ACI-Automation Components BACnet ROOM SERIES Installation Instructions

BACnet ROOM SERIES
Installation & Operation Instructions
GENERAL INFORMATION
The BACnet Room Series sensor is designed for use with electronic controllers in commercial heating and cooling building management systems. The ACI BACnet Room Series sensor can be ordered to monitor temperature, RH, or temp/RH in Commercial Room environments. It uses BACnet MS/TP for physical connection to a BAS or controller, has dip switches to set addresses and baud rate, and has on board end-of-line termination. There is no analog output.
WIRING INSTRUCTIONS
The BACnet Room Series temperature sensor has a depluggable terminal block located on the backside of the PCB. 16 to 22 AWG two conductor shielded cable is recommended for powering the sensors.
PRECAUTIONS
Do NOT run the wiring in any conduit with line
voltage (24/120/230 VAC).
FIGURE 1: LAYOUT
FRONT VIEW
LED
8421421
643216
BACK VIEW
BAUDADDRESS
RESET BUTTON
END OF LINE TERMINATION
EN DIS
Remove power before wiring. NEVER connect or
disconnect wiring with power applied.
It is recommended that you use an isolated
UL-listed Class 2 transformer when powering the unit with 24 VAC. Failure to wire the devices with the correct polarity when sharing transformers may result in damage to any device powered by the shared transformer.
• If the 24 VDC or 24VAC power is shared with devices that have coils such as relays, solenoids, or other inductors, each coil must have an MOV, DC/AC Transorb, Transient Voltage Suppressor (ACI Part:
142583), or diode placed across the coil or inductor. The cathode, or banded side of the DC Transorb or diode, connects to the positive side of the power supply. Without these snubbers, coils produce very large voltage spikes when de-energizing that can cause malfunction or destruction of electronic circuits.
D+ D- GN V
TERMINAL BLOCKS (LOCATED ON BACK)
BACNET PWR
TABLE 1: WIRING CONNECTIONS
TERMINAL BLOCKS
+V GN D­D+
CONNECTIONS
Power Supply Positive 12-36 VDC / 24VAC Power Supply Common or Ground EIA-485 Data Negative EIA-485 Data Positive
Page 1
Version 1.0
I0000803
MOUNTING INSTRUCTIONS
ACI recommends using BELDEN 3105 for communication wiring. This wire has 120 ohm input impendence. The terminal blocks allow for (1) or (2) wires to be connected in each position for daisy chaining. Daisy chain the RS-485 wiring and do not use “Star” or “T” wiring.
Avoid running communication wires next to AC line voltage wires. These can be sources of noise that can aect signal quality.
For optimal readings, follow these tips:
Do not install on external walls
Avoid air registers, diusers, vents, and windows
Avoid conned areas such as shelves, closed
cabinets, closets, and behind curtains
Eliminate and seal all wall and conduit penetrations.
Air migration from wall cavities may alter temperature readings.
Do not install near heat sources. eg: lamps,
radiators, direct sunlight, copiers, chimney walls, walls concealing hot-water pipes
A thermally-insulated backing should be used
when tting to solid walls (concrete, steel, etc.). ACI part: A/ROOM-FOAM-PAD. Be sure to cut out an area for slotting the detachable terminal block.
Separate the cover from the base. Attach the base directly to the wall or to a standard 2” x 4” junction box using the (2) #6-32 x 1” screws provided.
FIGURE 2: ENCLOSURE DIMENSIONS
1.12"
(28.36 mm)
2.75"
(69.85 mm)
4.50"
(114.30 mm)
FRONT
DETACHABLE TERMINAL BLOCK
BOTTOM
(5.05 mm)
FIGURE 3: MOUNTING DIAGRAM
DETACHABLE TERMINAL BLOCK
MOUNTING SCREW
(#6-32 x 1”)
CIRCUIT BOARD
COVER
OPTIONAL INSULATING GASKET
BACKPLATE
48” - 60”
(1.2 - 1.5 m)
0.20"
Refer to the wiring instructions (p. 1-2) to make necessary connections. After wiring, attach the cover to the base by snapping the top of the cover on rst and then the bottom. Tighten the cover down, using the (2) 1/16” Allen screws located in the bottom of the housing. A 1/16” Hex driver is needed to secure the cover to the base.
Take care when mounting. Check local code for mounting height requirements. Typical mounting heights are 48-60” (1.2-1.5 m) o the ground and at least 1.5’ (0.5 m) from the adjacent wall. The sensor should be mounted in an area where air circulation is well mixed and not blocked by obstructions.
*Reference FIGURE 2 and 3
BACnet MS/TP INTERFACE
The BACnet Master-Slave/Token-Passing (MS/TP) data link protocol uses EIA-485 as a two-wire, daisy chain network. A branch is
a discrete chain of devices connected to a controller.
Page 2
Version 1.0
I0000803
Loading...
+ 3 hidden pages