ACI-Automation Components A/XX-FRZ2” Instruction Sheet

A/XX-FRZ2”
RED
RED
WHITE
THERMISTOR/ RTD
SENSOR INPUT #1 OF DDC SYSTEM
DDC CONTROL
A/XX-SUBM-2"
PIPE
STRAPS
INSULATION
THERMAL GREASE (OPTIONAL)
Please Read Instruction Carefully Before Installation!
Applications
A few of the most common applications are listed below:
Monitoring Freezers or Glycol Temperatures Monitoring Cooling Towers and Tank Temperatures For Direct Fluid Insertion
Installation
The A/XX-FRZ2” probe temperature sensors are single point temperature sensors with Stainless Steel (304 or 316 Series)
probes. Use care when installing the 2” probes. Pay attention not to kink the cable. The red/red/white wires should be
securely connected to the controller. When using the A/XX-FRZ2 in a strap-on application, make sure to securely fasten
the probe to the outside surface of the pipe. A loose attachment could affect the accuracy. To ensure good contact, thermal grease is recommended. Insulating the sensor will help to eliminate the effects that the air temperature has on the sensor
readings. When installing the A/XX-FRZ2” sensor, it may be necessary to wire tie the cable, depending upon the
application.
Glycol Bottle Application
Tank Application Strap-on Application
      
Installation Instructions I0000320 Rev 3 Page 1 of 2
Troubleshooting
WHITE
THERMISTOR/ RTD
RED
RED
A/XX-SUBM-2"
OHMMETER
Sensor reads 0 ohms or very low Sensor or wires are shorted together Verify that all three of the leads are not shorted to the probe.
Sensor reads infinity or very high Sensor or wires are cut or open Erratic readings Bad wire connections - Condensation or Moisture problem
Inaccurate Sensor If you suspect that the sensor is not reading within the specified
tolerance, disconnect the sensor wires from the Building Management System (DDC Controller) and attach a NIST traceable ohmmeter across the three wires. Download the resistance chart for the given sensor type from the ACI website.
WEEE Directive
At the end of their useful life the packaging and product should be disposed of via a suitable recycle centre. Do not dispose of with household waste. Do not burn.
Installation Instructions I0000320 Rev 3 Page 2 of 2