ACI-Automation Components ANALOG OUTPUT Data Sheet

Automation Components, Inc.
ANALOG OUTPUTCURRENT
Split-Core
Solid-Core
ANALOG OUTPUT
Sensors with 4 to 20 mA Output
The A/CTA and A/SCTA Series current sensors monitor the current flowing to electrical equipment or buildings. The magnitude of this current is then converted into a linear and proportional 4 to 20 mA output signal. The A/CTA Series current sensors are available in either an Average or True RMS output version. Nearly all of these sensors have jumper selectable input ranges, with the exception of the 0 to 5 Amp input range on the A/CTA-5 and A/SCTA-5 Series sensors. This series is fast-acting and extremely accurate from 1 to 100% of the full scale output. The sensors are factory calibrated using an NIST traceable standard. Every device on this cutsheet features a patented Din-Rail mounting system (Pat. no. US 7,416,421) for ease of installation.
Automation Components, Inc. Made in the USA
79
ANALOG OUTPUTCURRENT
SPECIFICATIONS
Sensor Supply Voltage Amperage Rating Supply Current Output Max Load Resistance (A/CTA & A/SCTA) Max Load Resistance (A/CTA-VFD & A/SCTA-VFD) Response Time Isolation Voltage Maximum Sensing Current Voltage Aperture (Hole) Size Operating Temp Range (A/CTA & A/SCTA) Operating Temp Range (A/CTA-VFD & A/SCTA-VFD) Operating Humidity Range Product Dimensions Amp Range (A/CTA) (All Non-VFD Models) Amp Range (A/SCTA) (All Non-VFD Models) Amp Range (A/CTA-50-VFD) (10, 20 & 50A) Amp Range (A/SCTA-50-VFD) (10, 20 & 50A) Amp Range (A/CTA-250-VFD) (100A) Amp Range (A/CTA-250-VFD) (200 & 250A) Amp Range (A/SCTA-200-VFD) (100, 150 & 200A)
Automation Components, Inc.
+12 to 30 VDC 0-250A (See Ordering Information) 36 mA maximum 4-20 mA, 2-wire Loop Powered 700 Ohms @ 24 VDC (Vs-9)/0.02-40.2 700 Ohms @ 24 VDC (Vs-10)/0.02 A/CTA & A/SCTA: <75mS | A/CTA-VFD & A/SCTA-VFD: <2 seconds 2,200 VAC 600 VAC
0.75” DIA (insulated conductors required)
-15 to 40 0 to 40 0 to 95% RH, non-condensing Split Core: (L) 3.33” (W) 1.08” (H) 2.70” | Solid Core: (L) 3.38” (W) 0.98” (H) 2.27” 15-200Hz: Not Rated | 30-60Hz: +/- 0.75% Accuracy | 30Hz-1KHz:+/- 0.75% Accuracy 15-200Hz: Not Rated | 30-60Hz: +/- 0.75% Accuracy | 30Hz-1KHz:+/- 0.75% Accuracy 15-200Hz: +/- 1% Accuracy | 30-60Hz: +/- 0.75% Accuracy | 30Hz-1KHz: ---­15-200Hz: +/- 2% Accuracy | 30-60Hz: +/- 0.75% Accuracy | 30Hz-1KHz: ---­15-200Hz: +/- 1% Accuracy | 30-60Hz: +/- 0.75% Accuracy | 30Hz-1KHz: ---­15-200Hz: Not rated | 30-60Hz: +/- 0.75% Accuracy | 30Hz-1KHz: ---­15-200Hz: Not rated | 30-60Hz: +/- 0.75% Accuracy | 30Hz-1KHz: ----
o
C (5 to 104oF)
o
C (32 to 104oF)
ORDERING
Select one Current Sensor (A). NOTE: Current Switches are not to be used in Life & Safety applications, or in hazardous locations.
Current Switches
A/CTA-5 (Loop Powered, Solid-Core, 4-20 mA Average Output) A/CTA-50 A/CTA-250 A/CTA-50-VFD A/CTA-250-VFD A/SCTA-5 A/SCTA-50 A/SCTA-200 A/SCTA-50-VFD A/SCTA-200-VFD
(Loop Powered, Solid-Core, 4-20 mA Average Output)
(Loop Powered, Solid-Core, 4-20 mA Average Output)
(Loop Powered, Solid-Core, True RMS, 4-20 mA Output)
(Loop Powered, Solid-Core, True RMS, 4-20 mA Output)
(Loop Powered, Split-Core, 4-20 mA Average Output)
(Loop Powered, Split-Core, 4-20 mA Average Output)
(Loop Powered, Split-Core, 4-20 mA Average Output)
(Loop Powered, Split-Core, True RMS, 4-20 mA Output)
(Loop Powered, Split-Core, True RMS, 4-20 mA Output)
(Jumper Selectable Range: 0-5A (Not Selectable)) (Jumper Selectable Range: 0-10, 0-20, 0-50A) (Jumper Selectable Range: 0-100, 0-200, 0-250A) (Jumper Selectable Range: 0-10, 0-20, 0-50A) (Jumper Selectable Range: 0-100, 0-200, 0-250A) (Jumper Selectable Range: 0-5A (Not Selectable)) (Jumper Selectable Range: 0-10, 0-20, 0-50A) (Jumper Selectable Range: 0-100, 0-150, 0-200A) (Jumper Selectable Range: 0-10, 0-20, 0-50A) (Jumper Selectable Range:0-100, 0-150, 0-200A)
BUILD PART NUMBER
After completing (A) from the above table, fill in the Part Number Table below. An example part number is offered.
EXAMPLE: A/SCTA-200-VFD
CE Compliant CE Compliant CE Compliant Not CE Compliant Not CE Compliant CE Compliant CE Compliant CE Compliant Not CE Compliant Not CE Compliant
80
All Current Sensors, Switches and Command Relays have a UL94-5VB flammability rating for the enclosure.