"  .875"  1.000"  1.125"  1.250"
CFM
RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM
LwoA
BHP
800
1000
1200
464  557  653  745  829
1400
0.13 69 0.17 68 0.23 69 0.28 70 0.34 72 
531  611  694  780  858  931  1000
1600
0.19 70 0.24 70 0.29 71 0.36 72 0.42 73 0.49 74 0.56 75 
597  666  741  817  892  961  1026  1089
1800
0.27 72 0.32 72 0.38 73 0.45 74 0.53 75 0.60 76 0.67 76 0.75 76 
630  696  767  838  910  978  1040  1102  1162
1900
0.32 73 0.37 73 0.43 74 0.50 74 0.59 75 0.66 76 0.73 77 0.81 77 0.90 77 
663  726  793  859  928  995  1057  1115  1174  1230
2000
0.37 74 0.43 74 0.49 75 0.56 75 0.65 76 0.73 77 0.81 77 0.88 77 0.97 78 1.06 78 
696  757  820  881  948  1013  1074  1132  1187  1243  1296
2100
0.43 75 0.49 75 0.55 76 0.62 76 0.71 77 0.81 77 0.89 78 0.96 78 1.05 78 1.14 79 1.24 79 
729  788  847  906  969  1030  1092  1149  1202  1256  1308  1359
2200
0.49 76 0.56 76 0.62 77 0.69 77 0.78 78 0.88 78 0.97 78 1.05 79 1.13 79 1.23 79 1.33 80 1.42 80 
762  818  874  932  990  1050  1109  1166  1219  1269  1321  1371  1419
2300
0.56 77 0.63 77 0.70 78 0.77 78 0.85 78 0.96 78 1.06 79 1.15 79 1.23 79 1.32 80 1.42 80 1.52 81 1.62 81 
795  850  901  958  1011  1071  1127  1183  1236  1286  1334  1384
2400
0.64 78 0.71 78 0.78 79 0.86 79 0.93 79 1.04 79 1.15 79 1.25 80 1.34 80 1.43 80 1.51 81 1.62 81 
829  881  929  985  1036  1092  1147  1201  1254  1303  1351
2500
0.72 79 0.80 79 0.87 80 0.95 80 1.02 80 1.13 80 1.24 80 1.35 80 1.45 81 1.54 81 1.63 81 
862  912  958  1012  1062  1113  1167  1219  1271
2600
0.81 80 0.89 80 0.96 81 1.05 80 1.12 80 1.22 80 1.34 80 1.46 81 1.56 81 
928  975  1018  1066  1114  1160  1209
2800
1.02 82 1.10 82 1.18 82 1.26 82 1.35 82 1.43 81 1.55 82 
994  1038  1079  1120  1167
3000
1.25 84 1.34 83 1.42 83 1.51 83 1.61 83
1061  1102
3200
1.52 85 1.61 85
LwoA
BHP
429
0.05 69 
464  587
0.08 68 0.12 68 
505  618  716
0.12 68 0.17 68 0.22 69
BHP
LwoA
BHP
LwoA
BHP
LwoA
BHP
LwoA
Static Pressure
LwoA
BHP
BHP
LwoA
1.375"  1.500"
LwoA
BHP
Fan
Model
106E .25  429-716  125  189 
106F .33  630-829  127  191 
106G .50  663-931  130  194 
106H .75 762-1102  135  199 
106J 1.00 912-1230  142  206 
106K 1.50 994-1419  159  223
LwoA
BHP
BHP
HP RPM Range
LwoA
BHP
Est. Unit Wt. Est. Ship Wt.
lbs.  lbs.
LwoA
BHP
LwoA
Fan Size
HP
126F
.33
126G
50
.
126H
.75
126J
1.00
126K
1.50
126L
2.00
AFSI126
PERFORMANCE DATA
.000"  .125"  .250"  .375"  .500"  .625"  .750"  .875"  1.000"  1.125"  1.250"  1.500"  1.625"  1.750"  1.875"
CFM
RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM
LwoA
BHP
1400
1600
1800
2000
2200
2400
496  554  615  673  725  778  827  877  925  971  1014
2600
0.39 71 0.46 71 0.54 71 0.62 71 0.70 72 0.79 72 0.88 73 0.98 74 1.07 75 1.16 75 1.24 76 
534  588  645  699  750  799  848  893  939  984  1027  1109  1151
2800
0.49 72 0.56 72 0.65 72 0.73 72 0.82 73 0.91 73 1.01 74 1.11 75 1.21 75 1.31 76 1.40 77 1.60 78 1.72 79 
572  623  676  727  777  822  868  913  955  998  1041  1121  1158  1197  1237
3000
0.61 73 0.68 73 0.77 74 0.86 74 0.95 74 1.05 74 1.15 75 1.26 76 1.36 76 1.47 77 1.57 78 1.78 79 1.88 80 1.99 80 2.12 80 
611  659  707  756  803  848  890  934  975  1015  1055  1134  1172  1208
3200
0.74 75 0.82 75 0.91 75 1.00 75 1.10 75 1.20 76 1.30 76 1.42 77 1.53 77 1.64 78 1.75 78 1.98 80 2.09 81 2.19 80 
687  730  771  817  858  901  941  979  1017  1056  1093
3600
1.05 78 1.14 77 1.23 77 1.34 78 1.44 78 1.56 78 1.68 78 1.79 79 1.90 79 2.03 79 2.16 80 
763  803  839  879  919  956  995
4000
1.44 80 1.54 80 1.64 80 1.76 80 1.88 80 1.99 80 2.12 81 
839  876  909
4400
1.91 82 2.03 82 2.14 82 
878
4600
2.18 83
LwoA
BHP
490  560  622  683  741  798  850  903
0.30 69 0.37 69 0.44 69 0.51 70 0.59 71 0.67 72 0.74 72 0.83 73 
522  587  647  704  758  812  863  912  960
0.37 70 0.45 70 0.52 70 0.60 71 0.69 72 0.77 72 0.86 73 0.94 74 1.02 75
LwoA
BHP
470  555
0.15 66 0.20 67 
488  567  640
0.19 67 0.25 67 0.30 68 
509  581  652  716
0.24 67 0.30 68 0.36 69 0.43 70 
533  601  665  728  785
0.30 68 0.36 68 0.43 69 0.50 70 0.57 71
BHP
LwoA
BHP
LwoA
BHP
LwoA
BHP
Static Pressure
LwoA
BHP
LwoA
BHP
LwoA
BHP
LwoA
LwoA
BHP
Fan
Model
126F .33  470-652  170  244 
126G .50  496-728  173  247 
126H .75  572-850  178  252
126J 1.00 687-960  185  259
126K 1.50 730-1109  202  276 
126L 2.00 839-1237  207  281
LwoA
BHP
HP RPM Range
BHP
Est. Unit Wt. Est. Ship Wt.
LwoA
BHP
lbs.  lbs.
LwoA
BHP
LwoA
The AMCA Certified Ratings Seal for Sound and Air Performance does not apply to model AFSI. Values shown are for outlet LwoA sound power levels for Installation Type B: Free Inlet, Ducted 
Outlet. Ratings include the effects of duct end correction. Performance shown is for installation type B: Free inlet, Ducted outlet. Performance ratings include the effects of filters in the airstream. 
Power rating (BHP) does not include drive losses. Motors and drives are not mounted and are shipped in separate cartons. 
Supply Air Fans
Page 86
Page 4
Fan Size
HP
150G
50
.
150H
.75
150J
1.00
150K
1.50
150L
2.00
150M
3.00
AFSI150
PERFORMANCE DATA
.000"  .125"  .250"  .375"  .500"  .625"  .750"  .875"  1.000"  1.125"  1.250"  1.375"  1.500"  1.625"  1.750"
CFM
RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM
LwoA
BHP
2000
2500
332  368  404  448  500  550
3000
0.32 67 0.38 66 0.43 66 0.50 66 0.59 66 0.69 68 
387  419  450  479  518  563  608  649
3500
0.51 70 0.58 70 0.64 70 0.70 69 0.79 68 0.89 69 1.01 70 1.11 71 
442  470  497  524  549  583  623  663  701  737  775
4000
0.76 74 0.84 73 0.91 73 0.99 73 1.05 71 1.15 71 1.27 71 1.39 72 1.52 73 1.64 75 1.78 76 
464  491  516  543  567  592  631  668  707  743  777  813
4200
0.88 75 0.97 75 1.04 74 1.12 75 1.19 73 1.26 72 1.39 73 1.51 73 1.65 74 1.79 75 1.91 77 2.06 78 
486  512  536  561  585  607  640  676  712  748  782  814  849
4400
1.02 76 1.10 76 1.18 76 1.26 76 1.34 75 1.41 74 1.52 74 1.65 74 1.79 74 1.93 75 2.07 77 2.20 78 2.35 80 
508  533  557  580  603  625  648  685  719  753  787  820  851  883
4600
1.16 77 1.25 77 1.34 77 1.42 77 1.50 77 1.58 75 1.65 75 1.80 75 1.93 75 2.08 76 2.23 77 2.38 79 2.51 80 2.67 82 
530  555  577  599  622  643  664  693  727  759  793  825  856  886  917
4800
1.32 78 1.42 78 1.50 78 1.59 78 1.68 78 1.76 77 1.83 76 1.95 76 2.10 76 2.24 77 2.40 78 2.55 79 2.70 81 2.85 82 3.01 82 
552  576  597  618  641  662  681  701  735  767  798  831  861  891  920
5000
1.49 79 1.59 79 1.69 79 1.78 79 1.87 79 1.95 78 2.03 78 2.11 77 2.27 77 2.42 78 2.56 79 2.73 79 2.89 81 3.05 82 3.20 83 
575  597  618  638  659  680  699  718  744  776  806  836  867  897
5200
1.68 80 1.78 80 1.88 80 1.97 80 2.07 80 2.16 80 2.24 79 2.33 78 2.45 78 2.61 79 2.76 79 2.92 80 3.09 81 3.26 82 
597  618  639  658  678  698  718  736  754  784  814  843  872
5400
1.88 81 1.99 81 2.09 81 2.19 81 2.29 81 2.38 81 2.47 80 2.56 80 2.64 79 2.80 80 2.97 80 3.13 81 3.29 81 
619  640  659  678  697  717  736  754  771  792  822
5600
2.09 82 2.21 82 2.31 82 2.42 82 2.52 82 2.62 82 2.72 82 2.81 81 2.89 81 3.00 81 3.18 81 
641  661  680  699  717  736  754  772  789  806
5800
2.33 82 2.44 82 2.56 82 2.66 82 2.77 83 2.87 83 2.97 83 3.07 82 3.16 82 3.25 82 
663  683  701  719  736  755  773
6000
2.58 83 2.70 83 2.81 83 2.92 83 3.03 83 3.14 84 3.25 84 
685  704  722  740
6200
2.84 84 2.97 84 3.09 84 3.20 84
BHP
LwoA
LwoA
BHP
351
0.19 63 
368  431
0.28 63 0.36 64
BHP
LwoA
BHP
LwoA
BHP
LwoA
BHP
Static Pressure
LwoA
BHP
LwoA
BHP
LwoA
BHP
LwoA
LwoA
BHP
Fan
Model
150G .50  332-448  252  346 
150H .75  419-518  257  351
150J 1.00 464-608  264  358
150K 1.50 508-737  281  375
150L 2.00 575-814  286  380
150M 3.00 640-920  294  388
LwoA
BHP
HP RPM Range
BHP
Est. Unit Wt. Est. Ship Wt.
LwoA
BHP
lbs.  lbs.
LwoA
BHP
LwoA
Fan Size
HP
181J
1.00
181K
1.50
181L
2.00
181M
3.00
181N
5.00
AFSI181
PERFORMANCE DATA
.000"  .125"  .250"  .375"  .500"  .625"  .750"  .875"  1.000"  1.250"  1.500"  1.750"  2.000"  2.250"  2.500"
CFM
RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM
LwoA
BHP
3000
3500
4000
4500
5000
5500
378  403  425  455  484  522  558  590  620  675  727  775  824
6000
1.17 78 1.27 78 1.35 78 1.49 78 1.61 77 1.80 77 1.98 78 2.16 79 2.34 79 2.67 80 3.02 81 3.35 82 3.72 82 
410  433  453  479  507  535  570  603  633  687  737  786  831  874
6500
1.49 79 1.60 79 1.69 79 1.81 79 1.96 79 2.11 79 2.32 79 2.51 80 2.70 81 3.08 81 3.44 82 3.82 82 4.18 83 4.55 84 
442  463  482  502  529  554  583  616  646  701  750  796  841  883  923
7000
1.86 81 1.98 81 2.08 81 2.18 81 2.35 81 2.50 80 2.68 81 2.90 81 3.11 82 3.53 82 3.93 83 4.32 83 4.73 84 5.12 85 5.50 85 
473  493  512  529  552  577  600  628  658  714  763  808  851
7500
2.29 82 2.42 82 2.53 82 2.63 82 2.79 82 2.96 82 3.11 82 3.32 83 3.56 83 4.00 83 4.45 84 4.88 84 5.30 85 
505  523  541  558  576  600  622  644  671  727  777  822
8000
2.78 84 2.92 83 3.04 83 3.15 84 3.27 84 3.46 84 3.64 84 3.80 84 4.04 84 4.54 84 5.01 85 5.48 85 
536  554  571  586  602  623  645  666  686  739
8500
3.34 85 3.48 85 3.61 85 3.73 85 3.84 85 4.03 85 4.22 86 4.41 85 4.58 85 5.11 85 
568  584  600  616  630  646  668  688  708
9000
3.96 86 4.11 86 4.25 86 4.38 86 4.50 86 4.65 87 4.86 87 5.07 86 5.26 86 
599  615  630  645  659  672
9500
4.66 87 4.82 87 4.97 87 5.11 88 5.24 87 5.36 88 
631
10000
5.44 89
LwoA
BHP
373  400  433  470  510  545  577  607  664  717
0.99 76 1.08 76 1.20 76 1.35 76 1.52 76 1.68 77 1.84 78 1.99 78 2.31 79 2.62 80
LwoA
BHP
354  401  445  484  519  554  585
0.66 74 0.79 74 0.92 74 1.05 75 1.18 75 1.31 76 1.43 76 
377  413  458  497  532  564  596  654
0.85 75 0.97 75 1.12 75 1.27 75 1.41 76 1.55 77 1.70 77 1.98 79
LwoA
BHP
363  412
0.38 73 0.47 73 
375  420  462
0.49 73 0.59 74 0.69 74 
388  432  472  509  545
0.63 74 0.74 74 0.86 74 0.97 74 1.09 75
BHP
LwoA
BHP
LwoA
BHP
Static Pressure
LwoA
BHP
LwoA
BHP
LwoA
BHP
LwoA
LwoA
BHP
Fan
HP RPM Range
Model
181J 1.00 363-545  397  519
181K 1.50 378-585  414  536
181L 2.00 442-654  419  541 
181M 3.00 473-727  427  549 
181N 5.00 536-923  471  593
BHP
LwoA
LwoA
BHP
Est. Unit Wt. Est. Ship Wt.
BHP
lbs.  lbs.
LwoA
BHP
LwoA
Supply  A ir  Fans 
Supply Air Fans
Utility  B low ers
The AMCA Certified Ratings Seal for Sound and Air Performance does not apply to model AFSI. Values shown are for outlet LwoA sound power levels for Installation Type B: Free Inlet, Ducted 
Outlet. Ratings include the effects of duct end correction. Performance shown is for installation type B: Free inlet, Ducted outlet. Performance ratings include the effects of filters in the 
airstream. Power rating (BHP) does not include drive losses. Motors and drives are not mounted and are shipped in separate cartons. 
Page 87
Page 5
Fan Size
HP
200K
1.50
200L
2.00
200M
3.00
200N
5.00
200P
7.50
AFSI200
PERFORMANCE DATA
.000"  .125"  .250"  .375"  .500"  .625"  .750"  1.000"  1.250"  1.500"  1.750"  2.000"  2.250"  2.500"  2.750"
CFM
RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM
LwoA
BHP
4500
5000
5500
6000
6500
7000
7500
8000
8500
9000
425  454  480  507  532  556  579  630  676  721  763  803  842  880
9500
2.35 82 2.60 82 2.82 83 3.06 83 3.31 84 3.54 84 3.76 85 4.32 87 4.84 87 5.42 88 5.98 88 6.53 90 7.14 91 7.76 92 
448  475  501  525  550  573  595  643  688  731  774  813  850
10000
2.75 83 3.01 83 3.24 84 3.48 85 3.75 85 4.00 86 4.23 86 4.79 87 5.36 88 5.92 89 6.53 89 7.12 90 7.69 91 
537  561  583  603  623  644  665  703  740
12000
4.74 88 5.06 89 5.36 89 5.64 90 5.91 90 6.24 90 6.55 89 7.14 89 7.73 90 
627  647
14000
7.53 92 7.91 93
LwoA
BHP
413  441  471  498  524  553  605  655  701  745  787  827  865
1.90 79 2.10 80 2.33 80 2.53 81 2.74 82 3.00 83 3.47 83 3.98 86 4.48 87 5.00 89 5.56 89 6.11 91 6.64 91 
433  460  489  515  539  566  617  665  711  753  795  835  872  908
2.23 81 2.44 81 2.68 82 2.90 82 3.11 83 3.36 84 3.88 86 4.39 87 4.94 88 5.46 88 6.03 90 6.62 91 7.20 92 7.77 92
LwoA
BHP
423  453  481  511  540  594  645  692  737  779  819
1.80 79 2.01 79 2.20 79 2.42 80 2.65 81 3.11 84 3.59 85 4.06 87 4.59 88 5.10 89 5.61 90
LwoA
BHP
419  453  485  516  573  627  676  722
1.46 76 1.66 77 1.86 78 2.06 79 2.47 82 2.91 84 3.36 85 3.81 87 
436  466  498  527  584  635  684  729  772
1.72 77 1.91 78 2.13 79 2.34 80 2.78 83 3.22 85 3.71 86 4.19 88 4.67 89
LwoA
BHP
406  444  479
0.89 73 1.04 74 1.21 76 
417  453  487  549
1.05 74 1.21 75 1.38 76 1.74 79 
427  463  495  556  611
1.22 75 1.40 76 1.58 77 1.98 80 2.34 82 
440  473  505  564  619  668
1.43 76 1.61 77 1.81 78 2.20 81 2.62 83 3.03 85
LwoA
BHP
436
0.90 74
BHP
Static Pressure
LwoA
BHP
LwoA
BHP
LwoA
BHP
LwoA
LwoA
BHP
Fan
Model
200K 1.50 406-495  610  754
200L 2.00 413-564  615  759 
200M 3.00 425-668  623  767 
200N 5.00 537-779  667  811 
200P 7.50 603-908  686  830
LwoA
BHP
HP RPM Range
BHP
Est. Unit Wt. Est. Ship Wt.
LwoA
LwoA
BHP
BHP
lbs.  lbs.
LwoA
The AMCA Certified Ratings Seal for Sound and Air Performance does not apply to model AFSI. Values shown are for outlet LwoA sound power levels for Installation Type B: Free Inlet, Ducted 
Outlet. Ratings include the effects of duct end correction. Performance shown is for installation type B: Free inlet, Ducted outlet. Performance ratings include the effects of filters in the airstream. 
Power rating (BHP) does not include drive losses. Motors and drives are not mounted and are shipped in separate cartons. 
Supply Air Fans
Page 88
Page 6
AFSN/AFSL106
Fan Size
HP
106E
.25
106F
.33
106G
.50
106H
.75
106J
1.00
106K
1.50
PERFORMANCE DATA
BHP
Static Pressure
LwoAs 
BHP
LwoAs 
BHP
LwoAs 
BHP
LwoAs 
LwoAs 
BHP
Fan
Model
106E .25  356-724  116  206 
106F .33  593-814  122  212 
106G .50  652-898  125  215 
106H .75 760-1085  130  220
106J 1.00 830-1201  137  227
106K 1.50 929-1394  154  244
LwoAs 
BHP
HP RPM Range
BHP
Est. Unit Wt. Est. Ship Wt.
LwoAs 
BHP
lbs.  lbs.
.000"  .125"  .250"  .375"  .500"  .625"  .750"  .875"  1.000"  1.125"  1.250"  1.375"  1.500"  1.750"  1.875"
CFM
RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM
LwoAs 
BHP
600
800
1000
356  456  554  642  724  800
1200
0.07 70 0.10 70 0.15 69 0.19 69 0.24 69 0.30 71 
415  501  587  667  743  814  882
1400
0.11 70 0.15 70 0.19 70 0.25 70 0.30 71 0.36 72 0.42 73 
474  548  626  698  768  834  898  958  1017  1073
1600
0.16 71 0.20 71 0.25 71 0.31 71 0.37 72 0.44 73 0.50 74 0.56 76 0.64 76 0.71 76 
534  596  668  735  799  860  918  977  1033  1085  1138  1188
1800
0.23 72 0.27 72 0.33 73 0.39 73 0.46 74 0.53 74 0.60 75 0.67 76 0.74 77 0.81 77 0.90 77 0.98 78 
593  649  714  775  834  891  947  998  1052  1104  1154  1201  1248  1339
2000
0.32 74 0.36 74 0.42 74 0.49 75 0.56 75 0.63 76 0.71 77 0.79 77 0.87 77 0.95 78 1.03 78 1.10 79 1.20 79 1.39 81 
622  677  737  795  853  907  962  1013  1062  1114  1163  1210  1255  1345  1387
2100
0.37 75 0.42 75 0.48 75 0.54 76 0.61 76 0.69 77 0.77 77 0.85 78 0.93 78 1.02 78 1.10 79 1.19 79 1.27 80 1.46 81 1.56 82 
652  704  760  817  873  925  978  1029  1077  1123  1173  1220  1265  1351  1394
2200
0.42 76 0.47 76 0.53 76 0.60 77 0.68 77 0.75 78 0.84 78 0.92 78 1.01 78 1.09 79 1.18 79 1.27 80 1.36 80 1.54 82 1.64 82 
711  760  808  863  913  964  1011  1060  1107  1152  1195  1239  1284
2400
0.55 78 0.60 78 0.66 78 0.74 78 0.81 79 0.90 79 0.98 79 1.07 79 1.17 79 1.26 80 1.35 80 1.45 80 1.54 81 
771  816  856  909  957  1004  1050  1094  1138  1183  1225  1265
2600
0.69 79 0.76 79 0.81 80 0.90 80 0.98 81 1.06 81 1.16 81 1.24 80 1.34 80 1.44 81 1.54 81 1.64 81 
830  872  911  956  1003  1046  1090  1133  1173  1214
2800
0.87 81 0.94 81 1.00 81 1.08 82 1.17 82 1.25 82 1.35 82 1.45 82 1.54 82 1.64 82 
889  929  965  1004  1049  1091  1131
3000
1.07 83 1.14 83 1.21 83 1.28 83 1.38 83 1.48 83 1.56 83 
948  986  1020  1053  1096
3200
1.29 85 1.37 84 1.45 84 1.52 84 1.62 84
1008  1043
3400
1.55 86 1.64 85
LwoAs 
BHP
362
0.03 71 
384  509
0.05 71 0.08 70 
417  526  624
0.07 70 0.11 69 0.15 68
BHP
LwoAs 
BHP
LwoAs 
BHP
LwoAs 
BHP
LwoAs 
LwoAs 
BHP
LwoAs 
AFSN/AFSL126
PERFORMANCE DATA
Fan Size
HP
126F
.33
126G
.50
126H
.75
126J
1.00
126K
1.50
126L
2.00
The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for outlet LwoA sound power levels for Installation Type B: Free Inlet, Ducted Outlet. 
Ratings include the effects of duct end correction. sLwoA shown reflects levels for Model AFSN only. Subtract 1 db to find LwoA for Model AFSL  . Performance certified is for installation 
Type B: Free inlet, Ducted outlet. Performance ratings include the effects of filters. Power rating (BHP) does not include transmission losses.
.000"  .125"  .250"  .375"  .500"  .625"  .750"  .875"  1.000"  1.125"  1.250"  1.500 "  1.750"  1.875"  2.000"
CFM
RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM
LwoAs 
BHP
1400
1600
1800
2000
2400
540  604  663  721  776  830  879  927  974  1018  1060  1141  1220
2800
.40 73 .49 74 .56 74 .65  75  .74 75 .83 75 .92 77 1.02 76 1.11 77 1.20 77 1.29 78 1.49 79 1.72 81
559  621  679  735  788  841  890  936  982  1027  1069  1147  1226
2900
.45 74 .53 75 .62 74 .70  75  .79 76 .89 76 .98 77 1.08 76 1.17 77 1.27 77 1.37 78 1.55 80 1.79 82
579  638  695  749  802  853  901  947  991  1035  1077  1155  1231
3000
.50 75 .58 76 .67 75 .76  76  .85 76 .95 76 1.05 77 1.15 78 1.24 78 1.35 79 1.44 79 1.64 80 1.86 82
598  656  711  762  815  864  913  958  1000  1044  1086  1164  1237
3100
.55 76 .64 76 .73 76 .81  76  .91 76 1.01 78 1.12 78 1.22 79 1.31 78 1.42 80 1.53 81 1.73 80 1.93 82
617  674  727  776  828  876  924  969  1011  1053  1095  1173  1244
3200
.60 76 .70 76 .79 77 .87  77  .98 78 1.08 78 1.18 78 1.29 79 1.39 79 1.50 80 1.61 81 1.82 81 2.02 82
656  710  760  808  856  902  947  992  1034  1073  1113  1190
3400
.72 78 .83 77 .92 78 1.02 78 1.12 79 1.22 79 1.33 80 1.45 80 1.56 80 1.67 81 1.78 81 2.01 81
694  746  793  840  883  929  972  1015  1056  1096  1133
3600
.86 79 .97 79 1.07 79 1.17 80 1.27 80 1.39 81 1.50 81 1.62 81 1.74 81 1.86 81 1.97 82
771  818  861  904  945  984  1026  1065  1103
4000
1.17 81 1.30 81 1.41 82 1.53 82 1.64 82 1.75 82 1.88 82 2.00 83 2.13 83 
848  891  931  970  1009
4400
1.56 83 1.70 84 1.83 84 1.95 84 2.08 84 
926
4800
2.03 85
LwoAs 
BHP
537  604  669  730  786  841  892  939  987  1033  1119  1199  1239
.33 70 .39 71 .47  71  .55 72 .63 72 .71 73 .79 74 .86 75 .96 76 1.06 77 1.26 79 1.47 80 1.58 81
s
LwoA
BHP
505  586  658  725  785  845  900  952  1001  1093  1177  1217  1256
.17 62 .23  66  .28 70 .35 68 .42 70 .49 72 .57 74 .65 76 .73 77 .90 78 1.08 80 1.17 79 1.27 79
528  604  673  736  797  852  906  958  1007  1098  1182  1222
.22 64 .28  67  .34 67 .40 69 .47 70 .55 72 .63 73 .72 76 .80 77 .98 79 1.17 81 1.26 79
551  624  690  751  808  864  915  964  1012  1104  1188  1228
.27 68 .33  68  .40 68 .46 69 .53 71 .62 73 .70 74 .78 75 .87 76 1.07 77 1.26 79 1.36 80
LwoAs 
BHP
570  646  715  780  839  895  947  996  1088  1172  1212  1251
.19  66  .24 70 .31 68 .37 70 .44 72 .51 74 .59 75 .67 77 .83 78 .99 80 1.08 78 1.17 79
BHP
LwoA
s
LwoAs 
BHP
BHP
Static Pressure
LwoAs 
BHP
LwoA
s
BHP
LwoA
s
BHP
LwoAs 
LwoAs 
BHP
Fan
Model
126F .33  505-715  162  283 
126G .50  540-895  165  286 
126H .75  598-958  170  291
126J 1.00 694-1172  177  298
126K 1.50 771-1251  194  315
126L 2.00 848-1244  199  320
LwoAs 
BHP
HP RPM Range
LwoAs 
BHP
Est. Unit Wt. Est. Ship Wt.
LwoAs 
BHP
lbs.  lbs.
BHP
LwoAs 
Supply Air Fans
Utility  B low ers
Page 89
Page 7
Fan Size
HP
150G
.50
150H
.75
150J
1.00
150K
1.50
150L
2.00
150M
2.00
AFSN/AFSL150
PERFORMANCE DATA
.000"  .125"  .250"  .375"  .500"  .625"  .750"  .875"  1.000"  1.125"  1.250"  1.375"  1.500"  1.750"  1.875"
CFM
RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM
LwoAs 
BHP
2000
2400
2800
366  421  477  530  583  632  678  721  765  807  847  885  921
3200
0.30 70 0.37 72 0.45 73 0.52 73 0.61 74 0.69 73 0.78 75 0.87 76 0.98 77 1.08 78 1.19 79 1.29 80 1.39 81 
412  459  510  559  606  653  696  739  779  817  856  894  930  998  1030
3600
0.43 73 0.50 74 0.59 76 0.68 76 0.76 76 0.86 74 0.95 76 1.06 77 1.16 78 1.26 79 1.38 80 1.50 81 1.61 81 1.84 83 1.96 84 
458  500  546  590  634  676  718  758  797  834  870  904  939  1007  1039
4000
0.59 75 0.67 76 0.76 77 0.86 78 0.96 74 1.05 75 1.16 77 1.26 78 1.38 79 1.49 80 1.61 80 1.72 82 1.84 82 2.11 84 2.24 84 
480  521  564  606  649  688  730  769  806  843  879  912  945  1012  1044
4200
0.68 76 0.76 77 0.86 78 0.96 79 1.06 74 1.16 76 1.27 77 1.38 78 1.49 79 1.61 80 1.74 81 1.85 82 1.97 82 2.24 84 2.38 84 
503  543  583  623  664  703  742  781  817  852  888  921  954  1016  1048
4400
0.78 77 0.88 78 0.97 79 1.08 73 1.18 75 1.28 76 1.40 78 1.52 79 1.63 80 1.74 81 1.88 82 2.00 82 2.13 83 2.38 84 2.52 85 
526  564  602  641  680  718  754  792  828  863  896  930  962  1023  1053
4600
0.89 78 0.99 79 1.09 80 1.20 74 1.31 75 1.42 77 1.52 78 1.65 79 1.77 80 1.89 86 2.01 82 2.15 82 2.28 83 2.54 84 2.67 85 
549  586  621  660  696  734  768  804  840  874  907  939  971  1032  1061
4800
1.02 79 1.12 80 1.22 72 1.34 74 1.45 76 1.57 77 1.67 78 1.79 80 1.92 80 2.05 80 2.17 82 2.30 83 2.44 84 2.72 85 2.85 85 
572  607  640  678  713  749  784  816  852  886  918  949  980  1041  1070
5000
1.15 80 1.25 81 1.35 73 1.48 75 1.60 76 1.72 78 1.84 79 1.94 80 2.08 81 2.22 82 2.34 83 2.47 83 2.61 84 2.90 85 3.05 86 
595  629  660  696  731  765  799  831  864  897  930  960  990  1050  1079
5200
1.29 82 1.40 72 1.50 74 1.63 75 1.76 77 1.88 78 2.00 79 2.12 80 2.25 85 2.39 82 2.53 83 2.66 83 2.79 84 3.10 86 3.25 86 
617  650  681  715  749  781  815  846  876  909  941  972  1001  1059
5400
1.44 82 1.56 72 1.67 74 1.80 76 1.93 77 2.06 79 2.19 80 2.31 81 2.42 82 2.57 83 2.72 83 2.86 84 3.00 84 3.29 86 
640  672  702  734  767  798  830  862  892  921  953  983  1013
5600
1.61 71 1.73 73 1.84 75 1.97 76 2.11 78 2.24 79 2.38 80 2.51 86 2.64 82 2.76 83 2.92 83 3.06 84 3.22 85 
686  716  744  772  804  834  862  893  922  950
6000
1.98 72 2.11 74 2.23 76 2.36 78 2.51 79 2.66 80 2.79 86 2.94 82 3.08 83 3.21 83 
743  771  797  822  851  879
6500
2.52 74 2.66 76 2.79 78 2.92 79 3.08 80 3.24 81
LwoAs 
BHP
383  446  506  562  614  663  711  756  798
0.26 69 0.33 71 0.40 71 0.48 73 0.56 74 0.64 74 0.73 75 0.83 76 0.92 77
LwoAs 
BHP
398  470  535
0.17 62 0.23 67 0.30 69 
420  486  544  602  654
0.24 65 0.31 69 0.37 71 0.45 73 0.53 73
BHP
LwoAs 
BHP
LwoAs 
BHP
LwoAs 
BHP
Static Pressure
LwoAs 
BHP
LwoAs 
BHP
LwoAs 
BHP
LwoAs 
LwoAs 
BHP
Fan
Model
150G .50  349-495  269  313 
150H .75  430-555  278  338
150J 1.00 468-609  468  492 
150K1 1.50 
150K2 1.50 
150L1 2.00 
150L2 2.00
150M1 3.00 
150M2 3.00
LwoAs 
BHP
BHP
HP RPM Range
534-678 
577-740 
600-800 
619-817 
668-824
757-1079
LwoAs 
BHP
Est. Unit Wt. Est. Ship Wt.
lbs.  lbs.
485  509 
484  508 
487  511 
481  505 
518  542 
518  542
LwoAs 
BHP
LwoAs 
Utility  B low ers
Fan Size
HP
181J
1.00
181K
1.50
181L
2.00
181M
3.00
181N
5.00
AFSN/AFSL181
PERFORMANCE DATA
.000"  .125"  .250"  .375"  .500"  .625"  .750"  .875"  1.000"  1.250"  1.500"  1.750"
CFM
RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM
LwoAs 
BHP
4000
4500
5000
5500
6000
6500
7000
7200
7400
7600
7800
8000
9000
385  406  426  447  471  501  531  559  595
1.21  80  1.29  80  1.36  80  1.46  79  1.57  78  1.71  78  1.85  78  1.99  78  2.26  79 
417  436  455  475  496  517  547  574  600  663
1.54  81  1.62  81  1.71  82  1.80  82  1.91  80  2.03  79  2.20  79  2.35  79  2.49  80  3.05  81 
449  467  484  502  520  541  563  590  615  667  725
1.92  83  2.01  83  2.10  83  2.20  82  2.30  82  2.43  81  2.57  81  2.75  81  2.91  81  3.31  82  3.94  82 
462  479  496  513  531  551  570  596  622  669  727  781
2.09  84  2.18  84  2.27  84  2.37  84  2.48  83  2.61  83  2.74  81  2.92  81  3.09  82  3.41  82  4.06  83  4.71  83 
475  492  508  525  542  561  580  603  628  675  729  782
2.27  84  2.36  84  2.46  84  2.56  84  2.67  84  2.80  83  2.93  82  3.09  82  3.28  82  3.62  83  4.18  83  4.85  84 
488  504  520  536  553  570  589  609  634  681  730  784
2.46  85  2.56  85  2.65  85  2.75  85  2.87  84  2.99  84  3.13  83  3.28  82  3.47  83  3.83  83  4.31  83  4.99  84 
501  517  532  548  564  580  599  617  641  687  732  785
2.66  85  2.76  85  2.86  86  2.96  85  3.07  85  3.19  85  3.34  84  3.48  83  3.67  83  4.04  84  4.43  83  5.14  84 
514  529  544  560  575  591  609  627  647  693  736
2.87  86  2.97  86  3.07  87  3.18  86  3.29  85  3.41  86  3.55  85  3.70  84  3.87  83  4.27  85  4.62  83 
578  592  605  619  632  646  661  675  691
4.09  89  4.20  89  4.31  88  4.43  88  4.55  89  4.68  88  4.82  89  4.96  88  5.13  87
LwoAs 
BHP
375  398  423  453  485  517  555  591
1.00  79  1.08  77  1.17  77  1.29  77  1.42  77  1.56  76  1.81  78  2.06  78
LwoAs 
BHP
371  400  437  472  513
0.84  77  0.93  76  1.05  76  1.18  76  1.41  76
LwoAs 
BHP
368  418
0.58  75 0.75  75 
384  422  468
0.74  75 0.85  75  1.06  76
BHP
LwoAs 
BHP
Static Pressure
LwoAs 
BHP
LwoAs 
BHP
LwoAs 
LwoAs 
BHP
Fan
HP RPM Range
Model
181J 1.00 368-422  377  585 
181K 1.50 385-513  394  602 
181L 2.00 436-559  399  607
181M 3.00 475-615  407  615
181N 5.00 544-785  451  659
LwoAs 
BHP
BHP
Est. Unit Wt. Est. Ship Wt.
lbs.  lbs.
LwoAs 
BHP
LwoAs 
Supply Air Fans
The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for outlet LwoA sound power levels for Installation Type B: Free Inlet, Ducted Outlet. 
Ratings include the effects of duct end correction. sLwoA shown reflects levels for Model AFSN only. Subtract 1 db to find LwoA for Model AFSL.   Performance certified is for installation 
Type B: Free inlet, Ducted outlet. Performance ratings include the effects of filters. Power rating (BHP) does not include transmission losses.
Page 90
Page 8
Fan Size
HP
200K
1.50
200L
2.00
200M
3.00
200N
5.00
200P
7.50
AFSN/AFSL200
PERFORMANCE DATA
.000"  .125"  .250"  .375"  .500"  .750"  1.000"  1.250"  1.500"  1.750"  2.000"  2.250"  2.500"  2.750"  3.000"
CFM
RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM  RPM
LwoAs 
BHP
4000
5000
6000
6500
7000
7500
329  360  393  424  452  510  563  613  658  705  749  790  829
8000
1.31 77 1.47 78 1.66 78 1.86 79 2.06 79 2.49 80 2.94 81 3.41 82 3.86 84 4.39 86 4.92 89 5.43 90 5.94 91 
349  379  410  439  467  521  572  621  667  709  753  794  833  870
8500
1.57 79 1.74 79 1.94 80 2.14 80 2.36 80 2.81 81 3.27 82 3.77 83 4.27 85 4.76 87 5.32 89 5.88 90 6.43 91 6.97 92 
370  398  427  455  482  532  583  630  675  717  758  799  838  875  910
9000
1.87 80 2.05 81 2.25 81 2.45 81 2.69 82 3.15 82 3.65 83 4.14 84 4.69 86 5.20 87 5.74 89 6.34 90 6.93 91 7.51 93 8.08 93 
390  417  444  472  498  545  594  640  684  725  764  803  842  879
9500
2.20 81 2.39 82 2.59 82 2.81 83 3.05 83 3.53 84 4.06 84 4.56 85 5.12 86 5.68 88 6.23 89 6.81 90 7.44 91 8.06 93 
411  436  461  488  513  560  606  651  693  734  773  809  846
10000
2.56 83 2.76 83 2.96 83 3.21 84 3.44 84 3.96 85 4.49 86 5.04 86 5.58 87 6.19 89 6.77 90 7.34 90 7.96 92 
452  475  497  522  546  590  631  673  714  752  790
11000
3.41 85 3.63 86 3.83 86 4.10 86 4.36 87 4.92 88 5.46 88 6.08 88 6.68 89 7.25 90 7.92 90 
493  514  535  556  579  621  660  696  736
12000
4.43 87 4.67 88 4.90 88 5.16 89 5.45 89 6.02 90 6.65 90 7.23 90 7.92 90 
534  554  573  591  613  653  691
13000
5.63 90 5.90 90 6.15 91 6.38 91 6.71 92 7.32 91 7.99 91 
575  594  611  628  647
14000
7.03 92 7.32 93 7.59 93 7.84 93 8.16 94
LwoAs 
BHP
341  377  409  438  499  554  604  653  700  744
1.22 77 1.41 77 1.60 77 1.78 77 2.20 78 2.64 80 3.07 81 3.54 83 4.04 86 4.52 88
LwoAs 
BHP
330  368  404  471  532  589
0.83 74 0.99 74 1.15 74 1.50 75 1.88 77 2.27 79 
345  380  415  480  537  593  645
1.00 75 1.16 75 1.34 75 1.72 76 2.09 78 2.52 80 2.94 82 
361  394  427  488  545  598  649  696
1.19 76 1.37 76 1.56 76 1.94 77 2.35 79 2.78 80 3.24 83 3.69 85
LwoAs 
BHP
329  374
0.48 71 0.61 71 
346  386  459
0.70 72 0.85 72 1.16 74
BHP
LwoAs 
BHP
LwoAs 
BHP
Static Pressure
LwoAs 
BHP
LwoAs 
BHP
LwoAs 
BHP
LwoAs 
LwoAs 
BHP
Fan
Model
200K 1.50 329-471  573  827 
200L 2.00 370-589  578  832 
200M 3.00 411-649  586  840 
200N 5.00 452-790  630  884 
200P 7.50 534-910  649  903
LwoAs 
BHP
HP RPM Range
LwoAs 
BHP
BHP
Est. Unit Wt. Est. Ship Wt.
lbs.  lbs.
LwoAs 
BHP
LwoAs 
The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for outlet LwoA sound power levels for Installation Type B: Free Inlet, Ducted Outlet. 
Ratings include the effects of duct end correction. sLwoA shown reflects levels for Model AFSN only. Subtract 1 db to find LwoA for Model AFSL.   Performance certified is for installation 
Type B: Free inlet, Ducted outlet. Performance ratings include the effects of filters. Power rating (BHP) does not include transmission losses.
Supply Air Fans
Utility  B low ers
For more information on this product contact your sales support.
Page 91