The BACnet Duct Series sensor is designed for use with
electronic controllers in commercial heating and cooling
building management systems. The ACI BACnet Duct
Series sensor can be ordered to monitor temperature, RH,
or temp/RH in commercial HVAC ductwork. It uses BACnet
MS/TP for physical connection to a BAS or controller, has
dip switches to set addresses and baud rate, and has on
board end-of-line termination. There is no analog output.
WIRING INSTRUCTIONS
The BACnet Duct Series temperature sensor has a
depluggable terminal block located on the front of the
PCB. For ease of wiring, we recommend removing the
block, wiring, and reattaching before mounting. 16 to 22
AWG two conductor shielded cable is recommended for
powering the sensors.
ACI recommends using Belden 3105 or compatible cable
for RS-485 communication wiring. This wire has 120 ohm
input impendence. The terminal blocks allow for (1) or (2)
wires to be connected in each position for daisy chaining.
Daisy chain the RS-485 wiring and do not use “Star” or “T”
wiring. Avoid running communication wires next to AC
line voltage wires. These can be sources of noise that can
aect signal quality.
FIGURE 1: ENCLOSURE DIMENSIONS
PLASTIC BOX (-PB): TEMP. ONLY
3.60"
(91.44 mm)
2.25"
(57.15 mm)
4.79"
(121.55 mm)
2.35"
(59.80 mm)
EURO (-EH): RH and RH/TEMP.
4.30"
(109.22 mm)
1.51"
(38.25 mm)
3.01"
(76.51 mm)
3.80"
(96.56 mm)
1.90"
(48.28 mm)
PRECAUTIONS
Remove power before wiring. Never connect or
•
disconnect wiring with power applied.
It is recommended you use an isolated UL-listed
•
class 2 transformer when powering the unit with 24
VAC. Failure to wire the devices with the correct
polarity when sharing transformers may result in
damage to any device powered by the shared
transformer.
Page 1
2.12"
(53.72 mm)
10.05"
(255.32 mm)
Version 1.0
I0000804
PRECAUTIONS (Continued)
DO NOT RUN THE WIRING IN ANY CONDUIT WITH
•
LINE VOLTAGE (24/120/230 VAC).
If the 24 VDC or 24VAC power is shared with devices
•
that have coils such as relays, solenoids, or other
inductors, each coil must have an MOV, DC/AC
Transorb, Transient Voltage Suppressor (ACI Part:
142583), or diode placed across the coil or inductor.
The cathode, or banded side of the DC Transorb or
diode, connects to the positive side of the power
supply. Without these snubbers, coils produce very
large voltage spikes when de-energizing that can
cause malfunction or destruction of electronic
circuits.
MOUNTING INSTRUCTIONS
For optimal readings, follow these tips:
FIGURE 2: LAYOUT
TERMINAL BLOCKS
VD-GN
POWER
23618421421
46
ADDRESSBAUD
D+
BACNET
RESET BUTTON
LED
END OF LINE
TERMINATION
DIP SWITCH
EN DIS
The sensor should be mounted in the middle of the
•
duct where air circulation is well mixed (no
stratication), and not blocked by obstructions.
Stratication and obstructions can cause sensing
errors. An example is downstream from a heating or
cooling coil.
Duct probe should be placed (3) to (4) duct
•
TABLE 1: WIRING CONNECTIONS
TERMINAL
BLOCKS
+V
GN
D-
D+
CONNECTIONS
Power Supply Positive 12-36VDC / 24VAC
Power Supply Common or Ground
EIA-485 Data Negative
EIA-485 Data Positive
segments down from any bend or obstructions
and away from 90° bends.
Mount the sensor on the top or sides of duct work; mounting on the bottom risks damage due to moisture.
•
The BACnet Duct Temperature-only sensor uses the Plastic Box (-PB) enclosure. Alternatively, the Euro (-EH) enclosure is
used for the BACnet Relative Humidity (RH) sensor and BACnet RH/Temperature Combo sensor (see FIGURE 1). Be sure to
follow the instructions listed for your enclosure.
PLASTIC BOX (-PB) ENCLOSURE INSTALLATION
Drill a 3/8” hole in the duct and insert the probe through the hole until the foam pad is tight to the duct.
Drill pilot holes for the (2) mounting screws. Use the enclosure ange as a guide, or use the dimensions listed on page 1 to
measure out.
Now fasten and insert (2) screws #8 x ¾” TEK (provided and recommended) through the mounting holes in the ange and
tighten until the unit is held rmly to the duct.
Refer to the wiring instructions (p. 2) to make necessary connections. After wiring, shut the cover of the enclosure.
*Reference FIGURE 2
Page 2
Version 1.0
I0000804
MOUNTING INSTRUCTIONS (Continued)
EURO (-EH) ENCLOSURE INSTALLATION
Drill a 7/8” hole in the duct and insert the probe through
the hole until the foam pad is tight to the duct. Drill pilot
holes for the (2) mounting screws. Use the enclosure
flange as a guide, or use the dimensions listed on page 1
to measure out.
FIGURE 3: DUCT MOUNTING
0.375"
(9.525 mm)
EURO (-EH)
Now fasten and insert (2) screws #8 x ¾” TEK (provided
and recommended) through the mounting holes in the
flange and tighten until the unit is held firmly to the
duct.
Refer to the wiring instructions (p. 2) to make necessary
connections. After wiring, twist the cover until the enclosure is
tightly sealed.
*Reference FIGURE 2
PLASTIC BOX
(-PB)
0.875"
(22.23 mm)
BACnet MS/TP INTERFACE
The BACnet Master-Slave/Token-Passing (MS/TP) data link protocol uses EIA-485 as a two-wire, daisy chain network. A branch is
a discrete chain of devices connected to a controller. The max number of devices per segment is (32), as per the BACnet
specications. 4000 ft (1219.2 m) is the maximum recommended length for a segment, which includes all devices from the
controller to the last device in the daisy chain. ACI’s BACnet sensors are master devices. Only master nodes are allowed to send
and receive tokens on the MSTP network.
Each branch must have all devices connected with (+) connected to (+) and (-) connected to (-). If a shielded cable is used, this is
not to be connected to the devices. The shield cable should only be connected on one end to earth ground, usually at the
controller. The start and end of each branch should have a termination resistor at the device level or at the controller.
Each device must be congured for the correct baud rate and have a unique address in each branch. The baud rate for the branch
is set by the controller. This product has auto-baud for ease of network conguration but setting the baud rate using the DIP
switches is recommended.
ADDRESS SELECTION
Switches 1-7 are used to set the BACnet address. Refer to TABLE 2 for switch settings. Each device in a network branch must
have a unique address. The value of each position is printed on the board. By default, the address is (0). If the device is
powered when a change is made, the device must be power cycled or reset for changes in address to be made.
TABLE 2: ADDRESS SELECTION
ADDRESS
0
1
12
SW 1 (64)
0
0
0
SW 2 (32)
0
0
0
SW 3 (16)
0
0
0
SW 4 (8)
0
0
1
SW 5 (4)
0
0
1
SW 6 (2)
0
0
0
SW 7 (1)
0
1
0
Page 3
Version 1.0
I0000804
BAUD RATE SELECTION
Switches 8-10 are used to set the BACnet baud rate.
Refer to TABLE 3 for switch settings. Where (0) is low
and (1) is high. By default, the device is in auto-baud.
If the system’s baud rate is known, it is
recommended to set the specic baud rate to match
the system.If the device is powered when a change is
made, the device must be power cycled or reset for
changes in baud rate to be made.
TABLE 3: BAUD RATE SELECTION
BAUD RATE
Auto-Baud
9600
19200
38400
57600
76800
115200
SW 8
0
0
0
0
1
1
1
SW 9
0
0
1
1
0
0
1
SW 10
0
1
0
1
0
1
0
EOL TERMINATION
FIGURE 4: EOL TERMINATION JUMPERS
RESISTANCE SELECTION
RS-485 requires that the last device in a chain have
a termination resistor. This is controlled using a
jumper in the EN (enabled) position marked on
FIGURE 4 (right). When the jumper is set to EN
(enabled), a 120 Ω resistance is added in parallel to
the data line. When the jumper is set to DIS
(disabled), the resistance is not added. By default,
the jumper is placed in the DIS (disabled) position.
END OF LINE
TERMINATION ENABLED
ENDISENDIS
END OF LINE
TERMINATION DISABLED
DEVICE CONFIGURATION THROUGH BACnet
DEVICE INSTANCE
The Device Instance, by default, is 1035000 plus the Address. For example, an Address of 21 results in a default address
of 1035021. This can be changed once the device is connected to the network, but each device instance must be unique
within the network. The device instance must be unique throughout the entire BACnet network, not just this segment.
DEVICE LOCATION
The device location is optional but is intended to allow for further denition of the device’s location. The device location can
be a character string up to 64 characters in length.
DEVICE NAME
By default, the device name is based on the type of device and the address. The device name can be a character string up to
(32) characters in length. This can be changed once the device is connected to the network. For example: Temperature
Sensor - 034. The device name must be unique throughout the entire BACnet network, not just this segment.
DEVICE DESCRIPTION
By default, the device name is based on the type of device and the address. The device name can be a character string up to
(32) characters in length. This can be changed once the device is connected to the network. For example: Temperature
Sensor - 034. The device name must be unique throughout the entire BACnet network, not just this segment.
Page 4
Version 1.0
I0000804
DEVICE CONFIGURATION THROUGH BACnet (Continued)
LED INFORMATION
One LED indicates three statuses. Solid green shows that power is good, but no data is transmitting. A solid Amber indicates that
auto-baud is set and no data has been received to set a baud rate. Green/Amber ashing indicates data is being transmitted or
received. Solid Red LED status indicates an error state, usually loss of communication on the network. If this status remains for
(10) times the APDU timeout, the device will automatically reset. If this state remains longer than that, reset the device.
TEMPERATURE CONFIGURATION
One LED indicates three statuses. Solid green shows that power is good, but no data is
transmitting. A solid Amber indicates that auto-baud is set and no data has been
received to set a baud rate. Green/Amber ashing indicates data is being transmitted
or received. Solid Red LED status indicates an error state, usually loss of communication
on the network. If this status remains for (10) times the APDU timeout, the device
will automatically reset. If this state remains longer than that, reset the device.
TABLE 4: UNIT SETTING
UNITS
°F
K
VALUE
64
63
TEMPERATURE AND RH OFFSET
This device allows for a temperature oset of +/-5
+/-10%. By default, these values are set to (0), meaning no oset is added.
These are set by writing to the present value of the Temperature Calibration Oset (AV0) or RH Calibration Oset (AV1).
The value written must be within the specied range or an error will be returned. To set these back to factory settings,
write any changed values to (0).
TEST MODE
For the Sensor objects (AI0 and AI1), a test mode can be set by writing the Boolean value true to the “out-of-service”
property. Then the present-value can be set to any valid test value the user requires. This allows a user to test reactions
to specic values returned by this device.
RESET
The reset button can be used to reset the device without disconnecting power. The location of this button is shown in FIGURE 3.
At the end of their useful life the packaging and product should be disposed of via a suitable recycling centre. Do not
dispose of with household waste. Do not burn.
BACnet is a registered trademark of ASHRAE. ASHRAE does not endorse, approve or test products for compliance with ASHRAE standards. Compliance of listed products to the requirements of ASHRAE
Standard 135 is the responsibility of BACnet International (BI). BTL is a registered trademark of BACnet International.
Page 6
Version 1.0
I0000804
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.