ACI-Automation Components RELATIVE HUMIDITY Data Sheet

Automation Components, Inc.
RELATIVE HUMIDITYHUMIDITY
Outside Air/Euro
Room (Previous & New)
Featured Relative Humidity Product
Duct/Euro
Stainless Plate
RELATIVE HUMIDITY
Humidity Transmitter
The A/RH Series relative humidity transmitters utilize a capacitive sensing element to deliver a proportional analog output. This series features on board DIP switches which allow the user to select the desired output signal. In addition, field calibration can be performed by using the on board increment and decrement DIP switches. Duct and Outside Air configurations feature conformally coated circuit boards for moisture resistance. These enhancements provide increased flexibility and outstanding long-term performance.
35
HUMIDITY RELATIVE HUMIDITY
SPECIFICATIONS
Automation Components, Inc.
RH Supply Voltage (4 to 20 mA) RH Supply Voltage (4 to 20 mA) RH Supply Voltage (0-5 VDC) RH Supply Voltage (0-10 VDC) Supply Current RH Measurement Range RH Output Accuracy @ 77oF (25oC) Long Term Stability Repeatablity Sensitivity Operating Environment (Duct/Outside) Operating Environment (Room) RH Sensor Type Product Dimensions (Duct/Euro) Product Dimensions (Outside Air) Product Dimensions (Room 2) Product Dimensions (Room) Product Dimensions (Stainless Plate)
(250 Ohm Load): 15 to 40 VDC/18 to 28 VAC (500 Ohm Load): 18 to 40 VDC/18 to 28 VAC 12 to 40 VDC/18 to 28 VAC (4K Load minimum) 18 to 40 VDC/18 to 28 VAC (4K Load minimum) Voltage Output: 8 mA maximum | Current Output: 24 mA maximum 0-100% 2-wire: 4 to 20 mA (Factory Standard) | 3-wire: 0-5, 0-10 VDC or 4 to 20 mA +/- 1% over 20% span (between 20 to 90%) | +/- 2%, 3%, or 5% from 10 to 95% Less than 2% drift/5 years
0.5% RH
0.1% RH Duct/Outside: 0 to 100 % RH (non-condensing) | -40 to 140 Room: 0 to 95% RH (non-condensing) | 32 to 122 Capacitive Enclosure: (W) 3.60” (D) 2.25” | Probe: (L) 7.15” Cover: (H) 3.61” (W) 4.00” (D) 2.25” | Stem: (H) 3.00” (W) 1.13” (H) 4.50” (W) 2.75” (D) 1.12” (H) 4.51” (W) 2.75” (D) 2.90” Plate: (H) 4.51” (W) 2.76” (D) 0.19” | Filter: (L) 1.06”
o
F (0 to 50oC)
o
F (-40 to 60oC), Conformally Coated Boards
ORDERING
Select one Series (A). If A/RH1 is selected, you must specify a 20% range. Choose one Configuration (B) and one Output (C). NOTE: 4 to 20 mA output is not available for the SP configuration.
Accuracy Configuration
A/RH1 (+/-1%) (Specify a 20% Range)
(+/-2%)
A/RH2
(+/-3%)
A/RH3
(+/-5%)
A/RH5
D (Duct/Euro)
(Outside Air/Euro)
O
(Stainless Plate)
SP
(Room, New Enclosure)
R2
(Room, Previous Enclosure)
R
Output
---- (4 to 20 mA) (Field selectable output to 0-5 VDC or 0-10 VDC) (0 to 5 VDC) (Field selectable output to 0-10 VDC or 4 to 20 mA)
05
(0 to 10 VDC) (Field selectable output to 4 to 20 mA or 0-5 VDC)
010
BUILD PART NUMBER
After completing (A), (B), & (C) from the above table, fill in the Part Number Table below. An example part number is offered.
EXAMPLE: A/RH3 - D - 010
The Euro enclosure has a UL94-V0 flammability rating.
36