Automation Components, Inc.
ANALOG OUTPUTCURRENT
Split-Core
Solid-Core
ANALOG OUTPUT
Sensors with 4 to 20 mA Output
The A/CTA and A/SCTA Series current sensors monitor the current flowing to electrical equipment or
buildings. The magnitude of this current is then converted into a linear and proportional 4 to 20 mA output
signal. The A/CTA Series current sensors are available in either an Average or True RMS output version.
Nearly all of these sensors have jumper selectable input ranges, with the exception of the 0 to 5 Amp input
range on the A/CTA-5 and A/SCTA-5 Series sensors. This series is fast-acting and extremely accurate from
1 to 100% of the full scale output. The sensors are factory calibrated using an NIST traceable standard.
Every device on this cutsheet features a patented Din-Rail mounting system (Pat. no. US 7,416,421) for
ease of installation.
Automation Components, Inc. Made in the USA
79

ANALOG OUTPUTCURRENT
SPECIFICATIONS
Sensor Supply Voltage
Amperage Rating
Supply Current
Output
Max Load Resistance (A/CTA & A/SCTA)
Max Load Resistance (A/CTA-VFD & A/SCTA-VFD)
Response Time
Isolation Voltage
Maximum Sensing Current Voltage
Aperture (Hole) Size
Operating Temp Range (A/CTA & A/SCTA)
Operating Temp Range (A/CTA-VFD & A/SCTA-VFD)
Operating Humidity Range
Product Dimensions
Amp Range (A/CTA) (All Non-VFD Models)
Amp Range (A/SCTA) (All Non-VFD Models)
Amp Range (A/CTA-50-VFD) (10, 20 & 50A)
Amp Range (A/SCTA-50-VFD) (10, 20 & 50A)
Amp Range (A/CTA-250-VFD) (100A)
Amp Range (A/CTA-250-VFD) (200 & 250A)
Amp Range (A/SCTA-200-VFD) (100, 150 & 200A)
Automation Components, Inc.
+12 to 30 VDC
0-250A (See Ordering Information)
36 mA maximum
4-20 mA, 2-wire Loop Powered
700 Ohms @ 24 VDC (Vs-9)/0.02-40.2
700 Ohms @ 24 VDC (Vs-10)/0.02
A/CTA & A/SCTA: <75mS | A/CTA-VFD & A/SCTA-VFD: <2 seconds
2,200 VAC
600 VAC
0.75” DIA (insulated conductors required)
-15 to 40
0 to 40
0 to 95% RH, non-condensing
Split Core: (L) 3.33” (W) 1.08” (H) 2.70” | Solid Core: (L) 3.38” (W) 0.98” (H) 2.27”
15-200Hz: Not Rated | 30-60Hz: +/- 0.75% Accuracy | 30Hz-1KHz:+/- 0.75% Accuracy
15-200Hz: Not Rated | 30-60Hz: +/- 0.75% Accuracy | 30Hz-1KHz:+/- 0.75% Accuracy
15-200Hz: +/- 1% Accuracy | 30-60Hz: +/- 0.75% Accuracy | 30Hz-1KHz: ---15-200Hz: +/- 2% Accuracy | 30-60Hz: +/- 0.75% Accuracy | 30Hz-1KHz: ---15-200Hz: +/- 1% Accuracy | 30-60Hz: +/- 0.75% Accuracy | 30Hz-1KHz: ---15-200Hz: Not rated | 30-60Hz: +/- 0.75% Accuracy | 30Hz-1KHz: ---15-200Hz: Not rated | 30-60Hz: +/- 0.75% Accuracy | 30Hz-1KHz: ----
o
C (5 to 104oF)
o
C (32 to 104oF)
ORDERING
Select one Current Sensor (A). NOTE: Current Switches are not to be used in Life & Safety applications, or in hazardous locations.
Current Switches
A/CTA-5 (Loop Powered, Solid-Core, 4-20 mA Average Output)
A/CTA-50
A/CTA-250
A/CTA-50-VFD
A/CTA-250-VFD
A/SCTA-5
A/SCTA-50
A/SCTA-200
A/SCTA-50-VFD
A/SCTA-200-VFD
(Loop Powered, Solid-Core, 4-20 mA Average Output)
(Loop Powered, Solid-Core, 4-20 mA Average Output)
(Loop Powered, Solid-Core, True RMS, 4-20 mA Output)
(Loop Powered, Solid-Core, True RMS, 4-20 mA Output)
(Loop Powered, Split-Core, 4-20 mA Average Output)
(Loop Powered, Split-Core, 4-20 mA Average Output)
(Loop Powered, Split-Core, 4-20 mA Average Output)
(Loop Powered, Split-Core, True RMS, 4-20 mA Output)
(Loop Powered, Split-Core, True RMS, 4-20 mA Output)
(Jumper Selectable Range: 0-5A (Not Selectable))
(Jumper Selectable Range: 0-10, 0-20, 0-50A)
(Jumper Selectable Range: 0-100, 0-200, 0-250A)
(Jumper Selectable Range: 0-10, 0-20, 0-50A)
(Jumper Selectable Range: 0-100, 0-200, 0-250A)
(Jumper Selectable Range: 0-5A (Not Selectable))
(Jumper Selectable Range: 0-10, 0-20, 0-50A)
(Jumper Selectable Range: 0-100, 0-150, 0-200A)
(Jumper Selectable Range: 0-10, 0-20, 0-50A)
(Jumper Selectable Range:0-100, 0-150, 0-200A)
BUILD PART NUMBER
After completing (A) from the above table, fill in the Part Number Table below. An example part number is offered.
EXAMPLE: A/SCTA-200-VFD
CE Compliant
CE Compliant
CE Compliant
Not CE Compliant
Not CE Compliant
CE Compliant
CE Compliant
CE Compliant
Not CE Compliant
Not CE Compliant
80
All Current Sensors, Switches and Command Relays have a UL94-5VB flammability rating for the enclosure.