![](/html/f1/f1c5/f1c573964c45e3dc20c79fae75c08958c7660b2772cbdf6492a09cf5aa75dbd9/bg1.png)
Installation and Operation Instructions
#8 x 3/4" Tek Screw
(Qty. 2/Unit)
Part #A/MCS, A/MSCS
Please Read Instructions Carefully Before Installation!
Safety
This product is not intended to be used for Life or Safety applications.
This product is not intended for use in any hazardous or classified locations.
Disconnect and lock out all power sources before installation as severe injury or death may result from electrical
shock due to contact with high voltage wires.
Installation
Make sure that all installations are in compliance with all national and local electrical codes. Only qualified individuals that are
familiar with codes, standards, and proper safety procedures for high-voltage installations should attempt installation. The current
switches will not require external power, since the power for the current switch is induced from the conductor being monitored.
The A/MCS and A/MSCS Current Switches should be used on Insulated Conductors Only! The current switch may be mounted
in any position using the (2) #8 x 3/4” Tek screws and the mounting holes in the base. Leave a minimum distance of
1” (3 cm) between the current switch and any other magnetic devices such as contactors and transformers.
Figure 1: A/MCS Figure 2: A/MSCS
For applications in which the normal operating current is below the 0.20 Amps (A/MCS) or 0.55 Amps (A/MSCS)
trip point (See Figure 3 below), the conductor being monitored may be looped through the sensor 4 times giving you a total
operating current of 4X the original current. Example: A small fan operating at 0.2A should be wrapped through the sensor
4 times to give you a total operating current of 0.8Amps flowing through the A/MCS or A/MSCS.
Figure 3: Wires Through Sensors
Page 1 of 3 I0000557
Version : 1.0
![](/html/f1/f1c5/f1c573964c45e3dc20c79fae75c08958c7660b2772cbdf6492a09cf5aa75dbd9/bg2.png)
Insulated
Example: For currents up to 600 Amps
(and not below 70 Amps (A/MCS-A)
or 95 Amps (A/MSCS-A), where
Current Transformer (C.T.)
secondary falls below 1 Amp
use a 600:5 ratio C.T. as shown:
Nut
Conductor
600:5 Ratio 5A C.T.
Wire
Building Management
Digital Input #1
System
(Relay Coil or
120 VAC
Line
Transformer
24 VAC
Contactor)
24 VAC Coil
Relay / Contactor
DI
DO
(Status)
DDC Controller
Max. Sensing
Current Voltage
Max. Current for
6 seconds
Max. Current for
1 second
For applications in which the normal operating current is greater than 150 Amps or for conductor diameters larger than 0.530”
(1.35 cm) in diameter, an external 5 Amp Current Transformer must be used as shown in Figure 4 below.
Remember that the secondary of the 5A CT must be shorted together before the power may be turned onto the monitored
device.
Figure 4: Current Transformer
Wiring
ACI recommends the use of a two conductor 16 to 22 AWG shielded cable or twisted pair copper wire only for all current switch
applications. A maximum wire length of less than 30 meters (98.4 feet) should be used between the A/MCS and A/MSCS current
switches and the Building Management System or controller. Note: When using a shielded cable, be sure to connect only (1)
end of the shield to ground at the controller. Connecting both ends of the shield to ground may cause a ground loop. When
removing the shield from the sensor end, make sure to properly trim the shield so as to prevent any chance of shorting. The current
switch output terminals represent a solid-state switch for controlling both AC and DC loads and is not polarity sensitive. The
recommended torque to be used on the terminal block connections is 0.67 Nm or 5.93 in-lbs.. The aperture (hole) size of the
current switch is 0.53” (1.35 cm) and will accept a 1 AWG maximum wire diameter.
Operating Specifications
See Figure 5 and Figure 6 for two different current switch applications using your Building Management System (DDC/PLC
Controller). Figure 5 is showing the use of the Go/No Go Current Switch as a Digital Input to your DDC Controller, whereas
Figure 6 is showing you how to use the Go/No/Go Current Switch in conjunction with your building management system to
control a fan or pump for example.
Figure 5: Digital Circuit Figure 6: Analog Circuit
Version : 1.0
Page 2 of 3 I0000557