Automation Components, Inc.
CO AND NO2GAS
Duct Mount (CO & NO2)
Featured CO/NO2 Product
Room (CO & NO2)
NEMA 4X
CO AND NO2
Carbon Monoxide & Nitrogen Dioxide Sensors
The CO and NO2 Series transmitters monitor carbon monoxide, or nitrogen dioxide, and are designed
for the continuous monitoring of vehicle exhaust in non-hazardous areas. A wide spectrum, long life
electrochemical sensor measures the amount of carbon monoxide or nitrogen dioxide in the environment.
Both the Room and Duct transmitters are offered in a standard NEMA 1 rated ABS Polycarbonate plastic
enclosure. An optional NEMA 4X watertight and dust proof enclosure is available with the room transmitter.
Other options include an LCD display with (2) SPDT Form 1C relays and a buzzer.
Automation Components, Inc.
97
GAS CO AND NO2
SPECIFICATIONS
Automation Components, Inc.
Supply Voltage
Supply Current
Accuracy/Repeatability
Operating Range (CO)
Operating Range (NO2)
Temperature Range
Operating Humidity
Coverage Area
Indicators
Sensor Type
Outputs
Response Time
Mounting Height
Sensor Life Span
Relay Contact Arrangement
Relay Contact Rating
Relay Life Expectancy
Buzzer Rating
Operating Pressure
Product Dimensions (All CO & NO2)
Product Dimensions (NEMA 4X)
+24 VDC or 24 VAC Floating or one side ground
100 mA nominal/250 mA maximum
+/- 2.5% of Reading/+/- 1.0% of Reading
0-125 ppm (standard)/0-250 ppm (field adjustable)
0-6 ppm (factory set)/0-10 ppm (field adjustable)
o
-20
to 40oC (-4o to 104oF)
15 to 90%, non-condensing, 0 to 99% Intermittent (non-condensing)
7,500 Sq. Ft. maximum
Two line 8 digit Alpha Numberic LCD (standard) | (2) Red LED’s for Relay Status
Electrochemical
4-20 mA, 2-10 VDC, Digital RS-485, (2) SPDT Form 1C Relay
Less than 60 seconds typical for a 90% step change
4 to 6’ above floor (CO)/0.5 to 1.5’ above floor (NO2)
2 to 3 years typical (under normal conditions)
Two SPDT (2 Form C) Relays
1A @ 30 VDC / 0.5A @ 125 VAC (Resistive Load)
200,000 cycles minimum with 1A @ 30 VDC
Rated for 85 dB @ one foot
Atmosphereic +/-10%
(H) 6.00” (W) 3.50” (D) 1.09”
(H) 6.60” (W) 4.20” (D) 2.60”
ORDERING
Select one Gas Type (A), one Housing (B) (If any “Room Mount” was selected as a Configuration (A)), one Relay/Buzzer (C) & one Display (D).
NOTE:
The LCD option is not available for NEMA 4X related configurations.
Gas Type Housing Relay/Buzzer
CO-R (Room) (Complete B, C & D)
(Duct with Pitot Tube) (Only Complete C & D)
CO-D
(Room) (Complete B, C & D)
NO2-R
(Duct with Pitot Tube) (Only Complete C & D)
NO2-D
---- (NEMA 1) (Standard)
(NEMA 4X)
4X
---- (None) (Standard)
(2) (SPDT form 1C)
RB
Display
----
(No Display)
(LCD Display)
D
BUILD PART NUMBER
After completing (A), (B), (C) & (D) from the above table, fill in the Part Number Table below. An example part number is offered.
EXAMPLE: CO-D - RB - D
98