ACI-Automation Components TSENSE CO2 Data Sheet

Automation Components, Inc.
TSENSE: CO2GAS
TSENSE: CO2
CO2 Sensor with Temperature, RH & Display
TSENSE is an advanced and versatile 3 in 1 transmitter. Designed for installation in the air conditioned zone, it measures CO2 concentration, temperature and humidity in the ambient air. The data is transmitted to a BMS system or stand-alone controller using a standard output (analog or relay) or via BACnet™ or Modbus communication protocols. TSENSE combines all the necessary elements for effective climate control in commercial office buildings, hospitals, hotels, schools and other facilities, allowing for a comfortable and healthy environment for the occupants. It is flexible in design and is suitable for use in many different energy efficient ventilation strategies. The TSENSE incorporates a NDIR (non-dispersive infrared) technology and complies with ASHRAE
189.1. (TSENSE units can be configured in the field using the touch screen display or by UIP5 Software via a USB to Serial adapter cable with a 3.5 mm audio jack).
Automation Components, Inc.
95
GAS TSENSE: CO2
SPECIFICATIONS
Supply Voltage Power Consumption Measurement Range (CO2, Temp, RH) Output Signal Output Resolution Scales Linear Analog output, 0-10V, At Screw Terminal Relay Output Contact Ratings Digital Relay Output Communication Protocols Baud Rates (Field Adjustable) BACnet MAC Address Accuracy (CO2)
Accuracy (Temp, RH) Long-term Drift Pressure Dependence Measurement Interval Reponse Time Warm Up Time Operating Temperature/Relative Humidity Range Life Expectancy Display (Optional) Buttons Conformance With Standards Wiring Connections
Product Dimensions
ORDERING
12 VDC, 24 VDC or 24 VAC (50-60 Hz) ±20%, (min 10V, max 40V) 2W max,<0.35 W average (non-display), <0.60 W average (w/display) 0-2000 ppm (up to 3,000 ppm with software adjustment), 0-50°C, 0-95% RH
Voltage output 0-10 V, Rout: <100Ω, Max Load: >5 kΩ
10-bits, 10 mV steps, 0.1% steps of full ppm/°C/% RH range CO2: 0-2000 ppm, Temp: 0-50°C, RH: 0-100% RH On/Off, 1000/900 ppm CO2, SPDT Form 1C Relay
0.5 A @ 125 VAC, 2 A @ 30 VDC 1 (on) or 0 (off) BACnet (MS/TP) or MODBUS (RTU) 9600, 19200, 38400, 57600 0-127 (Default 104) ±50 ppm of measured value @ 1000 ppm, 17-28°C and 30 to 60% RH ±30 ppm +3% of measured value over full range ±0.5°C (@ 17-28°C), ±1.0°C (@ 0-50°C), ±5% RH (@ 20%-80% RH) <±0.5% RH +1.58% reading per kPa deviation from normal pressure, 101.3 kPa 15 seconds <3 min diffusion time (CO2), <6 min (Air velocity of 0.15 m/s) (Temp)
>1 min
32 to 122
>15 years (typical)
LCD with CO2 ppm, Temperature °C and Humidity %RH Touch screen display EMC directive 2004/108/EC, RoHS directive 2011/65/EU, complies w/ ASHRAE 189.1 Screw terminal, max 1.5 mm2, with Power, GND, Out1 (CO2), Out2 (Temp), Out 3 (RH) BACnet MS/TP over RS485, MODBUS over serial (H) 4.92” (W) 3.34” (D) .866”
o
F (0 to 50oC)/0 to 95% RH, non-condensing
Please select one Sensor Series (A). NOTE: The USB to Serial Cable (TTL-232-3V3-AJ) must be ordered to modify sensor settings for all units without display.
Sensor Series
TSENSE-LCD (TSENSE Model with LCD)
(TSENSE Model without LCD)
TSENSE
Additional Configurations
TTL-232-3V3-AJ (USB to Serial Cable, 3.5 mm Audio Jack)
BUILD PART NUMBER
After completing (A) from the above table, fill in the Part Number Table below. (1) is an additional configuration. An example part number is offered.
EXAMPLE: TSENSE-LCD
EXAMPLE: TTL-232-3V3-AJ
96