ACI-Automation Components BACnet ROOM SERIES Installation Instructions

BACnet ROOM SERIES
Installation & Operation Instructions
GENERAL INFORMATION
The BACnet Room Series sensor is designed for use with electronic controllers in commercial heating and cooling building management systems. The ACI BACnet Room Series sensor can be ordered to monitor temperature, RH, or temp/RH in Commercial Room environments. It uses BACnet MS/TP for physical connection to a BAS or controller, has dip switches to set addresses and baud rate, and has on board end-of-line termination. There is no analog output.
WIRING INSTRUCTIONS
The BACnet Room Series temperature sensor has a depluggable terminal block located on the backside of the PCB. 16 to 22 AWG two conductor shielded cable is recommended for powering the sensors.
PRECAUTIONS
Do NOT run the wiring in any conduit with line
voltage (24/120/230 VAC).
FIGURE 1: LAYOUT
FRONT VIEW
LED
8421421
643216
BACK VIEW
BAUDADDRESS
RESET BUTTON
END OF LINE TERMINATION
EN DIS
Remove power before wiring. NEVER connect or
disconnect wiring with power applied.
It is recommended that you use an isolated
UL-listed Class 2 transformer when powering the unit with 24 VAC. Failure to wire the devices with the correct polarity when sharing transformers may result in damage to any device powered by the shared transformer.
• If the 24 VDC or 24VAC power is shared with devices that have coils such as relays, solenoids, or other inductors, each coil must have an MOV, DC/AC Transorb, Transient Voltage Suppressor (ACI Part:
142583), or diode placed across the coil or inductor. The cathode, or banded side of the DC Transorb or diode, connects to the positive side of the power supply. Without these snubbers, coils produce very large voltage spikes when de-energizing that can cause malfunction or destruction of electronic circuits.
D+ D- GN V
TERMINAL BLOCKS (LOCATED ON BACK)
BACNET PWR
TABLE 1: WIRING CONNECTIONS
TERMINAL BLOCKS
+V GN D­D+
CONNECTIONS
Power Supply Positive 12-36 VDC / 24VAC Power Supply Common or Ground EIA-485 Data Negative EIA-485 Data Positive
Page 1
Version 1.0
I0000803
MOUNTING INSTRUCTIONS
ACI recommends using BELDEN 3105 for communication wiring. This wire has 120 ohm input impendence. The terminal blocks allow for (1) or (2) wires to be connected in each position for daisy chaining. Daisy chain the RS-485 wiring and do not use “Star” or “T” wiring.
Avoid running communication wires next to AC line voltage wires. These can be sources of noise that can aect signal quality.
For optimal readings, follow these tips:
Do not install on external walls
Avoid air registers, diusers, vents, and windows
Avoid conned areas such as shelves, closed
cabinets, closets, and behind curtains
Eliminate and seal all wall and conduit penetrations.
Air migration from wall cavities may alter temperature readings.
Do not install near heat sources. eg: lamps,
radiators, direct sunlight, copiers, chimney walls, walls concealing hot-water pipes
A thermally-insulated backing should be used
when tting to solid walls (concrete, steel, etc.). ACI part: A/ROOM-FOAM-PAD. Be sure to cut out an area for slotting the detachable terminal block.
Separate the cover from the base. Attach the base directly to the wall or to a standard 2” x 4” junction box using the (2) #6-32 x 1” screws provided.
FIGURE 2: ENCLOSURE DIMENSIONS
1.12"
(28.36 mm)
2.75"
(69.85 mm)
4.50"
(114.30 mm)
FRONT
DETACHABLE TERMINAL BLOCK
BOTTOM
(5.05 mm)
FIGURE 3: MOUNTING DIAGRAM
DETACHABLE TERMINAL BLOCK
MOUNTING SCREW
(#6-32 x 1”)
CIRCUIT BOARD
COVER
OPTIONAL INSULATING GASKET
BACKPLATE
48” - 60”
(1.2 - 1.5 m)
0.20"
Refer to the wiring instructions (p. 1-2) to make necessary connections. After wiring, attach the cover to the base by snapping the top of the cover on rst and then the bottom. Tighten the cover down, using the (2) 1/16” Allen screws located in the bottom of the housing. A 1/16” Hex driver is needed to secure the cover to the base.
Take care when mounting. Check local code for mounting height requirements. Typical mounting heights are 48-60” (1.2-1.5 m) o the ground and at least 1.5’ (0.5 m) from the adjacent wall. The sensor should be mounted in an area where air circulation is well mixed and not blocked by obstructions.
*Reference FIGURE 2 and 3
BACnet MS/TP INTERFACE
The BACnet Master-Slave/Token-Passing (MS/TP) data link protocol uses EIA-485 as a two-wire, daisy chain network. A branch is
a discrete chain of devices connected to a controller.
Page 2
Version 1.0
I0000803
BACnet MS/TP INTERFACE (Continued)
The max number of devices per segment is (32), as per the BACnet specications. 4000 ft (1219.2 m) is the maximum
recommended length for a segment, which includes all devices from the controller to the last device in the daisy chain. ACI’s
BACnet sensors are master devices. Only master nodes are allowed to send and receive tokens on the MSTP network.
Each branch must have all devices connected with (+) connected to (+) and (-) connected to (-). If a shielded cable is used, this is
not to be connected to the devices. The shield cable should only be connected on one end to earth ground, usually at the
controller. The start and end of each branch should have a termination resistor at the device level or at the controller.
Each device must be congured for the correct baud rate and have a unique address in each branch. The baud rate for the branch is set by the controller. This product has auto-baud for ease of network conguration but setting the baud rate using the DIP switches is recommended.
ADDRESS SELECTION
Switches 1-7 are used to set the BACnet address. Refer to TABLE 2 for switch settings. Each device in a network branch must have a unique address. The value of each position is printed on the board. By default, the address is (0). If the device is powered when a change is made, the device must be power cycled or reset for changes in address to be made.
TABLE 2: ADDRESS SELECTION
ADDRESS
0
1
12
SW 1 (64)
0
0
0
BAUD RATE SELECTION
Switches 8-10 are used to set the BACnet baud rate. Refer to TABLE 3 for switch settings. Where (0) is low and (1) is high. By default, the device is in auto-baud. If the system’s baud rate is known, it is recommended to set the specic baud rate to match the system. If the device is powered when a change is made, the device must be power cycled or reset for changes in baud rate to be made.
EOL TERMINATION RESISTANCE SELECTION
RS-485 requires that the last device in a chain have a termination resistor. This is controlled using a jumper in the EN (enabled) position
marked on FIGURE 4. When the jumper is set to EN (enabled), a 120 Ω resistance is added in parallel to the data line. When the jumper is set to DIS (disable), the resistance is not added. By default, the jumper is placed in the DIS (disabled) position.
SW 2 (32)
0
0
0
SW 3 (16)
0
0
0
SW 4 (8)
0
0
1
SW 5 (4)
0
0
1
SW 6 (2)
0
0
0
TABLE 3: BAUD RATE SELECTION
BAUD RATE
Auto-Baud
9600
19200
38400
57600
76800
115200
SW 8
0
0
0
0
1
1
1
SW 9
0
0
1
1
0
0
1
FIGURE 4: EOL TERMINATION JUMPERS
END OF LINE TERMINATION ENABLED
END OF LINE TERMINATION DISABLED
EN DIS EN DIS
SW 7 (1)
0
1
0
SW 10
0
1
0
1
0
1
0
Page 3
Version 1.0
I0000803
DEVICE CONFIGURATION THROUGH BACnet
DEVICE INSTANCE
The Device Instance, by default, is 1035000 plus the Address. For example, an Address of 21 results in a default address of 1035021. This can be changed once the device is connected to the network, but each device instance must be unique within the network. The device instance must be unique throughout the entire BACnet network, not just this segment.
DEVICE LOCATION
The device location is optional but is intended to allow for further denition of the device’s location. The device location can be a character string up to 64 characters in length.
DEVICE NAME
By default, the device name is based on the type of device and the address. The device name can be a character string up to (32) characters in length. This can be changed once the device is connected to the network. For example: Temperature Sensor - 034. The device name must be unique throughout the entire BACnet network, not just this segment.
DEVICE DESCRIPTION
By default, the device name is based on the type of device and the address. The device name can be a character string up to (32) characters in length. This can be changed once the device is connected to the network. For example: Temperature Sensor - 034. The device name must be unique throughout the entire BACnet network, not just this segment.
LED INFORMATION
One LED indicates three statuses. Solid green shows that power is good, but no data is transmitting. A solid Amber indicates that auto-baud is set and no data has been received to set a baud rate. Green/Amber ashing indicates data is being transmitted or received. Solid Red LED status indicates an error state, usually loss of communication on the network. If this status remains for (10) times the APDU timeout, the device will automatically reset. If this state remains longer than that, reset the device.
TEMPERATURE CONFIGURATION
One LED indicates three statuses. Solid green shows that power is good, but no data is transmitting. A solid Amber indicates that auto-baud is set and no data has been received to set a baud rate. Green/Amber flashing indicates data is being transmitted or received. Solid Red LED status indicates an error state, usually loss of communication on the network. If this status remains for (10) times the APDU timeout, the device will automatically reset. If this state remains longer than that, reset the device.
TEMPERATURE AND RH OFFSET
This device allows for a temperature oset of +/-5 °C (9 °F) and an RH oset of +/-10%. By default, these values are set to 0, meaning no oset is added.
These are set by writing to the present value of the Temperature Calibration Oset (AV0) or RH Calibration Oset (AV1). The value written must be within the specied range or an error will be returned. To set these back to factory settings, write any changed values to (0).
TEST MODE
For the Sensor objects (AI0 and AI1), a test mode can be set by writing the Boolean value true to the “out-of-service” property. Then the present-value can be set to any valid test value the user requires. This allows a user to test reactions to specic values returned by this device.
RESET
The reset button can be used to reset the device without disconnecting power. The location of this button is shown in
FIGURE 1 (p.1).
TABLE 4: UNIT SETTING
UNITS
°F
K
°C
VALUE
64
63
62
Page 4
Version 1.0
I0000803
TABLE 5: BACnet OBJECT TABLE
OBJECT TYPE
Device
Analog
Inputs
Analog
Values
OBJECT ID
- - - - - - - - - -
AI-0
AI-1
AV-0
AV-1
OBJECT NAME
BN11x0
Temperature Sensor
RH Sensor
Temperature
Calibration Oset
RH Calibration Oset
PRODUCT SPECIFICATIONS
Supply Voltage:
Current Consumption:
Temperature Measurement Range:
Temperature Measurement Accuracy:
Temperature Calibration Oset:
RH Measurement Range:
RH Measurement Accuracy:
RH Calibration Oset:
Temperature / RH Update Rate:
Communication Protocol:
Sensor Addresses:
Supported Baud Rates:
Device Instance Number:
Connections / Wire Size:
Terminal Block Torque Rating:
Operating Temperature Range:
Storage Temperature Range:
Operating Humidity Range:
Enclosure Material / UL Flammability:
RANGE
0-4194302
34.7 - 122.0
0.0 - 95.0
-9.0 - 9.0
-10.0 -10.0
BACnet ENGINEERING UNITS
- - - - - - - - - - - - - - - - - - - - - - - - - -
degrees-Fahrenheit (64) - default
percent-relative-humidity (29)
delta-degrees-Fahrenheit (120)
percent-relative-humidity (29)
12 to 36 VDC / 24 VAC +/- 10%, 50/60 Hz (Reverse Polarity Protected)
25 mA maximum (0.67 VA)
35 to 122°F (1.5 to 50°C)
@ 77°F (25°C): +/- 1.0°F (+/- 0.5°C)
+/- 9°F (+/- 5°C) (Field Congurable)
0 to 95%
@ 77°F (25°C): +/- 2% from 10 to 90% RH
+/- 10% RH (Field Congurable)
4 seconds
BACnet MS/TP; EIA RS-485
0 to 127 (0 (Default); Field Selectable)
Auto Baud (Default), 9600, 19200, 38400, 57600, 76800, 115200 (Field Selectable)
1035000 + Address (example: Address 127 = 1035127; Field Congurable)
Screw Terminal Blocks / 16 AWG (1.31 mm2) to 22 AWG (0.33 mm2)
0.45 lbf-in (0.5 Nm) nominal
35 to 122°F (1.5 to 50°C)
-40 to 185°F (-40 to 85°C)
10 to 95% RH, non-condensing
ABS Plastic / UL94-HB
W.E.E.E. DIRECTIVE
At the end of their useful life the packaging and product should be disposed of via a suitable recycling centre. Do not dispose of with household waste. Do not burn.
BACnet is a registered trademark of ASHRAE. ASHRAE does not endorse, approve or test products for compliance with ASHRAE standards. Compliance of listed products to the requirements of ASHRAE Standard 135 is the responsibility of BACnet International (BI). BTL is a registered trademark of BACnet International.
Version 1.0
I0000803
Loading...