Forty Eight (48) Channel Power Meter
The Powerscout™ PS48HD has been designed to be one of the safest and most exible power
meters on the market today since it can monitor up to 16 three phase or 48 single phase circuits
from a single voltage reference or two voltage references simultaneously. All four Modbus and
BACnet Serial/Ethernet communication protocols are included in a single meter reducing the
number of skus required. Unlike other power meters, the PS48 can be easily paired with any DENT
Standard or Revenue Grade CTs with a mV output to monitor operating currents from 0.25 to 4000
Amps. This reduces lead times since the PS48s don’t need to be congured at the factory and
shown on the Standard and Revenue Grade CTs product data sheets. Each meter also includes additional features such as the Tri-Color PhaseChek™
display, high voltage cover (safer installation), positive and negative Modbus Registers for bi-directional metering, ViewPoint™ HD conguration software,
Revenue Grade 0.2% accuracy, NIST Calibration Certicate, displays real time information, two pulse outputs and is internally fused. The ViewPoint™ HD
Conguration Software allows for easy conguration of the PS48 while sitting at your desk using a single USB Port and standard USB A-B cable. All setup
table information can be saved to allow for easy programming of multiple meters with similar congurations.
Applications: Energy and Demand Metering, Data Centers, Bi-Directional Metering, Load Surveys, LEED/Green Projects, Real Time Power Monitoring in
Commercial, Retail and Industrial Environments
PRODUCT SPECIFICATIONS
Service Type:
Power:
AC Protection:
Power Output:
Voltage Channels:
Current Channels:
Maximum Current Input:
Measurement Type:
Line Frequency:
Waveform Sampling:
Parameter Update Rate:
Measurements:
Accuracy:
Resolution:
Display:
Alarms:
Pulse Outputs:
Hardware:
Supported Protocols:
Maximum Distance:
Supported Baud Rates:
Data Bits | Parity | Stop Bit
Data Formats:
Operating Temperature Range:
Operating | Storage Humidity Range:
Enclosure Material | Flammability Rating:
High Voltage Cover IP Rating:
Enclosure Knockouts:
Wiring Connections
Wire Size:
Mounting:
ViewPoint™ HD Software System:
Security:
Agency Approvals:
Product Weight:
Product Dimensions (L x W x H):
allows for easy setup or reconguration of the meter in the eld. All CTs are sold separately, as
Single Phase, Split Phase, Three Phase - 4 Wire (Wye) | Three Phase - 3 Wire (Delta)
From L1 Phase to L2 Phase. 90 to 600 VAC RMS CAT III 50/60 Hz, 500 mA AC maximum
0.5A Fuse 200kA interrupt capacity
Unregulated 12 VDC Output, 200 mA, self-resetting fuse
Two Voltage Reference Inputs, 80 to 346 Volts AC Line to Neutral, 600 VAC Line to Line, Cat. III
48 Channels, 0.525 VAC max, 333 mV CTs, 0 to 4000 Amps with Rocoil™ CTs
150% of Current transducer rating (mV CTs) to maintain accuracy | Measure up to 4000 Amps (Rocoil™ CTs)
True RMS using High Speed Digital Signal Processing (DSP) with continuous sampling
50/60 Hz
1.8 kHz
1 second
Volts, Amps, kW, kVAR, kVA, aPF, dPF, kW Demand, kVA Demand, Import (Received) kWh, Export (Delivered)
kWh, Net kWh, Import (Received) kVAh, Export (Delivered) kVAh, Net kVAh, Import (Received) kVARh,
Export (Delivered) kVARh, Net kVARh, THD, Theta, Frequency, All parameters for each phase and system total
0.2% ANSI C12.20-2010 Class 0.2
Values reported in IEEE-754 single precision oating point format (32 Bit)
4-Line Display, Tri-Color Backlight (PhaseChek™)
Voltage Phase Loss Alarm (SPDT Relay – 30 VDC)
Open Collector, Optically Isolated, 5mA maximum current, 40V maximum open voltage (Quantity: 2)
RS-485, Ethernet and USB (For Conguration Only)
Modbus (Using SunSpec IEEE-754 Single Precision Floating Point Model) or BACnet
1200 meters (3,937 Feet) with data range of 100K bits/second or less
9600, 19200, 38400, 57600, 76800, 115200 Baud
8 | None, Even, One | 2, 1
Modbus, BACnet MS/TP, Modbus TCP or BACnet IP
-4 to 140ºF (-20 to 60ºC), At -20ºC (-4ºF) a minimum of 100 VAC is required to power the Meter
5 to 95%, non-condensing
ABS Plastic | UL 94V-0
IP40
1” EMT Conduit Knockouts (Quantity: 6) | No Drilling Required
De-pluggable, Screw/Push Lock Terminal Blocks (Polarity Sensitive - PhaseChek™ Indication)
12-22 AWG (5.48 to 0.397 mm)
Panel Mount/Enclosure or PCBA Version: 0.5” Standos, #6 (Quantity: 6) (User Supplied Screws)
Windows® 10, Windows® 8, Windows® 7 (Included with Purchase of Meter)
2 Password Levels
RoHS2, WEEE, ISO 9001-2008, Made in USA, BTL (BACnet) Certied
UL Recognized: Circuit Board Only Version | UL Listed: Indoor Enclosure Version (File # E186827)
CE (EN 61000-6-4: Class A) | ANSI C12.20 Class 0.2: NIST Traceable Calibration Certicate Included
See Ordering Grid for product weights, CTs not Included
Enclosure: 13.25” (336.55 mm) x 9.75” (247.65 mm) x 3.12” (79.24 mm)
PCBA Version (Circuit Board Only): 8.50” (215.90 mm) x 8.50” (215.90 mm) x 2.50” (63.50 mm)
Call: 1-888-967-5224 | Web: www.workaci.com
CURRENT | ##

CURRENT | POWER METERS | POWERSCOUT™ 48
DIMENSIONAL DRAWING
13.25”
(336.55mm)
9.68”
(246.06mm)
Front & Back View Right View Top View
9.50”
(241.30mm)
6.00”
(152.40mm)
3.00”
(76.20mm)
Automation Components, Inc.
Ø1.32”
(33.58mm)
Type 6 PLC
1.54”
(39.20mm)
3.12”
(79.24mm)
5.50”
9.75”
(139.70mm)
(247.65mm)
STANDARD ORDERING
Model #
PS48HD-C-D-N
PS48HD-C-N-N
PS48HD-P-D-N
PS48HD-P-N-N
Note*: Communication Protocols Included
Item #
143110
143111
143112
143113
Description
Powerscout™ PS48HD with Enclosure & Display
Powerscout™ PS48HD with Enclosure & No Display
Powerscout™ PS48HD with Mounting Plate & Display
Powerscout™ PS48HD with Mounting Plate & No Display
Model # Example:
PS48HD-C-N-N
-OR-
Product Weight
4.85 lbs. (2.20 kg)
4.60 lbs. (2.09 kg)
3.70 lbs. (1.68 kg)
3.45 lbs. (1.57 kg)
143111
Modbus* BACnet*
TCP/IP
RTU
•
•
•
•
MS/TP
•
•
•
•
IP
•
•
•
•
•
•
•
•
CURRENT | ##