ACI-Automation Components A/CTE-50, A/CTE-250, A/CTV-50, A/CTV-250 Instruction Sheet

Installation and Operation Instructions
3X
IND.CONT.EQ.
C
LISTED
US
3JHX
I
A/CTE-50
ACI
US
C
LISTED
3JHX
IND.CONT.EQ.
Middleton, WI
A/CTE-50
ACI
3X
!
Part # A/CTE-50, A/CTE-250,
A/CTV-50, A/CTV-250
Safety
This product is not intended to be used for Life or Safety applications. This product is not intended for use in any hazardous or classified locations.Disconnect and lock out all power sources before installation as severe injury or death may result from electrical
 
shock due to contact with high voltage wires.
Installation
Disconnect and lock out all power sources before installation as severe injury or death may result from electrical shock due to contact with high voltage wires. Make sure that all installations are in compliance with all national and local electrical codes. Only qualified individuals that are familiar with codes, standards, and proper safety procedures for high-voltage installations should attempt installation. The current sensor will not require external power, since the power for the current sensor is induced from the conductor being monitored.
The A/CTE & A/CTV Series Analog Current Sensors should be used on Insulated Conductors Only! The current sensors may
be mounted in any position using the (2) #8 x 3/4Tek screws and the mounting holes in the base or snapped directly on to the
35mm DIN rail (See Figures 1 & 2 below). Leave a minimum distance of 1(3 cm) between the current sensor and any other
magnetic devices such as contactors and transformers.
Figure 1: Sensor Placed on Rail Figure 2: Sensor Removed From Rail
Wiring
ACI recommends the use of a 2 conductor 16 to 22 AWG shielded cable, or copper wire only for all Analog current sensor
installations. A maximum wire length of less than 30 meters (98.4 feet) should be used between the A/CTE and A/CTV series current sensors and the Building Management System or controller. Note: When using a shielded cable, be sure to connect only (1) end of the shield to ground at the controller. Connecting both ends of the shield to ground may cause a ground loop. When removing the shield from the sensor end, make sure to properly trim the shield so as to prevent any chance of shorting. The current sensors terminals are polarity sensitive and represent a linear 0 to 5 or 0 to 10 VDC output signal. The recommended torque to be used on the terminal block connections is 0.67 Nm or 5.93 in-lbs. The aperture (hole) size of the current sensor is
0.75” (1.90 cm) and will accept a maximum cable diameter of 350 MCM’s.
   
  
Page 1 of 3 I0000141
Version : 1.0
_
+
Acquisition System
PLC, DDC, or Data
+ 0-5 or 0-10 VDC
(-) Signal Common
GND (Shield)
Analog Input
Connections: Shielded, twisted pair cable is
recommended for these connections.
Note: Ground shield at control
system end only!
Power: These current sensors DO NOT
need an external power source,
since the power is self-induced from the monitored load
or conductor.
Problem
Solution
No reading
- Verify that there is current flowing thru the conductor being monitored with a clamp-on current probe. The power for the current sensor is induced from the conductor being monitored.
- Check the polarity of the circuit.
- Verify that the terminals are screwed down, wires are firmly in place.
- Disconnect the wires from the current sensor output. Measure the voltage across the current sensor output with a Voltmeter to verify that the sensor is working properly.
Erratic readings
- Verify that the wires are terminated properly.
- In areas of high RF interference, shielded cable may be necessary to stabilize signal.
Inaccurate readings
- If you suspect that the current sensor is not reading within the accuracy specifications, please contact the factory for assistance.
ACI Model #
Output
Range
Jumper *
Max. Sensing
Current Voltage
Max. Continuous
Current
Max. Current for
6 seconds
A/CTE-50
0 to 5 VDC
0-10 Amps 0-20 Amps 0-50 Amps
Low
Middle
High
600 VAC
100 Amps 150 Amps 200 Amps
125 Amps 225 Amps 300 Amps
A/CTE-250
0 to 5 VDC
0-100 Amps 0-200 Amps 0-250 Amps
Low
Middle
High
600 VAC
200 Amps 360 Amps 400 Amps
250 Amps 450 Amps 500 Amps
A/CTV-50
0 to 10 VDC
0-10 Amps 0-20 Amps 0-50 Amps
Low
Middle
High
600 VAC
60 Amps
100 Amps 160 Amps
80 Amps
200 Amps
300 Amps
A/CTV-250
0 to 10 VDC
0-100 Amps 0-200 Amps 0-250 Amps
Low
Middle
High
600 VAC
160 Amps
320 Amps
400 Amps
200 Amps 400 Amps 500 Amps
Operating Specifications
*Note: All current sensors are shipped from the factory with the jumper set in the high range.
Wiring Example
Troubleshooting
      
Page 2 of 3 I0000141
Version : 1.0
Loading...
+ 1 hidden pages