ACI-Automation Components RH Duct, Outside Series Instruction Sheet

GENERAL INFORMATION
The RH Duct and Outside transmitter is a Relative Humidity transmitter that can be powered with either an AC or DC supply voltage. The transmitter can also include an optional temperature sensor for monitoring the space temperature.
All units are shipped from the factory set up with a 4-20 mA output. The RH Duct and Outside transmitter is field selectable with a 4-20 mA, 0-5 VDC, or 0-10 VDC output signal that is equivalent to 0 to 100% RH.
Factory Use Only
Wire Connections
Incorrect
Installation and Operation Instructions
RH Duct and Outside Series
PLEASE READ INSTRUCTIONS CAREFULLY BEFORE INSTALLATION!
MOUNTING INSTRUCTIONS
IMPORTANT: RH Remote Probes and some Outside units include a Black Rubber Cap that fits over the sensor filter. The Cap should be placed on the sensor filter during wet/wash down processes. The Cap must be removed for normal operation.
Duct Mounting Configuration Drill a ¾” diameter hole in the duct where the transmitter is to be mounted. Insert the stainless-steel probe into the hole until the foam is in direct contact
Push tab in and pull up on the sensor cable to remove from J13 connector
ON
1342765 8
Figure #1
Figure #2
Factory Use Only
Correct
with the duct. Attach the transmitter to the duct using the supplied #8 X ¾” self-tapping screws.
Remove the cover and install your conduit connector or watertight fitting. The outer knockout ring should not be removed when using a ½” NPT conduit fitting.
After wiring the unit, place the cover back on and gently turn until it is tight.
Outdoor Mounting Configuration The transmitter should be mounted under an eave, shield, or in an area out of the elements or direct sunlight. The aluminum tube should point down when mounting the outside transmitter. Refer to Figure #2 for the proper mounting position.
Place the unit where it is to be mounted with the cover facing out. Attach the unit with the supplied #8 X ¾” self-tapping screws.
Remove the cover and install the PG11 watertight fitting supplied with the unit. The outer knockout ring should not be removed when using a ½” NPT conduit fitting.
After wiring the unit, place the cover back on and gently turn until it is tight.
Page 1 of 4 I0000546
Version : 5.0
WIRING INSTRUCTIONS
16 to 22 AWG shielded cable is recommended for all RH Transmitters. Twisted pair may be used for 2-wire current output transmitters. If using 24 VAC power, two separate wires must be pulled for the transmitter to work properly; one 16 to 22 AWG shielded cable for the supply voltage, and a second 16 to 22 AWG shielded cable for the selected output(s). Signal wiring must be run separate from high voltage wires (120-Volt). The connections to the optional temperature sensor should be made with wire nuts or crimp style connectors. Refer to Figure #3 for wiring diagram.
Caution:
It is recommended that you use an isolated
UL-listed Class 2 transformer when powering the unit with 24 VAC. Failure to wire the devices with the correct polarity when sharing transformers may result in damage to any device powered by the shared transformer.
Remove power before wiring. Never connect
or disconnect wiring with power applied.
When using shielded cable, ground the
shield only at the controller end. Grounding both ends can cause a ground loop.
Figure #3
Version : 5.0
Page 2 of 4 I0000546
OUTPUT SELECTIONS
Switches 6, 7, and 8 are used to set the RH output signal. Refer to Figure #4 for switch settings.
Output Selection Switches (SW1)
4-20 mA Output
ON
ON
2 3
1
OFF
ON
OFF
ON
ON
4 8
5 6 7
0-10 VDC Output
2
3
4
6 81
5ON7
0-5 VDC Output
OFF
1 4 5 6
2 3
7 8
Figure #4
REVERSE ACTING OUTPUT
The output can be changed to reverse acting mode. The output range stays the same but the corresponding RH value is opposite.
Example: Direct Acting (DA)
0-10V output mode,
0V = 0% RH and 10V = 100% RH Reverse Acting (RA) 0-10V output mode, 0V = 100% and 10V = 0%
To change the transmitter to reverse acting or back to direct acting, set switch 4 ON to put the unit in setup mode. After switch 4 is on, switch 2 will put the unit in direct/reverse acting mode. When switch 2 is set to ON, the output can be used to show if the unit is in direct or reverse acting mode. For direct acting, the output will be 1V for 0-5V, 2V for 0-10V, and 7.2mA for 4-20mA. For reverse acting the output will be 4V for 0-5V, 8V for 0-10V, and 16.8mA for 4-20mA.
With switches 2 and 4 ON, each time switch 5 is set to ON the output will change to reverse acting or direct acting.
To reset the unit to the default setting, toggle both switches 5 and 6 ON then OFF while both switches 2 and 4 are ON.
When all calibration is completed, remember to place the switches back into the positions that correspond to the output needed as shown in Figure #4.
Loading...
+ 2 hidden pages