Automation Components, Inc.
Featured Relative Humidity Resistive Product
Duct/Euro
RH RESISTIVEHUMIDITY
Outside Air/Euro
Stainless Plate
Room 2
Room
Room 2, Setpoint
Room, Setpoint
Room 2, Override
Room, Override
Room 2, Setpoint,
Override
Room, Setpoint,
Override
RH RESISTIVE
RH with Resistive Temperature Output
The A/RH Series relative humidity transmitters (with resistive temperature output) utilize a capacitive
sensing element to deliver a proportional analog output. This series features on board DIP switches which
allow the user to select the desired output signal. In addition, field calibration can be performed by using
the on board increment and decrement DIP switches. These enhancements provide increased flexibility
and outstanding long-term performance. Duct and Outside Air configurations feature conformally coated
circuit boards for moisture resistance. Several RTD and thermistor temperature sensing elements are
available in this series.
Automation Components, Inc. Made in the USA
37
HUMIDITY RH RESISTIVE
SPECIFICATIONS
Automation Components, Inc.
RH Supply Voltage (4 to 20 mA)
RH Supply Voltage (4 to 20 mA)
RH Supply Voltage (0-5 VDC)
RH Supply Voltage (0-10 VDC)
Supply Current
RH Measurement Range
RH Output
RH Accuracy @ 77oF (25oC)
Long Term Stability
Repeatablity
Sensitivity
Operating Environment, Duct/Outside
Operating Environment, Room
RH Sensor Type
Temperature Specifications
Product Dimensions (Duct/Euro)
Product Dimensions (Outside Air)
Product Dimensions (Room 2)
Product Dimensions (Room)
Product Dimensions (Stainless Plate)
(250 Ohm Load): 15 to 40 VDC/18 to 28 VAC
(500 Ohm Load): 18 to 40 VDC/18 to 28 VAC
12 to 40 VDC/18 to 28 VAC (4K Load minimum)
0-10 VDC: 18 to 40 VDC/18 to 28 VAC (4K Load minimum)
Voltage Output: 8 mA maximum | Current Output: 24 mA maximum
0-100%
2-wire: 4 to 20 mA (standard) | 3-wire: 0-5 VDC, 0-10 VDC or 4 to 20 mA
+/- 1% over 20% span (between 20 to 90%) | +/- 2%, 3%, or 5% from 10 to 95%
Less than 2% drift/5 years
0.5% RH
0.1% RH
0 to 100% RH | -40 to 140
0 to 95% RH (non-condensing) | 32 to 122
Capacitive
See corresponding Temp data sheets
Enclosure: (W) 3.60” (D) 2.25” | Probe: (L) 7.15”
Cover: (H) 3.61” (W) 4.00” (D) 2.25” | Stem: (H) 3.00” (W) 1.13”
(H) 4.50” (W) 2.75” (D) 1.12”
(H) 4.51” (W) 2.75” (D) 2.90”
Plate: (H) 4.51” (W) 2.76” (D) 0.19” | Filter: (L) 1.06”
o
F (-40 to 60oC)
o
F (0 to 50oC)
ORDERING
Select one Series (A). If A/RH1 is selected, you must specify a 20% range. Choose a Temperature Sensor (B), one Configuration (C), & one RH
Output (D). When selecting your Configuration (A), if “R2S”, “RS”, “RSO” or “R2SO,” please choose a Pot Value (E), a Sticker (F) & a Pot Action
(G). If ”R2S”, “RS”, “RSO” or ”R2SO” is not selected, your Part Number is finished after completing RH Output (D). NOTE:
not available for the SP configuration.
Accuracy Temp Sensor
Configuration
4 to 20 mA output is
A/RH1 (+/-1%) (Specify 20% Range)
(+/-2%)
A/RH2
(+/-3%)
A/RH3
(+/-5%)
A/RH5
RH Output
----
(4 to 20 mA)
(0-5 VDC)
5
(0-10 VDC)
10
Setpoint Pot Value Sticker
4001K2K
3K
100-2W
100-3W
3K
AN
(Type III)
20K
1K-2W
1K-3W
10KS
CP
1.8K
AN-BC
100K5K8.5
10K
(Type II)
20K
Specify Pot Value
1K-NI
375
100KS
CSI
10KE
10KE1
D (Duct/Euro)
(Outside Air/Euro)
O
(Outside Air/NEMA 4X)
O-4X
(Stainless Plate)
SP
(Room)
R2
(Room, Setpoint)
R2S
(Room, Override)
R2O
Blue/Red
R2SO (Room, Setpoint, Override)
(Room)
R
(Room, Setpoint)
RS
(Room, Override)
RO
(Room, Setpoint, Override)
RSO
Pot Action
DA (Direct)
(Reverse)
RA
BUILD PART NUMBER
After completing (A), (B), (C), (D), (E), (F) & (G) from the above table, fill in the Part Number Table below. An example part number is offered.
EXAMPLE: A/RH3 - CP - D
38
The Euro enclosure has a UL94-V0 flammability rating.