ACI-Automation Components POWERSCOUT Data Sheet

Automation Components, Inc.
CURRENT
POWERSCOUT
TM
TM
POWERSCOUT
Networked Power Meters-Sub Meters
The PowerScoutTM 3037 is an intuitive, networked power meter designed to monitor and provide consumption data. The PowerScoutTM monitors voltage, current, power, energy, and many other electrical parameters on single and three phase circuit installations. Data updates occur once every second to ensure timely and accurate results. Convenient size and versatility make it the ideal device for monitoring and diagnosing consumption data in commercial, industrial, government, and retail environments. The PowerScoutTM features field-selectable Modbus or BACnet® protocols, digital pulse outputs, interchangeable split-core or RoCoil current transformers, and direct USB setup. Connect via serial RS-485 or optional Ethernet and use the optional back-lit display to verify setup and check real time values. The PowerScout makes over 50 total electrical measurements, including energy and demand.
Automation Components, Inc. Made in the USA
85
CURRENT
SPECIFICATIONS
Service Type Measurements Power Power Output Pulse Output Voltage Channels Current Channels Waveform Sampling Parameter Update Rate Accuracy Max. Current Input Environmental Temp, RH Resolution Safety Approvals Product Dimensions
COMMUNICATIONS
Direct Max Distance Baud Rate Data Bits Parity Stop Bit Data Formats
VIEWPOINT SOFTWARE
Operating System Communications
POWERSCOUT
Single phase, 3 phase-4 wire (Wye), 3 phase-3 wire (Delta) Volts, Amps, kW, kWh, kVAR, kVARh, kVA, kVAh, aPF, dPF L1 Phase to L2 Phase, 80-600 VAC CAT III 50/60Hz, 90 mA Max, Non-user replaceable 0.5 Amp internal fuse protection Unregulated 5 VDC output, 140 mA Max, resetting fuse Open collector, 5 mA max current, 30V max open voltage 80-346 VAC line-to-neutral, 600V Line-to-Line, CATIII 3 channels, 0.525 VAC max, 333 mV CTs, 0-4,000A 12 kHz
0.5 sec
0.2% (<0.1% typical) ANSI C12.20-2010 Class 0.2 158% of current transducer rating (mV CTs) to maintain accuracy. Measure up to 4000A with RoCoil Temp: -7 to 60°C (-20 to 140°F), RH: 5% to 95% non-condensing
0.01A, 0.1V, 0.01 Watt, 0.01 VAR, 0.01 VA, 0.01 Power Factor depending on Scalar Setting 4RH8 (file number: E186827) conforms to UL STD 61010-1; certified to CSA STD C22.2 No. 61010-1 (L) 9.5” x (W) 3.3” x (H) 1.6”
User selectable Modbus/BACnet Master Slave Token Passing protocol (MS/TP) or BACnet IP/Modbus TCP over ethernet 1200 meters with data range of 100K bits/second or less 9600 (Modbus default), 19200, 38400, 57600, 76800 (BACnet default), 115200 8 None, Even, Odd 2,1 Modbus or BACnet
Windows® 7, 8, Vista, XP RS-485 & USB standard. Ethernet available. One USB Port required on PC
Automation Components, Inc.
Automation Components, Inc.
TM
CTs
TM
MODBUS REGISTER/BACNET OBJECT DESCRIPTIONS (PARTIAL LIST)
System True Energy +/- (kWh) Instantaneous Total True Power +/- (kW) Peak Demand (Adj. Window) (kW) Max. Instantaneous Power +/- (kW) Min. Instantaneous Power +/- (kW) System Reactive Energy +/- (kVARh) System Apparent Energy (kVAh) System Apparent Power (kVA) System Displacement Power Factor (dPF) System Apparent Power Factor (aPF) Average Line to Line Voltage (Volts) Average Line to Neutral Voltage (Volts)
Individual Phase to Phase Voltages Individual Phases True Energy +/- (kWh) Individual Phases True Power +/- (kW) Individual Phases Reactive Energy +/- (kVARh) Individual Phases Reactive Power +/- (kVAR) Individual Phases Apparent Energy (kVAh) Individual Phases Apparent Power (kVA) Individual Phases Apparent Power Factor (aPF) Individual Phases Displacement Power Factor (dPF) Individual Phases Line to Neutral Voltages (Volts) Individual Phases Line to Line Voltages (Volts) PS3037: Net system true energy (kWh)
ORDERING
Please select one PowerScout
PowerScout
PS3037-S-N (Serial Communications Only (BACnet MS/TP or Modbus RTU), no Display) PS3037-S-D PS3037-E-N PS3037-E-D
(Serial Communications Only (BACnet MS/TP or Modbus RTU), with Display) (Ethernet (BACnet IP or Modbus TCP), Serial Communications (BACnet MS/TP or Modbus RTU), no Display) (Ethernet (BACnet IP or Modbus TCP), Serial Communications (BACnet MS/TP or Modbus RTU), with Display)
TM
(A).
TM
BUILD PART NUMBER
After completing (A) from the above table, fill in the Part Number Table below. An example part number is offered.
configure the PowerScout Modbus protocols. The USB cable will also power the meter when connected to a PC. USB cables are not included and must be purchased separately.
TM
Meter and to monitor real time values to ensure meter is configured properly. A type AB USB cable may be used between a PC and a PS3037 meter and is the preferred method for setting up a PS3037 with
All meters include the viewpoint software to
86
EXAMPLE: PS3037-S-N