ACI-Automation Components FREEZER RTDS Data Sheet

Automation Components, Inc.
FREEZER RTDSTEMPERATURE
Galvanized Raco Box
NEMA 4X
Featured Freezer RTD Product
Glycol Bottle (Left), 3PT Glycol Bottle (Right)
NEMA 3R
Lead Wire
FREEZER RTDS
Platinum RTDs
The A/100-LTS, A/1K-LTS, A/TT100-LTS, and A/TT1K-LTS Series sensors and temperature transmitters incorporate a Class B, wire wound platinum RTD sensor which conforms to DIN-IEC-751 and DIN 43760 platinum RTD standards. They are designed to withstand the extreme temperature fluctuations that cause issues with standard temperature sensors in your typical freezer application. The ACI A/TTM Series
offers a matched calibration of the sensor and transmitter, which improves the measurement accuracy. An N.I.S.T. certificate is provided with all A/TTM Series devices. Robust, high- end performance in addition to N.I.S.T certification makes this series suitable for applications such as pharmaceutical or scientific
Automation Components, Inc. Made in the USA
27
TEMPERATURE
SPECIFICATIONS
FREEZER RTDS
Automation Components, Inc.
Sensor Accuracy (single point) Sensor Accuracy (formula) Sensor Accuracy Class Combined Sensor & Transmitter Accuracy Stability Repeatability Sensor Operating Temperature Range Temperature Coeffcient Standardization Product Dimensions (Lead Wire) Product Dimensions (Glycol Kit) Product Dimensions (Glycol-3 PT-Kit) Product Dimensions (NEMA 3R) Product Dimensions (NEMA 4X) Product Dimensions (Galvanized Raco Box)
* [t] = Numerical value of the temperature in oC without taking into account positive or negative signs.
+/-0.54oF @ 32oF (0oC)
o
0.3
C + 0.005 X [t] = maximum error C* Class B Tolerance +/-1.5% span less than +/-0.1
o
+/-0.3
-198 to 150
0.00385 Ohm/Ohm/ DIN-IEC-751 (formerly DIN 43760) (L) 6, 10, 30, 50 & 100’ Bottle: (H) 3.39” (DIA) 1.53” Bracket: (L) 1.50” (W) 1.82” (H) 2.60” Bottle: (H) 4.04” (DIA) 2.62” Bracket: (L) 3.00” (W) 2.63” (H) 3.36” (H) 4.58” (W) 2.82” (D) 2.25” (H) 3.70” (W) 2.55” (D) 2.22” (H) 4.20” (W) 2.326” (D) 1.979”
o
C (+/-0.54oF)
C drift
o
C (-324 to 302oF)
o
C
ORDERING
Select one Series (A) & specify Span if necessary (parts with TT require spans & outputs). Choose one Output (B), one Housing (C) & one Lead Wire (D). If a Bottle, or an additional accessory is desired, please complete (1) below. NOTE: 10’ leads.
Sensor Series Output Housing
A/100-LTS (100Ω Platinum RTD) A/1K-LTS A/TT100-LTS A/TT1K-LTS A/TTM100-LTS A/TTM1K-LTS
(1,000Ω Platinum RTD)
(Transmitter, 100Ω RTD)
(Transmitter, 1,000Ω RTD)
(Matched Transmitter)
(Matched Transmitter)
---- (Resistive) 1
(1 to 5 VDC)
2
(2 to 10 VDC)
4
(4 to 20 mA)
---- (No Housing) GD
(Galvanized Raco Box)
4X
(NEMA 4X)
BB
(NEMA 3R)
The A/TT100-LTS Series is only available with 6 or
Lead Wire
6’ (6 Foot Leads) 10’
(10 Foot Leads)
30’
(30 Foot Leads)
50’
(50 Foot Leads)
Glycol (Bottle, Accessories)
A/GLYCOL-BOTTLE A/GLYCOL-BRACKET A/GLYCOL-KIT A/GLYCOL-3PT-BOTTLE A/GLYCOL-3PT-BRACKET A/GLYCOL-3PT-KIT
(Single Probe)
(Bracket Only)
(Mounting Bracket & Glycol Bottle)
(Single Probe)
(Bracket Only)
(Mounting Bracket & Glycol Bottle)
BUILD PART NUMBER
After completing (A), (B), (C) & (D) from the above table, fill in the Part Number Table below. (1) is an additional configuration. An example part number is provided.
EXAMPLE: A/TT100-LTS - 1 - 4 - 4X - 10’
EXAMPLE: A/GLYCOL BOTTLE
28