![](/html/24/24c1/24c1c8d547f092ac98e12e825b1755eea1c61096c63115c421003effff6cde63/bg1.png)
Automation Components, Inc.
TEMPERATURE | PRE-FILLED GLYCOL BOTTLE
PRE-FILLED GLYCOL BOTTLE
Temperature Sensor with Thermal Buer
The ACI Prelled Glycol Kit comes with a standard 4 inch probe, 10 foot or 20 foot long Plenum
rated FEP/FEP (Teon) cable installed in a Nalgene bottle with Food Grade Glycol. The
Platinum, Nickel and thermistor sensors are manufactured using ACI’s proven double encapsulation process and dual wall heat shrinking process to eliminate the eects of moisture on the
sensors using our high quality, thermally conductive epoxy. The sensor should be installed
inside the bottle such that the tip of the sensor is suspended approximately ½ inch above the
bottom of the bottle. A Velcro strap is included for easy mounting with an optional 304
Stainless Steel mounting bracket. Optional mounting brackets and NIST Certicates are
available as referenced in the product ordering grid on the back of the product data sheet.
Applications: Monitor Freezer and Refrigerator Temperatures, Pharmaceuticals, Thermal Buer
PRODUCT SPECIFICATIONS
Sensor Type | Curve Type | Sensing Points:
Number Wires:
RTD Sensor Output @ 0ºC (32ºF):
RTD Sensor Accuracy:
Din Standard | Temperature Coecient:
Sensor Stability:
Self-Heating | Maximum Operating Current:
Sensor Type | Curve Type | Sensing Points:
Number Wires:
Sensor Output @ 21.1ºC (70ºF):
Sensor Accuracy:
Din Standard | Temp. Coecient (0-100ºC):
Sensor Stability:
Self-Heating | Maximum Operating Current:
Sensor Type | Curve Type | Sensing Points:
Thermistor Output @ 25ºC (77ºF)
Thermistor Accuracy 0-70ºC (32-158ºF):
Stability:
Power Dissipation Constant:
Response Time (63% Step Change):
Operating | Storage Temperature Range:
Operating Humidity Range:
Lead Length | Conductor Size | Material:
Lead Wire Insulation | Wire Rating:
Probe Material | Probe Diameter:
Bottle Material | Chemical Resistance:
Bottle Sterility | Fluid Capacity:
Nalgene Bottle Operating Temperature:
Glycol Properties | Glycol Freezing Point
Standard Mounting (L x W x Dia.)
Product Dimensions:
Product Weight:
Agency Approvals:
Platinum RTD | PTC (Positive Temperature Coecient) | One
A/100/1K-2W-PO-4”: Two (Non-Polarity Sensitive) | A/100/1K-3W-PO-4”: Three (Polarity Sensitive)
A/100-xW-PO-4”: 100 Ohms nominal | A/1K-xW-PO-4”: 1000 Ohms nominal
+/- 0.06% Class A (Tolerance Formula: +/- ºC = (0.15ºC + (0.002 * |t|))
where |t| is the absolute value of Temperature above or below 0ºC in ºC)
-40ºC (-40ºF): +/-0.23ºC (+/-0.414ºF) | 0ºC (32ºF): +/-0.15ºC (+/-0.27ºF)
120ºC (248ºF): +/-0.39ºC (+/-0.71ºF)
Din EN 60751 (IEC 751) | 3850 ppm / ºC
+/- 0.03% after 1000 Hours @ 300ºC (572ºF)
100 Ohm RTD: 7 mW/ºC (Still Air) | 5 mA; 1K Ohm RTD: 4mW/ºC (Still Air) | 3 mA
Nickel RTD | PTC (Positive Temperature Coecient) | One
Two (Non-Polarity Sensitive)
1000 Ohms nominal
-40ºC (-40ºF): +/-1.52ºC (+/-2.73ºF) | 0ºC (32ºF): +/-0.4ºC (+/-0.72ºF) | 21.1ºC (70ºF): +/-0.17ºC
(+/-0.34ºF) | 54.4ºC (130ºF): +/-0.56ºC (+/-1.00ºF) | 121ºC (250ºF): +/-1.25ºC (+/-2.25ºF)
Din 43760 | 6370 ppm/ºC
+/- 0.05% after 1000 Hours @ 150ºC (302ºF)
0.3ºC/mW (Still Air) | 5 mA
Thermistor | NTC (Negative Temperature Coecient) | One
A/1.8K: 1.8KΩ nom.
A/3K: 3KΩ nom.
A/AN (Type III): 10KΩ nom.
+/-0.2ºC (+/-0.36ºF) | A/1.8K: +/-0.5ºC @ 25ºC (77ºF) & (+/-1.0ºC) (+/-1.8ºF)
Sensor Dependent; Contact ACI for more information on the sensor in question
3 mW/ºC except A/1.8K: 1 mW/ºC
25 Seconds Nominal
-40 to 120ºC (-40 to 248ºF) | -40 to 85ºC (-40 to 185ºF)
10 to 95% RH, condensing
10 Feet (3.05m) or 20 Feet (6.10m)** | 22 AWG (0.65mm) | Tin Plated Copper
FEP/FEP (Teon) Cable | CL2P/CMP Plenum Rated Cable (minimum)
304 Stainless Steel | 0.250” (6.35mm)
Nalgene ((HDPE) High Density Polyethylene) | Resistant to most acids, bases, and alcohols
Lab Quality, Non-Sterile | 67 ml (2 oz.)
-100ºC (-73.2ºF) to 120ºC (248ºF)
Food Grade USP (Propylene Glycol); Non-Toxic | -59ºC (-74.2ºF)
7” (17.78 cm) x 1” (2.54 cm) x 2 1/8 (5.40 cm) Velcro Strap;
Bottle: 3.40” (86mm) (H) x 1.535” (39.00 mm) (O.D.) | Probe: 4” (101.6 mm) Length
A/xx-PO-4”-10’CL2P: 0.015 lbs. (68.1g) | A/xx-PO-4”-20’CL2P: 0.025 lbs. (113.4g)
CE, RoHS2, WEEE
A/CP (Type II): 10KΩ nom.
A/AN-BC: 5.238KΩ nom.
A/CSI: 10KΩ nom.
A/10KS: 10KΩ nom.
A/100KS: 100KΩ nom.
A/20K: 20KΩ nom.
Call: 1-888-967-5224 | Web: www.workaci.com
TEMPERATURE | ##
![](/html/24/24c1/24c1c8d547f092ac98e12e825b1755eea1c61096c63115c421003effff6cde63/bg2.png)
TEMPERATURE | PRE-FILLED GLYCOL BOTTLE
DIMENSIONAL DRAWING
Automation Components, Inc.
2.59” (65.81mm)
Ø1.27”
(32.16mm)
1.53” (38.96”)
Front View Right View Top View
CUSTOM ORDERING
A. Sensor Series
B. Model Series
C. Number of Wires
D. Conguration
E. Probe Length
G. Lead Wire Type
I. NIST
Select One (1)
Note*: All 20’ Sensors are not CE compliant, but are RoHS2 compliant
No Selection Required
Select One (1)
Select One (1)
No Selection Required
No Selection Required
Select One (1)
No Selection Required
No Selection Required
A/
100 = 100 Ohm Platinum RTD
1K = 1000 Ohm Platinum RTD
1K-NI = 1000 Ohm Nickel RTD
1.8K = 1.8K Ohm Thermistor
3K = 3 K Ohm Thermistor
AN = 10K (Type III) Ohm Thermistor
---- = Any Thermistor/Nickel Sensor | 2W = Two Wire (100/1K RTD only)
3W = Three Wire (100/1K RTD Only)
PO = Probe Only
4” = 4” Probe
10’ = 10 Feet (3.05m) | 20’ = 20 Feet* (6.10m)F. Lead Length
CL2P = 2 Conductor Plenum Rated Cable
GF2 = Glycol Filled Bottle, 2 Oz. Glycol, Velcro StrapH. Glycol Filled
---- = No NIST Certicate | NIST = NIST Certicate (Must Specify 1, 3 or 5 Points)
3.63” (92.28mm)
Model # Example:
PO
A/
A.
C.
B.
3W
100
4”E.10’F.CL2PG.GF2H.NIST
D.
AN-BC = 10K Thermistor Ohm | 11K Shunt
CP = 10K (Type II) Ohm Thermistor
CSI = 10K Ohm Thermistor
10KS = 10K Ohm Thermistor
20K = 20K Ohm Thermistor
100KS = 100K Ohm Thermistor
1.81” (45.97mm)
I.
MODEL #
A/
PO
4”
CL2P
GF2
ACCESSORIES ORDERING
Model #
A/GLYCOL BRACKET
A/GLYCOL KIT
TEMPERATURE | ##
Item #
130126
130127
Description
304 SS Steel Mounting Bracket for 2 oz. bottle with Stainless Screws
2 oz. Glycol Bottle, 304 SS Mounting Bracket, Water Tight Fitting, Screws, No Glycol
Call: 1-888-967-5224 | Web: www.workaci.com
Model # Example:
A/GLYCOL KIT
Revision C0000002 | Rev 1.0
-OR-
130127