ACI-Automation Components CO, NO2 Data Sheet

Automation Components, Inc.
CO AND NO2GAS
Duct Mount (CO & NO2)
Featured CO/NO2 Product
NEMA 4X
CO AND NO2
Carbon Monoxide & Nitrogen Dioxide Sensors
The CO and NO2 Series transmitters monitor carbon monoxide, or nitrogen dioxide, and are designed for the continuous monitoring of vehicle exhaust in non-hazardous areas. A wide spectrum, long life electrochemical sensor measures the amount of carbon monoxide or nitrogen dioxide in the environment. Both the Room and Duct transmitters are offered in a standard NEMA 1 rated ABS Polycarbonate plastic enclosure. An optional NEMA 4X watertight and dust proof enclosure is available with the room transmitter. Other options include an LCD display with (2) SPDT Form 1C relays and a buzzer.
Automation Components, Inc.
97
GAS CO AND NO2
SPECIFICATIONS
Automation Components, Inc.
Supply Voltage Supply Current Accuracy/Repeatability Operating Range (CO) Operating Range (NO2) Temperature Range Operating Humidity Coverage Area Indicators Sensor Type Outputs Response Time Mounting Height Sensor Life Span Relay Contact Arrangement Relay Contact Rating Relay Life Expectancy Buzzer Rating Operating Pressure Product Dimensions (All CO & NO2) Product Dimensions (NEMA 4X)
+24 VDC or 24 VAC Floating or one side ground 100 mA nominal/250 mA maximum +/- 2.5% of Reading/+/- 1.0% of Reading 0-125 ppm (standard)/0-250 ppm (field adjustable) 0-6 ppm (factory set)/0-10 ppm (field adjustable)
o
-20
to 40oC (-4o to 104oF) 15 to 90%, non-condensing, 0 to 99% Intermittent (non-condensing) 7,500 Sq. Ft. maximum Two line 8 digit Alpha Numberic LCD (standard) | (2) Red LED’s for Relay Status Electrochemical 4-20 mA, 2-10 VDC, Digital RS-485, (2) SPDT Form 1C Relay Less than 60 seconds typical for a 90% step change 4 to 6’ above floor (CO)/0.5 to 1.5’ above floor (NO2) 2 to 3 years typical (under normal conditions) Two SPDT (2 Form C) Relays 1A @ 30 VDC / 0.5A @ 125 VAC (Resistive Load) 200,000 cycles minimum with 1A @ 30 VDC Rated for 85 dB @ one foot Atmosphereic +/-10% (H) 6.00” (W) 3.50” (D) 1.09” (H) 6.60” (W) 4.20” (D) 2.60”
ORDERING
Select one Gas Type (A), one Housing (B) (If any “Room Mount” was selected as a Configuration (A)), one Relay/Buzzer (C) & one Display (D). NOTE:
The LCD option is not available for NEMA 4X related configurations.
Gas Type Housing Relay/Buzzer
CO-R (Room) (Complete B, C & D)
(Duct with Pitot Tube) (Only Complete C & D)
CO-D
(Room) (Complete B, C & D)
NO2-R
(Duct with Pitot Tube) (Only Complete C & D)
NO2-D
---- (NEMA 1) (Standard) (NEMA 4X)
4X
---- (None) (Standard) (2) (SPDT form 1C)
RB
Display
----
(No Display)
(LCD Display)
D
BUILD PART NUMBER
After completing (A), (B), (C) & (D) from the above table, fill in the Part Number Table below. An example part number is offered.
EXAMPLE: CO-D - RB - D